• "Windows" is a registered trademark of Microsoft Corporation.
• Other system names and product names that appear in this manual are the trademarks or registered trademarks of
their respective companies.
OMRON, 2010
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by
any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice.
Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or
omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
About this Manual
Thank you for purchasing a GQ-CRM21 CompoNet Gateway Unit for CC-Link.
This manual contains information required to use a GQ-CRM21 CompoNet Gateway Unit for CC-Link.
Please read this manual carefully and be sure you understand the information provided before attempting to use the CompoNet Gateway Unit.
After reading this manual, keep it in a safe and convenient location for future reference.
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems
• Personnel in charge of designing FA systems
• Personnel in charge of managing FA systems and facilities
About this Manual
CompoNet Gateway Unit for CC-Link Operation Manual
1
Using this Manual
Using this Manual
Page Structure
The following page structure is used in this manual.
Level-2 heading
Level-2 heading
Gives the current level-2 heading.
Level-3 heading
Icon
(See next page.)
2-1 Specifications
2
2-1-1 General Specifications
snoit
a
cifi
c
epS
1-2
2 - 1
ItemSpecification
Unit power supply voltage 21.6 to 26.4 VDC (24 VDC ±10%) (Supplied from power supply connector.)
Current
Communications
consumption
Noise immunityConforms to IEC 61000-4-4, 2.0 kV
Vibration resistance
Shock resistance
Dielectric strength500 VAC
Installation methodMounted to DIN Track or by using M4 screws
Ambient operating temperature 0 to 55°C
Ambient operating humidity 10% to 90% (with no condensation)
Ambient storage temperature −25 to 65°C
Weight110 g max.
Ambient operating atmosphere No corrosive gases
Supplemental Information
To press the CompoNet setting buttons, open the cover as shown below.
3.80 A at 24 VDC
power supply
0.13 A at 24 VDC
Internal current
power
consumption
Malfunction: 10 to 60 Hz with 0.7-mm double amplitude, 60 to 150 Hz, 50 m/s
for 80 min in X, Y, and Z directions
2
150 m/s
, 3 times in 6 directions on 3 axes
Open from here.
CompoNet Gateway Unit for CC-Link Operation Manual
Description of Gateway Unit
2
Level-1 heading
Gives the current level-1 heading.
2
Page tab
Gives the number of the level-1 section.
Level-3 heading
Gives the current level-3 heading.
Manual name
CC-Link Communications Section
Station Number Switch
The station number switch sets the station number of the Gateway Unit on the CC-Link network.
X10X1
NumberDescriptionRemarks
1 to 61
Set the station number of the Gateway Unit on the
CC-Link network.
0 or 62 to 99
Do not set. The L ERR indicator will light.
Baud Rate DIP Switch
The baud rate DIP switch sets the baud rate of the Gateway Unit on the CC-Link network.
Set the baud rate of the Gateway Unit to the same value as the CC-Link Master Unit.
O
N
123
4
• Baud Rate Setting
Pin 1 Pin 2 Pin 3 Pin 4*1Baud rate
OFF OFF OFF OFF
OFF OFF ON O FF
OFF O N OFF OFF
OFF ONON OFF
ON OFF OFF OFF
*1 Always leave pin 4 turned OFF. It is reserved.
CompoNet Gateway Unit for CC-Link Operation Manual
156 kbps (default)
625 kbps
2.5 Mbps
5 Mbps
10 Mbps
sgnitteS hctiwS 2-2-2
Default: 00
2 - 10
This illustration is provided only as a sample.
The page shown in the illustration does not necessarily appear in this manual.
2
CompoNet Gateway Unit for CC-Link Operation Manual
Using this Manual
Icons
The following icons are used in this manual.
Precautions for Safe Use
Precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct Use
Precautions on what to do and what not to do to ensure proper operation and performance.
Supplemental Information
Supplemental information to increase understanding.
Additional Information
Additional information or information for reference in product application.
