Omega Products CN7200 User Manual

platinum resistance sensor (RTD) to the controller and please route
Ramp/soak pattern. Only displayed
Ratio of output 1 & output 2 when in
(This parameter is available only when ALA3
Set point
Dead band
Cooling hysteresis
PV
Dead band: dead
band width=positi ve
Figure 2. PID Dead Band is positive
CN7200/CN7500 CN7600/CN7800
Thank you very much for choosing Omega Engineering Series CN7200/CN7500/CN7600/CN7800 Temperature/Process Controller. Please read this instruction sheet before using your controller to ensure proper operation and please keep this instruction sheet handy for quick reference.
DANGER! Caution! Electric Shock!
1. Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2. Make sure the power is disconnected while checking the unit inside.
3. The symbol indicates that this Controller is protected throughout by DOUBLE INSULATION or REINFORCED
INSULATION (equivalent to Class II of IEC 536).
WARNING!
Mount the controller in a location that will not be subject to excessive temperature, shock, or vibration. All models are designed for mounting in an enclosed panel.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm (6.0mm for 32B
Series), hole diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Screw size for 32B Series: M3 x 4.5 (With 6.0 x 6.0 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm). Applicable wire: Solid/twisted wire of
2
, 12AWG to 24AWG. Please be sure to tighten them properly.
2 mm
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3. Never modify or disassemble the controller.
4. Do not connect anything to the “No used” terminals.
5. Make sure all wires are connected to the correct polarity of terminals.
6. Do not install and/or use the controller in places subject to: Dust or corrosive gases and liquid, high humidity and high
radiation, vibration and shock, high voltage and high frequency
7. Power must be off when wiring and changing a temperature sensor.
8. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple
wires.
9. Please use wires with resistance when extending or connecting a platinum resistance sensor (RTD).
10. Please keep the wire as short as possible when wiring a
power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping
water, corrosive materials, airborne dust and electric shock or vibration.
12. Please make sure power cables and signals from instruments are all installed properly before energizing the controller,
otherwise serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric
shock.
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal
circuit within this period.
15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install the
protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-lag fuse
17. Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent
protection device(s) must be added to ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-use installation.
Display, LED and Pushbuttons!
Instruction Sheet
Precaution!
displays process value
PV
displays setpoint value.
SV
INDEX: advances the display to the next menu item
UP ARROW: Increments a value or changes a menu item. DOWN ARROW: Increments a value or changes a menu item.
Note: CN7500 Series does not support an additional alarm output, however, the user can set 2nd output as alarm mode.
Input Temperature Sensor Type Register Value LED Display Temperature Range
0 ~ 50mV Analog Input 17
4 ~ 20mA Analog Input 16
0 ~ 20mA Analog Input 15
0V ~ 10V Analog Input 14
0V ~ 5V Analog Input 13
Platinum Resistance (Pt100) 12
Platinum Resistance (JPt100) 11
Thermocouple TXK type 10
Thermocouple U type 9
Thermocouple L type 8
Thermocouple B type 7
Thermocouple S type 6
Thermocouple R type 5
Thermocouple N type 4
Thermocouple E type 3
Thermocouple T type 2
Thermocouple J type 1
Thermocouple K type 0
Note: (in the operation mode) specifies the decimal point position. All input types except thermocouple B, S, and R type, allow the decimal point position to be specified. The default range of analog input is -999 ~ 9999. For example, when a 0~20mA analog input is selected as the input temperature sensor type, -999 indicates 0mA and 9,999 indicates 20mA. If change the input range to 0 ~ 2,000, then 0 indicates 0mA and 2000 indicates 20mA. One display scale is equal to 0.01mA.
Temperature Sensor Type and Temperature Range!
ENTER: stores the value or item change.
Operation!
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-200 ~ 600
-20 ~ 400
-200 ~ 800
-200 ~ 500
-200 ~ 850
100 ~ 1,800
0 ~ 1,700
0 ~ 1,700
-200 ~ 1,300
0 ~ 600
-200 ~ 400
-100 ~ 1,200
-200 ~ 1,300
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
There are three modes of operation: operation, regulation and initial setting. When power is applied, the controller will default
to the operation mode. Press the
the controller will switch to the initial setting mode. Pressing the forces the controller to return to the operation mode. PV/SV: Sets the temperature set point and displays the temperature
process value. Use
keys to set the temperature set point.
Setting method: While in any function mode, press the
change settings. Press
(Set in PID control & RUN mode)
When n=4, PID control is auto regulated.
