Mitsubishi PU-P35YGAA, PUH-P35VGAA, PUH-P50VGAA, PU-P50VGAA, PUH-P50YGAA Service Manual

...
Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT -TYPE, AIR CONDITIONERS
SERVICE MANUAL
R407C
Outdoor unit [model names]
PUH-P25VGAA PUH-P35VGAA PU-P35VGAA PUH-P35YGAA PU-P35YGAA PUH-P50VGAA PU-P50VGAA PUH-P50YGAA PU-P50YGAA PUH-P60VGAA PU-P60VGAA PUH-P60YGAA PU-P60YGAA
[Service Ref.]
Service Ref. is on page 2.
August 2005
No.OC336
• This manual describes only service data of the outdoor units.
PUH-P71VGAA PU-P71VGAA PUH-P71YGAA PU-P71YGAA PUH-P100VGAA PU-P100VGAA PUH-P100YGAA PU-P100YGAA PUH-P125YGAA PU-P125YGAA PUH-P140YGAA PU-P140YGAA
CONTENTS
1. REFERENCE MANUAL··································3
2. SAFETY PRECAUTION ··································4
3. PART NAMES AND FUNCTIONS··················6
4. SPECIFICATIONS ···········································7
6. OUTLINES AND DIMENSIONS····················18
7. WIRING DIAGRAM·······································22
8. WIRING SPECIFICATIONS ··························24
9.
REFRIGERANT SYSTEM DIAGRAM
10. TROUBLESHOOTING··································30
11. FUNCTION SETTING ···································65
12. DISASSEMBLY PROCEDURE·····················71
13. PARTS LIST··················································75
··············28
Page 2
[Service Ref.]
PUH-P25VGAA.UK PUH-P35VGAA.UK PU-P35VGAA.UK PUH-P35YGAA.UK PU-P35YGAA.UK PUH-P50VGAA.UK PU-P50VGAA.UK PUH-P50YGAA.UK PU-P50YGAA.UK PUH-P60VGAA.UK PU-P60VGAA.UK PUH-P60YGAA.UK PU-P60YGAA.UK PUH-P71VGAA.UK PU-P71VGAA.UK PUH-P71YGAA.UK PU-P71YGAA.UK PUH-P100VGAA.UK PU-P100VGAA.UK PUH-P100YGAA.UK PU-P100YGAA.UK PUH-P125YGAA.UK PU-P125YGAA.UK PUH-P140YGAA.UK PU-P140YGAA.UK
2
Page 3
1-1. INDOOR UNIT'S SERVICE MANUAL
Model name Service Ref. Service
Manual No. PLA-RP35/50/60/71AA PLA-RP35/50/60/71AA.UK OC335 PLA-RP100/125/140AA PLA-RP100/125/140AA.UK PLH-P35/50/60/71AAH PLH-P35/50/60/71AAH.UK PLH-P100/125/140AAH PLH-P100/125/140AAH.UK PMH-P25/35/50BA PMH-P25/35/50BA OC333
PCA-RP50/60/71/100/125/140GA PCA-RP50/60/71/100/125/140GA OC328 PCH-P50/60/71/100/125/140GAH PCH-P50/60/71/100/125/140GAH PCA-RP71/125HA PCA-RP71/125HA OC329
PKA-RP35/50GAL PKA-RP35/50GAL OC330 PKH-P35/50GALH PKH-P35/50GALH PKA-RP60/71/100FAL PKA-RP60/71/100FAL OC331 PKH-P60/71/100FALH PKH-P60/71/100FALH PSA-RP71/100/125/140GA PSA-RP71/100/125/140GA OC332 PSH-P71/100/125/140GAH PSH-P71/100/125/140GAH PEAD-RP35/50/60/71EA PEAD-RP35/50/60/71EA.UK ­PEAD-RP100/125/140EA PEAD-RP100/125/140EA.UK PEHD-P35/50/60/71EAH PEHD-P35/50/60/71EAH.UK ­PEHD-P100/125/140EAH PEHD-P100/125/140EAH.UK PEAD-RP60/71/100GA PEAD-RP60/71/100GA.UK -
1-2. TECHNICAL DATA BOOK
1
REFERENCE MANUAL
Manual No.OCS02
3
Page 4
2
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.
Use ESTER , ETHER or HAB as the lubricant to coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Use liquid refrigerant to charge the system.
If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant deterioration.
Store the piping to be used during installation indoors with keep both ends sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Gravimeter
Unit
SAFETY PRECAUTION
CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R407C
[1] Cautions for service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
4
Page 5
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2 Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3 Electronic scale 4 Gas leak detector ·Use the detector for R134a or R407C. 5 Adapter for reverse flow check. ·Attach on vacuum pump. 6 Refrigerant charge base. 7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8 Refrigerant recovery equipment.
5
Page 6
3 PART NAMES AND FUNCTIONS
Air intake
Air outlet (Expels warm air during cooling)
Air intake
Air outlet
Air intake
Air outlet
Air intake
Air outlet
PUH-P25VGAA.UK PUH-P35VGAA.UK PUH-P35YGAA.UK
PU-P35VGAA.UK PU-P35YGAA.UK
PUH-P50VGAA.UK PUH-P50YGAA.UK PUH-P60VGAA.UK PUH-P60YGAA.UK PUH-P71VGAA.UK PUH-P71YGAA.UK
PU-P50VGAA.UK PU-P50YGAA.UK PU-P60VGAA.UK PU-P60YGAA.UK PU-P71VGAA.UK PU-P71YGAA.UK
PUH-P100VGAA.UK PUH-P100YGAA.UK
PU-P100VGAA.UK PU-P100YGAA.UK
CHARGELESS SYSTEM PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
PU/PUH-P25, P35, P50, P60 : max 20m PU/PUH-P71, P100, P125, P140 : max 30m
The refrigerant circuit with LEV(Linear Expansion Valve) and a large accumulator always control the optimal refrigerant
level regardless of the length (20/30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality and reliability of the work done.It also helps to speed up the installation time.
PUH-P125YGAA.UK PUH-P140YGAA.UK
PU-P125YGAA.UK PU-P140YGAA.UK
6
Page 7
4 SPECIFICATIONS
A A
kW
W
kW
K
/min(CFM
)
dB
dB mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
L mm(in.) mm(in.)
Mode Power supply (phase, cycle, voltage)
Running current
Max current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater Heat exchanger Fan Fan(drive) o No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
OUTDOOR UNIT
REFRIGERANT PIPING
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Service Ref.
PUH-P25VAA.UK
PUH-P35VGAA / YGAA.UK
Cooling
5.32
Single,50Hz,230V
7.23
RE189VHSMT
0.9
45(1,590)
46 48
50(110)
1.7(3.8)
6.35(1/4)
12.7(1/2)
Max. 30m Max. 30m
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
Line start
30
Plate fin coil
Propeller (direct) o 1
0.07
Reverse cycle
900(35-7/16)
330+20(13+3/4)
650(25-5/8)
R407C
0.57(Ester)MEL56
Flared Flared
Heating
4.89
Cooling
7.61 / 2.54
Single,50Hz,230V / 3-ph,50Hz,400V
10.67/5.4
RE277VHSMT/RE277YFKM
1.3
45(1,590)
47 49
54(119)
2.5(5.5)
9.52(3/8)
15.88(5/8)
Max. 40m Max. 40m
Heating
7.85 / 2.62
Internal thermostat
HP switch
Discharge thermo
Thermal relay HP switch Discharge thermo
Internal thermostat HP switch Discharge thermo
A A
kW
W
kW
K
/min(CFM
)
dB
dB mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
L mm(in.) mm(in.)
Mode Power supply (phase, cycle, voltage)
Running current
Max current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater Heat exchanger Fan Fan(drive) o No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
OUTDOOR UNIT
REFRIGERANT PIPING
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Service Ref.
PUH-P50VGAA / YGAA.UK
PUH-P60VGAA / YGAA.UK
Cooling
10.97 / 3.98
15.35 /7.0
NE36VMJMT / NE36YEKMT
1.6
55(1,940)
49
74(163)
2.6(5.7)
Max. 40m Max. 40m
Single, 50Hz, 230V / 3-ph, 50Hz,400V(4wires)
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
Line start
38
Plate fin coil
Propeller (direct) o 1
0.07
Reverse cycle
48
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
R407C
1.2 (Ester)MEL56
9.52(3/8)
15.88(5/8) Flared Flared
Heating
11.30 / 3.95
Cooling
13.27 / 4.43
18.03 / 7.7
NE41VMJMT / NE41YEKMT
1.9
50(1,770)
50
79(174)
3.1(6.8)
Max. 50m Max. 50m
Heating
12.84/ 4.29
Internal thermostat
HP switch
Discharge thermo
Thermal relay HP switch Discharge thermo
4-1. HEAT PUMP
7
Page 8
Service Ref.
Mode Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger
OUTDOOR UNIT
Fan Fan(drive) o No.
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D. Connection method Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current Max current
Model Motor output Starter type Protection devices
Crankcase heater
Fan motor output Airflow
Charge Oil (Model)
K
/min(CFM
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
mm(in.) mm(in.)
kW
W
kW
dB dB
PUH-P71VGAA / YGAA.UK
A A
L
Cooling
15.66 / 5.23
NE52VNJMT / NE52YDKMT
)
Single, 50Hz, 230V / 3-ph, 50Hz, 400V(4wires)
22.66 / 10.8
Propeller (direct) o 1
50(1,770)
855(33-5/8)
79(174)
3.3(7.3)
15.88(5/8)
Heating
16.67 / 5.56 Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
2.5 Line start
Internal thermostat
HP switch
Discharge thermo
Plate fin coil
0.07 Reverse cycle
49 51
900(35-7/16)
330+20(13+3/4)
R407C
1.3 (Ester)MEL56
9.52(3/8) Flared
Flared
Max. 50m Max. 50m
PUH-P100VGAA / YGAA.UK
Cooling
16.43/ 5.48
23.57 / 10.8
NE56VNJMT / NE56YDKMT
Thermal relay HP switch Discharge thermo
38
Propeller (direct) o 2
0.07+0.07 85(3,000)
1,260(49-5/8)
97(214)
4.0(8.8)
19.05(3/4)
Heating
17.34 / 5.79
2.7
51 53
Service Ref.
Mode Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger
OUTDOOR UNIT
Fan Fan(drive) o No.
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D. Connection method Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current Max current
Model Motor output Starter type Protection devices Crankcase heater
Fan motor output Airflow
Charge Oil (Model)
/min(CFM
K
Cooling Heating
W D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
mm(in.) mm(in.)
A A
kW
W
kW
dB(A) dB(A)
L
PUH-P125YGAA.UK
Cooling
7.52
BE82YADMT
)
95(3,360)
4.6(10.1)
Heating
3-ph, 50Hz, 400V(4wires)
8.06
18.0 Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
3.5 Line start
Thermal relay, HP switch, Discharge thermo
38
Plate fin coil
Propeller (direct) o 2
0.07 +0.07
Reverse cycle 55 56
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
125(276)
R407C
1.7 (Ester) MEL56
9.52(3/8)
19.05(3/4) Flared Flared
Max. 50m Max. 50m
PUH-P140YGAA.UK
Cooling
8.92
20.4
BE96YADMT
4.2
100(3,530)
57 58
4.9(10.8)
Heating
9.45
8
Page 9
4-2. COOLING ONLY TYPE
A A
kW
W
kW
K
/min(CFM
)
dB mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
L mm(in.) mm(in.)
Mode Power supply (phase, cycle, voltage)
Running current
Max. current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater Heat exchanger Fan Fan(drive) o No.
Fan motor output
Airflow Defrost method Noise level Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
OUTDOOR UNIT
REFRIGERANT PIPING
Cooling
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Service Ref. PU-P71VGAA / YGAA.UK PU-P100VGAA / YGAA.UK
Cooling
15.66 / 5.23
22.66 / 10.8
NE52VNJMT / NE52YDKMT
2.5
Propeller (direct) o 1
0.07
50(1,770)
49
855(33-5/8)
79(174)
3.3(7.3)
15.88(5/8)
Single, 50Hz, 230V / 3-ph, 50Hz, 400V(4wires)
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
Line start
38
Plate fin coil
900(35-7/16)
330+20(13+3/4)
R407C
1.3 (Ester)MEL56
9.52(3/8) Flared
Flared
Max. 50m Max. 50m
Cooling
16.43/ 5.48
23.57 / 10.8
NE56VNJMT / NE56YDKMT
2.7
Propeller (direct) o 2
0.07+0.07 85(3,000)
51
1,260(49-5/8)
97(214)
4.0(8.8)
19.05(3/4)
Internal thermostat
HP switch
Discharge thermo
Thermal relay HP switch Discharge thermo
Service Ref.
Mode Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
OUTDOOR UNIT
Heat exchanger Fan Fan(drive) o No.
Defrost method Noise level
Dimensions Weight
Refrigerant
Pipe size O.D. Connection method Between the indoor &
REFRIGERANT PIPING
outdoor unit
Running current Max. current
Model Motor output Starter type Protection devices Crankcase heater
Fan motor output Airflow
Charge Oil (Model)
/min(CFM
K
Cooling
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
mm(in.) mm(in.)
A A
kW
W
kW
dB
L
PU-P35VGAA / YGAA.UK
Cooling
Single, 50Hz, 230V / 3-ph, 50Hz, 400V(4wires)
7.61 / 2.54
10.67 / 5.4
RE277VHSMT/RE277YFKM
Internal thermostat, HP switch, Discharge thermo / Thermal relay,Discharge thermo,HP switch
)
1.3
30
45(1,590)
47
650(25-5/8)
54(119)
2.5(5.5)
0.57 (Ester)MEL56
PU-P50VGAA / YGAA.UK
Cooling
10.97 / 3.98
15.35 / 7.0
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
NE36VMJMT/NE36YEKMT
1.6
Line start
Plate fin coil
Propeller (direct) o 1
0.07
55(1,940)
900(35-7/16)
330+20(13+3/4)
74(163)
R407C
2.6(5.7)
9.52(3/8)
15.88(5/8) Flared Flared
Max. 40m Max. 40m
PU-P60VGAA / YGAA.UK
Cooling
13.27 / 4.43
18.03 / 7.7
NE41VMJMT/NE41YEKMT
1.9
38
50(1,770)
48
855(33-5/8)
79(174)
3.1(6.8)
1.2 (Ester)MEL56
Max. 50m Max. 50m
9
Page 10
Service Ref.
Mode Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
OUTDOOR UNIT
Heat exchanger Fan Fan(drive) o No.
Defrost method Noise level Dimensions
Weight Refrigerant
Pipe size O.D. Connection method Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current Max. current
Model Motor output Starter type Protection devices Crankcase heater
Fan motor output Airflow
Cooling
Charge Oil (Model)
Indoor side Outdoor side Height difference Piping length
W
D H
Liquid
Gas
/min(CFM
K
mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
mm(in.) mm(in.)
kW
W
kW
dB
PU-P125YGAA.UK PU-P140YGAA.UK
Cooling
A A
)
L
7.52
18.0
BE82YADMT
3.5 Thermal relay, HP switch, Discharge thermo
95(3,360)
55
4.6(10.1)
3-ph, 50Hz,400V(4wires)
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
Line start
38
Plate fin coil
Propeller (direct) o 2
0.07+0.07 —
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
125(276)
R407C
1.7 (Ester) MEL56
9.52(3/8)
19.05(3/4) Flared Flared
Max. 50m Max. 50m
Cooling
8.92
20.4
BE96YADMT
4.2
100(3,530)
57
4.9(10.8)
10
Page 11
5 DATA
Piping length (one way)
10m 20m 30m
40m
50m
Factory charged
1.6
2.4
2.4
2.5
2.5
2.9
2.9
2.9
2.9
3.4
3.4
4.0
4.3
1.7
2.5
2.5
2.6
2.6
3.1
3.1
3.1
3.1
3.7
3.7
4.3
4.6
1.8
2.6
2.6
3.1
3.1
3.3
3.3
3.3
3.3
4.0
4.0
4.6
4.9
3.0
3.0
3.7
3.7
3.9
3.9
3.9
3.9
4.7
4.7
5.3
5.6
4.5
4.5
4.5
4.5
5.4
5.4
6.0
6.3
1.7
2.5
2.5
2.6
2.6
3.1
3.1
3.3
3.3
4.0
4.0
4.6
4.9
Service Ref.