CompoNet Gateway Unit for CC-Link Operation Manual
3
Read and Understand this Manual
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON
representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a
period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NONINFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which
liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
4
CompoNet Gateway Unit for CC-Link Operation Manual
Read and Understand this Manual
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the
combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying
ratings and limitations of use that apply to the products. This information by itself is not sufficient for a
complete determination of the suitability of the products in combination with the end product, machine,
system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not
intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses
listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or
uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical
equipment, amusement machines, vehicles, safety equipment, and installations subject to separate
industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any
consequence thereof.
CompoNet Gateway Unit for CC-Link Operation Manual
5
Read and Understand this Manual
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other
reasons.
It is our practice to change model numbers when published ratings or features are changed, or when
significant construction changes are made. However, some specifications of the products may be changed
without any notice. When in doubt, special model numbers may be assigned to fix or establish key
specifications for your application on your request. Please consult with your OMRON representative at any
time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when
tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does
not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must
correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and
Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no
responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
6
CompoNet Gateway Unit for CC-Link Operation Manual
Safety Precautions
Definition of Precautionary Information
The following notation is used in this manual to provide precautions required to ensure safe usage of
the CompoNet Gateway Unit for CC-Link.
The safety precautions that are provided are extremely important to safety. Always read and heed the
information provided in all safety precautions.
WARNING
Safety Precautions
Indicates a potentially hazardous situation
which, if not avoided, will result in minor or
moderate injury, or may result in serious
injury or death. Additionally there may be
significant property damage.
Indicates a potentially hazardous situation
Caution
Precautions for Safe Use
Precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct Use
Precautions on what to do and what not to do to ensure proper operation and performance.
which, if not avoided, may result in minor
or moderate injury, or property damage.
CompoNet Gateway Unit for CC-Link Operation Manual
7
Safety Precautions
Symbols
The circle and slash symbol indicates operations that you
must not do.
The specific operation is shown in the circle and explained
in text.
The symbol at the left means "do not disassemble."
The triangle symbol indicates precautions (including warnings).
The specific operation is shown in the triangle and explained in text.
The symbol at the left is for a general precaution.
The filled circle symbol indicates operations that you must
do.
The specific operation is shown in the circle and explained
in text.
The symbol at the left shows a general precaution for
something that you must do.
8
CompoNet Gateway Unit for CC-Link Operation Manual
WARNING
Always input the voltage and current to the Unit within the
specified ranges.
Using a voltage or current outside the specified range may result
in malfunction or fire.
Do not touch any part of the terminal section or disassemble the
Unit and touch internal parts while the power is being supplied.
Do not apply power while the cover is open.
Doing so may result in electric shock.
Safety Precautions
Fail-safe measures must be taken by the customer to ensure
safety in the event of incorrect, missing, or abnormal signals
caused by broken signal lines, momentary power interruptions, or
other causes. Serious accidents may result from abnormal
operation if proper measures are not provided.
Provide safety measures in external circuits (i.e., not in the
Programmable Controller), including the following items, to
ensure safety in the system if an abnormality occurs due to
malfunction of the PLC or an external factor affecting the PLC
operation.
Serious accidents may result from abnormal operation if proper
measures are not provided.
• Emergency stop circuits, interlock circuits, limit circuits, and
similar safety measures must be provided in external control
circuits (i.e., not in Slave Units or Repeater Units).
• The outputs from Slave Units or Repeater Units may remain
ON or OFF due to deposits on or burning of the output relays,
or destruction of the output transistors. As a countermeasure
for such problems, external safety measures (i.e., not in Slave
Units or Repeater Units) must be provided to ensure safety in
the system.
• When the 24-VDC output (service power supply) from a Slave
Unit or Repeater Unit is overloaded or shortcircuited, the
voltage may drop and result in the outputs being turned OFF.
As a countermeasure for such problems, external safety measures (i.e., not in Slave Units or Repeater Units) must be provided to ensure safety in the system.
CompoNet Gateway Unit for CC-Link Operation Manual
9
Safety Precautions
Confirm safety at the destination slave device before changing or
transferring parameters to another node. Changing or
transferring parameters without confirming safety may result in
unexpected equipment operation.
The output status from a slave device when problems occur in
communications will depend on the specifications of the slave
device. When using devices with outputs, confirm operating
specifications for communications error and implement suitable
safety measures.
