Omega Products CN710 Installation Manual

CN710/CN730/CN740 Temperature Controller
Instruction Sheet
Thank you very much for purchasing Omega Engineering CN700 Series Temperature Controller. Please read this instruction sheet before using your controller to ensure proper operation and please keep this instruction sheet handy for quick reference.
1 Precaution
DANGER! Caution! Electric Shock!
1. DO NOT touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2. Make sure power is disconnected while checking the unit inside.
3. The symbol
indicates this Controller is protected throughout by DOUBLE INSULATION or REINFORCED
INSULATION (equivalent to Class II of IEC 536).
WARNING!
Mount the controller in a location that will not be subject to excessive temperature, shock, or vibration. All models are designed for mounting in an enclosed panel.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm, hole diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm). Applicable wire: Solid/twisted wire of 2 mm properly.
2. DO NOT allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3. Never modify or disassemble the controller.
4. DO NOT connect anything to the “Not used” terminals.
5. Make sure all wires are connected to the correct polarity of terminals.
6. DO NOT install and/or use the controller in places subject to: Dust or corrosive gases and liquid, high humidity and high radiation, vibration and shock, high voltage and high frequency
7. Power must be off when wiring and changing a temperature sensor.
8. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Please use wires with resistance when extending or connecting a platinum resistance sensor (RTD).
10. Please keep the wire as short as possible when wiring a platinum resistance sensor (RTD) to the controller and please route power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water, corrosive materials, airborne dust and electric shock or vibration.
12. Please make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric shock.
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit within this period.
15. DO NOT use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-lag fuse
17. Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent protection device(s) must be added to ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-use installation.
2 Display, LED, & Pushbuttons
PV displays process value SV displays setpoint value.
INDEX: advances the display to the next menu item.
UP ARROW: Increments a value or changes a menu item.
DOWN ARROW: Increments a value or changes a menu item.
ENTER: stores the value or item change.
, 12AWG to 24AWG. Please be sure to tighten them
3 Model Number Identification
4 Temperature Sensor Type & Temperature Range
Input Temperature Sensor Type Register Value LED Display Temperature Range
Platinum resistance (Pt100) type3 15
0.0 ~ 100.0°C
Input Temperature Sensor Type Register Value LED Display Temperature Range
Platinum resistance (Pt100) type2 14
Platinum resistance (Pt100) type1 13
Platinum resistance (JPt100) type2 12
Platinum resistance (JPt100) type1 11
Thermocouple (TC) B type 10
Thermocouple (TC) S type 9
Thermocouple (TC) R type 8
Thermocouple (TC) N type 7
Thermocouple (TC) E type 6
Thermocouple (TC) T type2 5
Thermocouple (TC) T type1 4
Thermocouple (TC) J type2 3
Thermocouple (TC) J type1 2
Thermocouple (TC) K type2 1
Thermocouple (TC) K type1 0
Thermocouple (TC) L type 16
Thermocouple (TC) U type 17
Thermocouple (TC) Txk type 18
-20.0 ~ 500.0°C
-200 ~ 600°C
0.0 ~ 100.0°C
-20.0 ~ 400.0°C
100 ~ 1,800°C
0 ~ 1,700 °C
0 ~ 1,700 °C
-200 ~ 1,300 °C
0 ~ 600 °C
-20.0 ~ 400.0°C
-200 ~ 400°C
-20.0 ~ 400.0°C
-100 ~ 850°C
-20.0 ~ 500.0°C
-200 ~ 1,300°C
-200 ~ 850°C
-200 to 500°C
-200 to 800°C
5 Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, the controller will
default to the operation mode. Press
the controller will switch to the initial setting mode. Pressing forces the controller to return to the operation mode. PV/SV: Sets the temperature set point and displays the
temperature process value. Use
Setting method: While in any function mode, press
settings. Press
to save the changes. Menu items are listed below.
Regulation Mode Operation Mode Initial Setting Mode
Auto-tuning
(Set in PID control & RUN mode)
Press
Set proportional band (Kp)
(in PID control)
Press
Set integral time (Ki)
(in PID control)
Press
Set derivative time (Kt)
(in PID control)
Press
or P/PD control offset (when PID control is ON and Ki=0 set the value of PdoF. If Ki0, AT (Auto-tuning will automatically set the value of ioF.