See PID Control section.
is ON and Ti=0, set the value of PdoF).
(in ON/OFF control)
(in ON/OFF control)
control cycle setting (Set in PID control mode)
group (Set in PID control and dual loop output control mode)
dual output control. P value off 2
output group) (Set it up when in PID/programmable PID + dual output) ×
control mode)
value
output value (The setting is displayed when in analog output)
output value (The setting is displayed when in analog output)
Press
1 Scale = 2.8uA = 1.3mV for tuning output value
function are available. Each group contains a set value, proportional band, integral time, derivative time, and integral deviation settings (P, I, D, IOF) for PID control.
Regulation Mode Operation Mode Initial Setting Mode
Auto-tuning
Press
4 groups PID modes (n=0~3).
Press
PD control offset (when PID control
Press
Heating hysteresis
Press
Cooling hysteresis
Press
or Heating/cooling
Press
Control cycle setting of 2nd output
Press
nd
output group = (P value of 1st
Press
Dead Band (set in dual loop output
Press
Regulate temperature deviation
Press
Regulate upper-limit of analog
Press
Regulate lower-limit of analog
to return to “auto-tuning"
~ : PIDn, n = 0 ~ 4, found in the regulation mode, four groups of user-defined PID settings and an auto tuning
key to switch to regulation mode. If the key is pressed for more than 3 seconds,
key while in the regulation mode or initial setting mode,
key to select the desired function and use the keys to
key to save the changes. Menu items are listed below.
Use to set temperature
set point
V
Control setting RUN or STOP
V
See “Execution” in Section 6
Start pattern setting. Appears only
when
V
is set to
Press
Press
Press
Set the position of decimal point
for thermocouple R, S, B type)
(Not
V
Upper-limit alarm 1 (This parameter is available only when ALA1 function is enabled.)
V
Lower-limit alarm 1 (This parameter is available only when ALA1 function is enabled.)
V
Upper-limit alarm 2 (This parameter is available only when ALA2 function is enabled.)
V
Lower-limit alarm 2 (This parameter is available only when ALA2 function is enabled.)
V
Upper-limit alarm 2
function is enabled.)
V
Lower-limit alarm 3 (This parameter is available only when ALA3 function is enabled.)
V
Set lock mode
V
Display and adjust output value of
st
output group
1 (Displayed when in PID control mode and
manual RUN mode)
Display and adjust output value of
nd
output group
2 (Displayed when in dual loop PID control mode and manual RUN mode)
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
V
V
V
V
V
V
V
V
V
V
V
V
V
Set input type
Set temperature unit
(Not displayed when in analog input)
Set upper-limit of temperature
range
Set lower-limit of temperature
range
Set Control method: ON/OFF, PID, Prog, or manual. (Set to ProG for ramp/soak patterns) See 6. Pattern and Set editing.
when CtrL is set to ProG.
Select heating, cooling control or
dual loop output control.
Alarm 1 mode setting
Alarm 2 mode setting
Alarm 3 mode setting
Set system alarm
Communication write function enabled/disabled
Select ASCII/RTU communication
format
Communication address setting
Communication baud rate setting
Data length setting
Parity bit setting
Stop bit setting
Press
to return to “set input type”
PID Control!
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
: n = 4, is the auto PID parameter. The controller will automatically select a most useful PID parameter based on current
temperature setting. Displayed SV values correspond to
~
~ : is the temperature setting which corresponds to the selected PID parameter via user-defined or AT (auto-tuning).
After AT(auto-tuning) the values will be stored. PID mode selection (regulation mode): any one of four PID modes (n=0~3) can be selected. When n=4, the unit will perform auto-tuning.
Select n=0~4 to decide PID mode
Press Z 0~3 groups PID
V
V
Description of Function and Parameters Setting:
V
To set-up or edit the ramp/soak function, follow in the menu list.
The Ramp and Soak function is supported by 8 different patterns (Pattern No. 0 ~ 7). Each pattern contains 8 steps (step No. 0 ~ 7) for set point and execution time, one Link Pattern parameter, one Cycle parameter and one Actual Step parameter.
V
The set point (SV) should reach temperature X after the execution time T. The default of step No. 0 is soak control. The unit will control the temperature (PV) to reach the set point X and then keep the temperature at set point X. The execution time T is determined by step No, 0.
The following display is an example of operation of pattern No. 0.