Caution
10
CompoNet Gateway Unit for CC-Link Operation Manual
Precautions for Safe Use
Observe the following precautions when using a CompoNet Gateway Unit for CC-Link.
z Power Supply
• Always use the power supply voltages specified in this manual.
• Take appropriate measures to ensure that the specified power with the rated voltage and frequency is
supplied. Be particularly careful in places where the power supply is unstable.
• Always turn OFF the power supply to the PLC, Gateway Unit, Slave Units, and communications
before attempting any of the following.
• Mounting or dismounting any Units
• Assembling Units
• Setting rotary switches
• Connecting or wiring cables
• Connecting or disconnecting connectors
Precautions for Safe Use
z Installation
• Install and wire Units correctly as described in this manual.
• Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any
static build-up.
• Make sure that the terminal blocks, connectors, communications cables, and other items with locking
devices are properly locked into place.
• When mounting Units to DIN Track or mounting brackets, mount them securely.
• Make sure that all the Unit mounting screws and cable connector screws are tightened to the torque
specified in this manual.
• Use only the specified communications cables and connectors.
• Use correct wiring parts and wiring tools when wiring the cables in the CC-Link and CompoNet systems.
z Wiring
• Wire Units correctly as described in this manual.
• Double-check all wiring and switch settings before turning ON the power supply.
• Confirm polarity before wiring terminals.
• Observe the following precautions when wiring communications cables.
• Separate the communications cables from power lines and high-tension lines.
• Do not fold communications cables.
• Do not pull on the communications cables or bend them past their natural bending radius.
• Always lay communications cable inside ducts.
• Observe voltage specifications when wiring communications paths and power supplies and when wiring I/O crossovers. Incorrect wiring may result in malfunctions.
• Do not apply voltages or connect loads to the Output Units in excess of the maximum switching
capacity.
• When using Flat Cable I (standard or sheathed) or Flat Cable II (sheathed) for more than one CompoNet system, do not bundle the Flat Cables and separate them from each other by at least 5 mm.
• Do not apply power while the cover is open.
• Use only the specified communications cables and connectors.
• Observe the connection distance specifications when connecting communications cables.
• Make sure that metal scraps do not enter a Unit when wiring or processing it.
CompoNet Gateway Unit for CC-Link Operation Manual
11
Precautions for Safe Use
z Handling
• Use the special packing box when transporting a Unit. Also, protect the Unit from being exposed to
excessive vibration or impact during transportation.
• Do not drop the Units or expose them to excessive vibration or impact. Doing so may result in failure
or malfunction.
• Check the user program for proper execution before actually running it on the Unit.
• Do not attempt to dismantle the Unit for repairs or modify it in any way.
• Confirm that no adverse effect will occur in the system before attempting any of the following.
• Changing the operating mode of the PLC
• Starting or stopping the user program
• Force-setting/force-resetting any bit in memory
• Changing the present value of any word or any set value in the user program
• Performing I/O tests
• Using the user compensation functions for an Output Unit
• Do not use organic thinners to clean the Unit. Use commercially available alcohol.
z External Circuits
• Install external breakers and take other safety measures against short-circuiting in external wiring.
• Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing,
or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
• Construct the control circuits so that the power supply to the CompoNet Gateway Unit turns ON only
after the power supply to I/O Slave Units. If the power supply to I/O Slave Units is turned ON after the
power supply to the CompoNet Gateway Unit, normal operation may be temporarily inhibited.
12
CompoNet Gateway Unit for CC-Link Operation Manual
Precautions for Correct Use
• Follow the instructions in this manual to correctly perform installation.
The Unit may fail if it is not installed correctly.
• Observe the voltage specifications when wiring the power supply. An incorrect voltage may result in
malfunctions.
