Compact, 1⁄16 DIN Size, with NEMA 2, 3R,
and 12 Rated Front Panel.
Page 2
CN76030, compact
1
⁄16 DIN size, $494,
shown actual size.
Status LEDs indicate
status of setpoint
and alarm outputs.
°F/°C engineering units.
Both indicators are off for
non-temperature inputs.
INDEX key advances
menu for programming.
Also used with
decrement key to
reset an alarm
programmed for
manual reset.
Increment key raises
value or turns “on”
menu item chosen.
Also used with ENTER
key to display secondary
and secure menus.
Convenient screw terminal connections.
Upper display
continuously indicates
process value or value
of menu item selected.
Lower display
continuously indicates
set value or menu item
selected.
ENTER key enters new
settings or commands
into memory. Also
used with the
increment key to
display other menus.
Decrement key lowers
value or turns “off”
menu item chosen.
Also used with INDEX
key to reset an alarm
programmed for
manual reset.
The CN76000 1⁄16 DIN controllers provide economical
control for a wide variety of processes, including
heating, cooling, and heat/cool. When used with the
proper transmitters, these devices can also control
pressure, flow, humidity, motion, or pH. The front
panel is NEMA 2, 3R, and 12 rated for waterproof
protection and is corrosion resistant.
The sophisticated design of the CN76000 incorporates
the latest microprocessor and surface mount
technology, compressing an unprecedented number of
standard features into a compact 1⁄16 DIN package. The
user can program control functions from the front
panel; input types are DIP switch selectable. Multiple
tuning modes allow the user to select from 3 standard
tuning presets, manual tuning, or autotuning.
P
Standard features include self-diagnosis with fault
indication. Non-volatile memory retains all process
parameters when power is off, without battery backup.
Settings for the optional alarm are configurable. The
alarm action may be defeated on startup, or until the
process value exceeds the alarm setpoint. The power
interrupt feature will reset on power-up if the alarm
condition no longer exists.
Other standard features include min/max storage and
display, auto/manual control, percent output indication,
ramp and soak operation, 4 user-selectable security
levels with password protection, and jumper-selected
5 Vdc pulse output to drive external solid state relays.
Optional features include RS485 communications,
process recorder output, and 4-stage setpoint.
P-2
Page 3
OF F
AL
OF F
OF F
OF F
ENTER INDEX
A1
A2
MADE IN US A
PV
SV
48
(1.880)
48
(1.880)
125 (4.925)
1 14 (4.475)
12
(0.450)
*3
(0.125)
45
(1.760)
Panel cutout for all models is 45 x 45 mm (1.775 x 1.775").
Allow for 13 mm (0.5") clearance at rear of instrument.
* Present for all outputs other than relay.
12
1161
2
V
mA
3
4
5131410
9
10
9
8
77
–
+
8
+
–
7
8
+
RTD
T/C
+
–
ALARM
(IF EQUIPPED)
1/4 A
3 AG 250 Vac
Line
85 to 265 Vac/Vdc
50 to 400 Hz
5 V max
*SOFTWARE CONFIGURABLE
ASSP1 OR SP2
FOR OUTPUT RATINGSSEE
SPECIFICATIONS.
SOLID STATE
RELAYOR
RELAYOUTPUT
5 Vdc
LOGIC
OUTPUT
OUTPUT B*
SOLID STATE
RELAYOR
RELAYOUTPUT
5 Vdc
LOGIC
OUTPUT
4 to 20 mA DC
or
0 to 10 Vdc
–
AUX
IN/OUT
OUTPUT A *
Specifications
Inputs: Thermocouple, RTD,
voltage or current; see input chart
for ranges
Resolution: See range chart;
voltage and current input models
are fully field scalable to
engineering units with up to
2 decimal places
Error message is initiated on
shorted sensor or open heater
circuit; break time adjustable from
off to 99 min.