V
V
V
Select desired editing pattern
number Select OFF
VZ select number
Press Exit pattern and step editing selection
Switch to
Set step No.1-7 in order
and continue setting
Pattern and Set Editing (Ramp and Soak Programming)!
PID setting: n=0
Press V
Proportion band setting: n=0
Press V
Ti setting: n=1
Press V
Td setting: n=0
Press V
Integral deviation setting: n=0. AT
setting
V back to PID deviation setting
Press
in the initial setting mode must be set to . Will immediately
PAtn where n = 0-7.
Edit temperature of step No.0 of
pattern No.0
V
Press
Edit time of step No.0 of pattern
No.0. Unit: hh.mm
V
Press
Edit temperature of step No.7 of
pattern No.0
V
Press
Edit time of step No.7 of pattern
No.0. Unit: hh.mm
to set actual step No.
Press
PID setting: n=3
Proportion band setting: n=3
Ti setting: n=3
Td setting: n=3
Integral deviation setting: n=3. AT
setting
V back to PID deviation setting
Press
Select actual step No. when
program control is executing
Set additional execution cycle
number (0~99)
Set link pattern. OFF indicates the
program end
to return to pattern No. editing
Press mode
Actual Step Parameter : Offered for each pattern (0-7), the user can select to execute only certain steps in the
V
pattern. For example, when
Cycle Parameter
times. For example, when more times.
V
Link Pattern Parameter
For example, when
, the program will stop after executing the current pattern and the temperature will be maintained at the set point of the
last step.
V
Execution:
The execution of the ramp and soak function is initiated through
When
When
When
V
was stopped. Select
setting
appears in
When
program hold. Select
V
the time. Display : During ramp and soak program control, the SV default display is P-XX, P indicates the current execution pattern
is set to , the program will start to execute in order from the step 0 of the start pattern.
is set to , the program will stop and the control output is disabled.
is set to , the program will stop and the temperature will be maintained at the set point before program
is accessed when is set to and the INDEX key is pressed. (The start pattern setting only
mode).
is set to , the program will hold and the temperature at that time will be controlled at the set point before
and XX indicates the current execution step. Press
residual time
After selecting
V
display.
After selecting
V
V
V
V
Temperature control can be achieved either by heating or cooling. In the CN7200/CN7500/CN7600/CN7800 series, heating and cooling can be operated simultaneously (Dual Loop output control) to perform temperature control. When Dual Loop output control is used, two control outputs must be connected to the heating and cooling devices. Please refer to the following for the operation: Settings for heat, cool, or heat
and cool are found in the initial settings mode under
.
, press key, and then the temperature set point of the current execution step will display on SV
, press key, and then the residual time of the current execution step will display on SV display.
Select , for heating (reverse) control on Output 1.
Select
, for cooling (forward) control on Output 1. By selecting
is set to 2, pattern No 7 will only execute steps 0 through 2.
: Offered for each pattern (0-7), the cycle parameter will execute the selected pattern X amount of
is set to 2, pattern No. 4 will cycle through the steps and then cycle through the steps 2
: Offered for each pattern (0-7), the link parameter designates the next pattern to execute.
is set to 2, pattern No. 2 will execute next after the execution of pattern No. 0. If is set to
in the operation mode.
again, then the program will restart and execute from step 0 of start pattern. The start pattern
again, then the program will follow the step before hold and start to execute through the rest of
to change the SV display item to set point value or
Heating, Cooling or Dual Loop Output Control!
Heating hysteresis
ON
Heating
OFF
Figure 1. Output
Output
operation of ON/OFF control
during dual loop output control
or the 2nd output group is regarded as an alarm output.
For dual loop control, select the 1st output group is heating (reverse) control and the 2nd output
group is cooling (forward) control. When selecting group is cooling (forward) control and the 2nd output group is heating (reverse) control.
or . When selecting ,
, the 1st output
Heating Cooling
0
Set point
control,
Cooling
Press
V
Press V
Press V
Press V
V
Press
V
Press
PV
When dual loop control is selected
PV
Dead band: dead
Figure 3. PID Dead Ban d is negative
All
ON
SV+(AL-H)
ON
SV+(AL-H)
ON
ON
SV+(AL-H)
AL-L
AL-H
AL-H
AL-L
(SV value) and the value
ON
SV+(AL-H)
SV+(AL-H)
ON
SV-(AL-L)
ON
H). This
AL-L
AL-H
AL-H
AL-L
SV
, when Ti =
8, 8 indicates the program end. 0~7 indicates the next execution
65.0 min.