• Take appropriate and sufficient countermeasures when using the Unit in the following locations:
• Locations subject to static electricity or other forms of noise
• Locations subject to strong electromagnetic fields
• Locations subject to possible exposure to radioactivity
• Locations close to power supplies
• Do not install the Unit in the following locations:
• Locations subject to direct sunlight
• Locations subject to temperatures or humidity outside the range specified in the specifications
• Locations subject to condensation as the result of severe changes in temperature
• Locations subject to corrosive or flammable gases
• Locations subject to dust (especially iron dust) or salts
• Locations subject to exposure to water, oil, or chemicals
• Locations subject to shock or vibration
• Take appropriate and sufficient countermeasures when installing the Unit in the following locations:
• Locations subject to static electricity or other forms of noise
• Locations subject to strong electromagnetic fields
• Locations subject to possible exposure to radioactivity
• Locations close to power supplies
Precautions for Correct Use
CompoNet Gateway Unit for CC-Link Operation Manual
13
Conformance to EC Directives
Conformance to EC Directives
Applicable Directives
• EMC Directive
Concepts
z EMC Directive
The CompoNet Gateway Unit is an electrical device that is built into other machines. To enable more
easily building it into other machines, it has been checked for conformity to EMC standards.* EMCrelated performance of the Unit will vary depending on the configuration, wiring, and other conditions of
the equipment or control panel on which it is installed. Whether the products conform to the standards
in the system used by the customer, therefore, must be checked by the customer.
Applicable EMC (Electromagnetic Compatibility) standards are as follows: EMS (Electromagnetic Susceptibility):
*
EN 61131-2 and EN 61000-6-2, EMI (Electromagnetic Interference): EN 61131-2 and EN 61000-6-4 (Radiated
emission: 10-m regulations).
z Conformance to EC Directives
The CompoNet Gateway Unit complies with EC Directives. To ensure that the machine in which the Unit
is used complies with EC Directives, the Unit must be installed as follows:
• The Unit must be installed within a control panel.
• You must use reinforced insulation or double insulation for the DC power supplies for communications, internal power, and I/O. The DC power supplies must provide stable power even when a
momentary power interruption of 10 ms occurs in the input. *
• Products complying with EC Directives also conform to the emission standards (EN 61131-2 and EN
61000-6-4). Radiated emission characteristics (10-m regulations) may vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other conditions.
• Compliance was confirmed for I/O wiring of less than 30 m.
* EMC standard compliance was confirmed with an OMRON S82J Power Supply.
• This is a Class A product (designed for industrial environments). Radio interference may occur if it is
used in a residential area. If that occurs, suitable countermeasures will be required.
14
CompoNet Gateway Unit for CC-Link Operation Manual
Trademarks
• “CC-Link” is a registered trademark of Mitsubishi Electric Corporation.
• “GX-Developer” is a registered trademark of Mitsubishi Electric Corporation.
• “CompoNet” is a registered trademark of the ODVA (Open DeviceNet Vendors Association, Inc.).
Other system names and product names that appear in this manual are the trademarks or registered
trademarks of their respective companies.
Trademarks
CompoNet Gateway Unit for CC-Link Operation Manual
15
Related Manuals
Related Manuals
The following manuals are related to CompoNet. Use them together with this manual whenever
required.
Cat. No. Manual nameContents
W489
(this manual)
W484CompoNet Analog I/O
W456CS/CJ-series CompoNet
W457CompoNet Slave Units and
CompoNet Gateway Unit
for CC-Link Operation
Manual
Slaves with Numerical Indicator Operation Manual
Master Unit Operation
Manual
Repeater Unit Operation
Manual
Specifications and wiring procedures for the GQ-CRM21
CompoNet Gateway Unit for CC-Link.
Specifications for the CRT1-VAD02SD, CRT1VAD02MLD, CRT1-VDA02SD, and CRT1-VDA02MLD
CompoNet Analog I/O Slaves.
CompoNet network overview, communications specifications, and wiring procedures for CS/CJ-series CompoNet Master Units.
Specifications for CompoNet Slaves Units and Repeater
Units.
16
CompoNet Gateway Unit for CC-Link Operation Manual
Table of Contents
About this Manual .......................................................................................................................... 1
Using this Manual .......................................................................................................................... 2
Read and Understand this Manual ................................................................................................ 4
The GQ-CRM21 CompoNet Gateway Unit for CC-Link provides one CC-Link port and one CompoNet
1-1 Overview
CC-Link Master Unit
port. It cyclically transfers I/O data between the CompoNet Slave Units and the CC-Link Master Unit.
