Omega Products CN6201-R User Manual

Page 1
1
UU
16 DIN Ramp/Soak
Temperature/Process
Controllers
om
ega.
A
P
anel
P
v
ailable,
com
/panelpunches
unches
V
is
it
CN6201 Series
$
285
All Models
Ramp/Soak Program
RS485 CommunicationsAlarms (Optional)Retransmission Output
(Optional)
The CN6201 Series temperature controllers have 1 program pattern consisting of 16 segments that can easily be set and operated. The 2 event outputs are provided as standard. External contact input, RS485 communication and retransmission outputs are optional. The universal input supports thermocouple, RTD and voltage input types and the 3 types of outputs. The front panel has a splash-proof and dust-proof design (IP65).
Specifications
PV/SP Data Display: 4-digit, PV/SP
separately
PV Inputs:
Method: Universal input Thermocouple: Types K, J, T, E, R,
S, B, N, L, U, Platinel 2
RTD: Pt100, JPt100 Voltage: 0 to 100 mV, 0 to 5V,
1 to 5V, 0 to 10V
Input Accuracy:
Thermocouple: ±2°C ±1digit RTD: ±1°C ±1digit
Voltage (mV, V): ±0.3% ±1digit Sampling Period: 500 ms Number of Program Patterns: 1 Number of Program Segments: 16 Program Time Span: 0 s to 1599 hr Accuracy of Program Time Span:
±2% of program time span
CN6201-R, $285, shown actual size.
Event Output:
Number of Points: 2 relay Type: PV and time
Power Supply: 100 to 240 Vac or
24 Vac/dc (optional) Safety and EMC Standard: CSA, CE
and UL
Construction (Front Protection): IP65
Input Table
Input Type Range (°C) Range (°F)
-270 to 1370 -300 to 2500
-199.9 to 200 -300 to 400
-199.9 to 999.9 -300 to 2100
-199.9 to 400 -300 to 750
-199.9 to 999.9 -300 to 1800
-200 to 1300 -300 to 2400
-199.9 to 900 -300 to 1600
-199.9 to 400 -300 to 750
Platinel 2 0 to 1390 32 to 2500
-199.9 to 850 -199.9 to 999.9
Pt100
RTD Thermocouple
JPt100 -199.9 to 500 N/A
P-59
-199.9 to 200 -300 to 400
-19.9 to 99.9 -199.9 to 999.9
Dimensions: 48 W x 48 H x 100 mm D (1.89 x 1.89 x 3.94")
Weight: Approx. 200 g (0.44 lb) External Contact Input (Optional):
Run/reset, hold/cancel hold
PV Retransmission Output:
4 to 20 mAdc
0 to 600 32 to 999.9 0 to 400 32 to 750
0 to 1700 32 to 3100 0 to 1700 32 to 3100 0 to 1800 32 to 3200
0 to 400 32 to 750
Page 2
RS485 Communication (Optional):
MODBUS®/Ladder/PC-link protocol
24V Power Supply (Optional):
24 Vdc/24 Vac
Measured Value (PV) Input
Input: 1 point
Type: Universal, selectable by software
ccuracy (at 23 ±2°C Ambient
A
Temperature):
Thermocouple: ±2°C ±1digit
Input -200 to -100°C: ±4°C Input -100 to -0°C: ±3°C Types R and S: ±5°C (±9°C for
0 to 500°C) Type B: ±9°C (accuracy is not guaranteed for 0 to 400°C)
RTD: ±1°C ±1digit
Voltage (mV, V): ±0.3% ±1digit Sampling Period for Measured Value
Input: 500 ms Burn-Out Detection: Functions for
thermocouple or RTD input (burn-out upscale only; cannot be switched off)
Input Resistance: 1 M or greater for thermocouple or mVdc inputs; approx. 1 M for Vdc input
Maximum Allowable Signal Source Resistance: 250 for thermocouple or
mVdc inputs; 2 k for Vdc input
Maximum Allowable Wiring Resistance for RTD Input: 10 /wire (the resistance
values of 3 wires must be the same) Allowable Input Voltage: ±10 Vdc for
thermocouple or mVdc inputs; ±20 Vdc for Vdc input
Noise Rejection Ratio:
Normal Mode Noise: Minimum 40 dB
(50/60 Hz)
Common Mode Noise: Minimum
120 dB (90 dB for Vdc input)
Error of Reference Junction Compensation: ±1.5°C (at 15 to 35°C);
±2.0°C (at 0 to 50°C) The reference junction compensation cannot be switched off
Applicable Standards: Thermocouple and RTD, JIS/IEC/DIN, (ITS90)
Retransmission Output (Optional)
Output Signal: Measured value in
4 to 20 mAdc can be scaled.
