Advanced Digital Temperature Controller
96 × 96 mm
E5AN-H
48 × 96 mm
E5EN-H
For the most recent information on models that have been certified fo
safety standards, refer to your OMRON website.
E5AN-HSS@-500, E5EN-HSS@-500 in this catalog have
been discontinued at the end of March 2018.
Refer to Safety Precautions for E5@N/E5@N-H.
Refer to Operation for E5@N/E5@N-H for operating
procedures.
• Auto/manual switching
• Temperature Controller
status display
• Simple program
function
• Logic operations
• Control output ON/OFF
count alarm
• PV change rate alarm
• Models available with
RS-485, RS-422, or
RS-232C
communications
Event Inputs
• None
• Two
• Four
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
(current/voltage) inputs.
Indication Accuracy
• Thermocouple/Pt input:
±0.1% of PV
• Analog input:
±0.1% FS
Sampling Period
• 60 ms
PF Key
(Programmable
key function)
Auxiliary Outputs
• Two
• Three
Remote SP Input
• One
3-level Display
Simultaneously displays set items, such as the
PV, SV, and MV.
5-digit Display with high resolution of 0.01°C
Infrared port
E5AN-H E5EN-H
Computer Support Software
CX-Thermo
USB
Control Output 1
(built-in)
• SSR outputs *
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
Control Output 2
(built-in)
• SSR outputs *
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
* Orders will not be accepted after
March 31, 2018.
E5AN-H/E5EN-H
(96 x 96 mm and 48 x 96 mm)
A New High-performance Controller: High Resolution, High Speed, and
High Input Accuracy.
Logic Operations and Preventive Maintenance Function. Plus Infrared
Port on Front Panel.
• High-resolution display with 5 digits/0.01°C display.
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog
input) to handle various sensors with one Controller. Models
also available with Remote SP.
A PV/SV-status display function can be set to automatically alternate
•
between displaying the status of the Temperature Controller (auto/
manual, RUN/STOP, and alarms) and the PV or SV.
• Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo Ver. 4.0)
• Preventive maintenance for relays in the Temperature
Controller using a Control Output ON/OFF Counter.
• Model available with position-proportional control
CSM_E5AN-H_E5EN-H_DS_E_3_13
Main I/O Functions
1
Lineup
1 23456789 1110
E5AN/E5EN-@@@@@@@M@-@-500
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
E5AN-H/E5EN-H
E5AN-H/E5EN-H
Advanced Type
Note: The Controller can be used for heating/cooling control even if only 1 control output is used.
Terminal block
Fully universal input
Model Number Structure
Model Number Legend
Controllers
1. Type
H: Advanced
2. Control Mode
Blank: Standard or heating/cooling control
P: Position-proportional control
3. Control Output 1
A: Control Output Unit
R: Relay output
S: SSR output *
4. Control Output 2
A: Control Output Unit
R: Relay output
S: SSR output *
5. Auxiliary Outputs
2: Two outputs
3: Three outputs
6. Option 1
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
7. Option 2
B: Two event inputs
BF: Event input + Transfer output
8. Option 3
M: Option Unit can be mounted.
9. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
10.Case Color
Blank: Black
W: Silver
11.Terminal Cover
-500: With Terminal Cover
Option Units
1. Function
EN01: RS-232C communications
EN02: RS-422 communications
EN03: RS-485 communications
AKB: Event input
Output Units
1. Control Output
R: Relay output
Q: Voltage output (for driving SSR)
Q3: Voltage output (for driving SSR) + 24 VDC (NPN)
Q4: Voltage output (for driving SSR) + 24 VDC (PNP)
C3: Current output + 4 to 20 mA DC
C3D: Current output + 0 to 20 mA DC
V34: Linear voltage output + 0 to 10 VDC
V35: Linear voltage output + 0 to 5 VDC
2. Version
Blank: Available for E5AN-E5EN-H.
N: Available only for E5AN-H/E5EN-H.
1 control output
2 control outputs
2 auxiliary outputs
2 auxiliary outputs
* Orders will not be accepted after March 31, 2018.
2
Ordering Information
E5AN-H
Power
Case
Size
1/4 DIN
96 × 96 × 78
(W × H × D)
color
Black
Silver
supply
voltage
100 to
240 VAC
24 VAC/
VDC
100 to
240 VAC
24 VAC/
VDC
* Orders will not be accepted after March 31, 2018.
