Overview of Smart Functions Section 6-1
6-1 Overview of Smart Functions
This section gives an overview of the smart functions of the CompoNet SmartSlice system.
6-2 Registration Table
You can use the DIP switch on the CompoNet Communications Unit to record
the connected SmartSlice I/O Units in a table. The table tells the sequence
and I/O capacity of each SmartSlice I/O Unit.
When the power is subsequently turned ON, the CompoNet Communications
Unit automatically compares the information in the Registration Table with the
connected SmartSlice I/O Units.
6-2-1 Making a Registration Table
Function Overview Method
Registration
Ta bl e
The Registration Table contains information
on the SmartSlice I/O Units in the SmartSlice I/O Terminal.
DIP switch
Backup Function You can read the parameter settings from all
SmartSlice I/O Units in the SmartSlice I/O
Terminal and save them.
DIP switch
Automatic
Restore Function
You can automatically restore the parameter
settings that you backed up in the CompoNet Communications Unit.
DIP switch
Replacing Units
Online
You can replace a SmartSlice I/O Unit without turning OFF the power supply.
---
Automatic Baud
Rate Recognition
The CompoNet Communications Unit automatically uses the same baud rate as the
CompoNet Master Unit.
---
Software Setting
of I/O Allocations
You can set Dummy Units (SmartSlice I/O
Units that are not installed at this time) in a
Software Setting Table. The settings include
the node address and I/O configuration
information.
DIP switch
(You use the CXIntegrator to make,
download, and clear
the Software Setting Table.)
Unit Conduction
Time Monitor
The system calculates and records the time
that the internal power supply in the Unit is
ON in increments of 0.1-hour.
CX-Integrator or
explicit messages
Unit Comments You can set a comment (for example, a
name) for each SmartSlice I/O Unit.
CX-Integrator or
explicit messages
Network Communications
Error History
Monitor
The system records the last four errors in
communications with the CompoNet network.
CX-Integrator or
explicit messages
I/O Communications Error History Monitor
The system records the last 64 errors in
communications between the CompoNet
Communications Unit and the SmartSlice
I/O Units.
CX-Integrator or
explicit messages
Last Maintenance Date
You can record the last date you did maintenance.
CX-Integrator or
explicit messages
• Before making the Registration Table, make sure that all SmartSlice I/O Units
are participating in communications. The TS indicators must be lit in green.
• Before making the Registration Table, make sure that pin 2 (I/O) on the DIP
switch is OFF (Automatic I/O Allocation Mode). You cannot make the Registration Table if pin 2 is ON (Software I/O Allocation Mode).
Precaution for
Correct Usage