Maximum Load Resistance: 600 Output Accuracy: ±0.3% of span (at
23 ±2°C ambient temperature)
Power Supply and Isolation
Power Supply:
Voltage: 110 to 240 Vac (±10%)
24 Vac/Vdc, 20 to 29V of
allowable range
Frequency: 50 or 60 Hz Maximum Power Consumption: 8 VA
max (4 W max); 3 W max (-LV option)
Memory: Non-volatile Withstanding Voltage:
Between Primary and Secondary
Terminals: 1500 Vac for 1 minute
(see Notes 1, 2 and 3)
Insulation Resistance:
etween Primary and Secondary
B Terminals: 20 M or more
at 500 Vdc (see Notes 1, 2 and 3)
Note 1: The primary terminals are the power supply terminals and event output terminals. The secondary terminals are the analog input and output terminals, the voltage pulse output terminals, and the contact input terminals.
Note 2: The withstanding voltage is specified as 2300 Vac per minute to provide a margin of safety.
Note 3: AC/DC 24V terminals are secondary terminals.
Contact Inputs (Optional)
Functions: Hold/cancel hold switching,
Run/reset switching Input: 2 points (with the shared
common terminal)
Type: Non-voltage contact or transistor contact input
Contact Capacity: At least 12V/10 mA On/Off Judgment: On-state for 1 k or
less; off-state for 20 k or greater
Control Output
Output: 1 point
Output Type: Choose one from (1) to (3) below:
(1) Relay Contact Output Contact Capacity: 3 A at 240 Vac or
3 A at 30 Vdc (with resistance load)
Note: The control output relay cannot be replaced by users.
(2) Voltage Pulse Output On Voltage: 12 to 18 Vdc
Load Resistance: 600 or greater Off Voltage: 0.1 Vdc or less
Short-Circuit Current: Approx. 30 mA (3) Current Output Output Signal: 4 to 20 mA Maximum Load Resistance: 600 Output Accuracy: ±0.3% of span
(at 23 ±2°C ambient temperature)
Dimensions: mm (in)
AVAILABLE FOR FAST DELIVERY!
To Order (Specify Model Number)
Model No. Price Description CN6201-R $285 Single output, relay CN6201-DC 285 Single output, DC Pulse CN6201-F 285 Single output, 4 to 20 mA
Comes complete with operator’s manual.
Options
Ordering Suffix Add’l Price Description
-AL $20 Dual alarms
-PV 40 4 to 20 mA retransmission output
-LV N/C 24 Vac/Vdc power
-C4* 95 RS485 communications
-DI * 20 Digital input switching
Only one option can be ordered.
*
Accessories (Field Installable)
Model Number Price Description CNQUENCHARC $8 Noise suppression kit, 110 to 230 Vac
1
DPP-4 475 GE-2117 23 Reference Book: Controller Tuning, PID
Ordering Example: CN16201-R-C4, single output controller, mechanical relay, RS485 communications, $285 + 95 = $380.
P-60
16 DIN panel punch
P
Page 3
One Omega Drive | Stamford, CT 06907 | 1-888-TC-OMEGA (1-888-826-6342) | info@omega.com
EPG05
www.omega.com
UNITED KINGDOM
www. omega.co.uk
Manchester, England
0800-488-488
UNITED STATES
www.omega.com
1-800-TC-OMEGA
Stamford, CT.
CANADA
www.omega.ca
Laval(Quebec)
1-800-TC-OMEGA
GERMANY
www.omega.de
Deckenpfronn, Germany
0800-8266342
Karviná, Czech Republic
FRANCE
www.omega.fr
Guyancourt, France
088-466-342
CZECH REPUBLIC
www.omegaeng.cz
596-311-899
BENELUX
www.omega.nl
Amstelveen, NL 0800-099-33-44
More than 100,000 Products Available!
Temperature
Calibrators, Connectors, General Test and Measurement Instruments, Glass Bulb Thermometers, Handheld Instruments for Temperature Measurement, Ice Point References, Indicating Labels, Crayons, Cements and Lacquers, Infrared Temperature Measurement Instruments, Recorders Relative Humidity Measurement Instruments, RTD Probes, Elements and Assemblies, Temperature & Process Meters, Timers and Counters, Temperature and Process Controllers and Power Switching Devices, Thermistor Elements, Probes and Assemblies,Thermocouples Thermowells and Head and Well Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level Measurement, Magnetic Flowmeters, Mass Flowmeters, Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen Instrumentation, Environmental Instrumentation, pH Electrodes and Instruments, Water and Soil Analysis Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems, Communication Products and Converters, Data Acquisition and Analysis Software, Data Loggers Plug-in Cards, Signal Conditioners, USB, RS232, RS485 and Parallel Port Data Acquisition Systems, Wireless Transmitters and Receivers
Pressure, Strain and Force
Displacement Transducers, Dynamic Measurement Force Sensors, Instrumentation for Pressure and Strain Measurements, Load Cells, Pressure Gauges, Pressure Reference Section, Pressure Switches, Pressure Transducers, Proximity Transducers, Regulators, Strain Gages, Torque Transducers, Valves
Heaters
Band Heaters, Cartridge Heaters, Circulation Heaters, Comfort Heaters, Controllers, Meters and Switching Devices, Flexible Heaters, General Test and Measurement Instruments, Heater Hook-up Wire, Heating Cable Systems, Immersion Heaters, Process Air and Duct, Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
click here to go to the omega.com home page