Omega Products CN63200-DC1-AL User Manual

1
16 DIN Autotune Temperature
and Process Controllers
CN63200 and
CN63400 Series
U PID Control With
Reduced Overshoot
Thermocouples and RTDs
U CN63400 Accepts 0 to 10 Vdc
and 0/4 to 20 mA Signals
U On-Demand Auto-Tuning
of PID Settings
U DC Analog Output
(Optional)
U User Programmable
Function Button
U Front Panel Programming
The CN63200 controllers accepts signals from a variety of temperature sensors (thermocouple or RTD), while the CN63400 controllers accepts either a 0 to 10 Vdc or 0/4 to 20 mAdc input signal. Both controllers can provide an accurate output control signal (time proportional or DC analog output) to maintain a process at a setpoint value. Dual 4-digit displays allow viewing of the process/ temperature and setpoint simultaneously. Front panel indicators inform the operator of the controller and output status. The comprehensive programming allows these controllers to meet a wide variety of application requirements.
Specifications
Display: 2-line by 4-digit, LCD negative
image transmissive with backlighting Top (Process) Display: 7.6 mm H (0.3") digits with red backlighting Bottom (Parameter) Display: 5.1 mm H (0.2") digits with green backlighting
Power:
Line Voltage Models: 85 to 250 Vac, 50/60 Hz, 8 VA Low Voltage Models: DC Power: 18 to 36 Vdc, 4 W AC Power: 24 Vac, ±10%, 50/60 Hz, 7 VA Controls: 3 rubber push buttons for modification and setup of controller parameters, 1 additional button (F1) for user programmable function, 1 external user input (models with alarms) for parameter lockout or other user programmable functions Memory: Non-volatile E all programmable parameters Isolation Level: AC power with respect to all other I/O; 250V working (2300V for 1 minute) Sensor Input to Analog Output: 50V working (500V for 1 minute) Relay Contacts to All Other I/O: 300V working (2300V for 1 minute)
DC Power with Respect to Sensor Input and Analog Output: 50V working
(500V for 1 minute)
Environmental Conditions: Operating Temperature Range:
0 to 50°C (32 to 122°F) Storage Temperature Range:
-40 to 80°C (-40 to 176°F)
CN63200-R1.
P-53
2
PROM retains
Operating and Storage Humidity: 85% max relative humidity (non­ condensing) from 0 to 50°C (32 to 122°F)
Altitude: Up to 2000 meters Connection: Wire-clamping screw
terminals Construction: Black plastic alloy case and collar style panel latch; panel latch can be installed for vertical or horizontal instrument stacking; black plastic textured bezel with transparent display window; controller meets NEMA 4X (IP65) requirements for indoor use when properly installed; Installation Category II, Pollution Degree 2 Weight: 179 g (6.3 oz)
Extended Warranty
OMEGACARESM extended warranty program is available for models shown on this page. Ask your sales representative for full details when placing an order. OMEGACARE labor and equivalent loaners.
Panel Punches Available, Visit
omega.com/
panelpunches
SM
Program
SM
covers parts,
Input Specifications
Sensor Input:
Sample Period: 100 ms (10 Hz rate) Step Response Time: 300 ms typical, 400 msec max to
within 99% of final value with step input
Failed Sensor Response:
Main Control Output(s): Programmable preset output Display: “OPEN” Alarms: Upscale drive Analog Output: Upscale drive when assigned to retransmitted input
Normal Mode Rejection: >40 dB @ 50/60 Hz Common Mode Rejection: >120 dB, DC to 60 Hz Overvoltage Protection: 120 Vac @ 15 s maximum
RTD Inputs (CN63200 Only)
Type: 2- or 3-wire Excitation: 150 µA typical Lead Resistance: 15 Ω max per input lead Resolution: 1 or 0.1° for all typesable, enable or disable Hysteresis: Programmable
Input Type Type Range Standard
100 Ω platinum, -200 to 600°C
385
Alpha = 0.00385 (-328 to 1112°F)