40.0 mi
n
.
mm
(in)
65.0 min.
60.
0 min
.
Only visible when dual loop output and PID control method is
configured. The parameter sets the P value of the 2 P value of the 1
2nd output group is
equal to (P value of 1st output group) x 2nd output group are the same as the value of I and D of 1st output group.
area in which the heating and cooling control output is 0 centering around the set point in a Dual Loop output control mode.
st
output which is set in parameter . The P value of
Dead Band, shown in figures 1, 2 and 3. This parameter sets an
nd
output based on the
and the value of I and D of
Output
0
Heating
Set point
control,
band width=negat ive
Cooling
: Settings lock. To avoid incorrect operation, two key lock functions are provided. : Lock 1 can lock all settings.
parameters and temperature settings can be locked to disable changes. : Lock 2 can lock settings except the SV (Set
AL-L
and
SV
SV
SV
SV
SV
SV
SV
AL-H
point) value. All parameters and temperature settings can be locked with the exception of the SV value. Press key simultaneously, the “Lock” status can be released.
Auto-tuning parameter, automatically sets P (Proportional Band), I(Integral Time) and D(Derivative Time) parameters.
Correct input must be connected to the unit for this parameter to be changed.
Depending on the controller model, there can be up to three alarm outputs. Each alarm output can be configured for an alarm type listed below. Alarm types are set in the initial setting mode. The alarm output is activated whenever the process temperature value (PV) is getting higher or lower than the set point of alarm limit.
Set Value
0 Alarm function disabled Output is OFF
Deviation upper- and lower-limit:
1
This alarm output operates when PV value is higher than the setting value SV+(AL-H) or lower than the setting value SV-(AL-L). Deviation upper-limit:
2
This alarm output operates when PV value is higher than the setting value SV+(AL-H).
Deviation lower-limit: This alarm output operates when PV value is lower than the setting value SV-(AL-L).
3
Reverse deviation upper- and lower-limit:
4
This alarm output operates when PV value is in the range of the setting value SV+(AL-H) and the setting value SV-(AL-L). Absolute value upper- and lower-limit:
5
This alarm output operates when PV value is higher than the setting value AL-H or lower than the setting value AL-L. Absolute value upper-limit:
6
This alarm output operates when PV value is higher than the setting value AL-H.
Absolute value lower-limit:
7
This alarm output operates when PV value is lower than the setting value AL-L.
Deviation upper- and lower-limit with standby sequence:
8
This alarm output operates when PV value reaches set point is higher than the setting value SV+(AL-H) or lower than the setting value SV-(AL-L). Deviation upper-limit with standby sequence:
9
This alarm output operates when PV value reaches set point (SV value) and the reached value is higher than the setting value SV+(AL-H). Deviation lower-limit with standby sequence:
10
This alarm output operates when PV value reaches the set point (SV value) and the reached value is lower than the setting value SV-(AL-L). Hysteresis upper-limit alarm output:
11
This alarm output operates if PV value is higher than the setting value SV+(AL­alarm output is OFF when PV value is lower than the setting value SV+(AL-L). Hysteresis lower-limit alarm output:
12
This alarm output operates if PV value is lower than the setting value SV-(AL-H). This alarm output is OFF when PV value is higher than the setting value SV-(AL-L). CT alarm output: This alarm operates when the current measured by transformer (CT) is lower than
13
AL-L or higher than AL-H (This alarm output is available only for the controller with current transformer).
14 When program control is end status, alarm output is ON. 15 When RAMP UP status happens to PID program control, alarm output is ON. 16 When RAMP DOWN status happens to PID program control, alarm output is ON. 17 When SOAK status happens to PID program control, alarm output is ON. 18 When RUN status happens to PID program control, alarm output is ON.
Note: AL-H and AL-L include AL1H, AL2H, AL3H and AL1L, AL2L, AL3L)
Input Voltage 100 to 240VAC 50/60Hz
Alarm Outputs!
Alarm Type Alarm Output Operation
OFF
SV-(AL-L)
OFF
OFF
SV-(AL-L)
OFF
SV-(AL-L)
ON
OFF
ON
OFF
ON
OFF
OFF
SV-(AL-L)
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Specifications!