Press
or Heating/cooling hysteresis (in ON/OFF control)
Press
or Heating/cooling control cycle setting (Set in PID control mode)
Press
Regulate temperature deviation value
Press
Regulate upper-limit of analog output value (The setting is displayed when in analog output)
Press
to switch to regulation mode. If is pressed for more than 3 seconds,
while in the regulation mode or initial setting mode,
to set the temperature set point.
to select the desired function and use to change
Use to set
temperature set point
V
Press
Control setting RUN or STOP
V
Press
Upper-limit alarm 1 (This parameter is available only when ALA1 function is enabled.)
V
Press
Lower-limit alarm 1 (This parameter is available only when ALA1 function is enabled.)
V
Press
Upper-limit alarm 2 (This parameter is available only when ALA2 function is enabled.)
V
Press
Lower-limit alarm 2 (This parameter is available only when ALA2 function is enabled.)
V
Press
Set lock mode
V
Press
Display and adjust output value.
V
Press
V
V
V
V
V
V
V
V
Set input type
Set temperature unit
(Not displayed when in analog input)
Set upper-limit of
temperature range
Set lower-limit of
temperature range
Set Control method:
ON/OFF, PID, or manual.
Select heating or cooling
control.
Alarm 1 mode setting
Alarm 2 mode setting
Communication write
function enabled/disabled
V
Press
Press
Press
Press
Press
Press
Press
Press
Press
V
V
V
V
V
V
V
V
V
Regulate lower-limit of analog output value (The setting is displayed when in analog output)
Press
to return to “auto-tuning"
Communication address
setting
Press
Communication baud rate
setting
Press
Data length setting
Press
Parity bit setting
Press
Press
Stop bit setting
to return to “set input type”
Parameters List
1. Operation Mode: The default mode after start-up
LED Display Explanation Default
RUN/STOP: Control setting. Run ( ) or Stop ( ) mode on the SV display.
ALARM 1 HIGH: Upper limit for alarm 1. (Only available when alarm is set in the initial setting mode).
ALARM 1 LOW: Lower limit for alarm 1. (Only available when alarm is set in the initial setting mode).
ALARM 2 HIGH: Upper limit for alarm 2. (Only available when alarm is set in the initial setting mode).
ALARM 2 LOW: Lower limit for alarm 2. (Only available when alarm is set in the initial setting mode).
Lock Function Setting: LoC1, LoC2, or OFF. LoC1 mode will lock all settings, LoC2 locks everything except the set point value, and OFF will not lock any settings.
Press
OUT: The Output value adjustment and display in manual tuning control. (Not available in ON/OFF or Auto-tuning control).
and keys simultaneously, to release the lock status.
2. Regulation Mode: Control parameters Settings
LED Display Explanation Default
AT (Auto-Tuning): ON or OFF, when set ON, the execution of the auto-tuning function in PID control mode is automatically started. (Only available when PID control is selected in initial settings)
P (Proportional Band in PID control): Sets P value. 47.6
I (Integral Time in PID control): Sets I value. 260
D (Derivative Time in PID control): Sets D value. 41
PdoF: Offset output when P or PD control function is on. PID in initial settings is selected and the value of Ki (Integral Time in regulation mode) is equal to zero.
ioF: Default value of integral volume when PID control is ON and the Ki (Integral Time in regulation mode) is not equal to zero. AT function can automatically set this parameter when PID control is active and Ki≠0.
HtS (Heating Hysteresis): Available only in ON/OFF control. Sets the value the heating hysteresis.
CtS (Cooling Hysteresis): Available only in ON/OFF control. Sets the value the cooling hysteresis.
HtPd: PID heating control cycle setting. Only available when a PID control is selected in the initial settings.
ClPd: PID cooling control cycle setting. Only available when a PID control is selected in the initial settings.
TPoF: Regulates the temperature deviation value. 0
CrHi: Regulates the 20mA output deviation value. 0
CrLo: Regulates the 4mA output deviation value. 0
HtS (Heating Hysteresis): Available only in ON/OFF control. Sets the value the heating hysteresis.