PUH-P140YGAA.UK PU-P140YGAA.UK
PUH-P125YGAA.UK PU-P125YGAA.UK
PUH-P100VGAA.UK PU-P100VGAA.UK
PUH-P100YGAA.UK PU-P100YGAA.UK
PUH-P71YGAA.UK PU-P71YGAA.UK
PUH-P71VGAA.UK PU-P71VGAA.UK
PUH-P60YGAA.UK PU-P60YGAA.UK
PUH-P60VGAA.UK PU-P60VGAA.UK
PUH-P50YGAA.UK PU-P50YGAA.UK
PUH-P50VGAA.UK PU-P50VGAA.UK
PUH-P35YGAA.UK PU-P35YGAA.UK
PUH-P35VGAA.UK PU-P35VGAA.UK
PUH-P25VGAA.UK
Compressor model
Winding
Resistance
( " )
U-V
(R-C)
U-W
(S-C)
W-V
U-V
(R-C)
U-W
(S-C)
W-V
RE277VHSMT RE277YFKM
Unit
NE36VMJMT
1.80
3.00 —
10.8
10.8
10.8
5.01
5.01
5.01
NE36YEKMT
0.89
2.03 —
Unit
Compressor model
Winding
Resistance
( " )
(at 20°C)
BE96YADMTBE82YADMT
2.123
2.123
2.123
NE52VNJMT
0.64
1.67 —
3.59
3.59
3.59
1.963
1.963
1.963
NE56YDKMT
3.32
3.32
3.32
PUH-P35VGAA.UK PU-P35VGAA.UK
PUH-P35YGAA.UK PU-P35YGAA.UK
PUH-P50VGAA.UK PU-P50VGAA.UK
PUH-P50YGAA.UK PU-P50YGAA.UK
PUH-P25VGAA.UK
PUH-P60YGAA.UK PU-P60YGAA.UK
PUH-P60VGAA.UK PU-P60VGAA.UK
PUH-P71VGAA.UK PU-P71VGAA.UK
PUH-P100VGAA.UK PU-P100VGAA.UK
PUH-P71YGAA.UK PU-P71YGAA.UK
PUH-P125YGAA.UK PU-P125YGAA.UK
PUH-P100YGAA.UK PU-P100YGAA.UK
U-V
(R-C)
U-W
(S-C)
W-V
Unit
Compressor model
Winding
Resistance
( " )
NE41VMJMT
NE41YEKMT
5.00
5.00
5.00
NE56VNJMT
0.62
1.59 —
RE189VHSMT
2.79
3.36 —
0.87
2.22 —
NE52YDKMT
PUH-P140YGAA.UK PU-P140YGAA.UK
5-1. REFILLING REFRIGERANT CHARGE (R407C : kg)
PRE- CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
5-2. COMPRESSOR TECHNICAL DATA
11
Page 12
5-3. NOISE CRITERION CURVES
1m
1m
MICROPHONE
UNIT
GROUND
SPL(dB)48LINE
PUH-P25VGAA.UK
90
MODE
COOLING
HEATING
SPL(dB)49LINE
46
PUH-P35VGAA.UK PUH-P35YGAA.UK PU-P35VGAA.UK
MODE
COOLING
HEATING
47
PU-P35YGAA.UK
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PUH-P50VGAA
.UK PUH-P50YGAA.UK PU-P50VGAA.UK PU-P50YGAA.UK
90
80
MODE COOLING HEATING
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
SPL(dB) LINE
48 49
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PUH-P60VGAA.UK PUH-P60YGAA.UK PU-P60VGAA.UK PU-P60YGAA.UK
90
80
MODE COOLING HEATING
SPL(dB) LINE
48 50
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
70
60
50
40
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
12
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
Page 13
PUH-P71VGAA.UK PUH-P71YGAA.UK PU-P71VGAA.UK PU-P71YGAA.UK
90
MODE COOLING HEATING
SPL(dB) LINE
49 51
PUH-P100VGAA.UK PUH-P100YGAA.UK PU-P100VGAA.UK PU-P100YGAA.UK
90
MODE
COOLING
HEATING
SPL(dB)
51 53
LINE
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PUH-P125YGAA.UK PU-P125YGAA.UK
90
MODE COOLING
HEATING
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
SPL(dB) LINE
55 56
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PUH-P140YGAA.UK PU-P140YGAA.UK
90
MODE COOLING HEATING
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
SPL(dB) LINE
57 58
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
13
Page 14
5-4. STANDARD OPERATION DATA
Heat pump type
Representative matching
Mode
Capacity
TotalElectrical circuitRefrigerant circuitIndoor side
Input
Indoor unit
Phase , Hz Volts Amperes
Outdoor unit
Phase , Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
side
Outdoor
SHF
BF
D.B.
W.B.
D.B. D.B.
W.B.
W
kW
V A
V
A MPa MPa
°C °C °C
m
°C °C °C °C °C
PMH-P25BA
Cooling
3,100
1.14
PMH-P25BA
0.19
PUH-P25VGAA.UK
1, 50
230
5.13
2.01
0.55 71 48
8.0
5 27 19
13.3 35 24
0.77
0.09
Heating
3,350
1.05
1, 50
230
0.19
1, 50
230
4.72
1.85
0.44 70 44
4.0
5 20 15
41.5 7 6
— —
PLA-RP35AA
Cooling
4,500
1.72
PLA-RP35AA PLA-RP50AA PLA-RP60AA
PUH-P35VGAA.UK PUH-P35YGAA.UK
7.43/1.94
2.01
0.59 78 48 11
5 27 19
14.1 35 24
0.75
0.16
Heating
4,950
1.70
1 , 50
230
0.79
1/3 , 50
230/400
7.33/1.91
1.92
0.37 77 48
1
5 20 15
38.9 7 6
— —
PLA-RP50AA
Cooling
5,600
2.53
PUH-P50VGAA.UK PUH-P50YGAA.UK
11.30/3.23
2.48
0.59 85 55 10
5 27 19
14.6 35 24
0.82
0.12
Heating
1 , 50
230
0.79
1/3 , 50
230/400
9.72/2.70
6,350
2.20
1.96
0.38 76 45
0
5 20 15
38.9 7 6
— —
PLA-RP60AA
Cooling
6,700
2.57
1 , 50
230
0.79
PUH-P60VGAA.UK PUH-P60YGAA.UK
1/3 , 50
230/400
11.49/3.29
2.18
0.54 80 51
9
5 27 19
12.9 35 24
0.72
0.14
Heating
7,300
2.40
10.68/3.02
1.92
0.38 75 47
1
5 20 15
41.9 7 6
— —
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is : 1(MPa)=10.2(kgf/ff)
14
Page 15
Representative matching
PLA-RP71AA PLA-RP100AA
PLA-RP125AA
PLA-RP140AA
Mode
Capacity
TotalElectrical circuitRefrigerant circuitIndoor side
Input
Indoor unit
Phase , Hz Volts Amperes
Outdoor unit
Phase , Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
side
Outdoor
SHF
BF
D.B.
W.B.
D.B. D.B.
W.B.
Cooling
W
7,700
kW
MPa MPa
°C °C °C
°C °C °C °C °C
3.42
V A
PUH-P71VGAA.UK PUH-P71YGAA.UK
V A
15.55/4.64
2.30
0.47 81 44
m
27 19
13.4 35 24
0.74
0.13
Heating
9,200
3.48
PLA-RP71AA PLA-RP100AA
1 , 50
230
0.79
1/3 , 50
230/400
15.84/4.74
2.38
0.39
5 5
45.1
Cooling
9,600
3.68
PUH-P100VGAA.UK PUH-P100YGAA.UK
16.33/4.59
1.98
0.54 88 45
0
5 20 15
7
6 — —
71 42
8
5 27 19
14.0 35 24
0.78
0.12
Heating
10,500
3.91
1 , 50
230
1.25
1/3 , 50
230/400
17.43/4.96
2.12
0.42 75 47
1
5 20 15
40.1 7 6
— —
Cooling
13,300
5.09
PLA-RP125AA
1 , 50
230
1.64
PUH-P125YGAA.UK
3 , 50
400
6.44
2.11
0.48 71 41
6
5 27 19
11.7 35 24
0.72
0.06
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is : 1(MPa)=10.2(kgf/ff)
Heating
15,600
5.54
7.16
2.39
0.42 79 44
0
5 20 15
48.7 7 6
— —
Cooling
14,200
5.90
PLA-RP140AA
PUH-P140YGAA.UK
7.73
2.27
0.45
11.3
0.69
0.09
81 45
27 19
35 24
2 5
Heating
17,000
6.35
1 , 50
230
1.64
3 , 50
400
8.44
2.36
0.41 84 46
-1 5
20 15
51.2 7 6
— —
15
Page 16
Cooling only type
Representative matching
Mode
Capacity
TotalElectrical circuitRefrigerant circuitIndoor side
Input
W
kW
PLA-RP35AA
Cooling
4,500
1.72
PLA-RP50AA
Cooling
5,600
2.53
PLA-RP60AA
Cooling
6,700
2.57
Indoor unit
Phase , Hz Volts Amperes
Outdoor unit
Phase , Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
side
Outdoor
SHF
BF
D.B.
W.B.
D.B. D.B.
W.B.
V A
V
A MPa MPa
°C °C °C
m
°C °C °C °C °C
PLA-RP35AA
1 , 50
230
0.79
PU-P35VGAA.UK PU-P35YGAA.UK
1/3 , 50
230/400
7.43/1.94
2.01
0.59 78 48 11
5 27 19
14.1 35 24
0.75
0.16
PLA-RP50AA
1 , 50
230
0.79
PU-P50VGAA.UK PU-P50YGAA.UK
1/3 , 50
230/400
11.30/3.23
2.48
0.59 85 55 10
5 27 19
14.6 35 24
0.82
0.12
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is : 1(MPa)=10.2(kgf/ff)
PLA-RP60AA
1 , 50
230
0.79
PU-P60VGAA.UK PU-P60YGAA.UK
1/3 , 50
230/400
11.49/3.29
2.18
0.54 80 51
9
5 27 19
12.9 35 24
0.72
0.14
16
Page 17
Representative matching
Mode
Capacity
TotalElectrical circuitRefrigerant circuitIndoor side
Input
W
kW
PLA-RP71AA PLA-RP100AA
Cooling
7,700
3.42
Cooling
9,200
3.68
PLA-RP125AA
Cooling
13,300
5.09
PLA-RP140AA
Cooling
14,200
5.90
Indoor unit
Phase , Hz Volts Amperes
Outdoor unit
Phase , Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
side
Outdoor
SHF
BF
D.B.
W.B.
D.B. D.B.
W.B.
V A
PU-P71VGAA.UK PU-P71YGAA.UK
V
A MPa MPa
°C °C °C
m
°C °C °C °C °C
PLA-RP71AA PLA-RP100AA
1 , 50
230
0.79
1/3 , 50
230/400
15.55/4.64
2.30
0.47 81 44
5
5 27 19
13.4 35 24
0.74
0.13
1 , 50
230
1.25
PU-P100VGAA.UK PU-P100YGAA.UK
1/3 , 50
230/400
16.33/4.59
1.98
0.54 71 42
8
5 27 19
14.0 35 24
0.78
0.12
PLA-RP125AA
1 , 50
230
1.64
PU-P125YGAA.UK PU-P140YGAA.UK
3 , 50
400
6.44
2.11
0.48 71 41
6
5 27 19
11.7 35 24
0.72
0.06
PLA-RP140AA
1 , 50
230
1.64
3 , 50
400
7.73
2.27
0.45 81 45
2
5 27 19
11.3 35 24
0.69
0.09
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is : 1(MPa)=10.2(kgf/ff)
17
Page 18
6 OUTLINES AND DIMENSIONS
321
T SR
w1 248
w1 196
500
Power Supply Wiring Hole
(2-[27Knock-Out)
Right Piping Hole
(Knock-Out)
Power Supply Wiring Hole
(2-[27Knock-Out)
Terminal Connections
Left...Power supply Wiring
Right..Indoor/Outdoor Wiring
70
70
15515515510930
21585
Bottom Piping Hole
(Knock-Out)
Drain Hole
(5-[33holes)
18
18
424
900
318
Handle for moving
Earth Point
Service Panel
Front Piping Cover
Rear Piping Cover
1
2
Side Air
Intake
200200
53
370
(14)
412
29
330
55
4351
Rear Air Intake
Air Discharge
2-U Shaped notched holes
(Foundation Bolt M10)
2-12x40 oval holes
(Foundation Bolt M10)
20
28
58
Installation Feet
Rear
Air
Intake
Side
Air
Intake
Handle for
moving
3
230220220230
637
650
3030
Rear Trunking Hole
(Knock-Out)
< Rear Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
40
33
22 55
68 63
65
92
Rear Piping Hole
(Knock-Out)
[
92
Piping Knock-Out Hole Details
. .
Refrigerant GAS pipe connection (FLARE)P35V(Y)GAA: [15.88 (5/8F)
. .
Refrigerant LIQUID pipe connection (FLARE)P35V(Y)GAA: [9.52 (3/8F)
. .
Height of STOP VALVE connection location.
1
2
< Right Side >< Front Side >
Explanation of Notes
40
68 63
22 55
65
92
33
27
100
50
50
100
33
[92
Front Piping Hole
(Knock-Out)
5540
3
. .
3-[3.6 holes (for securing the top of the unit)
These holes are provided for cases where the unit must
be secured by the base AND by the top surface.
Use Self Tapping screws 5 x L15 or less.(Obtained locally)
w1
. .
Refrigerant GAS pipe connection (FLARE)P25VGAA : [12.7 (1/2F)
. .
Refrigerant LIQUID pipe connection (FLARE)P25VGAA : [6.35 (1/4F)
1
2
O
ve
r 10m
m
FRE
E
O
ver 500m
m
Less than
30mm
FREE SPACE (Around the Unit)
Piping and wiring connections
can be made from 4 directions:
Front, Right, Rear and Below.
FOUNDATION BOLTS
1
The diagram below shows a
basic example.
Explanation of particular details are
given in the installation manuals etc.
SERVICE SPACE
Dimensions of space needed
for service access are
shown in the below diagram.
2
Over500
Over500
PIPING-WIRING DIRECTIONS
43
FOUNDATION
<Foundation bolt height>
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally).
Service Space
O
ve
r 1
00m
m
O
ver 1
0m
m
Over10
Over100
OUTDOOR UNIT PUH-P25VGAA.UK PUH-P35VGAA.UK PUH-P35YGAA.UK PU-P35VGAA.UK PU-P35YGAA.UK
Unit : mm
18
Page 19
PUH-P50VGAA.UK PUH-P50YGAA.UK PUH-P60VGAA.UK PUH-P60YGAA.UK PUH-P71VGAA.UK PUH-P71YGAA.UK PU-P50VGAA.UK PU-P50YGAA.UK PU-P60VGAA.UK PU-P60YGAA.UK PU-P71VGAA.UK PU-P71YGAA.UK
412 (14) 29
200500200
2-U Shaped notched holes
(Foundation Bolt M10)
370
55
28 53
43
51
58
Terminal Connections
Left...Power supply Wiring
Right..Indoor/Outdoor Wiring
Service Panel
Handle
321TSR
Earth Point
Unit : mm
627
w1 428
w1 376
Rear Piping Cover
Bottom Piping Hole
1
2
Front Piping Cover
18 70
(Knock-Out)
70
18
Drain Hole
(5-[33holes)
PIPING-WIRING DIRECTIONS
4
Piping and wiring connections
can be made from 4 directions:
Front, Right, Rear and Below.
FOUNDATION
FOUNDATION BOLTS
3
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally).