Control
method
Basic
Valve 2
Basic
Valve 2
Basic 2
Auxiliary
output
2
3
2
3
Control Output Unit × 21 2
SSR outputs × 212
Control Output Unit × 22 2
SSR outputs × 222
Control Output Unit × 22
SSR outputs × 22
Relay outputs × 22
Relay outputs × 22
Control Output Unit × 21 2
SSR outputs × 212
Control Output Unit × 22 2
SSR outputs × 222
Control Output Unit × 22
SSR outputs × 22
Relay outputs × 22
Relay outputs × 22
Control Output Unit × 21 2
Control Output Unit × 22 2
Control Output Unit × 21 2
Control output 1/2
Heater
burnout
Optional functions
Event
inputs
Transfer
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
output
RSP
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
E5AN-H/E5EN-H
Model
E5AN-HAA2HBM-500
E5AN-HSS2HBM-500 *
E5AN-HAA2HHBFM-500
E5AN-HSS2HHBFM-500 *
E5AN-HAA3BFM-500
E5AN-HSS3BFM-500 *
E5AN-HPRR2BM-500
E5AN-HPRR2BFM-500
E5AN-HAA2HBMD-500
E5AN-HSS2HBMD-500 *
5AN-HAA2HHBFMD-500
E
E5AN-HSS2HHBFMD-500 *
E5AN-HAA3BFMD-500
E5AN-HSS3BFMD-500 *
E5AN-HPRR2BMD-500
E5AN-HPRR2BFMD-500
E5AN-HAA2HBM-W-500
E5AN-HAA2HHBFM-W-500
E5AN-HAA2HBMD-W-500
3
E5EN-H
Size
1/8 DIN
48 × 96 × 78
(W × H × D)
Case
color
Black
Silver
* Orders will not be accepted after March 31, 2018.
Power supply
voltage
100 to 240 VAC
24 VAC/VDC
100 to 240 VAC
24 VAC/VDC Control Output Unit × 21 2
Control
method
Basic
Valve 2
Basic
Valve 2
Basic 2
Auxil-
output
2
3
2
3
Control output 1/2
iary
Control Output Unit × 21 2
SSR outputs × 212
Control Output Unit × 22 2
SSR outputs × 222
Control Output Unit × 22
SSR outputs × 22
Relay outputs × 22
Relay outputs × 22
Control Output Unit × 21 2
SSR outputs × 212
Control Output Unit × 22 2
SSR outputs × 222
Control Output Unit × 22
SSR outputs × 22
Relay outputs × 22
Relay outputs × 22
Control Output Unit × 21 2
Control Output Unit × 22 2
Heater
burn-
out
Optional Functions
Event
inputs
Transfer
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
4 to 20-mA
output
E5AN-H/E5EN-H
RSP
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
4 to 20-mA
input
E5EN-HAA2HBM-500
E5EN-HSS2HBM-500 *
E5EN-HAA2HHBFM-500
E5EN-HSS2HHBFM-500 *
E5EN-HAA3BFM-500
E5EN-HSS3BFM-500 *
E5EN-HPRR2BM-500
E5EN-HPRR2BFM-500
E5EN-HAA2HBMD-500
E5EN-HSS2HBMD-500 *
N
-HAA2HHBFMD-500
E5E
E5EN-HSS2HHBFMD-500
E5EN-HAA3BFMD-500
E5EN-HSS3BFMD-500 *
E5EN-HPRR2BMD-500
E5EN-HPRR2BFMD-500
E5EN-HAA2HBM-W-500
E5EN-HAA2HHBFM-W-500
E5EN-HAA2HBMD-W-500
Model
*
Accessories (Order Separately)
Output unit Model Specifications
Relay
output
Voltage
output
(for driving
SSR)
Current
output
Linear
E53-RN
E53-QN
E53-Q3
E53-Q4
E53-C3N
E53-C3DN
E53-V34N
voltage
output
E53-V35N
USB-infrared Conversion Cable
USB-Serial Conversion Cable
SPST-NO, 250 VAC, 5 A (resistive load),
electrical life: 100,000 operations
12 VDC (PNP), max. load current:
40-mA, with short-circuit protection
24 VDC (NPN), max. load current:
20-mA, with short-circuit protection
24 VDC (PNP), max. load current:
20-mA, with short-circuit protection
4 to 20-mA DC, load: 600 Ω max.,
resolution: approx. 10,000
0 to 20-mA DC, load: 600 Ω max.,
resolution: approx. 10,000
0 to 10 VDC, load: 1 kΩ min., resolution:
approx. 10,000
0 to 5 VDC, load: 1 kΩ min., resolution:
approx. 10,000
Model
E58-CIFIR
Model
E58-CIFQ1
Terminal Cover
Connectable models Model
E5AN-H
E5EN-H
E53-COV16
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
Mounting Brackets
Model
Y92H-9
Note:
These Mounting Brackets are provided with the Digital Controller.
