Wire your control following the instructions on page 5. If you are using a two-wire
2.
transmitter as an input, see the drawing and instructions on page 7. Option wiring
instructions are on page 6. Option descriptions are on page 4, and specific
instructions start on page 17.
Most controls do not need many (if any) program changes to work on your
3.
process. For best results when programming changes are necessary, make all
the necessary changes in the Secure Menu (page 26) before making changes to
the Secondary Menu (page 19). If error messages occur, check the Diagnostic
Error Messages on page 34 and 35 for help.
Take the example of a Series CN74000 that comes from the factory programmed for
type J thermocouples. Suppose for this example you wish to change the input to
type K and limit the set point range between 0° and 1000° C.
First, enter the Secure menu as instructed on page 5. Press the INDEX key until the
display shows Inp and press the DOWN ARROW until the display shows CA. Don't
forget to press the ENTER key to retain your setting.
Next, press the INDEX key to display Unit. Press the DOWN ARROW until the display shows C. Press ENTER.
Next, press the INDEX key until SPL is displayed (pass the dPt and InPt selections).
Press the UP ARROW until the display shows 0. Press ENTER.
Finally, press INDEX key to display SPH. Press the DOWN ARROW until the display
shows 1000. Press ENTER.
The necessary program changes are now complete. After 60 seconds the display will
switch back to the temperature reading. If you want to return faster, press the UP
ARROW and ENTER keys (at the same time) and then press the DOWN ARROW and
INDEX keys ( again at the same time). This will 'back out' of the menu and immediately display the temperature reading.
If you want to use Self T une®, Auto/Manual, or the Ramp/Soak Programmer features,
see the special sections on these items. Page numbers for these are in the Contents
section on the previous page.
Page 3
CN74
MODEL IDENTIFICATION
Alarm
0 = No
1 = Yes
Options:
C4RS-485 Serial Communications. Allows remote computer to read and write
all control parameters.
LV12-24 VDC/VAC 50-400 Hz power supply (control operates on low voltage
equipment).
Note:Only Option LV may be combined with another option. No other options
may be combined.
Output A
2 = 5 VDC
3 = Relay
Output B
0 = None
3 = Relay
Options
C4 = RS485
LV = Low Voltage
INSTALLATION
Mount the instrument in a location that will not be subject to excessive temperature,
shock, or vibration. All models are designed for mounting in an enclosed panel.
Select the position desired for the instrument on the panel. If more than one instrument is required, maintain the minimum of spacing requirements as shown on the
drawing opposite. Closer spacing will structurally weaken the panel, and invalidate
the IP66, UL type 4 rating of the panel.
Page 4
It is not necessary to remove the control chassis from the
housing for installation. If the control chassis is removed from
the housing, you must follow industry standard practice for
control and protection against Electro-Static Discharge (ESD).
Failure to exercise good ESD practices may cause damage to
the control.
Prepare the panel by cutting and deburring the required opening(s).
From the front of the panel, slide the housing through the cutout. The housing gasket should be flat against the housing flange before installing.
From the rear of the panel slide the mounting collar over the housing. Hold the
housing with one hand and using the other hand, push the collar evenly against
the panel until the spring loops are slightly compressed. The ratchets will hold the
mounting collar and housing in place. To remove,gently lift the ratchets and slide a
piece of heavy paper or mylar sheet under each ratchet (a business card works
well). Slide the collar off of the housing.
WIRING
Do not run thermocouple or other class 2 wiring in the same conduit as power
leads. Use only the type of thermocouple or RTD probe for which the control has
been programmed. Maintain separation between wiring of sensor, auxiliary in or
out, and other wiring. See the "Secure Menu" for input selection.
For thermocouple input always use extension leads of the same type designated
for your thermocouple.
For supply connections use No. 18 AWG wires rated for at least 75°C. Use copper conductors only. All line voltage output circuits must have a common disconnect and be connected to the same pole of the disconnect.
Input wiring for thermocouple, current, and RTD; and output wiring for current, DC
SSR, and 5 VDC is rated CLASS 2.
Page 5
Control wiring is as shown.
The wiring terminals for the CN74000
are compression type. To open the
wiring terminal, turn the screw for that
terminal counterclockwise. Slide the
wire into the terminal space. While
holding the wire in place, turn the
screw clockwise to tighten. Maximum
torque is 0.424 N•m (3.75 in lb). Do
not overtighten. The wire should be held snugly in place.
Wiring for Optional Inputs and Outputs
Wire power and outputs as shown on page 5 and 6. Wiring for options is shown
below. All wiring shown below is Class 2. Shielded twisted pair is r equired for Option
C4.
DO NOT RUN SIGNAL WIRING IN THE SAME CONDUIT OR
CHASE AS THE POWER WIRING. ERRATIC OPERATION OR
DAMAGE TO THE CONTROL CIRCUITRY WILL RESULT.
OPTION
C4
Note 1:
Last control in chain must have
120 ohm ±1% resistor across 5 and 6.
Page 6
Term. 5
Note 1
Terminal 5 is line A (-)
Terminal 6 is line B (+)
Term. 6
Wiring for 4 to 20mA Transmitter Inputs
Wire power and outputs as shown above. Two-wire transmitters wire as shown
below.
For three or four wire transmitters, follow the wiring instructions provided with your
transmitter.