30mm
Less than
<Foundation bolt height>
Over100
Rear Air Intake
Over500
Installation Feet
Side Air
Intake
92
[
68 63
15515515510930
Rear Piping Hole
(Knock-Out)
92
65 22 55 33
900
Air Discharge
330
20
2-12x40 oval holes
318
(Foundation Bolt M10)
Rear
Side
Air
Intake
230220220230
3
Handle
Air
Intake
442
3030
840
855
21585
Rear Trunking Hole
(Knock-Out)
< Rear Side >
40
Power Supply Wiring Hole
(2-[27Knock-Out)
Over500
SERVICE SPACE
2
Dimensions of space needed
for service access are
shown in the below diagram.
Over10
m
ver 100m
FRE
FREE SPACE (Around the Unit)
The diagram below shows a
basic example.
Explanation of particular details are
1
ver 10m
given in the installation manuals etc.
O
O
E
m
r 10m
ve
O
m
00m
ver 5
O
Service Space
m
Refrigerant LIQUID pipe connection (FLARE) [9.52 (3/8F)
Height of STOP VALVE connection location.
3-[3.6 holes (for securing the top of the unit)
Refrigerant GAS pipe connection (FLARE) [15.88 (5/8F)
. . .
. . .
. . .
These holes are provided for cases where the unit must
. . .
1w12
Explanation of Notes
be secured by the base AND by the top surface together.
3
19
Use Self Tapping screws 5 x L15 or less.
(Obtained Locally)
Handle
5540
< Right Side >
100
Power Supply Wiring Hole
(2-[27Knock-Out)
40
< Front Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
50
33
100
27
68 63
33 22 55
92
[92
Piping Knock-Out Hole Details
Front Trunking Hole
(Knock-Out)
Right Piping Hole
(Knock-Out)
50
65
Front Piping Hole
(Knock-Out)
Page 20
PUH-P100VGAA.UK
4
PIPING-WIRING DIRECTIONS
3
FOUNDATION BOLTS
FOUNDATION
Piping and wiring connections
can be made from 4 directions:
Front, Right, Rear and Below.
SERVICE SPACE
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally).
30mm
<Foundation bolt height>
Less than
Over500
Over100
Service Space
Over500
1
FREE SPACE (Around the Unit)
Dimensions of space needed
for service access are
shown in the below diagram.
2
The diagram below shows a
basic example.
Explanation of particular details are
given in the installation manuals etc.
Over10
O
ver 10m
m
FRE
E
O
v
er 5
00
m
m
O
ver 100m
m
O
ver 10m
m
Explanation of Notes
. . .
Refrigerant GAS pipe connection(FLARE) [19.05 (3/4F)
. . .
Refrigerant LIQUID pipe connection(FLARE) [9.52 (3/8F)
. . .
Height of STOP VALVE connection location.
. . .
3-[3.6 holes (for securing the top of the unit)
These holes are provided for cases where the unit must
be secured by the base AND by the top surface together.
Use Self Tapping screws 5 x L15 or less.
(Obtained Locally)
3
2
w1
1
PUH-P100YGAA.UK PU-P100VGAA.UK PU-P100YGAA.UK
Unit : mm
29
200500200
2-U Shaped notched holes
(Foundation Bolt M10)
Installation Feet
Rear Air Intake
Side Air
Intake
370 (14)
330
412
50
58
Terminal Connections
28 53
4351
Air Discharge
20
2-12x40 oval holes
(Foundation Bolt M10)
Left...Power supply Wiring
Right..Indoor/Outdoor Wiring
Service Panel
900
318
Rear
Intake
Air
Side
Air
Intake
Earth Point
598
Handle
Handle
1033
W1 428
W1 376
1
2
33
352
Rear Piping Cover
Front Piping Cover
70
18
70 18
Bottom Piping Hole
(Knock-Out)
85 215
Drain Hole
(5-[33Holes)
30 109 155 155 155
230220220
230
3
1246
1260
3030
< Rear Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
Rear Trunking Hole
(Knock-Out)
40
92
[
6368
5522
Rear Piping Hole
(Knock-Out)
92
65
33
Handle
Right Piping Hole
(Knock-Out)
4055
1002733
6368
5522
[92
50
50
33
65
92
< Right Side >
100
Power Supply Wiring Hole
(2-[27Knock-Out)
40
< Front Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
Piping Knock-Out Hole Details
Front Piping Hole
Front Trunking Hole
(Knock-Out)
(Knock-Out)
20
Page 21
PUH-P125YGAA.UK PUH-P140YGAA.UK PU-P125YGAA.UK PU-P140YGAA.UK
Unit : mm
29
225600
2-U Shaped notched holes
(Foundation Bolt M10)
Installation Feet
Rear Air Intake
Side Air
Intake
PIPING-WIRING DIRECTIONS
4
Piping and wiring connections
can be made from 4 directions:
Front, Right, Rear and Below.
1033
Terminal Connections
Left...Power supply Wiring
370 (14)
53
50
4453
58
Right..Indoor/Outdoor Wiring
Service Panel
1050
Earth Point
Handle
w1 478
w1 422
1
2
Rear Piping Cover
Bottom Piping Hole
70 18
Front Piping Cover
1870
(Knock-Out)
Drain Hole
(5-[33Holes)
14814814817230 109
Air Discharge
398
330
20
598
352
21585
Handle
2-12x40 oval holes
(Foundation Bolt M10)
Rear
Air
Side
Air
Intake
230295295230
Intake
55
FOUNDATION
FOUNDATION BOLTS
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally).
30mm
Less than
<Foundation bolt height>
Over100
Over500
Over500
SERVICE SPACE
23
Dimensions of space needed
for service access are
shown in the below diagram.
Over10
m
ver 100m
FRE
E
FREE SPACE (Around the Unit)
The diagram below shows a
basic example.
Explanation of particular details are
1
v
given in the installation manuals etc.
O
O
m
er 10m
m
ver 10m
O
ver 500m
O
Service Space
m
3
Refrigerant GAS pipe connection(FLARE) [19.05 (3/4F)
Refrigerant LIQUID pipe connection(FLARE) [9.52 (3/8F)
Height of STOP VALVE connection location.
3-[3.6 holes (for securing the top of the unit)
. . .
. . .
. . .
. . .
These holes are provided for cases where the unit must
Explanation of Notes
1
be secured by the base AND by the top surface together.
2
3
w1
21
1246
1260
Handle
Use Self Tapping screws 5 x L15 or less.
(Obtained Locally)
Rear Trunking Hole
(Knock-Out)
92
92
[
< Rear Side >
40
5522
6368
4055
1002733
6368
5522
[92
33
50
33
92
Power Supply Wiring Hole
(2-[27Knock-Out)
< Right Side >
100
Power Supply Wiring Hole
(2-[27Knock-Out)
40
< Front Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
Piping Knock-Out Hole Details
Front Trunking Hole
(Knock-Out)
Rear Piping Hole
(Knock-Out)
65
Right Piping Hole
(Knock-Out)
50
65
Front Piping Hole
(Knock-Out)
Page 22
<Notes when servicing> Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with your finger and pull it out.
SYMBOL NAME SYMBOL NAME
MC COMPRESSOR (INNER THERMOSTAT) MF FAN MOTOR (INNER THERMOSTAT) TH3 THERMISTOR LIQUID TEMP TH4 DISCHARGE TEMP TH6 COND. / EVA. TEMP C3 MF CAPACITOR C4 MF CAPACITOR C5 MC CAPACITOR CH CRANKCASE HEATER 52C MC CONTACTOR
21S4 4-WAY VALVE SOLENOID COIL
63H HIGH PRESSURE PROTECT SWITCH 49C INNER THERMOSTAT FOR MC TB1 TERMINAL BLOCK LEV LINEAR EXPANSION VALVE TB2 TERMINAL BLOCK
O.B OUTDOOR CONTROLLER BOARD FUSE1 (O.B) FUSE (6.3A) FUSE2 (O.B) FUSE (6.3A) FUSE3 (O.B) FUSE (6.3A) FUSE4 (O.B) FUSE (6.3A) X51 (O.B) MC/CH RELAY
X52 (O.B) 21S4 RELAY
F.C (O.B) FAN CONTROLLER SW1 (O.B) GROUP NUMBER ADDRESS SW4 (O.B) TEST RUN SW5 (O.B) FUNCTION SELECTION J1)~J6 (O.B) MODEL SELECTION T (O.B) TRANSFORMER CT (O.B) CURRENT TRANS LED1 (O.B)
OPERATION CHECK DISPLAY LED
LED2 (O.B)
OPERATION CHECK DISPLAY LED
CN31 (O.B) EMERGENCY OPERATION CONNECTER
O.B
INDOOR
UNIT
SCR
MC
R E D
W H T
B L U
R E D
Y L W
O R N
B R N
B L U
C3
WHT BLK
WHT WHT
BRN BRN
RED
BLU
49C
J1J2J3J4J5
J6
MF
LEV
CT
MF3
(WHT)
C4
*1
*1 PU(H)-P100VGAA MODEL ONLY *2 PUH-P25~ P100VGAA MODEL ONLY
WHT BLK
MF
MF4
(WHT)
52C
(PNK)
CH
(BLU)
52C
S1
S1
SW1 SW4
SW5
CNM
LED1 (GRN) LED2 (RED)
S1
TB4
POWER SUPPLY
~/ N
230V 50Hz
S2
S2
S2
S3
S3
FUSE3
FUSE4
S3
a b
63H
CH
52C
TB1
TB2
LN
T
OFF
ON
CNLEV
(WHT)
CNVMNT
(WHT)
CNMNT
(WHT)
TH4
(WHT)
TH3/TH6
(RED)
RED
BLU
BLK
GRY
BLK
ORN YLW WHT
BRN
TH4
TH6
TH3
CN31
F.C
X51
C5
2 / T 1
6 / T 3
1 / L 1
5 / L 3
4/S
R
FUSE2
FUSE1
BLU BLU
21S4
(GRN)
21S4
X52
*2
7 WIRING DIAGRAM
PUH-P25VGAA.UK PUH-P35VGAA.UK PUH-P50VGAA.UK PUH-P60VGAA.UK PUH-P71VGAA.UK PUH-P100VGAA.UK PU-P35VGAA.UK PU-P50VGAA.UK PU-P60VGAA.UK PU-P71VGAA.UK PU-P100VGAA.UK
22
Page 23
PUH-P35YGAA.UK PUH-P50YGAA.UK PUH-P60YGAA.UK PUH-P71YGAA.UK PUH-P100YGAA.UK PUH-P125YGAA.UK PUH-P140YGAA.UK PU-P35YGAA.UK PU-P50YGAA.UK PU-P60YGAA-UK PU-P71YGAA.UK PU-P100YGAA.UK PU-P125YGAA.UK PU-P140YGAA.UK
SYMBOL NAME SYMBOL NAME
MC COMPRESSOR MF FAN MOTOR (INNER THERMOSTAT) TH3 THERMISTOR LIQUID TEMP TH4 DISCHARGE TEMP TH6 COND. / EVA. TEMP C3 MF CAPACITOR C4 MF CAPACITOR CH CRANKCASE HEATER 52C MC CONTACTOR
21S4 4-WAY VALVE SOLENOID COIL
SV BYPASS VALVE SOLENOID COIL 63H HIGH PRESSURE PROTECT SWITCH 51C THERMAL RELAY TB1 TERMINAL BLOCK LEV LINEAR EXPANSION VALVE TB2 TERMINAL BLOCK 63L LOW PRESSURE PROTECT SWITCH
MC
UVW
R
W
B
E
H
L
T
K
6
4
/
/
T
T
3
2
51C
52C
5
3
/
/
L
L
3
2
BLK WHT RED
W
B
B
H
L
L
T
K
U
3N~
400V 50Hz
C4
*2
C3
CH
*4
*1
*3
D
2 / T 1
1 / L 1
R E D
L1 L2 L3 N
TB1
POWER SUPPLY
<Notes when servicing> Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with your finger and pull it out.
52C
21S4
SV
PE
MF
MF
51C
63L
a b
63H
WHT BLK
WHT BLK
BRN BRN
WHT WHT
BLU BLU
BLK BLK ORN ORN
WHT WHT
TB2
MF4
(WHT)
MF3
(WHT)
52C
(PNK)
(*1BLK)
CH
(*1BLK)
(BLU)
21S4
(GRN)
SV
(BLK)
51CM (ORN)
63L
(RED)
4/S
Y
O
B
L
R
R
W
N
N
S1
S2
S3
O.B OUTDOOR CONTROLLER BOARD FUSE1 (O.B) FUSE (6.3A) FUSE2 (O.B) FUSE (6.3A) FUSE3 (O.B) FUSE (6.3A) FUSE4 (O.B) FUSE (6.3A) X51 (O.B) MC/CH RELAY X52 (O.B) 21S4 RELAY X53 (O.B) SV RELAY F.C (O.B) FAN CONTROLLER SW1 (O.B) GROUP NUMBER ADDRESS SW4 (O.B) TEST RUN SW5 (O.B) FUNCTION SELECTION J1~J6 (O.B) MODEL SELECTION T (O.B) TRANSFORMER CT (O.B) CURRENT TRANS LED1 (O.B) OPERATION CHECK DISPLAY LED LED2 (O.B) OPERATION CHECK DISPLAY LED CN31 (O.B) EMERGENCY OPERATION CONNECTER
X51
X52
X53
FUSE2
F.C
RST
CT
CNM
ON
OFF
FUSE1
FUSE4
FUSE3
CNVMNT
SW5
CN31
(WHT)
LED1 (GRN) LED2 (RED)
SW1 SW4
J1J2J3J4J5
S1 S2
S3
CNMNT
(WHT)
J6
TH3/TH6
(RED)
T
*1 PUH-P125/140YGAA MODEL ONLY *2 PU(H)-P100/125/140YGAA MODEL ONLY *3 PU(H)-P125/140YGAA MODEL ONLY *4 PUH-P35~ P140YGAA MODEL ONLY
S3
INDOOR
S2
UNIT
S1
TB4
CNLEV
(WHT)
TH4
(WHT)
O.B
BRN RED
BLU ORN YLW
WHT
BLK
BLK
GRY
LEV
TH4
TH6
TH3
23
Page 24
8 WIRING SPECIFICATIONS
1 2
S1 S2 S3
S1 S2 S3
Indoor/outdoor unit connection cable
Indoor unit
Unit power supply
Outdoor unit
Remote controller
L
B
N
B Earth leakage breaker C wiring circuit breaker or
isolating switch
C
B
B Earth leakage breaker C wiring circuit breaker or
isolating switch
C
L
N
1 2
1 2
S1
Indoor unit
S2 S3
S1 S2 S3
S1 S2 S3
Unit power supply
Indoor/outdoor unit connection cable
Indoor unit
Outdoor unit
Remote controller
B
B Earth leakage breaker C wiring circuit breaker or
isolating switch
C
1 2
1 2
1 2
S1 S2 S3
S1 S2 S3
S1 S2 S3
S1 S2 S3
Indoor/outdoor connection cable
Indoor unit
Unit power supply
Indoor unit
Indoor unit
Outdoor unit
Remote controller
L N
8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model Outdoor unit power supply
Outdoor unit input capacity *1 Main switch (Breaker)
Outdoor unit power supply
)
2
Outdoor unit power supply earth Indoor unit-Outdoor unit *2
Wiring
Indoor unit-Outdoor unit earth *2
Wire No. o
size (mm
Remote controller-Indoor unit *3 Outdoor unit L-N (single) Outdoor unit L1-N, L2-N, L3-N (3 phase) Indoor unit-Outdoor unit S1-S2 *4 Indoor unit-Outdoor unit S2-S3 *4
Circuit rating
Remote controller-Indoor unit *4
*1. A breaker with at least 3 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV). *2. Refer to 8-2. *3. The 10 m wire is attached in the remote controller accessory. *4. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulataed by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed fle xib le cord. (Design 245 IEC 57)
3. Install an earth longer than other cables.
230V
Single phase
P25,35V P50,60V P71,100V P35,50,60,71,100Y P125, 140Y
~/N (single), 50 Hz, ~/N (single), 50 Hz, ~/N (single), 50 Hz, 3N ~ (3phase), 50 Hz,3N ~ (3phase), 50 Hz,
230 V 230 V 230 V 400 V400 V
16 A 25 A 32 A 16 A 25 A
2 o Min. 1.5 2 o Min. 2.5 2 o Min. 4 4 o Min. 1.5 4 o Min. 2.5 1 o Min. 1.5 1 o Min. 2.5 1 o Min. 4 1 o Min. 1.5 1 o Min. 1.5
3 o 1.5 (Polar) 3 o 1.5 (Polar) 3 o 1.5 (Polar) 3 o 1.5 (Polar) 3 o 1.5 (Polar)
1 o Min. 1.5 1 o Min. 1.5 1 o Min. 1.5 1 o Min. 1.5 1 o Min. 1.5
2 o 0.3 (Non-polar) 2 o 0.3 (Non-polar) 2 o 0.3 (Non-polar) 2 o 0.3 (Non-polar) 2 o 0.3 (Non-polar)
*4
AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V
DC 24 V DC 24 V DC 24 V DC 24 V DC 24 V DC 12 V DC 12 V DC 12 V DC 12 V DC 12 V
A-Control
Outdoor Unit
Isolator
S1
S2
S3
3 poles isolator
S1
S2
S3
A-Control
Indoor Unit
Warning: In case of A-control wiring, there is high v oltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between po wer line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-poles type.
