Thank you very much for choosing Omega Engineering Series CN7500/CN7800 Temperature/Process Controller.
Please read this instruction sheet before using your controller to ensure proper operation and please keep this
instruction sheet handy for quick reference.
1 Precaution
DANGER!Caution! Electric Shock!
1. Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2. Make sure the power is disconnected while checking the unit inside.
3. The symbol
REINFORCED INSULATION (equivalent to Class II of IEC 536).
WARNING!
Mount the controller in a location that will not be subject to excessive temperature, shock, or vibration.
All models are designed for mounting in an enclosed panel.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm
(6.0mm for 32B Series), hole diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Screw
size for 32B Series: M3 x 4.5 (With 6.0 x 6.0 square washer). Recommended tightening torque: 0.4 N.m
(4kgf.cm). Applicable wire: Solid/twisted wire of 2 mm
properly.
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3. Never modify or disassemble the controller.
4. Do not connect anything to the “No used” terminals.
5. Make sure all wires are connected to the correct polarity of terminals.
6. Do not install and/or use the controller in places subject to: Dust or corrosive gases and liquid, high humidity
and high radiation, vibration and shock, high voltage and high frequency
7. Power must be off when wiring and changing a temperature sensor.
8. Be sure to use compensating wires that match the thermocouple types when extending or connecting the
thermocouple wires.
9. Please use wires with resistance when extending or connecting a platinum resistance sensor (RTD).
10. Please keep the wire as short as possible when wiring a platinum resistance sensor (RTD) to the controller
and please route power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature,
humidity, dripping water, corrosive materials, airborne dust and electric shock or vibration.
12. Please make sure power cables and signals from instruments are all installed properly before energizing the
controller, otherwise serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to
prevent an electric shock.
indicates that this Controller is protected throughout by DOUBLE INSULATION or
2
, 12AWG to 24AWG. Please be sure to tighten them
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not
touch any internal circuit within this period.
15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required,
install the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current
1 A. Fuse type: Time-lag fuse
17. Note: This controller does not provide overcurrent protection. Use of this product requires that suitable
overcurrent protection device(s) must be added to ensure compliance with all relevant electrical standards
and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the
controller in the end-use installation.
2 Display, LED and Pushbuttons
displays process value
PV
displays setpoint value.
SV
INDEX: advances the display to the next menu item
UP ARROW: Increments a value or changes a menu item.
DOWN ARROW: Increments a value or changes a menu item.
Note: CN7500 Series does not support an additional alarm output, however, the user can set 2nd output as alarm mode.
ENTER: stores the value or item change.
3 Temperature Sensor Type and Temperature Range
Input Temperature Sensor Type Register Value LED Display Temperature Range
0 ~ 50mV Analog Input 17
4 ~ 20mA Analog Input 16
0 ~ 20mA Analog Input 15
0V ~ 10V Analog Input 14
0V ~ 5V Analog Input 13
Platinum Resistance (Pt100) 12
Platinum Resistance (JPt100) 11
Thermocouple TXK type 10
Thermocouple U type 9
Thermocouple L type 8
Thermocouple B type 7
Thermocouple S type 6
Thermocouple R type 5
Thermocouple N type 4
Thermocouple E type 3
Thermocouple T type 2
Thermocouple J type 1
Thermocouple K type 0
-999 ~ 9999
-999 ~ 9999
-999 ~ 9999
-999 ~ 9999
-999 ~ 9999
-200 ~ 600
-20 ~ 400
-200 ~ 800
-200 ~ 500
-200 ~ 850
100 ~ 1800
0 ~ 1700
0 ~ 1700
-200 ~ 1300
0 ~ 600
o
-200 ~ 400
-100 ~ 1200
-200 ~ 1300
o
o
C
o
o
o
o
o
o
C
C
o
C
C
C
C
C
o
C
o
o
C
C
C
C
Note 1: An internal precision resistor for the current input is built-in, please refer to item 15, How To Set Up Current Input.
Note 2:
type, allow the decimal point position to be specified.
The default range of analog input is -999 ~ 9999. For example, when a 0~20mA analog input is selected as the input
temperature sensor type, -999 indicates 0mA and 9999 indicates 20mA. If change the input range to 0 ~ 2000, then 0 indicates
0mA and 2000 indicates 20mA. One display scale is equal to 0.01mA.
(in the operation mode) specifies the decimal point position. All input types except thermocouple B, S, and R
4 Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, the controller
will default to the operation mode. Press the
than 3 seconds, the controller will switch to the initial setting mode. Pressing the key while in the
more
regulation mode or initial setting mode, forces the controller to return to the operation mode. PV/SV: Sets the
temperature set point and displays the temperature process value. Use
point.
Setting method: While in any function mode, press the
keys to change settings. Press key to save the changes. Menu items are listed below.
4 groups PID modes(n=0~3).When n=4,PID control isauto regulated.
