The CN72000 Series temperature/
process controllers set a new
standard in quality, versatility,
ease-of-use and value. Posessing
many high-level standard features,
additional function setup items also
appear in the control menu when a
function is selected, simplifying the
selection process. Units feature a
universal input for thermocouple
Types J, K, E, T, L, N, B, C, S and
R, RTD’s, a differential input
(-10 to 10 mVdc), and a process
input (0 to 20 mAdc, 0 to 10 Vdc).
A standard 24 V isolated, regulated
power supply is included; operates
most standard 4 to 20 mA
transmitters. Standard features
include autoune, fuzzy logic, fully
adjustable PID, auto/manual control
with smooth transfer and front panel
activation key, percent output
indicator, peak and valley indicator,
loop break protection and indication.
For process inputs, the display is
fully programmable from -1999 to
9999 with selectable decimal point
location. Most thermocouple and
CN72033, $465.
RTD inputs show whole or tenth
degree displays. The CN72000
Series can be programmed for
on/off, PID, heat/cool, or latching
alarm. All outputs are isolated from
the inputs. Outputs include 10 A
relay, and scalable 0 to 20 mAdc.
nominal, 10 to 15%, 50 to 400 Hz
Single Phase: 132 to 240 Vdc, nominal,
10 to 20%
Operating Temperature:
-10 to 55°C (14 to 131°F)
Control Output Ratings:
Relay: SPDT, 10 A @ 240 Vac
Resistive:
1
⁄3 hp @ 240 Vac
Alarm Relay: SPST,
3 A @ 240 Vac resistive
Proportional Current (Isolated):
0 to 20 mAdc, scalable into
600 Ω maximum
SSR: 2.5 A @ 240 Vac @ 25°C (77°F);
derates to 1.25 A @ 55°C (130°F)
DC Pulse (Isolated):
15 Vdc @ 20 mA
Weight: 369 g (13 oz)
1
⁄2 hp @ 120 Vac,
Page 2
Inputs
AL 1 AL 2
° F
° C
REM
%
HOL D MA N
PV
SV
SP1
SP2
95.9
(3.774)
95.9
(3.774)
13.5
(0.530)
100.8
(3.970)
1 14.3
(4.500)
91.3
(3.596)
Maximum Panel Thickness
6.35 (0.250)
Panel
Extended Warranty
Program
SM
Input TypesRange
Dimensions: mm (in)
Thermocouple-129 to 1371°C (-200 to 2500°F)
Thermocouple-73 to 871°C (-100 to 1600°F)
Thermocouple-212 to 398°C (-350 to 750°F)
Thermocouple-73 to 982°C (-100 to 1800°F)
Thermocouple-73 to 1300°C (-100 to 2372°F)
Thermocouple-17 to 1760°C (0 to 3200°F)
Thermocouple-17 to 1760°C (0 to 3200°F)
Thermocouple24 to 1820°C (75 to 3308°F)
(J DIN) Thermocouple-73 to 871°C (-100 to 1600°F)
Thermocouple-17 to 2320°C (0 to 4208°F)
Pt100 RTD (0.00385)-200 to 875°C (-328 to 1607°F)
Pt100 RTD (0.00392)-200 to 875°C (-328 to 1607°F)
RTD, 120 Ω nickel (0.00628)-80 to 320°C (-112 to 608°F)
RTD, Pt1000 (0.00385)-200 to 875°C (-328 to 1607°F)
0 to 20 mA*, 4 to 20 mA*-1999 to 9999
0 to 10Vdc*, -10 to 10 Vdc*,
-10 to 10 mVdc*
Note: All thermocouple and RTD inputs can be set for 0.1° display. If temperature
goes above 999.9° or below -199.9°, the display will return to whole-degree resolution.
Process Input Types: The 0 to 20 mAdc, 4 to 20 mAdc, 0 to 10 Vdc, 2 to 10 Vdc,
*
and -10 to 10 mVdc inputs are fully scalable from a minimum of 100 counts span
placed anywhere within the range of -1999 to 9999. Decimal point position is
adjustable from the zero place (9999), tenths (999.9), hundredths (99.99) or
thousandths (9.999).
-1999 to 9999
Side View
Front View
OMEGACARESMextended warranty
program is available for models shown on
this page. Ask your sales representative
for full details when placing an order.
OMEGACARE
SM
covers parts, labor and
equivalent loaners.
Options
Ordering Add’l
SuffixPrice Description
-RSP1$80 Remote setpoint,
0 to 20 mA
-RSP280 Remote setpoint,
0 to 10 Vdc
-PV180 Retransmission
output, 0 to 20 mA
-PV280 Retransmission
output, 0 to 10 Vdc
-4SP80 4-stage remote
setpoint
Recommended Reference Book:
Controller Tuning, PID,GE-2117, $25.
Accessory (Field Installable)
Model NumberPriceDescription
CNQUENCHARC$10Noise suppression RC snubber (2 leads), 110 to 230 Vac
Visit omega.com/bobi
for Additional Books
To Order (Specify Model Number)
Model Number Price Description
CN72130$479 Single output relay/DC pulse with alarm
CN72150519 Single output 0 to 20 mA with alarm
CN72033465 Dual output 2 relay/DC pulse
CN72011465 Dual output 2 AC SSR/DC pulse
CN72053519 Dual output 0 to 20 mA and relay/DC pulse
CN72055550 Dual output two 0 to 20 mA
CN72111502 Dual output 2 AC SSR/DC pulse with alarm
CN72133502 Dual output 2 relay/DC pulse with alarm
CN72153543
CN72155594 Dual output two 0 to 20 mA with alarm
Comes complete with operator’s manual.
Ordering Examples: CN72130, single output relay/DC pulse with alarm, $479.
OCW-3, OMEGACARE
Calibrators, Connectors, General Test and Measurement
Instruments, Glass Bulb Thermometers, Handheld Instruments
for Temperature Measurement, Ice Point References,
Indicating Labels, Crayons, Cements and Lacquers, Infrared
Temperature Measurement Instruments, Recorders Relative
Humidity Measurement Instruments, RTD Probes, Elements
and Assemblies, Temperature & Process Meters, Timers and
Counters, Temperature and Process Controllers and Power
Switching Devices, Thermistor Elements, Probes and
Assemblies,Thermocouples Thermowells and Head and Well
Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level
Measurement, Magnetic Flowmeters, Mass Flowmeters,
Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel
Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area
Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen
Instrumentation, Environmental Instrumentation, pH
Electrodes and Instruments, Water and Soil Analysis
Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems,
Communication Products and Converters, Data
Acquisition and Analysis Software, Data Loggers
Plug-in Cards, Signal Conditioners, USB, RS232, RS485
and Parallel Port Data Acquisition Systems, Wireless
Transmitters and Receivers
Band Heaters, Cartridge Heaters, Circulation Heaters,
Comfort Heaters, Controllers, Meters and Switching
Devices, Flexible Heaters, General Test and Measurement
Instruments, Heater Hook-up Wire, Heating Cable
Systems, Immersion Heaters, Process Air and Duct,
Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
click here to go to the omega.com home page
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.