1:1 system Synchronized twin and triple system Electrical wiring
• Synchronized twin
• Synchronized triple
24
Page 25
Cross section
of cable
Round
2.5
2.5
1.5
2.5
3
3
4
4
(50)
2
(45)
3
60 4
Not
applicable
5
Flat
1 : Power supply cords of appliances shall not be lighter than design 245 IEC or 227 IEC.2 : In case that cable with stripe of yellow and green is available.3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
2
.
4 : In case of regular polarity connection (S1-S2-S3). 5 : In the flat cables are connected as this picture, they can be used up to 80m.
6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, Humidity or materials, etc.
Flat
Round
Wire size
(mm
2
)
Number of wires
Clockwise : S1-S2-S3 w Pay attention to stripe of yellow and green
Clockwise : S1-S2-S3-Open w Connect S1 and S3 to the opposite angle
Not applicable (Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Polarity
L(m)
6
(3C Flat cable 2)
S1 S2 S3
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections). Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the intermediate connection point. (If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.)
8-2. INDOOR-OUTDOOR CONNECTING CABLE
25
Page 26
8-3. M-NET WIRING METHOD
Group remote controller
Refrigerant address 00
M-NET address 01
A-control remote controller
A-control remote controller
A-control remote controller
Refrigerant address 00
M-NET address 02
Refrigerant address 00
M-NET address 03
Power supply unit for transmission wire
Central remote controller
M-NET transmission wire
Bad example (Multi spot grounding of shield wire)
Good example 1 (Single spot grounding of shield wire)
Power supply appliance
M-NET type outdoor unit
Central remote controller
Power supply appliance
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET transmission wire
M-NET type outdoor unit
M-NET type outdoor unit
Central remote controller
Power supply appliance
M-NET type outdoor unit
M-NET transmission wire
M-NET type outdoor unit
M-NET type outdoor unit
Good example 2 (Single spot grounding of shield wire)
(Points to notice) (1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET p.c. board may be burn out.
(3) Use 2-core x 1.25mm2shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this because this may cause a malfunction.
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit. “0403” error will appear on the central-control remote controller.
If there are more than two grounding spots on the shield wire, noise may enter into the shield wire because the ground wire
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
and shield wire form one circuit and the electric potential difference occurs due to the impedance difference among ground­ing spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and shield wire do not form one circuit.
installation manual.
26
Page 27
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
12
~
50
M-NET Address No.
<Setting example>
Switng setting
SW11 ones digit
SW12 tens digit
OFF
ON
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
0
Refrigerant address
OFF
ON
8
OFF
ON
1
OFF
ON
9
OFF
ON
10
OFF
ON
11
OFF
ON
12
OFF
ON
13
OFF
ON
14
OFF
ON
15
OFF
ON
2
OFF
ON
3
OFF
ON
4
OFF
ON
5
OFF
ON
6
OFF
ON
7
System controller
A-control remote controller
Group A Group B Group C
A-control remote controller
TB5
A-control remote controller
Refrigerant address 00
M-NET address 01
Refrigerant address 00
M-NET address 02
Refrigerant address 01
M-NET address 03
Refrigerant address 00
M-NET address 04
Power supply unit for transmission wire
A-control remote controller
A-control remote controller
TB5
Group A Group B
Refrigerant address 00
M-NET address 01
Refrigerant address 01
M-NET address 02
Refrigerant address 00
M-NET address 04
Refrigerant address 01
M-NET address 03
Refrigerant address 02
M-NET address 05
System controller
Power supply unit for transmission wire
M-NET wiring
(1) Use 2-core x 1.25mm
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block.Connect one core of the
transmission wire (non-polar) to Aterminal and the other to B. Peel the shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(A, B, S) on M-NET terminal block should be individually wired to the other
2
shield wire for electric wires.
M-NET terminal block
ABS
Transmission
wire
Shield part
Ground wire
outdoor unit’s terminal, i.e. Ato A, B to B and S to S.In this case, choose one of those outdoor units and drive a screw to fix an ground wire on the plate as shown on the right figure.
8-3-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to Free Combo system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as that of the indoor unit in Free Combo system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches (SW11 for ones digit and SW12 for tens digit), which is located on the M-NET board of outdoor unit. (Factory setting: all addresses are set to “0”.)
8-3-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group set­ting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Factory setting: all switches are OFF. (All refrigerant addresses are “00”.)]
8-3-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above sec­tion. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
w Refrigerant addresses can be overlapped if they are in the different group.
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the group for the outdoor unit whose refrigerant address is “00”.
27
Page 28
9
Service port
Accumulator
Compressor
Refrigerant GAS pipe
19.05A({3/4")
Refrigerant LIQUID pipe
9.52A({3/8") Stop valve (with service port)
4-way valve
Service port
High pressure protect switch
Thermistor (TH3)
Capillary tube (O.D.4.0I.D.3.0-L350)2pcs
Refrigerant flow in cooling Refrigerant flow in heating
Liner expansion valve
Thermistor (TH4)
Muffler
Thermistor (TH6)
Distributor with strainer
Ball valve
(#50)
Strainer
(#100)
Strainer
(#100)
Strainer
Service port
Accumulator
Ball valve
Compressor
Refrigerant GAS pipe P25···12.7A({1/2") P35~P71···15.88A({5/8")
Refrigerant LIQUID pipe P25···6.35A({1/4") P35~P71···9.52A({3/8")
Stop valve (with service port)
4-way valve
Service port
High pressure protect switch
Outdoor heat exchanger
Thermistor (TH3)
Thermistor (TH6)
Distributor with strainer
Muffler
Thermistor(TH4)
Linear expansion valve
Refrigerant flow in cooling Refrigerant flow in heating
(#50)
Strainer
(#100)
Strainer
(#100)
Strainer
Service port
Accumulator
Compressor
Refrigerant GAS pipe
19.05A({3/4")
Refrigerant LIQUID pipe
9.52A({3/8")
4-way valve
Service port
High pressure protect switch
Thermistor (TH3)
Capillary tube (O.D.4.0I.D.3.0-L200)2pcs
Drier
Liner expansion valve
Muffler
Thermistor (TH4)
Thermistor (TH6)
Distributor with strainer
Refrigerant flow in cooling Refrigerant flow in heating
w1 : O.D.4.0I.D.2.0-L400(PUH-P125)
O.D.4.0I.D.3.0-L450(PUH-P140)
Ball valve
(#50)
Strainer
Strainer
(#100)
Strainer
(#100)
Strainer
(#50)
Low pressure protect switch
Stop valve
(with service port)
Capillary tube w1
REFRIGERANT SYSTEM DIAGRAM
PUH-P25VGAA.UK PUH-P35VGAA.UK PUH-P50VGAA.UK PUH-P60VGAA.UK PUH-P71VGAA.UK PUH-P35YGAA.UK PUH-P50YGAA.UK PUH-P60YGAA.UK PUH-P71YGAA.UK
<4-way valve solenoid coil>
Heating : ON Cooling : OFF
PUH-P100VGAA.UK PUH-P100YGAA.UK
PUH-P125YGAA.UK PUH-P140YGAA.UK
28
Page 29
Service port
Accumulator
Compressor
Refrigerant GAS pipe
19.05A({3/4")
Refrigerant LIQUID pipe
9.52A({3/8")
Stop valve (with service port)
Service port
High pressure protect switch
Thermistor (TH3)
Capillary tube (O.D.4.0I.D.3.0-R350)2pcs
Refrigerant flow in cooling
Liner expansion valve
Thermistor (TH4)
Thermistor (TH6)
Distributor with strainer
Ball valve
(#50)
Strainer
(#100)
Strainer
(#100)
Strainer
PU-P35VGAA.UK PU-P50VGAA.UK PU-P60VGAA.UK PU-P71VGAA.UK
Service port
Accumulator
Compressor
Refrigerant GAS pipe
15.88A({5/8")
Refrigerant LIQUID pipe
9.52A({3/8")
Stop valve (with service port)
Service port
High pressure protect switch
Outdoor heat exchanger
Thermistor (TH3)
Thermistor (TH6)
Distributor with strainer
Thermistor(TH4)
Linear expansion valve
Refrigerant flow in cooling
Ball valve
(#50)
Strainer
(#100)
Strainer
(#100)
Strainer
Service port
Accumulator
Compressor
Refrigerant GAS pipe
19.05A({3/4")
Refrigerant LIQUID pipe
9.52A({3/8")
Service port
High pressure protect switch
Thermistor (TH3)
Capillary tube (O.D.4.0I.D.3.0-L200)2pcs
Drier
Thermistor (TH4)
Thermistor (TH6)
Distributor with strainer
Refrigerant flow in cooling
Stop valve (with service port)
Liner expansion valve
Ball valve
(#50)
Strainer
Strainer
(#100)
Strainer
(#100)
(#50)
Strainer
Low pressure protect switch
PU-P35YGAA.UK PU-P50YGAA.UK PU-P60YGAA.UK PU-P71YGAA.UK
PU-P100VGAA.UK PU-P100YGAA.UK
PU-P125YGAA.UK PU-P140YGAA.UK
29
Page 30
10 TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “10-4. Self-diagnosis action table”.
Conduct trouble shooting and ascertain the cause of the inferior phenomenon according to “10-5. Troubleshooting by inferior phenomena”.
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, matters related to wiring and etc. 2Reset error code logs and restart the unit after finishing service. 3There is no abnormality concerning of parts such as electrical component, controller board, remote controller and etc.
1Re-check the abnormal symptom. 2Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “10-5. Troubleshooting by inferior phenomena”. 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality concerning of parts such as electrical component, controller board, remote controller and etc.
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit. Actions to be taken for service, which depends on whether or not the inferior phenomenon is reoccurring at service, are sum­marized in the table below. Check the contents below before investigating details.
10-2. CHECK POINT UNDER TEST RUN
(1) Before test run
After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Merger and check that it is 1.0M" or over.
wDon’t use 500V Merger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
Make sure that test run switch (SW4) is set to OFF before turning on power supply.
Turn on power supply twelve hours before test run in order to protect compressor.
For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “Selection of Functions through Remote Controller”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
30
Page 31
[TEST] button
Pipe (liquid) temperature
Displays the remaining test run time.
"TEST RUN" and the currently selected operation mode are displayed altemately.
A
B
C
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after two hours.
Remote Controller Display
Symptoms in test run mode
OUTDOOR BOARD LED Display
Cause
Remote controller displays “PLEASE WAIT”, and
cannot be operated.
After power is turned on, “PLEASE WAIT” is displayed for 3 minutes, then error code is displayed.
No display appears even when remote controller operation switch is turned on. (Operation lamp does not light up.)
Display appears but soon disappears even when remote controller is operated.
• After power is turned on, “PLEASE WAIT” is displayed for 2 minutes during
system startup. (Normal)
• Incorrect connection of outdoor terminal block (L
1, L2, L3 and
S1, S2, S3.)
• Outdoor unit’s safeguard installation connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity is wrong for S1, S2, S3.)
• Remote controller transmission wire short.
• There is no outdoor unit of address 0. (Address is other than 0.)
• Remote controller transmission wire burnout.
• After canceling function selection, operation is not possible for about 30 seconds. (Normal)
After “startup” is displayed, only green lights up. <00> After “startup” is displayed, green(once) and red(once) blink alternately. <F1> After “startup” is displayed, green(once) and red(twice) blink alternately. <F3, F5, F9> After “startup” is displayed, green(twice) and red(once) blink alternately. <EA. Eb>
After “startup” is displayed, only green lights up. <00>
After “startup” is displayed, only green lights up. <00>
< > indicates digital display.
2. Press TEST button twice.
1. Turn on the main power supply.
3. Press OPERATION SWITCH button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for correct running.
6. Press the ON/OFF button to reset the test run in progress.
7. Register the contact number.
While the room temperature display on the remote controller is “PLEASE WAIT”, the remote controller is disabled. Wait until “PLEASE WAIT” disappears before using remote controller. “PLEASE WAIT” appears for about 2 minutes after power supply is turned on. w1
The outdoor unit features automatic capacity control to provide optimum fan speeds. Therefore, the fan keeps running at a low speed to meet the current outside air condition unless it exceeds its available maximum power. Then, in actuality, the fan may stop or run in the reverse direction depending on the outside air, but this does not mean malfunction.
Check for correct motion of auto-vanes.
Cooling mode:
Check if cool air blows and water is drained. Heating mode: Check if warm air blows. (It takes a little while until warm air blows.)
The TEST RUN appears on the screen.
Operating procedures
B
C
A
LCD
Contents of inferior phenomena
P1 P2 P4 P5 P6 P8 P9 Fb
Abnormality of room temperature thermistor Abnormality of pipe temperature thermistor/Liquid Abnormality of drain sensor Drain overflow protection is working. Freezing/overheating protection is working. Abnormality of pipe temperature Abnormality of pipe temperature thermistor/Cond./Eva Abnormality of indoor controller board
LCD
Contents of inferior phenomena
U1~UP
F3~F9 E0~E5 E6~EF
----
FFFF
Malfunction outdoor unit Malfunction
outdoor unit Remote controller transmitting error Indoor/outdoor unit communication error No error history No applied unit
LED1
(microcomputer power supply)
LED2
(remote controller)
LED3
(indoor/outdoor communication)
Lits when power is supplied. Lits when power is supplied for wired remote controller. The indoor unit should be connected to the outdoor unit with address “0” setting.
Flash when indoor and outdoor unit are communicating.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin and triple operation. Malfunctions may not be displayed regardless of incorrect wiring.
w1 After turning on the power supply, the system will go into startup mode, “PLEASE WAIT” will blink on the display section of
the room temperature, and lamp(green) of the remote controller will flash. As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case the address is not 0. LED3 will blink. As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will light up. (After the startup mode of the system finishes, LED2(red) will be turned off.) In case OUTDOOR BOARD LED is digital display, and will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from the symptoms. The below symptoms are under test run mode. “startup” in the table means the display status of w1 written above.
w Press the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the contents of LCD
display.
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
31
Page 32
7
MODE
MODE
COOL
HEAT
TEST RUN
FAN
VANE
TEST RUN
ON
SW4
12
A Stop B Cooling C Operation D Heating
A
CD
B
(Factory setting)
3,4
2
ON/OFF
MODE
CHECK
TEST RUN
SET
TEST RUN
FAN
VANE
LOUVER
RESET
CLOCK
TEMP
AUTO STOP
AUTO START
h
min
5
6
Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on the outdoor unit and ground with a 500V Megger and check that it is equal to or greater than 1.0M
1 Turn on the main power to the unit. 2 Press the button twice continuously.
(Start this operation from the status of remote controller display turned off.) A and current operation mode are displayed.