3. Initial Setting Mode: Initial settings of the controller and communication parameters
LED Display Explanation Default
INPUT: Select input temperature sensor type (Please refer to the contents of the “Temperature Sensor Type and Temperature
Range” for detail)
Engineering Unit(°F or °C): Select engineering unit F or C. °C
T-High: Upper limit for temperature range. 500.0
T-Low: Lower limit for temperature range. -20.0
CONTROL METHOD (ON/OFF, PID, or manual tuning [ ]): Sets the control method for the set point value.
Control Action (Direct or Reverse Acting): Cooling [Cool] or heating [HEAT]. HEAT
RUN
4.0°C
4.0°C
4.0°C
4.0°C
OFF
OFF
Output Selection:
Voltage: 4 sec. Relay : 20 sec.
PT2
PID
V
V
V
V
0
0
0
0
0
0
LED Display Explanation Default
A
M
ALARM 1: Alarm 1 setting. (See Alarm Output Section for set values and descriptions).
ALARM 2: Alarm 2 setting. (See Alarm Output Section for set values and descriptions).
C WE: Write-in function disabled/enabled. Can be set only when unit is equipped with serial communication.
C NO: Address setting. Can be set only when unit is equipped with serial communication.
BPS: Baud rate setting. Can be set only when unit is equipped with serial communication.
Length: Data length setting. Can be set only when unit is equipped with serial communication.
Parity: Parity bit setting. Can be set only when unit is equipped with serial communication.
Stop Bit: Stop bit setting. Can be set only when unit is equipped with serial communication.
0
0
OFF
1
9,600
7
E
1
Execution:
The programming execution is initiated through
When
When
is set to , the program will start to execute in order from the step 0 of the start pattern.
is set to , the program will stop and the control output is disabled
in the operation mode.
6 Heating & Cooling
Temperature control can be achieved either by heating or cooling. Please refer to the following for the operation:
Settings for heat or cool operation are found in the initial settings mode under
Select
Select
, for heating (reverse) control on Output 1.
, for cooling (forward) control on Output 1
.
Input Error Indication
Setting value
PV
SV
Temperature sensor is not
connected
Measured temperature value
exceeds the temperature range
Unknown input
7 Alarm Outputs
Depending on the controller model, there can be up to two alarm outputs. Each alarm output can be configured for an alarm type listed below. Alarm types are set in the initial setting mode. The alarm output is activated whenever the process temperature value (PV) is getting higher or lower than the set point of alarm limit.
Set
Value
0 Alarm function disabled Output OFF
Deviation upper- and lower-limit:
1
This alarm output operates when PV value is higher than the setting value SV+(AL-H) or lower than the setting value SV-(AL-L).
Deviation upper-limit:
2
This alarm output operates when PV value is higher than the setting value SV+(AL-H).
Deviation lower-limit:
3
This alarm output operates when PV value is lower than the setting value SV-(AL-L).
Reverse deviation upper- and lower-limit:
4
This alarm output operates when PV value is in the range of the setting value SV+(AL-H) and SV-(AL-L).
Absolute value upper- and lower-limit:
5
This alarm output operates when PV value is higher than the setting value AL-H or lower than setting value AL-L.
Absolute value upper-limit:
6
This alarm output operates when PV value is higher than the setting value AL-H.
Absolute value lower-limit:
7
This alarm output operates when PV value is lower than the setting value AL-L.
Deviation upper- and lower-limit with standby sequence: This alarm output operates when PV value reaches set point (SV value)
8
and the value is higher than the setting value SV+(AL-H) or lower than the setting value SV-(AL-L).
Deviation upper-limit with standby sequence:
9
This alarm output operates when PV value reaches set point (SV value) and the reached value is higher than the setting value SV+(AL-H).
Deviation lower-limit with standby sequence:
10
This alarm output operates when PV value reaches the set point (SV value) and the reached value is lower than the setting value SV-(AL-L).
Hysteresis alarm output: Heating control: This alarm output operates if PV value is higher than the
11
setting value SV+ (AL-H). This alarm output is OFF when PV value is lower than the setting value SV+ (AL-L).