The GQ-CRM21 CompoNet Gateway Unit for CC-Link is referred to as the “Gateway Unit” in this manual.
CC-Link Network
Refer to CC-Link documentation from Mitsubishi Electric Corporation
or other sources for details on CC-Link.
Remote
stations
Repeater
Unit
Gateway Unit
In the CC-Link system, the Gateway Unit
is set as a remote device station with a
4-station allocation.
Slave Units
Slave Units
CompoNet Network
Refer to the CompoNet Slave Unit and Repeater Unit Operation Manual
(Cat. No. W457) for the specifications of CompoNet networks.
Refer to documentation for individual Slave Units and Repeater Units for
details on those Units.
Gateway Unit settings and wiring are
described later in this manual.
1 - 1
CompoNet Gateway Unit for CC-Link Operation Manual
Overview
1-1-2 Gateway Unit Features
A Gateway Unit can be used to take advantage of CompoNet features to simplify wiring.
z A Selection of Communications Cables
The following communications cables can be used with CompoNet systems: Round Cable I
(2-conductor), Round Cable II (4-conductor), Flat Cable I (standard), and Flat Cable II (sheathed).
Note: Refer to the CompoNet Slave Unit and Repeater Unit Operation Manual (Cat. No. W457) for details on
cable types.
z Multinode Connections
CompoNet systems can be used for multinode, high-density remote I/O communications.
Maximum I/O capacity:2,560 points
Maximum nodes:384 nodes per Gateway Unit
Up to 6,144 CompoNet Slave Units can be connected to a CC-Link Master Unit. (Communications
mode 4 must be set.)
z Bit-level Distribution
CompoNet Slave Units with industry-standard e-CON connectors, clamping terminal blocks, or small
connectors can be used to distribute I/O at the bit level. This enables distributed control in distributed
devices, such as sensors and other devices located over a wide area on conveyors or in warehouses.
1
1-1-2 Gateway Unit Features
z Easy Installation and Setup
CompoNet systems can be easily installed and set up.
• Seven-segment Display
The number of connected CompoNet Slave Units is shown on the seven-segment display.
This enables easily checking system operation.
• Participation Flags and Communications Error Flags
The network participation status of CompoNet Slave Units can be checked at the PLC.
When a CompoNet Slave Unit joins the network, a Participation Flag that corresponds to the node
address of the Unit turns ON. If a CompoNet Slave Unit that was participating in the network is
disconnected from the network, a Communications Error Flag that corresponds to the node
address of the Unit turns ON. (Communications mode 0 to 3 must be set.)
• Automatic Baud Rate Detection
The CompoNet Slave Units will automatically detect and use the baud rate that is set in the Gateway Unit. Setting the baud rate is not necessary for any of the CompoNet Slave Units.
z Repeater Units for Greater Flexibility
Repeater Units can be used in a CompoNet network to enable the following network expansions.
• Extending the cable length
• Increasing the number of nodes
• Branching from the trunk line
• Changing the type of cable
Repeater Units can be used to extend up to two segment layers (called sub-trunk lines) from the
trunk line. Up to 64 Repeater Units can be connected per Gateway Unit and up to 32 Repeater Units
can be connected per segment.
Note: Supply communications power to a sub-trunk line from the Repeater Unit.
Refer to the CompoNet Slave Unit and Repeater Unit Operation Manual (Cat. No. W457) for detailed wiring methods.
CompoNet Gateway Unit for CC-Link Operation Manual
1 - 2
z Easy Maintenance with Complete System Monitoring Functions
1
1-1 Overview
The CompoNet Network is constantly monitored to enable confirming system safety by quickly identifying errors and checking communications status.
• Gateway Unit Detection of Network Participation, Errors, and Status
When a CompoNet Slave Unit joins the network, a Participation Flag that corresponds to the node
address of the Unit turns ON. If a CompoNet Slave Unit that was participating in the network is
disconnected from the network, a Communications Error Flag that corresponds to the node
address of the Unit turns ON.