3 Press the ( ) button to activate mode, then
check whether cool air is blown out from the unit.
4 Press the ( ) button to activate mode, then
check whether warm air is blown out from the unit.
5 Press the button and check whether strong air is blown out
from the unit.
6 Press the button and check whether the auto vane operates
properly.
7 Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver while following steps 22to 77.
• It is not possible to run the in FAN, DRY or AUTO mode.
".
(2) Outdoor Unit
1) Check Items
• After installation of indoor and outdoor units, and tubing and electric wiring work, check that the unit is free from leaks of refrigerant, loosened connections, and incorrect polarity.
• Check that there is no negative phase and open phase. (The F1 message for negative phase and the F2 message for open phase will flash at digital indicator LED 1 on the outdoor substrate. If this happens, rewire correctly.)
• Measure the impedance between power terminals (Single phase: L,N,;;/ triple phase: L1,L2,L3,;;) and the ground with a 500V Merger and check that it is 1.0Mor more. Do not operate the equipment if measurement is less than 1.0mΩ. *Never conduct this operation on the out- door connection wiring terminals (S1,S2,S3) as this causes damage.
• When there is no error at the outdoor unit. (If there is an error at the outdoor unit, it can be evaluated at LED 1 [digital display] of the outdoor substrate.)
• The stop valves are open both the liquid and gas sides. After checking the above, execute the test run in accordance with the following.
2) Test run start and finish
• Operation from the indoor unit Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit. Execute settings for test run start, finish and operation mode (cooling, heating) using the DIP switch SW 4 on the outdoor substrate.
1 Set the operation mode (cooling, heating) using SW4-2. 2 Turn ON SW 4-1, The operation mode for SW 4-2 will be adhered to, and the test run will commence. 3 Turn OFF SW 4-1 to finish the test run.
• There may be a faint knocking noise emitted from the proximity of the fan during the test run. This is torque fluctuation occurring due to control of fan revolutions. There is no problem with the product.
Note: The SW 4-2 operation mode cannot be changed during the test run. (To change run mode, stop the equipment with SW 4-1, change the operation mode, then restart test run with SW 4-1.)
32
Page 33
10-3. HOW TO PRECEED "SELF-DIAGNOSIS"
10-3-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop, and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the temperature display, and the error code and unit number are displayed alternately as shown below.
1 (If the outdoor unit is malfunctioning, the unit number will be "00".) 2 In the case of group control, for which one remote controller controls
multiple refrigerant systems, the refrigerant address and error code of the unit that first experienced trouble (i.e., the unit that transmitted the error code) will be displayed.
3 To clear the error code, press the
button.
When using remote-/handheld-controller combined operation, cancel the error code after turning off remote operation. During central control by a MELANS controller, cancel the error code by pressing the
button.
10-3-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote controller or power is shut off.
Check the error code history for each unit using the remote controller.
1
Switch to self-diagnosis mode.
H
Press the
button twice within three seconds. The display content
will change as shown below.
2
Set the unit number or refrigerant address you want to diagnose.
F
Press the [TEMP] buttons ( and ) to select the desired number or address. The number (address) changes between [01] and [50] or [00]
3
Display self-diagnosis results. <When there is error code history> (For the definition of each error code, refer to the indoor unit's installation manual or service handbook.)
4
Reset the error history. Display the error history in the diagnosis result display screen (see step
3
).
E
B
A
Error code (2 or 4 digits)
(Alternating Display)
Address (3 digits) or unit number (2 digits)
The refrigerant address will begin to flash approximately three seconds after being selected and the self-diagnosis process will begin.
Unit number or refrigerant address to be diagnosed
Error code (2 or 4 digits)
(Alternating Display)
Address (3 digits) or unit number (2 digits)
<When there is no error code history> <When there is no corresponding unit>
and
[15].
ON/OFF
I
F
G
C
D
H
ON/OFF
CHECK
33
Page 34
D Press the
ON/OFF
button twice within three seconds. The self-diagnosis
address or refrigerant address will flash.
When the error history is reset, the display will look like the one shown below. However, if you fail to reset the error history, the error content will be displayed again.
5 Cancel self-diagnosis.
Self-diagnosis can be cancelled by the following two methods.
H Press the
button twice within three seconds. Self-diagnosis will be cancelled and the screen will return to the previous state in effect before the start
of self-diagnosis.
5 Press the
button. Self-diagnosis will be cancelled and the indoor unit will stop.
10-3-3. Remote Controller Diagnosis
If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.
1 First, check that the power-on indicator is lit.
If the correct voltage (DC12 V) is not supplied to the remote controller, the indicator will not light. If this occurs, check the remote controller's wiring and the indoor unit.
2 Switch to the remote controller self-diagnosis mode.
H Press the
button for five seconds or more. The display content will
change as shown below.
A Press the
button to start self-diagnosis.
3 Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
Check for other possible causes, as there is no problem with the remote controller.
[When the remote controller malfunctions] (Error display 1) "NG" flashes. The remote controller's transmitting-receiv-
ing circuit is defective.
The remote controller must be replaced with a new one.
[Where the remote controller is not defective, but cannot be operated.] (Error display 2) [E3], [6833] or [6832] flashes.
Transmission is not possible.
There might be noise or interference on the transmission path, or the indoor unit or other remote controllers are defective. Check the transmission path and other controllers.
(Error display 3)
"ERC" and the number of data errors are displayed. Data error has occurred.
The number of data errors is the difference between the number of bits sent from the remote controller and the number actually transmitted through the transmis­sion path. If such a problem is occurring, the transmitted data is affected by noise, etc. Check the transmission path.
4 To cancel remote controller diagnosis
H Press the
button for five seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will flash. After
approximately 30 seconds, the state in effect before the diagnosis will be restored.
Power on indicator
CHECK
ON/OFF
CHECK
FILTER
CHECK
When the number of data errors is "02": Transmission data from remote controller Transmission data on transmission path
34
Page 35
10-3-4. Malfunction-diagnosis method by wireless remote controller
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK display
Temperature button
CHECK button
Refrigerant address display
HOUR button
ON/OFF button
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and refrigerant address "00" flashes.
• Check that the remote controller's display has stopped before continuing.
2. Press the temperature buttons.
3. Point the remote controller at the
sensor on the indoor unit and press the HOUR button.
4. Point the remote controller at the
sensor on the indoor unit and press the ON/OFF button.
• Select the refrigerant address of the indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1). (For more information, see the outdoor unit installation manual.)
• If an air conditioner error occurs, the indoor unit's sensor emits an intermit­tent buzzer sound, the operation light flashes, and the error code is output. (It takes 3 seconds at most for error code to appear.)
• The check mode is cancelled.
35
Page 36
• Refer to the following tables for details on the check codes. [Output pattern A]
Beeper sounds OPERATION
INDICATOR lamp flash pattern
Beep
Self-check starts (Start signal received)
Beep Beep Beep Beep Beep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
rd
n
On
0.5 sec.
th
[Output pattern B]
Beeper sounds OPERATION
INDICATOR lamp flash pattern
Beep Beep Beep Beep Beep Beep Beep
1st2nd3
Off
Self-check starts (Start signal received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes Check code
(Number of times)
1P1 2
P2 Pipe (TH2) sensor error P9 Pipe (TH5) sensor error
3 E6,E7
Intake sensor error
Indoor/outdoor unit communication error
4 P4 Drain sensor error 5
P5 PA
Drain pump error
Forced compressor stop 6 P6 Freeing/Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4, E5 Remote controller signal receiving error
10 11
– –
– –
12 Fb Indoor unit control system error (memory error, etc.)
E0, E3
Remote controller transmission error – E1, E2 Remote controller control board error
nd
1st2
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check code in the following table
rd
th
n
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Symptom Remark
· · · Repeated
Off
nd
1st2
Number of flashes/beeps in pattern indicates the check code in the following table
· · · Repeated
As for indoor unit, refer to indoor unit's service manual.
[Output pattern B]
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes Check code
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
Symptom Remark
(Number of times)
1 2
3 4
5
6 7
8 9
10 11 12
13 14
E9 UP
U3,U4 UF
U2
U1,Ud U5
U8 U6 U7
U9,UH
– –
Others
*1If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
Compressor overcurrent interruption Open/short of outdoor unit thermistors Compressor overcurrent interruption (When compressor locked) Abnormal high discharging temperature/49C worked/
insufficient refrigerant Abnormal high pressure (63H worked)/Overheating
safeguard operation Abnormal temperature of heat sink
Outdoor unit fan safeguard stop
Compressor overcurrent interruption/Abnormal of power module Abnormality of super heat due to low discharge temperature Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
– Other errors
two beeps to confirm the self-check start signal was received and
there are no error records.
For details, check the LED display of the outdoor controller board.
*2If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
36
Page 37
10-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is put on>
Error Code
None
F1
(4103)
F2
(4102)
F3
(5202)
F4
(4124)
F7
(4118)
F9
(4119)
FA
(4108)
Meaning of error code and detection method
1 No voltage is supplied to termi-
2 Electric power is not charged
3 Defective outdoor controller
Reverse phase detection, Power supply and indoor/outdoor unit connecting wire converse connection
1. Three seconds after power on, judge reverse phase by detecting voltage phase of each phase.
2. Abnormal four minutes after power on if power supply and indoor/outdoor unit connecting wire have converse connection.
L3-phased open phase detection
Detect open phase two seconds after power on.
63L connector open
Abnormal if 63L connector circuit is open for three minutes continuously after power supply. 63L: Low-pressure switch
(PU/PUH-P125, 140YGAA.UK Only.)
The connector of 49C is open
Consider the unit abnormal when the cir­cuit of connector (49C) remains open for three consecutive minutes with the power on. 49C: Inner thermostat (Compressor)
Reverse phase detector circuit (controller board) fault
Abnormal if some of each phase detection signal is not input three seconds after power supply.
2 or more connectors open
Abnormal if two more out of connector (63L, 49C, 51CM) circuits are open for three minutes continuously after power on.
51CM connector open
Abnormal if 51CM connector circuit is open for three minutes continuously after power on. 51CM: Thermal Relay
1 L1, L2, L3 are not connected 2 Converse wiring of outdoor
1 L3-phased open-phase 1 Check power supply.
1 Disconnection or contact fail-
2 Disconnection or contact fail- 3 63L is working due to refrigerant 4 Defective outdoor controller
1 The connector of 49C on out-
2 The switch of 49C has contact 3 Power supply was turned on 4 49C has been tripped (defec- 5 Outdoor controller board is
Detective outdoor controller board
1 Disconnection or contact fail-
2 Disconnection or contact fail- 3 Defective (63L, 49C, 51C) 4 Defective outdoor controller
1 Disconnection or contact
2 Disconnection or contact 3 Defective 51CM (defective 4 Defective outdoor controller
(Note 1) The number in ( ) is the error cord of upper remote controller (M-NET)
Case Judgment and action
nal block (TB1) of indoor unit. a) Power supply breaker is put
off.
b) Contact failure or discon-
nection of power supply ter­minal
c) L1-phased open phase to power supply terminal of
controller board. a) Contact failure of power
supply terminal
b) Disconnection of terminal R
or 4/S on controller board
board a) Fuse 6.3A on controller
board is blown.
b) Defective parts
correctly. power supply line (TB1) and
indoor power supply wire (TB4)
ure of 63L connector on out­door controller board
ure of 63L leakage or defective parts. board
door controller board has con­tact failure or disconnection.
failure or disconnection. when 49C has been tripped. tive parts). defective.
ure of connector (63L, 49C, 51CM) on outdoor controller board
ure of (63L, 49C, 51C). (defective parts) board.
failure of 51CM connector on outdoor controller board
failure of 51CM parts)
1 Check following items.
a) Power supply breaker b) Connection of power supply terminal
block (TB1).
c) Connection of power supply terminal
block (TB1).
2 Check following items.
a) Connection of power supply terminal
block (TB1).
b) Connection of terminal on controller board
3 Replace following items.
a) Fuse 6.3A b) Controller board (When items above are
checked but the units can not be repaired)
1
• Check outdoor power supply connection (TB1)
• Replace two phases (for example phase L1 and phase L2) out of three phases of outdoor power supply line (TB1)
2 Check wiring connection.
1 Check connection of 63L connector on
outdoor controller board. Refer to 10-7.
2 Check the 63L side of connecting wire. 3 Check refrigerant pressure.
Charge additional refrigerant. Check continuity by tester. Replace the parts if the parts are defective.
4 Replace outdoor controller board. 1 Check connection of 49C connector on
outdoor controller board. Refer to 10-7.
2 Check the 49C side of connecting wire. 34
Check the continuity by tester. Replace defective parts.
5 Replace the outdoor controller board.
Replace outdoor controller board.
1 Check connection of (63L, 49C, 51CM)
connector on outdoor controller board. Refer to 10-7.
2 Check the (63L, 49C, 51CM) side of
connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller board.
1 Check connecting wire. 2 Check connecting wire. 3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller board.
37
Page 38
Error Code
EA
(6844)
Eb
(6845)
EC
(6846)
Ed
(0403)
Meaning of error code and detection method Indoor/outdoor unit connector mis-
wiring, excessive number of units (5 units or more)
1. Outdoor controller board can automati­cally check the number of connected indoor units. Abnormal if the number of connected indoor units can not be set within four minutes after power on because of mis-wiring of indoor/outdoor unit connecting wire and the like.
2. Abnormal if outdoor controller board rec­ognizes the number of connected indoor units as “5 units or more”.
Mis-wiring of indoor/outdoor unit con­necting wire (converse wiring or dis­connection)
Outdoor controller board can automatically set the unit number of indoor units. Abnormal if the indoor unit number can not be set within four minutes after power on because of mis-wiring (converse wiring or disconnection) of indoor/outdoor unit con­necting wire.
Start-up time over
The unit can not finish start-up process within four minutes after power on.
Serial communication error
The communication between outdoor con­troller board and M-NET p.c. board is not available.
1 Contact failure or mis-wiring of
2 Diameter or length of
3 Five or more indoor units are 4 Defective transmitting receiv-
5 Defective transmitting receiv-
6 Noise has entered into power
7 Remote controller is wired up
8 Two or more outdoor units has
1 Contact failure or mis-wiring of
2 Diameter or length of
4 Defective transmitting receiving 5 Defective transmitting receiving 6 Noise has entered into power
7 Remote controller is wired up
8 Two or more outdoor units has
9 Outdoor power supply board is
1 Contact failure of indoor/out- 2 Diameter or length of indoor/
6 Noise has entered into power
7 Remote controller is wired up
8 Two or more outdoor units has
1 Breaking of wire or contact
2 Contact failure of M-NET p.c. 3 Entrance of noise into trans- 4 Defective transmitting receiv- 5 Defective serial transmitting
Case
indoor/outdoor unit connecting wire.
indoor/outdoor unit connecting wire is out of specified capacity.
connected to one outdoor unit. ing circuit of outdoor controller
board ing circuit of indoor controller
board supply or indoor/outdoor unit
connecting wire. among indoor units (twin, triple
or quadro units). refrigerant address “0.”
(In case of group control).
indoor/outdoor unit connecting wire
indoor/outdoor unit connecting wire is out of specified capacity.
circuit of outdoor controller board circuit of indoor controller board supply or indoor/outdoor unit
connecting wire. among indoor units (twin, triple
or quadro units). refrigerant address “0.”
(In case of group control).
defective.
door unit connecting wire outdoor unit connecting wire is
out of specified capacity. supply or indoor/outdoor unit
connecting wire. among indoor units (twin, triple
or quadro units). refrigerant address “0.”
(In case of group control).
failure of connector between outdoor controller board and M-NET p.c. board.
board power supply line mission wire ing circuit of M-NET p.c. board receiving circuit of outdoor
controller board
Judgment and action
1 Check disconnection or looseness or polarity
of indoor/outdoor unit connecting wire of indoor and outdoor units.
2 Check diameter and length of indoor/outdoor
unit connecting wire. Outdoor-indoor units’ interval: 50m maximum Indoor-indoor units’ interval: 30m maximum Also check if the connection order of flat cable (VVF etc.) is S1, S2, S3.