Alarm Type Alarm Output Operation
ON
OFF
SV-(AL-L)
ON
OFF
ON
OFF
ON
OFF
SV-(AL-L)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
SV-(AL-L) SV+(AL-H)
ON
OFF
SV-(AL-L)
AL-L
AL-L
SV
SV
SV
SV
SV
SV+(AL-H)
SV+(AL-H)
SV
SV+(AL-H)
AL-H
L-H
SV+(AL-H)
ON
OFF
SV-(AL-L)
ON
OFF
SV
SV
AL-L
AL-H
Set
Value
Hysteresis alarm output: Cooling control: This alarm output operates if PV value is lower than the
12
setting value SV-(AL-H). This alarm output is OFF when PV value is higher than the setting value SV- (AL-L).
(Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L)
Alarm Type Alarm Output Operation
ON
OFF
AL-H AL-L
SV
With the standby sequence, the alarm output will be temporarily disabled until the PV value reaches the set value. Then, the alarm output will operate. Once the alarming output operation is activated, there is a 1.5 sec. delay time to avoid any malfunction.
8 Specification
Input voltage 100 to 240VAC 50/60Hz
CN740
65.0 min. (2.56)
-
14Vdc
+
Tc
DC 4~20mA
RTD
+
or
-
mm (in)
5A 250Vac
2
6
0
.
.
0
0
0
0
+
-
+
-
) 7
0
.
7
.
5
1
4
(
. n
)
i
6
m
3
.
0
.
2 (
0 6
+0.6
45.0
-0 +0.02
(1.77)
-0
6
1
7
2
8
3
DATA-
9
4
RS-485
5
10
DATA+
11
12
13
14
15
L
AC 100~240V
N
50~60Hz /5VA
ALM2
ALM1
COM
3A 250Vac
Operation voltage range 85% to 110% of rated voltage
Power consumption 5VA max.
Memory protection EEPROM 4K bit (non-volatile memory (number of writes: 100,000)
Display method
Sensor type
2 line x 4 character 7-segment LED display Process value (PV): Red color, Set point (SV): Green color
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
3-wire Platinum RTD: Pt100, JPt100
10 External Dimensions
Dimensions are in millimeter (inch)
CN710
CN730
Control mode PID, ON/OFF, manual or auto-tuning.
Relay output: SPDT (SPST on the 1/16 DIN size series16C), Max. load 250VAC, 5A
Control output
resistive load
Voltage pulse output: DC 14V, Max. output current 40mA
Current output: DC 4 ~ 20m A output (Load resistance: Max. 600Ω)
Display accuracy 0.1% of measuring range.
Sampling rate 0.5 sec.
RS-485 communication
MODBUS ASCII communication protocol (only on models designated with serial communication).
Vibration resistance 10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions
Shock resistance Max. 300m/ s2, 3 times in each 3 axes, 6 directions
Ambient temperature 32°F to 122°F (0°C ~ +50°C)
Storage temperature -4°F ~ 150°F (-20°C ~ +65°C)
Altitude 2,000m or less
CN740
Relative humidity 0% ~ 80% (non-condensing)
9 Plan Cutout & External Dimensions
Panel Cutout [dimensions are in mm (in.)]
CN710
CN730
Terminals Identification
RTD
+
Tc
-
RTD
+
Tc
-
DATA+
RS-485
DATA-
or
DATA+
RS-485
DATA-
or
L
1
11
2
12
3
13
4
14
15
5
16
6
17
7
18
8
19
9
20
10
1
11
2
12
13
3
14
4
15
5
16
6
17
7
18
8
19
9
20
10
COM
ALM2
COM
ALM1
NC
NO
COM
COM
ALM2
COM
ALM1
NC
NO
CO
N
L
N
AC 100~240V 50~60Hz /5VA
3A 250Vac
3A 250Vac
5A 250Vac
DC 4~20mA
3A 250Vac
3A 250Vac
5A 250Vac
DC 4~20mA
14Vdc
AC 100~240V 50~60Hz /5VA
14Vdc
11 Mounting
Mounting Method
Step 1: Insert the controller through the panel cutout. Step 2: Insert the mounting bracket into the mounting groove at the top and bottom of the controller
-
+
Step 3: Push the mounting bracket forward until the bracket stops at panel wall. Step 4: Insert and tighten screws on bracket to secure the controller in place. (The screw torque should be 0.8kgf-cm
to 1.5kgf-cm)
Mounting Bracket Installation
1. 2.
-
+