Loop Break Alarm: On alarm relay
equipped units, unit can be
programmed to alarm on loop break
LED, 7.6 mm (0.3") high; process
variable in red, setpoint in green
Control Action: Reverse (heat) or
direct (cool) action; selectable for
single or dual setpoint models
Control Modes: Time-proportioning
and proportional control modes;
selectable preset tune, autotune or
manual PID, P, PI or PD with reset
anti-windup
Proportional Band: 6 to 5000°F
or equivalent °C units; 6 to 9990 for
voltage/current inputs
Integral Time:
0.1 to 99.9 minutes, or off
Derivative Time:
0.01 to 99.99 minutes, or off
Cycle Time: 2 to 80 s
Approach Rate: Off to 99.99 min
On-Off Control: Adjustable on-off
differential 2° to full scale in
1° steps, 2 counts to full scale in
1-count steps (voltage/current inputs)
Ramp and Soak: One ramp time
and soak time each adjustable from
0 to 100 hours; end procedure can
be set for HOLD or OFF
Power:
85 to 265 Vdc or Vac, 50 to 400 Hz
Power Consumption: 5 VA max
Line Voltage Stability:
±0.05% over supply voltage range
Temperature Stability:
4 µV/°C (2.3 µV/°F) typical,
8 µV/°C (4.5 µV/°F) max
Common-Mode Rejection:
140 dB minimum at 60 Hz
Normal-Mode Rejection:
65 dB typical, 60 dB at 60 Hz
External Wiring
Dimensions:
mm (in)
Isolation: Relay and SSR outputs
are isolated; current, voltage and
logic outputs must not share
common grounds with the input
Memory:
Non-volatile; no batteries required
Mechanical Relay Output: SPST
(form A), 3 A @ 250 Vac, resistive;
1.5 A @ 250 Vac, inductive;
250 VA pilot duty rating,
2 A @ 125 Vac or 1 A @ 250 Vac,
1
⁄8 hp @ 125 Vac or 250 Vac
Solid State Relay Output: 3.5 A up
to 240 Vac at 25°C (77°F); derates
to 1.25 A @ 55°C (131°F)
Voltage Output:
Non-isolated; 0 to 10 Vdc, 500 Ω min
Current Output: Non-isolated;
0 to 20 mA, 600 Ω max; zero and
span adjustable
DC Pulse Output:
Non-isolated; 5 Vdc @ 25 mA
Operating Ambient: -10 to 55°C
(-4 to 131°F); 0 to 90% RH up to
40°C (104°F), non-condensing;
10 to 50% at 55°C (131°F),
non-condensing
P-3
Storage Ambient:
-40 to 80°C (-40 to 175°F)
Alarms: 2 alarms operate the same
relay; 3.0 A resistive 250 Vac;
form A contact (SPST); field
programmable for absolute
(non-tracking) or deviation
(tracking); can be set anywhere
within the scaling of the controller;
selectable inhibit and power
interrupt; automatic/manual reset
Process Signal Output (Optional):
Linearized, non-isolated
0 to 10 Vdc @ 5 mA; user-selectable
scale positioning of zero and full scale;
scaling span is 50 to 11,998 counts
RS485 Communications
(Optional): Unit with RS485
compatible communications
(no CE rating for RS485 option)
Dimensions: 48 H x 48 W x 125 mm D
(1.88 x 1.88 x 4.925");
115.3 mm (4.54") depth behind panel
Panel Cutout:
45 mm (1.775") square;
1
⁄16 DIN
Weight: 227 g (8 oz)
Front-Panel Ratings: NEMA 2,
3R and 12; dust and splash resistant
Page 4
Input Types and Ranges
Input TypeRangeResolutionRangeResolution
Iron-constantan
Iron-constantan DIN
CHROMEGA®-ALOMEGA
CHROMEGA®-constantan
Copper-constantan
OMEGALLOY
®
-100 to 1600°F1°F-73 to 87°C1°C
-100 to 990°F0.1°F-73 to 871°C0.1°C
-100 to 1600°F1°F-73 to 87°C1°C
-100 to 990°F0.1°F-73 to 871°C0.1°C
-200 to 2500°F1°F-129 to 137°C1°C
®
-190 to 990°F0.1°F-129 to 990°C0.1°C
-100 to 1800°F1°F-73 to 982°C1°C
-100 to 990°F0.1°F-73 to 990°C0.1°C
-350 to 750°F1°F-212 to 398°C1°C
-190 to 750°F0.1°F-212 to 398°C0.1°C
-100 to 2372°F1°F-73 to 1300°C1°C
nicrosil-nisil-100 to 990°F0.1°F-73 to 990°C0.1°C
Pt/13%Rh-Pt0 to 3200°F1°F-17 to 1760°C1°C
Pt/10%Rh-Pt0 to 3200°F1°F-17 to 1760°C1°C
Pt/6%Rh-Pt/30%Rh75 to 3308°F1°F24 to 1820°C1°C
W/5%Re-W/26%Re0 to 4208°F1°F-17 to 2320°C1°C
100 Ω Pt-328 to 1607°F1°F-200 to 875°C1°C
0 0385 curve-190 to 990°F0.1°F-190 to 875°C0.1°C
100 Ω Pt-328 to 1607°F1°F-200 to 875°C1°C
0 0392 curve-190 to 990°F0.1°F-190 to 875°C0.1°C
120 Ω Ni
-112 to 608°F1°F-80 to 320°C1°C
-112 to 608°F0.1°F-80 to 320°C0.1°C
Process Current0 to 20 mA, 4 to 20 mA
Process Voltage0 to 5 Vdc, 1 to 5 Vdc
† Voltage and current inputs are fully scalable for zero and span.