3 Check the number of indoor units that are
connected to one outdoor unit. (If EA is detected.)
45 Put the power off, and on again to check.
Replace outdoor controller board or indoor controller board if abnormality is displayed again. Check the indoor/ outdoor unit connecting wire.
6 Inspect transmission line to solve the problem. 7 Wire the remote controller to one of the mul-
tiple indoor units.
8 Set the refrigerant address of outdoor units
with different number starting from “0.”
9 Unless the wire has contact failure, discon-
nect CN2S on indoor power supply board to measure the voltage. When CN2S does not have a current of DC12V to DC16V, replace the indoor power supply board.
w The descriptions above, 1-9, are for EA, Eb
and EC.
1 Check disconnection, looseness, or breaking
of connecting wire between outdoor con­troller board CN1 and M-NET p.c. board CN5.
2 Check departure or looseness of M-NET p.c.
board power supply line (CND-TB1).
3 Replace M-NET p.c. board. 4 Replace outdoor controller board.
38
Page 39
Error Code
Model
P25V P35V P35Y P50V P50Y P60V P60Y
Detected current
1.0
1.3
1.0
1.6
1.0
1.8
1.0
Model
P71V
P71Y P100V P100Y P125Y P140Y
Detected current
2.4
1.0
1.0
1.0
1.5
1.7
[A]
U1
(1302)
Meaning of error code and detection method
Abnormal high pressure (High-pressure switch 63H worked)
Abnormal if high-pressure switch 63H worked (more than 3.24 MPa) during com­pressor operation. 63H: High-pressure switch Use current sensor to detect work or
return of 63H.
Abnormal low current or open phase
• An extreme degradation of current value causes abnormal stop.
• Abnormal if current detected phase (V­phase) is open phase after first compres­sor start-up after supplying the power by three phase power supply model.
• When compressor is operating, compres­sor is suspended under the following condition: and when current detector (CT) detects a current, which is lower than the detected current specified in the table below, under the following condi­tion:
1 Short cycle of indoor unit 2 Clogged filter of indoor unit 3 Decreased airflow caused by
4 Dirt of indoor heat exchanger 5 Locked indoor fan motor 6 Malfunction of indoor fan
7 Defective operation of stop 8 Clogged or broken pipe
9 Locked outdoor fan motor
0 Malfunction of outdoor fan 1 Short cycle of outdoor unit
2 Dirt of outdoor heat exchanger 3 Disconnection or contact failure
4 Defective outdoor controller 5 Defective action of liner expan- 6 Refrigerant overcharge
1 Shortage of refrigerant 2 Abnormal pressure degrada-
3 V-phased open phase of com- 4 Abnormal compressor
Case
dirt of indoor fan
motor valve (Not full open)
motor
of 63H connection board sion valve
tion by pomp down operation pressor Not abnormal if V is instantly
displayed when the main power is put off.
Judgment and action
1-6 Check indoor unit and repair defectives. 7 Check full open stop valve. 8 Check piping and repair defectives. 9-2 Check indoor unit and repair defectives.
3,4 Put the power off and check UH display
when the power is put again. Follow the UH display if UH is displayed.
5 Check linear expansion valve.
Refer to 10-6.
6 Replace refrigerant.
1 Check if refrigerant pressure is not degraded. 2 Check current of compressor operation when
abnormality occurred.
3 Check wiring of compressor. 4 Check or replace compressor.
<Condition> 1 For PUH-P25V and PU/PUH-P35 ~
P100V
Current detector (CT) has detected a
U1
U2
(1102)
current, which is lower than the detected current specified in the table below, for
0.7-0.8 second.
2 For PU/PUH-P35 ~ P140Y
Current detector (CT) has detected a current, which is lower than the detected current specified in the table below, for
0.4-0.5 second.
Abnormal high discharging temperature
Abnormal if discharging temperature ther­mistor (TH4) exceeds following tempera­ture during compressor operation. Normal operation: 115:(P25-P100)/
During defrosting: 135:
125:(P125,P140) or more for three min­utes continuously or 135:
1 Over-heated compressor oper-
ation caused by shortage of refrigerant
2 Defective operation of stop
valve
3 Defective thermistor 4 Defective outdoor controller
board
5 Defective action of linear
expansion valve
39
1 Check intake super heat.
Check leakage of refrigerant. Charge refrigerant.
2 Check if stop valve is full open. 34 Put the power off and check if U3 is
displayed when the power is put again. When U3 is displayed, refer to “Judgement and action” for U3.
5 Check linear expansion valve.
Refer to 10-6.
Page 40
Error Code
U2
(1501)
Meaning of error code and detection method
Abnormal shortage of refrigerant
Abnormal if intake super heat exceeds fol­lowing temperature during heating com­pressor operation. 70: or more, and indoor pipe <con­denser- evaporator> temperature (TH5) is 35: or less.
1 Leakage or shortage of refrig- 2 Defective operation of stop 3 Defective thermistor (TH4, 4 Defective outdoor controller 5 Defective action of electric
Case
erant valve (not full open) TH5, TH6) board expansion valve
Judgment and action
1 Check leakage of refrigerant.
Charge refrigerant.
2 Check if stop valve is full open. 34 Put the power off and check if U3 or U4 is
displayed when the power is put again. When U3 or U4 is displayed, refer to “Judgement and action” for U3 or U4.
6 Check linear expansion valve.
Refer to 10-6
U3
(5104)
U4 (5105) (5107)
U6 (4101)
Ud (1504)
UE
(1302)
UL
(1300)
Open/short circuit of discharging ther­mistor (TH4)
Abnormal if open (0: or less) or short (216: or more) is detected during com­pressor operation. (Detection is inoperative for five minutes of compressor starting process and for 10 minutes after defrosting.)
Open/short circuit of the liquid pipe thermistor (TH3) or outdoor Condenser­Evaporator pipe thermistor (TH6)
Abnormal if open (-39: or less) or short (88: or more) is detected during com­pressor operation. (Detection is inoperative for seven minutes after 10 seconds of compressor starting and for 10 minutes after defrosting.)
Compressor over current (overload) breaking (only P35Y-P140Y)
Abnormal if current value exceeds over­load set value during compressor opera­tion. P35 ·····4.5 P50 ·····5.8 P60 ·····6.4 P71 ·····8.0 P100 ·····9.0 P125 ·····15.0 P140 ·····17.0
Over heat protection (over-load opera­tion protection/abnormal fan)
Abnormal if pipe thermistor detects the value that exceeds set value during com­pressor operation. P25-P140 ··70:
Abnormal High pressure (63H worked)
This error is detected (3.24MPa) from 63H action within 20 seconds of compressor starting in the first heating mode after power on. 63H: high-pressure switch
Abnormal low pressure (63L worked)
Abnormal if connector (63L) is open (under- 0.03MPa) during compressor oper­ation.
1 Disconnection or contact failure
of connector (TH4) on the indoor controller board.
2 Defective thermistor 3 Defective outdoor controller
board
1 Disconnection or contact failure
of connector (TH3/TH6) on the indoor controller board.
2 Defective thermistor 3 Defective outdoor controller
board
1 Gas pipe side ball valve and
liquid pipe side stop valve are shut during operation.
2 Abnormal compressor 3 Abnormal power supply voltage 4 Overload operation
1 In cooling mode: defective
outdoor fan (fan motor) or short cycle of air path
2 Defective thermistor 3 Defective outdoor controller
board
1 Gas pipe side ball valve and
liquid pipe side stop valve are shut during operation.
2 Disconnection or contact failure
of 63H
3 Defective outdoor controller board 4 Power supply reset is detected
while indoor filter clogs and overload heating operation.
5 Defective outdoor controller
board
6 Defective action of linear
expansion valve
1 Gas pipe side ball valve and
liquid pipe side stop valve are shut during operation.
2 Disconnection or contact fail-
ure of connector (63L) on out­door controller board.
3 Disconnection or contact fail-
ure of 63L.
4 Defective outdoor controller
board
5 Leakage or defective of refrig-
erant
6 Defective action of linear
expansion valve
1 Check contact of connector (TH4) on the
indoor controller board. Refer to 10-7 Check breaking of the lead wire for thermistor (TH4). Refer to 10-6
2 Check resistance value of thermistor
(Refer to 10-6.), or check temperature by microcomputer(Mode switch of SW2).
3 Replace outdoor controller board. 1 Check contact of connector (TH3/TH6) on
the indoor controller board. Refer to 10-7. Check breaking of the lead wire for thermistor (TH3/TH6). Refer to 10-6.
2 Check resistance value of thermistor
(Refer to 10-6.), or check temperature by microcomputer(Mode switch of SW2).
3 Replace outdoor controller board.
1 Open ball valve and stop valve. 2 Check or replace compressor.
Refer to 5-2.
3 Check power supply voltage. 4 Check short cycle.
1 Check outdoor fan (fan motor)
Refer to 10-6.
24 Put the power off and operate again to
check if U4 is displayed. If U4 is displayed, follow the U4 process­ing direction.
1 Open ball valve and stop valve. 23 Put the power off, and operate again to
check if F5 is displayed. If F5 is displayed, follow the F5 processing direction.
4 Check indoor filter. 5 Replace outdoor controller board. 6 Check linear expansion valve.
Refer to 10-6.
1 Open ball valve and stop valve. 234 Put the power off and on again to check
if F3 is displayed on restarting. If F3 is displayed, follow the F3 process­ing direction.
5 Leakage or defective of refrigerant 6 Check linear expansion valve
Refer to 10-6.
40
Page 41
Note: E1, E2 and E4 to E7, refer to indoor unit service manual.
Error Code
UF
(4100)
Meaning of error code and detection method Compressor over current (start-up
locked) breaking
Abnormal if compressor current exceeds
1.2 times of overload set value.
1 Abnormal compressor 2 Clogged indoor filter 3 Open-phase compressor
Case
Judgment and action
1 Check compressor.
Refer to 5-2.
2 Check indoor unit and repair defective. 3 Check connection.
UH
(5300)
E0
(No display)
Current sensor error
Abnormal if compressor current is not detected on first compressor start-up after power supply is put on.
Remote controller communication error (Signal receiving error)
(1) Abnormal if any signal from IC of refrig-
erant address “0” could not normally received for three minutes.
(2) Abnormal if sub remote controller could
not receive any signal for two minutes.
1 Disconnection or contact fail-
ure of connector (52C) on out­door controller board
2 Disconnection or contact fail-
ure of coil 52C
3 Defective outdoor controller
board
4 Defective parts of 52C 5 Compressor V-phased wire
does not penetrate through current detector.
1 Defective communication cir-
cuit of remote controller
2 Defective communication cir-
cuit of indoor controller board of refrigerant address “0”.
3 Noise has entered transmis-
sion wire of remote controller.
4 All remote controllers are set
as “sub” remote controller. In this case, E4 is displayed at outdoor LED, and E0 is dis­played at remote controller.
5 Wiring regulations are not
observed.
•Length of wires
•Number of remote controllers
•Diameter of wires
•Number of indoor units
12 Check connection. 3 Replace outdoor controller board. 4 Check 52C. 5 Check wiring.
123 Diagnose remote controller
Dispose as follows according to diagno­sis result. a) When “RC OK” is displayed,
Remote controllers have no problem. Put the power off, and on again to check. If, “PLEASE WAIT” is displayed for four minutes or more, replace indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c) When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnor­mality.
4 Set one of the remote controllers “main”, if
outdoor LED is E4 while E0 is displayed at remote controller.
E3
(No display)
E8
(6840)
E9
(6841)
Remote controller communication error (Transmitting error)
(1) Abnormal if sub remote controller could
not find blank of transmission path for six seconds.
(2) Abnormal if remote controller could not
finish transmitting 30 times continuous­ly.
Indoor/outdoor unit communication error (Signal receiving error) (Outdoor unit)
(1) Abnormal if outdoor controller could not
receive anything normally for three minutes.
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
(1) Abnormal if “0” receiving is detected 30
times continuously though indoor con­troller has transmitted “1”.
(2) Abnormal if outdoor controller could not
find blank of transmission path for three minutes.
1 Defective communication cir-
cuit of remote controller.
2 Noise has entered transmis-
sion wire of remote controller.
3 Two or more remote con-
trollers are set as "main."
1 Contact failure of indoor/out-
door unit connecting wire
2 Defective communication cir-
cuit of indoor controller board
3 Defective communication cir-
cuit of indoor controller board
4 Noise has entered indoor/ out-
door unit connecting wire.
1 Defective communication circuit
of outdoor controller
2 Noise has entered power supply. 3 Noise has entered indoor/
outdoor unit connecting wire.
4 Indoor/ outdoor unit connecting
wire has contact failure.
5 Defective communication circuit
between indoor and outdoor unit on indoor controller board.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor or out­door units.
234 Put the power off, and on again to
check. Replace indoor controller board or outdoor controller board if abnormality is displayed again.
123 Put the power off, and on again to
check. Replace outdoor controller board if abnormality is displayed again.
41
Page 42
Error Code
EF
(6607
or
6608)
Ed
(0403)
Meaning of error code and detection method Not defined error code
This code is displayed when not defined error code is received.
Serial communication error
Abnormal if communication between
outdoor controller circuit board and M-NET board is not available.
1 Noise has entered transmis- 2 Noise has entered indoor/
1 Breaking of wire or contact
2 Contact failure of M-NET 3 Noise has entered into M-NET
Case
sion wire of remote controller. outdoor unit connecting wire.
failure of connector between outdoor controller circuit board and M-NET board
board power supply line transmission wire.
Judgment and action
12 Put the power off, and on again to check.
Replace indoor controller board or outdoor controller board if abnormality is displayed again.
1 Check disconnection, looseness, or breaking of
connection wire between outdoor controller cir­cuit board (CNMNT) and M-NET board (CN5).
2 Check disconnection, looseness, or breaking of
connection wire between outdoor controller cir­cuit board(CNMNT) and M-NET board (CND).
3 Check M-NET transmission wiring method.
<M-NET communication error>
Error Code
A0
(6600)
A2
(6602)
A3
(6603)
A6
(6606)
Meaning of error code and detection method
Address duplicate definition
This error is displayed when transmission from the units of same address is detect­ed. Note) The address and attribute displayed
at remote controller indicate the con­troller that detected abnormality.
Hard ware error of transmission Pline
Transmission processor intended to trans­mit “0”, but “1” appeared on transmission wire. Note) The address and attribute display at
remote controller indicate the con­troller that detected abnormality.
BUS BUSY
1. Over error by collision damage Abnormal if transmitting is not possible for 8-10 minutes continuously because of collision of transmission.
2. Data could not reach transmission wire for 8-10 minutes continuously because of noise or etc.
Note) The address and attribute displayed
at remote controller indicate the con­troller that detected abnormality.
Communication error with communica­tion Pline
Defective communication between unit processor and transmission processor Note) The address and attribute display at
remote controller indicate the con­troller that detected abnormality.
(Note) “Indoor unit” in the text indicates M-NET p.c. board in outdoor unit.
Case Judgment and action
1 There are two or more same
address of controller of out­door unit, indoor unit, FRESH MASTER, or LOSSNAY.
2 Noise has entered into trans-
mission signal and signal was transformed.
1 Error is detected if waveform is
transformed when wiring works of transmission wire of outdoor unit, indoor unit, FRESH MAS­TER or LOSSNAY are done, or polarity is changed with the power on and transmission data collide each other.
2 Defective transmitting receiv-
ing circuit of transmission processor
3 Transmission data is changed
by the noise on transmission.
1 Transmission processor could
not transmit because short cycle voltage of noise and the like have entered into trans­mission wire continuously.
2 Transmission quantity has
increased and transmission is not possible because there was wiring mistake of terminal block for transmission wire (TB3) and terminal block for central control (TB7) in outdoor unit.
3 Transmission are mixed with
others and occupation rate on transmission wire rose because of defective repeater (a function to connector or disconnect transmission of control and central control system) of outdoor unit, then abnormality is detected.
1 Data of transmission proces-
sor or unit processor is not transmitted normally because of accidental trouble such as noise or thunder surge.