100 Ω platinum, -200 to 600°C No official
392
Alpha = 0.00385 (-328 to 1112°F) standard
120 Ω nickel, -80 to 215°C No official
672
Alpha = 0.00672 -112 to 419°F standard
Ω Linear
resistance
Temperature Indication Accuracy (CN63200 Only): ±(0.3% of span, +1°C) at 23°C (73°F) ambient after 20 minute warm up; includes NIST conformity, cold junction effect, A/D conversion errors and linearization conformity
Span Drift (Maximum): 130 PPM/°C User Input (Only Controllers with Alarms Have a User Input Terminal): Internally pulled up to 7 Vdc (100 KΩ) V
Max: 35V
IN
V
: 0.6V max
IL
V
: 1.5V min
IH
I
: 40 µA max
OFF
Response Time: 120 ms max Functions: Programmable
0.0 to 320.0 Ω N/A
Output Specifications
Control and Alarm Outputs:
Relay Output: Type: Form “A” Contact Rating: 3 A @ 250 Vac or 30 Vdc;
1
/
10 HP @ 120 Vac (inductive load)
Life Expectancy: 100,000 cycles at max load rating (decreasing load and/or increasing cycle time, increases life expectancy)
Logic/SSR Output (Main Control Output Only): Rating: 45 mA max @ 4V min, 7V nominal Main Control: Control: PID or on/off Output: Time proportioning or DC analog
Cycle Time: Programmable Auto-Tune: When selected, sets proportional band, integral time, derivative time, and output dampening time; also sets input filter and (if applicable) cooling gain
Probe Break Action: Programmable Alarms (Optional): 2 relay alarm outputs Reset Action: Programmable; automatic or latched Standby Mode: Programmable; enable or disable Hysteresis: Programmable Sensor Fail Response: Upscale
IEC 751
Thermocouple Inputs (CN63200 Only)
Types: T, E, J, K, R, S, B, N, C, and linear mV Input Impedance: 20 MΩ for all types Lead Resistance Effect: 0.25 µV/Ω Cold Junction Compensation:
<±1°C typical (1.5°C max) error over ambient temperature range Resolution: 1° for types R, S, B and 1 or 0.1° for all other types
TC Display Type Range ANSI BS1843 Standard
-200 to 400°C (+) Blue (+) White
-328 to 752°F (-) Red (-) Blue
-200 to 750°C (+) Violet (+) Brown
-328 to 1382°F (-) Red (-) Blue
-200 to 760°C (+) White (+) Yellow
-328 to 1400°F (-) Red (-) Blue
-200 to 1250°C (+) Yellow (+) Brown
-328 to +2282°F (-) Red (-) Blue 0 to 1768°C No (+) White
32 to 3214°F standard (-) Blue 0 to 1768°C No (+) White
32 to 3214°F standard (-) Blue 149 to 1820°C No No
300 to 3308°F standard standard
-200 to 1300°C (+) Orange (+) Orange
-328 to 2372°F (-) Red (-) Blue 0 to 2315°C No No ASTM
(W5/W6) 32 to 4199°F standard standard E988-96
-5.00 mV to
mV
56.00 mV
Signal Input (CN63400 Only) Max
Input Continuous Range Accuracy* Impedance Overload Res
10 Vdc 0.30 % of rdg
(-1 to 11) + 0.03V 20 mAdc 0.30 % of rdg
(-2 to 22) + 0.04 mA
Accuracies are expressed as percentages over 0 to 50°C
*
(32 to 122°F) ambient range after 20 minute warm-up.
Annunciator: “A1” and “A2” programmable for normal or reverse acting
Cooling: Software selectable (overrides alarm 2) Control: PID or on/off Output: Time proportioning Cycle Time: Programmable Proportional Gain Adjust: Programmable Heat/Cool Deadband Overlap: Programmable Analog DC Output (Optional): Action: Control or retransmission Update Rate: 0.1 to 250 s
Output Range** Accuracy* Compliance Resolution
0 to 10V
+
0 to 20 mA
+
4 to 20 mA
+
Accuracies are expressed as percentages over 0 to 50°C
*
(32 to 122°F) ambient range after 20 minute warm-up.
Outputs are independently jumper selectable for either 10V or
**
20 mA. The output range may be field calibrated to yield approximately 5% overrange and a small underrange (negative) signal.
0.3% of FS
1
2 LSD
0.3% of FS
1
2 LSD
0.3% of FS
1
2 LSD
Wire Color
N/A N/A N/A
ITS-90
ITS-90
ITS-90
ITS-90
ITS-90
ITS-90
ITS-90
ITS-90
1 MΩ 50V 10 mV
10 Ω 100 mA 10 µA
10 kΩ min
500 Ω max
500Ω max
1
/
8000
1
/
8000
1
/
6400
P
P-54