Network status, such as communications errors and duplicated Slave Unit node addresses, and
Slave Unit diagnostic results are detected by the Gateway Unit and displayed on the seven-segment display on the front panel and reflected in the Status Flags. (Communications mode 0 to 3
must be set.)
• Registration Table
A table of the Slave Units that should be participating at the nodes (including the node addresses
and corresponding Slave Unit model numbers) can be registered to verify the Slave Units actually
participating in the network and prevent unregistered Slave Units from participating in the network.
• Communications Status on Gateway Unit Seven-segment Display
The seven-segment display on the front of the Gateway Unit can be used to check communications status. The number of connected nodes is normally displayed, but if an error occurs, the
error code is displayed in hexadecimal and the error node address is displayed in decimal.
1 - 3
CompoNet Gateway Unit for CC-Link Operation Manual
*1 A baud rate of 4 Mbps is not supported for branch lines and thus cannot be used for
Slave Units with Cables.
ModulationBaseband
CodingManchester code
Error controlManchester code rules, CRC
Communications mediaRound Cable I (2-conductor cable, JIS C3306)
Round Cable II (4-conductor cable, JIS C3306)
Flat Cable I (DCA4-4F10 Standard Flat Cable)
Flat Cable II (DCA5-4F10 Sheathed Flat Cable)
Communications
distance
Maximum I/O capacityWord Slave Units: 1,024 inputs and 1,024 outputs (2,048 I/O points total)
Baud rateMax.
segment
length
4 Mbps*30 m
3 Mbps*30 m
1.5 Mbps
(Round
Cable I)*
1.5 Mbps (Round
Cable II or Flat
Cable I/II)
93.75 kbps (Round
Cable I)
93.75 kbps (Round
Cable II or Flat
Cable I/II)
No
branches
Branches 30 m
(90 m)
(90 m)
100 m
(300 m)
(90 m)
30 m
(90 m)
500 m
(1,500 m)
Unrestricted wiring is enabled for a total length of 200 m per segment.
Bit Slave Units: 256 inputs and 256 outputs (512 I/O points total)
Branch
length per
segment
0 m0 m------------
0.5 m8 m3 branches/m 10 m0 m
2.5 m25 m3 branches/m 3------
2.5 m25 m3 branches/m 30.1 m2 m
6 m120 m3 branches/m 3------
To t al
branch
length per
segment
------------------
Branch
location
restriction
Connected
nodes per
branch
Max. subtrunk length
per segment
Total subtrunk length
per segment
When the Gateway Unit is used, I/O capacities are as follows depending on the CompoNet
communications mode.
Max. number of connected
nodes
Max. number of connected
nodes per trunk line or sub-trunk
line
Communications
mode 0 or 4
Word Slave
Units
Bit Slave Units
Word Slave Units: 64 input nodes and 64 output nodes
Bit Slave Units: 128 input nodes and 128 output nodes
When the Gateway Unit is used, the maximum number of connected nodes is as follows
depending on the CompoNet communications mode.
Word
Slave
Units
Bit Slave
Units
32 nodes (number of Slave Unit and Repeater Unit nodes)
1,024 inputs and
1,024 outputs
256 inputs and
256 outputs
Communications
mode 0 or 4
IN0 to IN63 and
OUT0 to OUT63
IN0 to IN127 and
OUT0 to OUT127
Communications
mode 1 or 5
512 inputs and
512 outputs
192 inputs and
192 outputs
Communications
mode 1 or 5
IN0 to IN31 and
OUT0 to OUT31
IN0 to IN95 and
OUT0 to OUT95
* Lengths given in parentheses are for when two Repeater Units are used.
Communications
mode 2 or 6
256 inputs and
256 outputs
96 inputs and 96
outputs
Communications
mode 2 or 6
IN0 to IN15 and
OUT0 to OUT15
IN0 to IN47 and
OUT0 to OUT47
Communications
mode 3
128 inputs and
128 outputs
32 inputs and
32 outputs
Communications
mode 3
IN0 to IN7 and
OUT0 to OUT7
IN0 to IN15 and
OUT0 to OUT15
2 - 3
CompoNet Gateway Unit for CC-Link Operation Manual
Description of Gateway Unit
2-2Component Names and Functions
The Gateway Unit is separated into sections, one for CC-Link communications and one for CompoNet
communications.