2 Address forwarding from unit
processor is not transmitted normally because of defective transmission processor hard­ware.
Search the unit with same address as abnor­mality occurred. If the same address is found, shut of the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or more after the address is corrected, and put the power on again. Check transmission waveform or noise on transmission wire. 1 If the works of transmission wire is done with
the power on, shut off the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or more, and put the power on again.
2 Check transmission waveform or noise on
transmission wire.
1 Check if transmission wire of indoor unit,
FRESH MASTER, LOSSNAY, or remote controller is not connected to terminal block for central control (TB7) of outdoor unit.
2 Check if transmission wore of indoor unit,
FRESH MASTER or LOSSNAY is not connected to terminal block for transmission wire of outdoor unit.
3 Check if terminal block for transmission wire
(TB3) and terminal block for central control (TB7) is not connected.
4 Check transmission waveform or noise on
transmission wire.
Shut of the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or more, and put the power on again. System returns nor­mally if abnormality was accidental malfunction. If the same abnormality generates again, abnormality-generated controller may be defec­tive.
42
Page 43
Error Code
A7
(6607)
Meaning of error code and detection method
NO ACK
1. Transmitting side controller detects abnormal if a massage was transmitted but there is no reply (ACK) that a mas­sage was received. Transmitting side detects abnormality every 30 seconds, six times continuously.
Note) The address and attribute displayed
at remote controller is indicate the controller that did not reply (ACK).
2. If displayed address or attribute is out­door unit, Indoor unit detects abnormality when indoor unit transmitted to outdoor unit and there was no reply (ACK).
3. If displayed address or attribute is indoor unit, Remote controller detects abnormality when remote controller transmitted to indoor unit and there was no reply (ACK).
4. If displayed address or attribute is remote controller, Indoor unit detects abnormality when indoor unit transmitted to remote con­troller and there was no reply (ACK).
Common factor that has no rela­tion with abnormality source.
1 The unit of former address
2 Extinction of transmission wire
3 Extinction of transmission wire
4 Extinction of transmission wire
5 Accidental malfunction of
6 Defective of abnormality-gen-
1 Contact failure of transmission
2 Disconnection of transmission
3 Defective transmitting receiv-
1 During group operation with
2 Contact failure of transmission
3 Disconnection of transmission
4 Defective trnamsitting receiv-
1 During group operation with
2 Contact failure of transmission
3 Disconnection of transmission
4 Defective trnamsitting receiv-
Case Judgment and action
does not exist as address switch has changed while the unit was energized.
voltage and signal is caused by over-range transmission wire.
• Maximum distance ······200m
Remote controller line
voltage and signal is caused by type-unmatched transmis­sion wire. Type······
With shield wire-
CVVS, CPEVS
With normal wire (no shield)-
VCTF, VCTFK, CVV CVS, VVR, VVF, VCT
Diameter····125mm2or more voltage and signal is caused
by over-numbered units. abnormality-detected controller
(noise, thunder surge) erated controller
wire of outdoor unit or indoor unit
connector (CN2M) of outdoor unit
ing circuit of outdoor unit or indoor unit
indoor unit of multi- refrigerant system, if remote controller transmit to indoor unit while outdoor unit power supply of one refrigerant system is put off or within two minutes of restart, abnormality is detect­ed.
wire of remote controller or indoor unit
connector (CN2M) of indoor unit
ing circuit of indoor unit or remote controller
indoor unit of multi- refrigerant system, if indoor unit transmit to remote controller while out­door unit power supply of one refrigerant system is put off or within two minutes of restart, abnormality is detected.
wire of remote controller or indoor unit
connector (CN2M) of indoor unit
ing circuit of indoor unit or remote controller
··(12m)
Always try the followings when the error “A7” occures.
1 Shut off the power supply of outdoor unit,
indoor unit,and FRESH MASTER or LOSS­NAY at the same time for two minutes or more, and put the power on again. If mal­function was accidental, the unit returns to normal.
2 Check address switch of abnormality-gener-
ated address.
3 Check disconnection or looseness of abnor-
mality-generated or abnormality-detected transmission wire (terminal block and con­nector)
4 Check if tolerance range of transmission wire
is not exceeded.
5 Check if type of transmission wire is correct
or not.
If there were some trouble of 1-5 above, repair the defective, then shut off the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or more, and put the power on again.
• If there was no trouble with 1-5 above in sin­gle refrigerant system (one outdoor unit), con­troller of displayed address or attribute is defective.
• If there was no trouble with 1-5 above in dif­ferent refrigerant system (two or more outdoor units), judge with 6.
6 If address of abnormality source is the
address that should not exist, there is the unit that memorizes nonexistent address information. Delete useless address informa­tion with manual setting function of remote controller. Only the system FRESH MASTER or LOSS­NAY are connected to, or the system that is equipped with group setting of different refrigerant system.
If there was no trouble with 1-6 above, replace the controller board of displayed address or attribute. If the unit does not return normally, multi-con­troller board of outdoor unit may be defective
Continued to the next page.
43
Page 44
From the previous page.
Error Code
A7
(6607)
A8
(6608)
Meaning of error code and detection method
5. If displayed address or attribute is FRESH MASTER, Indoor unit detects abnormality when indoor unit transmitted to FRESH MAS­TER and there was no reply (ACK).
6. If displayed address or attribute is LOSSNAY, Indoor unit detects abnormality when indoor unit transmitted to LOSSNAY and there was no reply (ACK).
7. If displayed address or attribute is nonexistent,
M-NET•NO RESPONSE
Abnormal if a massage was transmitted and there were reply (ACK) that massage was received, but response command does not return. Transmitting side detects abnormality every 30 seconds, six times continuously. Note) The address and attribute displayed
at remote controller is indicate the controller that did not reply (ACK).
Case Judgment and action
1 During sequential operation of
indoor unit and FRESH MAS­TER of other refrigerant sys­tem, if indoor unit transmits to FRESH MASTER while out­door unit power supply of same refrigerant system with FRESH MASTER is put off or within two minutes of restart, abnormality is detected.
2 Contact failure of transmission
wire of indoor unit or FRESH MASTER
3 Disconnection of transmission
connector (CN2M) of indoor unit or FRESH MASTER
4 Defective transmitting receiv-
ing circuit of indoor unit or FRESH MASTER
1 If the power supply of LOSS-
NAY is off, indoor unit detects abnormality when it transmits to LOSSNAY.
2 During sequential operation of
indoor unit and LOSSNAY of other refrigerant system, if indoor unit transmits to LOSS­NAY while outdoor unit power supply of same refrigerant sys­tem with LOSSNAY is put off or within two minutes of restart, abnormality is detect­ed.
3 Contact failure of transmission
wire of indoor unit of LOSS­NAY
4 Disconnection of transmission
connector (CN2M) of indoor unit
5 Defective transmitting receiv-
ing circuit of indoor unit or LOSSNAY
1 The unit of former address
does not exist as address switch has changed while the unit was energized.
2 Abnormality is detected when
indoor unit transmitted because the address of FRESH MASTER and LOSS­NAY are changed after sequential operation of FRESH MASTER and LOSS­NAY by remote controller.
1 Transmitting condition is
repeated fault because of noise and the like.
2 Extension of transmission wire
voltage and signal is caused by over-range transmission wire.
• Maximum distance ······200m
Remote controller line
3 Extension of transmission wire
voltage and signal is caused by type-unmatched transmis­sion wire. Type······
With shield wire-
CVVS, CPEVS
With normal wire (no shield)-
VCTF, VCTFK, CVV CVS, VVR, VVF, VCT
Diameter····125mm2or more
4 Accidental malfunction of
abnormality-generated controller
··(12m)
Same as mentioned in “A7” of the previous page.
1 Check transmission waveform or noise on
transmission wire.
2 Shut off the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSS­NAY at the same time for two minutes or more, and put the power on again. If mal­function was accidental, the unit returns to normal. If the same abnormality generates again, controller of displayed address and attribute may be defective.
44
Page 45
10-5. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena Factor Countermeasure
(1)Remote controller display does not
work. (Electric current marker “ ” is not displayed on the remote controller.)
Indoor control p.c.board LED
LED1
off off off
1
Lighting off
2
Lighting
3
(2)Remaining “PLEASE WAIT” display
on the remote controller.
(3)When pressing the remote controller
operation switch the OPERATION display is appeared but it will be turned off soon.
(4)Even controlling by the wireless
remote controller no beep and not working. (Display is available on the wireless remote controller)
(5)When operating by the wireless
remote controller, beep sound is heard without working.
(6)Upward/downward vane performance
fault.
LED2 LED3
(or blinking)
Blinking
(or lighting)
off
Reference (Meaning of the indoor control board LED)
LED1 : Micro computer power supply
....Display of DC14V is supply or not from indoor power.
LED2 : Power output supplied to remote controller
....Display the power condition supplied to wired remote controller. When the
refrigerant address is “0” supplied power output ON.
LED3 : Indoor outdoor communication monitor
....Blinking, when receiving the signal normally from the outdoor unit.
1Main power is not turned on. (Power supply inferior) 2Mis-wiring, breaking or contact failure of the connect-
ing line.
1Refrigerant address excepts “0”. 2Mis-wiring, breaking or contact failure of the connect-
ing line.
1Short circuit, miswiring and breaking
1At longest 2 minutes after the power supply “PLEASE
WAIT” is displayed to start up.
1Communication fault between the remote controller
and indoor.
2Communication fault between the indoor and outdoor. 3Outdoor unit protection device is opened.
(Abnormal code will be displayed after 2~6 minutes.)
1After cancelling to select function from the remote
controller, the remote controller operation switch will be not accepted for approx 30 seconds.
1The pair number settings of the wireless remote
controller and indoor control PCB are mismatched.
2Disconnecting of wireless receiving board and contact
failure.
3Factor of the above (1).
1No operation for max. 2 minutes after the power sup-
ply ON.
2Remote operation is prohibited.
•Remote controlling adaptor is connected to the indoor controller board (CN32).
•Remote operation is prohibited by centralised con­troller etc. since it is connected to MELANS.
3Factor of the above (2). 1When the unit is as follows in the HEAT mode, the
vane is not downward. (Working of COOL protection function)
•During HEAT preparation.
•During defrosting.
•During compressor stop.
2When setting the downward vane in the cool/dry
mode, the vane changes to Horizontal position after 1 hour.
3Vane motor does mot rotate.
A) Vane motor fault. B) Disconnecting, breaking and contact fault of the
connector.
C) Setting to no vane unit.
4Standard position reading fault (Vane motor does not
stop). A) Limited switch fault. B) Disconnecting breaking and contact fault of the
connector.
w Only AC timing motor adopting mode. (No limited
switch for stepping motor adopting model.)
1
Check the power wiring to the outdoor unit and the breaker.
2
Check for incorrect wiring, wiring breaks and poor connections between the indoor and outdoor units.
1
Set the refrigerant address to "0" (only 1 refrigerant can be "0" for group control).
2
Check for incorrect wiring, wiring breaks and poor connections between the indoor and outdoor units.
Check for shorts, incorrect wiring and wiring breaks in the
1
remote controller wires.
2
Replace the remote controller if the voltage to the remote controller terminal block (TB6) is between 10 and 16V DC.
Normal operation
Turn the power supply OFF/ON, and check the following:
1
If an error is displayed on the remote controller or outdoor unit's LED within 6 minutes: Refer to the self-diagnosis table on p. 115 to take appropriate action.
2
If "H0" display remains for 6 minutes: Failure in indoor control PCB or remote controller
Normal operation
1Check the pair number settings. 2Check the indoor controller board connec-
tor (CN90). Check the wireless receiving board con­nector (CNB)
3Check the details of above (1). 1Normal operation
2Normal operation
3Check the details of above (2).
1Normal operation 2Normal operation
3 A) Vane motor resistance value check.
B) Disconnecting, breaking, and contact
fault of the connector. Stepping motor adopting model
.... CN6V check
AC timing motor adopting model
.... CNV check
C) Check the setting details by selecting
the remote controller function. Setting check of the indoor controller board J11~J15 (SW1).
4 A) Limiteds witch (LS) conductance
check.
B) Check the removing of indoor con-
troller board (CN23), breaking line and contact fault.
45
Page 46
Phenomena Factor Countermeasure
(7)Left/right louver performance fault.
1Louver motor fault. 2Disconnecting, breaking and contact fault of the con-
nector.
1Louver motor resistance value check 2Check the removing of indoor controller
board (CNL) breaking line and contact fault.
(8)Though the remote controller dis-
play is normal in cool mode, the capacity is not enough.
(9)Though the remote controller dis-
play is normal in Heat mode, the capacity is not enough.
1Filter clogging (dirt)
2Heat exchanger clogging (dirt)
3Air duct short cycle. 4Refrigerant shortage. 5Operation failure in electronic expansion valve
6Thermistor connection failure 7Incorrect piping size 8Piping is too long.
1Filter clogging (dirt)
2Heat exchanger clogging (dirt)
3Air duct short cycle. 4Refrigerant shortage. 5Outdoor unit bypass circuit failure 6Indoor reverse check valve failure
Reverse check valve failure may cause refrigerant leakage and restrictor failure.
7Heat insulator of refrigerant pipes is defective. 8Malfunction of LEV. 9Loose connection in thermistor.
1Open the grille to check the filter.
Clean the filter and remove dust or dirt away.
2Clean the heat exchanger.
Lowering the indoor piping temperature and intake pressure means clogging in the heat exchanger.
3Remove screen in the air duct (air outlet/
intake).
4Check if gas leaks or not in the piping
joint.
5,6Check the refrigerant circuit operation
status.
7Check the piping size. 8Check the capacity loss characteristic for
the piping length.
1Open the grille to check the filter.
Clean the filter and remove dust or dirt away.
2Clean the heat exchanger.
Rising the indoor piping temperature and outlet pressure means clogging in the heat exchanger.
3Remove screen in the air duct (air outlet/
intake).
4Check if gas leaks or not in the piping
joint.
5Operating condition check in the refriger-
ant cycle.
6Since outlet temperature and indoor heat
exchanger temperature does not rise, measure the outlet pressure and deter­mine the countermeasure.
7Check the heat insulator. 8,9Check the function of refrigerant circuit.
46
Page 47
[for wired remote controller]
Before you call out a repair man, check the following table to see whether there is a simple solution to your problem.
The room neither gets cool nor
Problem
warm very much.
The unit does not blow air out right away in the heating mode. The unit stops operating before arriving at the set temperature in the heating mode.
The airflow direction suddenly changes.
Air direction doesn't move (change). (Up/down vane, left/right louver)
When changing the airflow direc­tion, the vanes make at least a complete rotation before stopping in place.
There is a “swishing” noise that occurs from the unit when water flows.
Unit occasionally makes a gurgling sound.
Unit occasionally thuds.
Outdoor unit occasionally rattles.
Clean the filter. (Dust and rebris that collects in the filter will decrease air-flow.) Check the temperature setting and adjust it if necessary. Increase the space surrounding the outdoor unit. Is the air intake or air outlet blocked? Is a window or door open? The unit is preparing to deliver warm air. Frost forms when the outdoor tem­perature is low and humidity is high. Wait for about 10 minutes for the frost to melt. After one hour of cooling-mode operation with the airflow in a downward direction, the unit will automatically change to the “Horizontal air-flow” mode. This is to prevent any moisture that may have collected from dripping. When the unit is in the heating or defrosting mode, it will automati­cally change to the “Horizontal air­flow mode”. The vanes will go through a test run before they situate into the specified angle.
1) Check whether the vane has been set to a fixed position (check whether the vane motor connector has been removed).
2) Check whether the unit has a function for switching the air direc­tion. If the unit doesn't have this function, "FUNCTION DOESN'T EXIST" appears when you press the remote control's UP/DOWN VANE or LOUVER button.
The vanes will go through a test run before they situate into the specified angle
This sound is made when refriger­ant inside of the unit is flowing or refilling.
Not an error. This sound is caused by the flow of the refrigerant in the air conditioner being switched.
Not an error. This sound is emitted when the air conditioner (outdoor unit) starts operating.