DO NOT WIRE THE 24 VOLT POWER SUPPLY ACROSS THE
INPUT OF THE CONTROL. DAMAGE TO THE CONTROL INPUT
CIRCUITRY WILL RESULT.
Page 7
FRONT PANEL KEY FUNCTIONS
The decimal point flashes when Self-Tune is operating.
Keys are illuminated when pressed. Key functions are as follows:
INDEX: Pressing the INDEX key advances the display to the next menu
item. May also be used in conjunction with other keys as noted below.
UP ARROW: Increments a value, changes a menu item, or selects the item
to ON. The maximum value obtainable is 9999 regardless of decimal point
placement.
DOWN ARROW: Decrements a value, changes a menu item, or selects the
item to OFF. The minimum value obtainable is -1999 regardless of decimal
point placement.
ENTER: Pressing ENTER stores the value or the item changed. If not
pressed, the previously stored value or item will be retained. The display will
flash once when ENTER is pressed.
UP ARROW & ENTER: Pressing these keys simultaneously brings up the secondary menu starting at the alarm, tune, or cycle item (depending on programming).Pressing these keys for 5 seconds will bring up the secure menu.
INDEX & DOWN ARROW: Pressing these keys simultaneously will allow backing
up one menu item, or if at the first menu item they will cause the display to return to
the primary menu. If an alarm condition has occurred, these keys may be used to
reset the alarm. To reset an alarm press and hold both keys for three seconds.
INDEX & ENTER: Pressing these keys simultaneously and holding them for 5 seconds allows recovery from the various error messages. The following menu items will
be reset:
Correct the problems associated with the above conditions before using
these reset keys. More than one error could be present. Caution is advised since
several items are reset at one time.
Page 8
While in the Primary or Secondary Menu, if no key is pressed for a period of 30
seconds, the display will return to the HOME position displaying the temperature
value. While in the Secure Menu, if no key is pressed for a period of 60 seconds,
the display will return to the HOME position displaying the temperature value.
Outputs are disabled (turned off) when the Secure Menu is active.
NOTE: To move to the Primary Menu quickly from any other menu, press the UP
ARROW & ENTER keys followed by pressing the INDEX & DOWN ARROW keys.
SECURITY LEVEL SELECTION
Four levels of security are provided. The display shows the current security level. To
change security levels change the password value using the UP & DOWN ARROW
keys and pressing the ENTER key. Refer to the password table (following) for the
correct value to enter for the security level desired. The SECr menu item security
level may be viewed or changed at any time regardless of the present security level.
To set the access level to, for example, 2, at the SECr menu item press the UPARROW key until the upper display show the password, 1101. Press the ENTER
key. The display will blink, and return with the level value, 2, in the upper display.
The password values shown in the table cannot be altered, so retain a copy of these
pages for future reference. This is the only r eference made to passwor d values in this
instruction book.
Security Level
Menu
Primary
Secondary
Secure
Primary
Secondary
Secure
Primary
Secondary
Secure
Primary
Secondary
Secure
Status
Locked
Locked
Locked
Unlocked
Locked
Locked
Unlocked
Unlocked
Locked
Unlocked
Unlocked
Unlocked
PASSWORD TABLE
Displayed Value
When Viewed
1
2
3
4
Password Value
to Enter
1110
1101
1011
111
Page 9
NOTATION CONVENTIONS FOR THE MENUS
Because of the number of features available in this control, information is included
that may not apply to your specific control. All usable features are included in this
book, but may not be used in your process. To increase clarity the following conventions are used:
1. Certain features, Menu Items, and functions shown in this book may or may not
appear on your control, depending on other Menu Item selections. At various places
in the Menus there are notes identifying Menu Items that "control" or "direct" other
menu items. If you are looking for a particular menu item and can't find it, check the
menu item that is its "control" for proper setting.
2. The "#" symbol is used in two ways. It is used inside a group of characters to
indicate which set point function (SP1 or SP2) is being affected. It is also used before
a group of characters of a menu item to indicate that there may be more than one
selection or value for that menu item. This is used for certain repeated items such as
in the Ramp/Soak Program section.
3. Features that apply only to Options will be printed in Italics.
THE HOME DISPLAY
The home display is the normal display while the control is operating. If no errors or
functions are active, the HOME display will indicate the Process Variable (the temperature, pressure, flow, RH, etc., that is being measured) on the top display and the
Set Variable (Set Point 1) on the bottom.
Items that can change the HOME display are the Auto/Manual function, the Prog
function, the PctO function, and any error message. Description of these special displays follow.
If Auto/Manual is enabled, the Manual indicator lights, and the home display is
changed. The upper display continues to show the Process Variable (PV), but the
lower display changes to show the percentage of output in tenths of a percent to
99.9% (0.0 to 99.9), or 100 if 100%. The display digit to the right of the number
shows a flashing letter oto indicate that the value displayed is no longer the SV, but
percent output. The SP2 output is indicated by the use of an overline on the letter
o
. Access to the SP2 value is done by the INDEX key. See Auto/Manual Operation
on Page 13 for further information.
If Prog is turned On, the HOME display changes the SV display from SP1to the
Present Set Variable as calculated by the Ramp/Soak Programmer function. See
Programming and Operation for Ramp/Soak Feature for more information.
Page 10
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.