Station number switchSets the station number of the Gateway Unit on
Baud rate DIP switchSets the baud rate of the Gateway Unit on the
CC-Link communications
connector
CompoNet
communications
section
CompoNet communications
indicators
CompoNet seven-segment
display
Mode switchSets the CompoNet communications mode. 2-2-2 Switch
CompoNet DIP switchEnables or disables the baud rate setting and
CompoNet setting buttonsCreates the registration table on the CompoNet
CompoNet communications
connector
Power connectorConnects to the power supply for the Gateway
Mode switch
124
GQ-CRM21
CompoNet DIP switch
SDNSMS
.
RD
REG
REGIST RESET
DR0
DR1
DCN
REGS
CompoNet communications
connector
.
8 8
CompoNet sevensegment display
CompoNet
communications
indicators
CompoNet
setting buttons
Used to check CC-Link data link status. 2-2-1
Indications
2-2-2 Switch
the CC-Link network.
Settings
2-2-2 Switch
CC-Link network.
Settings
Connects to the CC-Link cable. 2-2-3 Terminal
Arrangement
Used to check the communications status of
CompoNet remote I/O.
Normally shows the number of connected
CompoNet Slave Units. An error code is
2-2-1
Indications
2-2-1
Indications
displayed if a communications error occurs.
Settings
2-2-2 Switch
registration table on the CompoNet network.
Settings
2-2-2 Switch
network, resets the Gateway Unit, etc.
Settings
Connects the CompoNet network cable. 2-2-3 Terminal
Arrangement
2-2-3 Terminal
Unit.
Arrangement
2
CompoNet Gateway Unit for CC-Link Operation Manual
2 - 4
2-2-1 Indications
Indications of both CompoNet and CC-Link status are provided on the Gateway Unit.
2
2-2 Component Names and Functions
CompoNet Communications Section
z CompoNet Communications Indicators
The following LED indicators are provided for CompoNet communications.
MS (Module Status): Shows the status of the node itself (two colors: green and red).
NS (Network Status): Shows the status of communications (two colors: green and red).
SD (Send Data):Shows the transmission status from the Gateway Unit to CompoNet (one
color: yellow).
RD (Receive Data):Shows the reception status from CompoNet to the Gateway Unit (one color:
yellow).
REG (Registration):Shows if the registration table is enabled or disabled (one color: green).
IndicatorStatusStatus definitionMeaning
MSLit greenNormalThe Unit is operating normally.
Lit redFatal errorUnit hardware error, such as a watchdog timer error
(WDT)
Not litPower OFF/PreparingPower OFF, resetting, or initializing
NSLit greenOnline with remote I/O
communications in
progress
Flashing
green
Online with no remote I/O
communications in
progress
Power is being supplied, remote I/O communications have
started, there are no communications errors at any Slave
Unit or Repeater Unit, there are no registration table
errors, and there are no node address duplication errors
for Slave Units or Repeater Units.
Remote I/O communications have not started or have
stopped.
Flashing
red
Not litPower OFF/PreparingPower OFF, resetting, or initializing
SDLit yellowNormal transmissionFrames are being sent normally from the Gateway Unit to
Not litNo transmissionData is not being sent by the Gateway Unit
RDLit yellowNormal receptionFrames are being received normally from CompoNet
Not litNo receptionData is not being received by the Gateway Unit.
REGLit greenRegistration table enabled The registration table has been created and is enabled.
Flashing
green
Not litRegistration table
Non-fatal communications
error
Registration table creation The registration table is being created.
disabled
A communications error has occurred at one or more
Slave Units or Repeater Units.
A verification error (non-existent or unregistered Slave
Unit) has occurred at one or more Slave Units.
Communications have stopped due to a communications
error, an illegal configuration error (number of Repeater
Units) has occurred, or an address duplication error has
occurred at one or more Slave Units or Repeater Units.
CompoNet.
Slave Units.
The registration table has been created.
The registration table is disabled or has not been created.
2 - 5
CompoNet Gateway Unit for CC-Link Operation Manual
Loading...
+ 73 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.