Operation Voltage Range 85% to 110% of rated voltage Power Consumption 5VA max. Memory Protection EEPROM 4K bit (non-volatile memory (number of writes: 100,000) Display Method 2 line x 4 character 7-segment LED display Process value (PV): Red color, Set point (SV): Green color
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Sensor Type
3-wire Platinum RTD: Pt100, JPt100 Analog input: 0~5V, 0~10V, 0~ 20 m A, 4 ~ 20 m A, 0 ~ 50mV
Control Mode PID, ON/OFF, Manual or PID program control (Ramp/Soak control)
Relay output: SPDT (SPST: 1/16 DIN and 1/32 DIN size), Max. load 250VAC, 5A resistive load
Control Output
Voltage pulse output: DC 14V, Max. output current 40mA Current output: DC 4 ~ 20m A output (Load resistance: Max. 600Ω) Linear voltage output: 0~10V
*(B Series only)
Display Accuracy 0 or 1 digit to the right of the decimal point (selectable) Sampling Rate Analog input: 150 msec/ per scan Thermocouple or Platinum RTD: 400 msec/per scan RS-485 Communication MODBUS ASCII / RTU communication protocol Vibration Resistance 10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions Shock Resistance Max. 300m/ s2, 3 times in each 3 axes, 6 directions Ambient Temperature 32oF to 122oF (0oC to + 50oC) Storage Temperature -4oF to 150oF (-20oC to + 65oC) Altitude 2000m or less Relative Humidity 35% to 80% (non-condensing)
10
RS-485 Communication!
1. Supporting transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps
2. Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2
3. Communication protocol: Modbus (ASCII or RTU)
4. Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read the bits data (Max. 16 bits). 05H to write 1 (one) bit into register.
5. Address and Content of Data Register:
Address
Content Explanation
Measuring unit is 0.1, updated one time in 0.4 second The following reading value display indicates error occurs: 8002H: Initial process (Temperature value is not got yet)
1000H Process value (PV)
8003H: Temperature sensor is not connected 8004H: Temperature sensor input error 8006H: Cannot get temperature value, ADC input error
8007H: Memory read/write error 1001H Set point (SV) Unit is 0.1, oC or oF 1002H Upper-limit of temperature range The data content should not be higher than the temperature range 1003H Lower-limit of temperature range The data content should not be lower than the temperature range
1004H Input temperature sensor type
Please refer to the contents of the “Temperature Sensor Type and
Temperature Range” for detail 1005H Control method 0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram control 1006H Heating/Cooling control selection 0: Heating, 1: Cooling, 2: Heating/Cooling, 3: Cooling/Heating 1007H 1st group of Heating/Cooling control cycle 0 ~ 99, 0:0.5 sec 1008H 2nd group of Heating/Cooling control cycle 0 ~ 99, 0:0.5 sec 1009H PB Proportional band 0.1 ~ 999.9 100AH Ti Integral time 0 ~ 9,999 100BH Td Derivative time 0 ~ 9,999 100CH Integration default 0 ~ 100%, unit is 0.1%
100DH
100EH
100FH
1010H Hysteresis setting value of the 1st output group 0 ~ 9,999 1011H Hysteresis setting value of the 2nd output group 0 ~ 9,999
Proportional control offset error value 0 The setting of COEF when Dual Loop control are used
output
The setting of Dead band when Dual Loop output control are used
0 ~ 100%, unit is 0.1%
0.01 ~ 99.99
-999 ~ 9,999
Panel Cutout (dimensions are in millimeter & inch)
CN7200
CN7500
(2.56)
2
6
0
.
.
0
0
0
0
+
+
-
-
) 8 5
. 1 (
(1.76)
) 7
0
.
8
2
.
2
0 (
+0.6
-0
44.8
+0.02
-0
CN7600
12
Dimensions are in millimeter (inch) CN7200 CN7500
External Dimensions !
CN7800
(2.56)
) 6 3 . 2 (
45.0
(1.77)
2
6
0
.
.
0
0
0
0
+
-
+
-
)
0
7
.
7
5
.