Maximum setting range is -1999 to 9999 counts.
MOST POPULAR MODELS HIGHLIGHTED!
Options
Ordering Add’l
SuffixPrice Description
-PV$93
-485A**115 RS485
Note: Only 1 option may be installed in a unit.
No CE rating for -485A option.
**
Scalable recorder;
output 0 to 10 Vdc
communications
To Order (Specify Model Number)
Single Output Models
Model No.PriceOutput
CN76(*)30$494Relay/DC Pulse
CN76(*)20494DC pulse/AC SSR
CN76(*)505130 to 20 mA
CN76(*)605130 to 10 Vdc
Comes complete with mounting bracket and operator's manual.
Specify 0 for standard unit, 1 for alarm unit; for alarms, add $35 to price.
*
†† These outputs are logic jumper selectable between relay and DC pulse, or between DC
pulse and AC SSR.
Ordering Example: CN76030-485A, CN76000 controller with single relay/DC pulse output
and optional RS485 communications, $494 + 115 = $609.
†
†
††
††
Recommended Reference Book:
Controller Tuning PID Without Math,
GE-2117, $23. Visit omega.com/bobi
for Additional Books.
Accessories
Model No.PriceDescription
1
DPP-4$475
CNQUENCHARC
⁄
16 DIN panel punch
10Noise suppression kit for mechanical relay models driving AC contactors
or solenoids
Dual Output Models
Model No.PriceOutput 1Output 2
CN76(*)33$534 Relay/DC pulse
CN76(*)22534 DC pulse/AC SSR
††
Relay/DC pulse
††
DC pulse/AC SSR
CN76(*)53554 0 to 20 mARelay/pulse
CN76(*)63554 0 to 10 VdcRelay/DC pulse
Specify 0 for standard unit, 1 for alarm unit; for alarms, add $45 to price.
*
†† These outputs are logic jumper selectable between relay and DC pulse, or between DC
pulse and AC SSR.
Ordering Example: CN76133-485, CN76000 controller with dual relay/DC pulse outputs,
alarms and optional RS485 communications, $579 + 115 = $694.
Calibrators, Connectors, General Test and Measurement
Instruments, Glass Bulb Thermometers, Handheld Instruments
for Temperature Measurement, Ice Point References,
Indicating Labels, Crayons, Cements and Lacquers, Infrared
Temperature Measurement Instruments, Recorders Relative
Humidity Measurement Instruments, RTD Probes, Elements
and Assemblies, Temperature & Process Meters, Timers and
Counters, Temperature and Process Controllers and Power
Switching Devices, Thermistor Elements, Probes and
Assemblies,Thermocouples Thermowells and Head and Well
Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level
Measurement, Magnetic Flowmeters, Mass Flowmeters,
Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel
Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area
Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen
Instrumentation, Environmental Instrumentation, pH
Electrodes and Instruments, Water and Soil Analysis
Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems,
Communication Products and Converters, Data
Acquisition and Analysis Software, Data Loggers
Plug-in Cards, Signal Conditioners, USB, RS232, RS485
and Parallel Port Data Acquisition Systems, Wireless
Transmitters and Receivers
Band Heaters, Cartridge Heaters, Circulation Heaters,
Comfort Heaters, Controllers, Meters and Switching
Devices, Flexible Heaters, General Test and Measurement
Instruments, Heater Hook-up Wire, Heating Cable
Systems, Immersion Heaters, Process Air and Duct,
Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
click here to go to the omega.com home page
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.