Press
See PID Control Section
set temperature setpoint
Press
Press
See “Execution” under Section 6
key to switch to regulation mode. If the key is pressed for
keys to set the temperature set
key to select the desired function and use the
Use key to
Control setting RUN or STOP
donot display whenanalog input
Press
Press
Set input type
Set temperatureunit
PD control offset
(When PID control is ON andTi=0, set the value of PdoF.
Press
(SetinON/OFF control mode)
Press
(Set in ON/OFF control mode)
Press
(SetinPID control mode)
Press
(Set in PIDcontroland Dual Loop outputcontrol mode)
Press
setting
Heating hystereisissetting
Cooling hystereisissetting
or
Control cycle settingof 2nd output group
Heating/Coolingcontrol cyclesetting
Start pattern setting.
Appears only when
to
isset
Press
Set upper-limitoftemperature range
Decimal point position selection(except forB,S, Rtype, all the other typescan beset)
Press
Upper-limit alarm1
(This parameter is available only whenALA1 function enables)
Press
Press
pid, Prog, or manual. (Set to ProG for ramp/soak patterns) See Patternand set editing.
Set lower-limitoftemperature range
Sets Control Mode: on/off,
Lower-limit alarm 1
(This parameter is available only whenALA1 functionenables)
Press
Upper-limit alarm 2
(This parameter is available only whenALA2function enables)
Press
displayed when CtrL is set to ProG.
Ramp/soak pattern. Only
Select heating/coolingcontrolor dualloop output control
Press
P value of 1st & 2nd output groupduring dual loop outputcontrol
P value of 2nd output group =
Press
Lower-limit alarm 2
(Thisparameter is available onlywhen
x (P valueof 1st output group)
ALA2function enables)
Press
Press
Alarm 1mode setting
Dead Band (Setin DualLoopoutput controlmode)
Press
Regulate temperaturedeviation value
Press
Regulate upper-limitof analogoutput value
(The settingdisplaywhen analog output)Press
Regulate lower-limitofanalog
(The setting display when analogoutput)
Press
output value
to returntoauto-tuning mode
(This parameter is available only whenALA3 functionenables)
Press
(This parameter isavailable only whenALA3 function enables)
Press
Press
(Display in PID control mode and manual RUN mode)
Press
(Display in dual loop PID controlmode and manual RUN mode)
Press
Upper-limit alarm3
Lower-limit alarm3
Setting lock mode
Displayand adjust output valueof 1st output group
Display and adjust output valueof 2nd output group
Press
Press
Press
Press
Press
Press
Alarm 2 mode setting
Alarm3 mode setting
Set system alarm
Communication writefunctionenable/disable
ASCII, RTUcommunicationformat selection
Communication addresssetting
Communication baud
Press
rate setting
Data lengthsetting
Press
Parity bit setting
Press
Press toreturn input type setting
1 Scale = 2.8uA = 1.3mV for tuning output value
Stop bitsetting
5 PID Control
~: PIDn, n = 0 ~ 4, found in the regulation mode, four groups of user-defined PID settings and
an auto tuning function are available. Each group contains a set value, proportional band, integral time, derivative
time, and integral deviation settings (P, I, D, IOF) for PID control.
: n = 4, is the auto PID parameter. The controller will automatically select a most useful PID parameter
based on current temperature setting. Displayed SV values correspond to
~
~: is thetemperature setting which corresponds to the selected PID parameter via user-defined
or AT (auto-tuning).
After AT(auto-tuning) the values will be stored.
PID mode selection (regulation mode): any one of four PID modes (n=0~3) can be selected. When n=4, the unit
will perform auto-tuning.
Select n=0~4todecide PIDmode.
Press
0~3 groupsPID
PID setting: n=0.
Proportion band setting: n=0.
Press
Press
PID setting:n=3.
Proportion bandsetting: n=3.
Press
Press
Press
Ti setting: n=0.
Td setting: n=0.
Integral deviation setting: n=0.AT setting.
back toPID deviation setting
Press
Press
Press
Ti setting:n=3.
Td setting:n=3.
Integral deviation setting: n=3.AT setting.
back toPID deviation setting
Press
Press
6 Pattern and Set Editing (Ramp and Soak Programming)
Description of Function and Parameters Setting:
To set-up or edit the ramp/soak function,
immediately follow in the menu list.
The Ramp and Soak function is supported by 8 different patterns (Pattern No. 0 ~ 7). Each pattern contains 8
steps (step No. 0 ~ 7) for set point and execution time, one Link Pattern parameter, one Cycle parameter and one
Actual Step parameter.
The set point (SV) should reach temperature X after the execution time T. The default of step No. 0 is soak control.
The unit will control the temperature (PV) to reach the set point X and then keep the temperature at set point X.
The execution time T is determined by step No, 0.
The following display is an example of operation of pattern No. 0.