4
1 (
+0.6
mm
-0 +0.02
(in)
-0
1012H Output value read and write of Output 1 Unit is 0.1%, write operation is valid under manual tuning mode only. 1013H Output value read and write of Output 2 Unit is 0.1%, write operation is valid under manual tuning mode only. 1014H Upper-limit regulation of analog linear output 1 Unit = 2.8uA (Current Output) = 1.3mV (Linear Voltage Output) 1015H Lower-limit regulation of analog linear output 1 Unit = 2.8uA (Current Output) = 1.3mV (Linear Voltage Output) 1016H Temperature regulation value -999 ~ +999, unit: 0.1 1017H Analog decimal setting 0 ~ 3 101CH PID parameter selection 0 ~ 4
CN7600 CN7800
101DH SV value corresponded to PID value Only valid within available range, unit: 0.1 scale 1020H Alarm 1 type Please refer to the contents of the “Alarm Outputs” for detail 1021H Alarm 2 type Please refer to the contents of the “Alarm Outputs” for detail 1022H Alarm 3 type Please refer to the contents of the “Alarm Outputs” for detail 1023H System alarm setting 0: None (default), 1 ~ 3: Set Alarm 1 to Alarm 3 1024H Upper-limit alarm 1 Please refer to the contents of the “Alarm Outputs” for detail 1025H Lower-limit alarm 1 Please refer to the contents of the “Alarm Outputs” for detail 1026H Upper-limit alarm 2 Please refer to the contents of the “Alarm Outputs” for detail 1027H Lower-limit alarm 2 Please refer to the contents of the “Alarm Outputs” for detail 1028H Upper-limit alarm 3 Please refer to the contents of the “Alarm Outputs” for detail 1029H Lower-limit alarm 3 Please refer to the contents of the “Alarm Outputs” for detail 102AH Read LED status b0: Alm3, b1: Alm2, b2: F, b3:, b4: Alm1, b5: OUT2, b6: OUT1, b7: AT 102BH Read pushbutton status b0: Set, b1: Select, b2: Up, b3: Down. 0 is to push 102CH Setting lock status 0: Normal, 1: All setting lock, 11: Lock others than SV value 102FH Software version V1.00 indicates 0x100 1030H Start pattern number 0 ~ 7
1040H~
1047H
1050H~
1057H
1060H~
1067H
2000H~
203FH
2080H~
20BFH
6. Address and Content of Bit Register: (First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit
0810H Communication write-in selection
0811H Temperature unit display selection
0812H Decimal point position selection
0813H AT setting OFF: 0 (default), ON: 1 0814H Control RUN/STOP setting 0: STOP, 1: RUN (default) 0815H STOP setting for PID program control 0: RUN (default), 1: STOP 0816H Temporarily STOP for PID program control 0: RUN (default), 1: Temporarily STOP
7. Communication Transmission Format : Command Code: 02: read N bits, 05: write 1 bits, 03: read N words, 06: write 1
11
Actual step number setting inside the correspond pattern Cycle number for repeating the execution of the correspond pattern Link pattern number setting of the correspond pattern Pattern 0~7 temperature set point setting Pattern 0 temperature is set to 2000H~2007H Pattern 0~7 execution time setting Pattern 0 time is set to 2080H~2087H
clear)
words
0 ~ 7 = N, indicate that this pattern is executed from step 0 to step N
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
0 ~
pattern number after executing the current pattern
-999 ~ 9,999
Time 0 ~ 900 (1 minute per scale)
Communication write in disabled: 0 (default), Communication write in enabled: 1
o
C/linear input (default): 1 , oF : 0
Except for the thermocouple B, S, R type, all the other thermocouple type are valid. (0 or 1)
Panel Cutout and Terminal Identification!
Terminal Identification
CN7200/CN7600
CN7500
13
Mounting Method Mounting Bracket Installation
Step 1: Insert the controller through the panel cutout. Step 2: Insert the mounting bracket into the mounting groove at the top and
bottom of the controller Step 3: Push the mounting bracket forward until the bracket stops at panel wall. Step 4: Insert and tighten screws on bracket to secure the controller in place.
(The screw torque should be 0.8kgf-cm to 1.5kgf-cm)
Mounting!
CN7500 Mounting Method:
CN7200/CN7600/CN7800 Mounting Method:
14
Error Acknowledgement and Display!
Communication error code response description:
Error Status 102EH / 4750H PV read back 1000H / 4700H Error status
0001H M/A PV unstable 0002H 8002H Re-initial, no temperature at this time 0003H 8003H Input sensor did not connect 0004H 8004H Input signal error 0005H N/A Over input range 0006H 8006H ADC fail 0007H N/A EEPROM read/write error
Display message:
Power ON Normal display
CN7800
PV SV Sensor didn’t connect Input error PV SV EEPROM error Input over range PV SV
CN7200/CN7500CN7600/CN7800 series, Firmware V1.50 Output VR type with Event option
No Connect
Error EEPROM
Present value Set value
Error Input
PV flash when over
M-4437/0207
Loading...