Waterproof Packing
Connectable models Model
E5AN-H Y92S-P4
E5EN-H Y92S-P5
Note: The Waterproof Packing is included with the Controller.
Current Transformers (CTs)
Hole diameter Model
5.8 dia. E54-CT1
12.0 dia. E54-CT3
CX-Thermo Support Software
Model
EST2-2C-MV4
4
E5AN-H/E5EN-H
Specifications
Ratings
Power supply voltage
Operating voltage range 85% to 110% of rated supply voltage
Power consumption
Sensor input
Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB-N.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
Relay output
Voltage output
(for driving SSR)
Control
output
Auxiliary
output
Event
input
Logic
operations
Transfer
outputs
RSP
input
Setting method Set digitally using keys on the front panel or by using the RSP input.
Indication method
Bank switching
Other functions
Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
Ambient operating humidity 25% to 85%
Storage temperature −25 to 65°C (with no condensation or icing)
Current output
Linear voltage output
Relay output for
position-proportional
control
Number of outputs 2 or 3 max.
Output specifications
Number of outputs 2 or 4 (with an E53-AKB)
External contact input
specifications
Number of operations 8 max.
Operations
Output One work bit per operation
Work bit
assignment
Number of outputs 1 max. (Depends on model. Models with transfer output (F in model number)
Output specifications Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000
Number of inputs 1
Signal type Current input: 4 to 20 mA (input impedance: 150 Ω ±10%)
Analog input scaling
Accuracy (±0.2% of FS) ±1 digit max.
Input sampling period 60 ms
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Output Unit (Install the Output Unit (sold separately).)
Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations min.
Potentiometer input: Must be between 100 Ω and 2.5 kΩ for maximum open position.
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
10 mA
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
• Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
• Delay: ON delay or OFF delay for the results of the logic operation given above.
• Output inversion: Possible
Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary
outputs, or control outputs.
Scaling of signal to engineering units (EU)
−19,999 to 30,000 (display: 30,000 max.)
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain
Number of digits: 5 for PV and SV, 4 for MV
Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40%
AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output
ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling
coefficient adjustment
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D
(A, B, C, and D are four inputs.)
Setting time: 0 to 9999 s or 0 to 9999 min
5
Input Ranges
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs)
Input
type
Name Pt100 JPt100 K J T E L U N R S B W
Temperature range (°C)
−100.0
−200.0
Setting
number
Platinum resistance
thermometer
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
850.0 850.0 850.0
900
800
700
600
500.0 500.0 500.0
500
400
300
200
100
0
−200.0−199.9 −199.9 −200.0 −200.0−199.9 −200.0 −200.0 −199.9−200.0
200.00 200.00 200.00 200.00
100.0 100.0
0.0 0.0 0.0 0.0 0.0 0.0
−50.00 −20.0 −50.00 −100.0 −20.0 −50.00 −50.00 −100.0
1300.0 1300.0 1300.0
400.0 400.0 400.0 400.0 400.0
Thermocouple Analog input
1800.0
1700.01700.0
600.0
100.0
01224345 6 21 7 8 22 9 102311121314151617181920 25 26 27 28 29
E5AN-H/E5EN-H
4 to
0 to
20 m
A
1 to 5V0 to 5V0 to
20 m
A
Usable in the following
ranges by scaling:
−19999 to 32400,
−1999.9 to 3240.0,
−199.99 to 324.00, or
−19.999 to 32.400
2300.0
PL
II
10 V
6