Omega Products CN616TC1 User Manual

1
4 DIN Economical 6-Zone
PID Temperature Controllers
CN616 Series
U 6-Loop PID Controller U Autotune or
Manual Tuning
U Heat or Cool Control U 20-Segment Ramp/Soak
Profile Per Zone
U Password Protected U User Programmable U RS232 Digital
Communications Standard
U Front Panel Calibration U High, Low or High/Low
Alarm, Latching or Non-Latching
U Programmable
Thermocouple Types J, K, T, R, S, E, B, or C
U 1⁄4 DIN Aluminum Case
The CN616 Series is a highly versatile 6-loop microprocessor­based controller designed for easy front panel or remote setup and operation. Each of 6 zones is sequentially scanned, and active zones are displayed. Individual zones can be locked for monitoring. Each instrument is programmable to meet operator needs for: thermocouple type, temperature units; high, low or high/low alarm configured as latching or non-latching; and autotune with manual trim or manual PID setting. The zone display scan time and ramp/soak can be set by the operator. Parameters and setpoints are retained when power is turned off. Password protection is provided to prevent accidental changes to calibration, PID setting and ramp/
CN616TC1 shown actual size.
soak profile. If power loss occurs, the controller retains all the latest parameters and returns to “RUN” mode.
All CN616 controllers have RS232 3-wire serial communications. The RS232 program is capable of monitoring up to 10 daisy­chained units.
Line voltage is 120 Vac or 240 Vac selectable by external jumper assembly. Connections are made to the back of the instrument through easy-to-use screw terminal plugs.
The CN616 Series implements a security password to protect settings. The password can be enabled or disabled on the front panel and changed via RS232. Calibration is performed via the front panel and is separately password protected. Higher level passwords are available.
The instrument is housed in a
1
4 DIN
aluminum box which does not have to be removed for mounting. The unit mounts in a 1⁄4 DIN panel cutout and is secured by slide brackets. The device is controlled via 6 DC pulse outputs (1 for each zone).
A single output relay is provided to indicate an alarm condition on any zone. The instrument shows an alarm condition by flashing the main temperature display while indicating the zone in alarm with a flashing zone number display. When set to non-latching, the alarm automatically resets when the condition changes. The alarm must be manually reset in the latching setting.
The controller functions in 2 modes— “RUN”, the basic operating mode, and “FUNCTION SELECT”, the password protected settings selection and control mode.
Panel punches
available, visit
omega.com/
panelpunches
P-83
Specifications
Number of Loops: 6 Accuracy: ±0.1% of max range Resolution: ±1°C or °F Temperature Units: °C or °F Thermocouple Input:
Selectable J, K, E, T, S, R, B or C
PID: Autotune or manual Password Protection: Calibration and
PID changes Profiling: Ramp/soak,
20 segments/loop
Loop Configuration: Heat or cool Control Output: 6 DC pulse outputs
(1 per zone); designed to drive 3 to 32 Vdc input solid-state relays
Control Output Voltage:
5 Vdc at 10 mA per loop
Alarms Rating: 5 A @ 120 Vac Alarms Selectable: High, low, or high/
low; latching or non-latching single relay for 6 loops
Zone in Alarm: Flashing Latch Reset: Manual RS232 Communications: Single-drop
daisy-chain up to 10 controllers Baud Rate: 4800 Data Bits: 8 Parity: N Stop: 1 Protocols:
ASCII line computer interface Communication Software: Windows
compatible, written in Visual Basic
Terminals: Headers for plug-in wiring Enclosure:
152 mm (6") L Power Loss: Controller retains
the last setting
Display: 14 mm (0.56") LED, 4-digit Front Bezel: 99 mm
1
4 DIN
CN616
1
4 DIN aluminum,
2
(3.90 in2)
Dimensions: mm (inch)
Temperature/ Setpoint Display
Zone Setting
Set/Shift/ Reset Button
SM
Extended Warranty
Program
OMEGACARE warranty program is available for models shown on this page. Ask
your sales representative for full
details when placing an order. OMEGACARE
labor and equivalent loaners.
SM
extended
SM
covers parts,
152 (6.0)
92 (3.62)
Advance Digit Button
Software Configuration Screen
Load Button
Temperature Scale Selection
92 (3.62)
Function Setting
Input Types and Ranges Standard Range Extended Range
Thermocouple Input Type CN616 (TC1) CN616 (TC2)
Pt/30% Rh-Pt/6% Rh
32 to 3300°F
W/5% Re-W/26% Re
32 to 4200°F
CHROMEGA®–Constantan
32 to 1000°F 32 to 1652°F
Iron–Constantan
32 to 1300°F
CHROMEGA®–ALOMEGA
32 to 1800°F 32 to 2282°F
Pt/13% Rh-Pt
32 to 3200°F
Pt/10% Rh-Pt
32 to 3200°F
Copper–Constantan
32 to 750°F
0 to 1750°C
0 to 1750°C
0 to 1800°C
0 to 2300°C
0 to 550°C 0 to 900°C
0 to 700°C
®
0 to 1000°C 0 to 1800°C
0 to 400°C
P
1
4 DIN
CN606 Series companion scanner, also available. Visit omega.com/cn606_612 for details.
To Order Visit omega.com/cn616 for Pricing and Details
Model No. Description CN616TC1 6-zone thermocouple input controller CN616TC2 CNQUENCHARC
Comes complete with software and operator’s manual. Ordering Example: CN616TC1, 6-loop temperature controller with 20-segment ramp and
soak on each loop and RS232 communications. OCW-3, OMEGACARESM extends standard 2-year warranty to a total of 5 years.
6-zone thermocouple input controller with extended range Noise suppression RC snubber (2 leads), 110 to 230 Vac
P-84