Not an error. This sound is caused by the blower air volume control that the outdoor unit performs to maintain the optimum operation status.
Solution Problem Solution
A ticking noise is heard from inside of the unit.
An odour is detected in the room.
A white mist is expelled from the indoor unit.
Water or moisture is expelled from the outdoor unit.
The indicators of the remote con­troller do not light up when oper­ated. CENTRALLY CONTROLLED indi­cator is displayed in the remote controller.
The start and stop functions are not available just after restarting the unit.
Fan speed doesn't match set fan speed during DRY operation. (Sometimes no air comes out dur­ing DRY operation.)
Fan speed doesn't match set fan speed during HEAT operation. (Sometimes no air comes out dur­ing HEAT operation.)
Air sometimes comes out when operation is stopped after HEAT operation.
This sound is made when internal parts of the unit expand or contract when the temperature changes. This is caused when the unit expels odours that have been absorbed from the walls, carpets, furniture or clothing. This may occur just after the unit is turned on when a high level of humidity is present in the room. This occurs to expel water or mois­ture that may have collected in the pipes or around piping fixtures. This occurs to dispel water from the heat exchanger. Turn on the power switch “ • “ will be displayed.
The start and stop function of the remote controller are not available when the CENTRALLY CON­TROLLED indicator is displayed.
Wait about three minutes (opera­tion has stopped to prevent dam­age to the air conditioner).
Not an error. During the DRY operation, blower ON/OFF is controlled by a micro­processor to prevent overcooling and to ensure efficient dehumidifi­cation. The fan speed can't be set by the remote controller during DRY operation.
Not an error.
1). When the HEAT operation starts, to prevent the unit from emitting cold air, the fan speed is gradually increased from zero to the set speed, in proportion to the temperature rise of the air emitted.
2). When the room temperature reaches the set temperature and the outdoor unit stops, the unit starts the LOW AIR operation.
3). During the HEAT operation, the DEFROST operation is performed to melt the frost adhering to the outdoor unit. During the DEFROST operation, the blower is stopped to prevent cold air coming from the indoor unit.
Not an error. The blower operates to eliminate the residual heat in the heated air conditioner. It stops after about 1 minute. This operation is performed when operation is stopped with the electric heater ON.
47
Page 48
The unit started even though the
Problem
start/stop button was not pushed.
The unit stopped even though the start/stop button was not pushed.
The remote controller`s timer can­not be set. “PLEASE WAIT” is displayed in the remote controller.
"FILTER" is displayed.
"STAND BY" is displayed.
Solution Problem Solution
Is this timer on? Press the start/stop button to stop the unit. Was a distant commend sent from the remote controller? Find out if the remote controller was used. Is the CENTRALLY CON­TROLLED indicator displayed? Find out if the remote controller was used. Is the automatic (cooling/heating) mode selected? Press the start/ stop button to stop the unit. Is the timer on? Press the start/stop button to restart the unit. Was a distant command sent from the remote controller? Find out if the remote controller was used. Is the CENTRALLY CON­TROLLED indicator displayed? Find out if the remote controller was used. Set the schedule timer if one is connected. An automatic startup test is being performed (will last for about two minutes).
Indicates that it is time to clean the air filter. Clean the air filter. Press the FILTER button on the remote controller twice to make the dis­play disappear. See the instruction manual that came with the product for how to clean the filter.
Displayed when the unit starts HEAT operation, when the air con­ditioning function puts the com­pressor in operation mode, or when the outdoor unit ends DEFROST operation and returns to HEAT operation. The display disappears after about 10 minutes. "STAND BY" displayed on the remote controller indicates that the indoor unit's heat exchanger hasn't fully heated up, so the blower air volume is restricted. To prevent cold air from being felt at this time, the up/down vane is automatically set to horizontal blow. When "STAND BY" is released, the up/down vane returns to the set­ting specified by the remote con­troller.
"DEFROST" is displayed (no air comes out the unit).
An error code is displayed in the remote controller.
No display appears on the wire­less remote controller. Signals are not received by the thin sensor unless sent from close up.
The operating display of the wire­less remote controller`s receiver is flashing.
Frost adheres to the outdoor unit when the outside air temperature is low and the humidity is high. This display indicates that the DEFROST operation is being per­formed to melt this frost. The DEFROST operation ends after about 10 minutes (15 minutes maximum). During the DEFROST operation, the indoor unit's heat exchanger becomes cold, so the blower is stopped. The up/down vane is automatically set to horizontal blow. When the DEFROST opera­tion ends, the unit switches to the HEAT SETUP operation.
A self-diagnostic function is being performed to preserve the air con­ditioner. * Do not attempt to make repairs
yourself. Turn the main switch off and contact the dealer from whom you bought the air condi­tioner. Provide him or her with the name of the unit and the information displayed in the remote controller.
The batteries are becoming weak. Replace the batteries and press the reset button. * If the display does not appear
after replacing the batteries, make sure that the (+,–) cells are aligned correctly.
A self-diagnostic function is being performed to preserve the air con­ditioner. * Do not attempt to make repairs
yourself. Turn the main switch off and contact the dealer from whom you bough the air condi­tioner. Provide him or her with the name of the unit.
48
Page 49
[for wireless remote controller]
Before you call out a repair man, check the following table to see whether there is a simple solution to your problem.
Problem
Unit does not operate at all.
Unit discharges air well, but fails to cool or heat the room well.
When POWER ON/OFF button is pushed, there is not beep and nothing is displayed.
Liquid-crystal display indicates that the unit operates.
Display reading Cause Solution
Main power switch is turned off.
Main power fuse has blown. Outdoor unit`s ground fault breaker is open. A power cut has occurred (see NOTE below).
Improper temperature setting.
Turn main power on. Then press the POWER ON/OFF button to turn the unit on. Replace the fuse. Replace the ground fault breaker.
Wait until power is restored, then press the POWER ON/OFF button to turn the unit on. After checking the temperature setting.
Filters are clogged.
Outdoor unit`s intake or outlet is obstructed.
Unit does not start immediately.
NOTE: After a power cut, the unit will not restart automatically. You will have to restart it by pressing the POWER - ON/OFF button
on the remote controller.
If none of the above apply, turn the main switch off and contact the dealer from whom you bough the air-conditioner, telling him the model name and the nature of the problem. Do not try to fix the unit yourself.
In any of the following cases, turn off the main power switch and contact your local dealer for service:
• The operation lamp (on the main unit) flashes.
• The switches do not work properly.
• The circuit breaker trips frequently (or the fuse blows frequently).
• Water has accidentally been splashed into the unit.
• Water leaks from the unit.
• Something is accidentally dropped into the air-conditioner.
• An unusual noise is heard during operation.
The following do not indicate any malfunction:
·Odours :Smells such as tobacco or cosmetic odours may persist after they have been sucked into
·Sound of liquid flowing inside indoor unit :This can occur during or after operation and is simply the sound of refrigerant being
·Ticking sound coming from indoor unit :This can occur when cooling or heating has just begun or has just stopped. It is caused by
·The CENTRALLY CONTROLLED indicator appearing on the LCD panel : From time to time, this message may come up on the LCD panel.
Liquid-crystal display indicates that the unit operates.
the unit. circulated inside the unit. the indoor unit shrinking or expanding slightly due to the change in temperature.
This does not indicate any malfunction.
A door or window has been open. Unit is waiting three minutes before restarting.
Clean the filter and resume opera­tion.
Remove the obstruction. Shut door or window.
Wait until the unit restarts automat­ically. The compressor may hesi­tate resuming because a three­minute resume prevention circuit is incorporated in the outdoor unit for protection of the compressor.
49
Page 50
M
4
6
2 3
5
1
Blue
Brown
Yellow
Orange
Red
White
Linear expansion valve (LEV)
Parts name
Check points
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 20:)
(Refer to the next pege for a detail.)
Liquid temperature thermistor (TH3)
Discharge temperature thermistor (TH4)
Condenser/evaporator temperature thermistor (TH6)
Normal
4.3k"~9.6k"
160k"~410k"
4.3k"~9.6k"
TH3 TH4 TH6
Abnormal
Open or short
Measure the resistance between the terminals using a tester. (Surrounding temperature 20C°)
4-WAY VALVE SOLENOID COIL (21S4)
Normal
1430"
Normal
(1) - (5)
White - Red
(2) - (6)
Yellow - Brown
(3) - (5)
Orange - Red
(4) - (6)
Blue - Brown
Abnormal
Abnormal
150" ±10%
Open or short
Open or short
Measure the resistance between the terminals using a tester. (Surrounding temperature 20°)
BYPASS VALVE SOLENOID COIL (21R)
Only PUH-P125, P140
Normal
P125, 140
1970"
P25, P35
1920" ±7%
P50~P140
1516" ±7%
Abnormal
Open or short
Measure the resistance between the terminals using a tester.
CRANKCASE HEATER (HC)
Normal Abnormal
Open or short
Measure the resistance between the terminals using a tester. (Surrounding temperature 20C°)
FAN MOTOR(MF)
P25~P71
77.4" ±10%
99.1" ±10%
P100~P140
57.4" ±10%
99.7" ±10%
Normal
Motor lead wire
Abnormal
Open or short
White — Black White — Red
Red
Black
White
Orange
Protector OPEN :130i5: CLOSE :88i15:
Red
Black
P25~P71
P100 P125 P140
White
Black
Protector OPEN :135i5:
FUSE OPEN : 162~169:
10-6. HOW TO CHECK THE PARTS PUH-P25, P35, P50, P60, P71, P100VGAA.UK PUH-P35, P50, P60, P71, P100, P125, P140YGAA.UK PU-P35, P50, P60, P71, P100VGAA.UK PU-P35, P50, P60, P71, P100, P125, P140YGAA.UK
50
Page 51
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (k")
500
400
300
200
100
0
25
50 75 100 120
< Thermistor for higher temperature >
Temperature (:)
Resistance (k")
<Thermistor characteristic graph>
Thermistor for lower temperature
Liquid temperature thermistor(TH3) Condenser/evaporator temperature thermistor(TH6)
Thermistor R0=15k' ±3% Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
1
273+t
1
273
0: 15k' 10: 9.6k' 20: 6.3k' 25: 5.2k' 30: 4.3k' 40: 3.0k'
Thermistor for
Discharge temperature thermistor(TH4)
higher temperature
Thermistor R120=7.465k' ±2% Fixed number of B=4057 ±2%
Rt=7.465exp { 4057( ) }
1
273+t
1
393
20: 250k' 30: 160k' 40: 104k' 50: 70k' 60: 48k' 70: 34k' 80: 24k' 90: 17.5k' 100: 13.0k' 110: 9.8k'
Linear expansion valve
Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the controller board and the linear expansion valve>
Linear expansion valve
Blue
4
6
2 3
Orange
Brown
Yellow
White
M
5
1
Red
Controller board
DC12V
Brown
Red
[4 [3
[2 [1
Blue
Orange
Yellow
White
Connector(CNLEV)
6 5
4 3
2 1
Drive circuit
[4 [3
[2 [1
51
Page 52
Problem Check point Corrective measure
Remove the connector from the controller board and connect diagnostic LEDs.
Pulse signal will be sent out for 10 seconds as soon as the main switch is turn on. If there is LED with lights on or lights off, it means the operation circuit is abnormal.
Motor will idle and make ticking noise when motor is operated while the linear expansion valve is locked. This ticking sound is the sign of the abnormality.
Measure the resistance between the each coil (red-white, red-orange, brown-yellow, brown-blue) using a tester. It is normal if the resistance is in the range of 150'±10%.
 1 Check improperly connected connector terminals and the wire colors. 2 Remove the connector on the controller board side and check electrical
conductance
Operation circuit failure of the micro processor.
Exchange the linear expansion valve.
Exchange the indoor controller board at drive circuit failure.
Exchange the linear expansion vale.
Disconnect the connector at the controller board, then check the continuity.
Wrong connection of the connector or contact failure.
Short or breakage of the motor coil of the linear expansion valve.
Linear expansion valve mechanism is locked.
6 5 4 3 2 1
1k" LED
<Output pulse signal and the valve operation>
D
A
E
B
C
Open
Extra tightning (32 pulse)
Pulse number
2000 pulse Opening a valve all the way
Close
Valve position (capacity)
Output
(Phase)
{1 {2 {3 {4
Linear expansion valve operation
1 ON ON
OFF OFF
2
OFF
ON ON
OFF
Output
3 OFF OFF
ON ON
4
ON OFF OFF
ON
Closing a valve : 1 2 3 4 1 Opening a valve : 4 3 2 1 4
The output pulse shifts in above order.
1. When linear expansion valve operation stops, all output phase
become OFF.
2. At phase interruption or when phase does not shift in order, motor does not rotate smoothly and motor will locks and vibrates.
When the switch is turned on, 2200 pulse closing valve signal
will be send till it goes to tion.
When the valve move smoothly, there is no noise or vibration occurring from the linear expansion valve : however, when the pulse number moves from E to A or when the valve is locked, more noise can be heard than normal situation.
Noise can be detected by placing the ear against the screw dri-
ver handle while putting the screw driver to the linear expansion valve.
A point in order to define the valve posi-
Trouble shooting
52
Page 53
10-7. TEST POINT DIAGRAM
Outdoor controller board
PUH-P25, P35, P50, P60, P71, P100VGAA.UK PUH-P35, P50, P60, P71, P100, P125, P140YGAA.UK PU-P35, P50, P60, P71, P100VGAA.UK PU-P35, P50, P60, P71, P100, P125, P140YGAA.UK
MF4, MF3 (MF4 is only for PUH-P100V, PU-P100V, PUH-P100~140Y and PU-P100~140Y) Connect to fan motor Between 1 and 3 220V~240V AC
52C MC contactor Between 1 and 3 220V~240V AC
CH Crankcase heater Between 1 and 3 220V~240V AC
21S4
w1
R.V. coil Between 1 and 3 220V~240V AC
SV
w2
Baypass valve
solenoid coil Between 1 and 3 220V~240V AC
SW1 Group number
address
CNM When connecting A-control Service Tool [ PAC-SK52ST], operation mode can be displayed by means of 7SEG
SW5 Fan 100% fix Outdoor LEV opening fix
TH4 Discharge temperature thermistor
TH3 Liquid temperature thermisor TH6 Condenser/Evaporator temperature thermisor
63L
w3
Low pressure switch
SW4 Test run
Jumper wire J1~J6 Model selection
w1. 21S4 is only for PUH-P25~100V and PUH-P35~140Y. w2. SV is only for PUH-P125Y and PUH-P140Y. w3. 63L is only for PUH-P125, 140YGAA and PU-P125, 140YGAA.
53
+
Communication power supply D71 Voltage developed across: 16-30V DC
Page 54
10-8. EMERGENCY OPERATION
Display
U4 E8
E9
E0~E7
Inspections details
Piping thermistor (TH3) or condenser thermistor (TH6) open/short Transmission between indoor and outdoor unit Receiving trouble (outdoor unit) Transmission between indoor and outdoor unit Transmission trouble (outdoor unit) Transmission trouble except for outdoor unit
SW4
12
ON
SW4
1 2 Cooling
Heating
ON
Parts name Operation
Compressor Four way valve Outdoor fan motor LEV Indoor fan motor
Always ON Changeable with SW 4-2 Max. speed Full opening High
1. When the outdoor unit becomes under mentioned inspection display. Also when the wired remote controller or micro com­puter in the indoor unit is broken. If there is not any wrong section, short-circuited connector (CN31) in the outdoor con­troller board is possible to emergency operation.
Trouble to which emergency operation can be set
2. Check items and notices as the emergency operation (1) Be sure that there is no trouble in the outdoor unit any more besides above mentioned.
(When there is trouble besides above mentioned, emergency operation is not available.) (2) When the emergency operation, their switch (SWE) setting in the indoor controller board is necessary. (3) Emergency operation will be serial operation by the power supply ON/OFF.
ON/OFF or temperature, etc. adjustment is not operated by the remote controller. (4) Do not operate for a long time as cold air is blown from the indoor unit, when the outdoor unit starts defrosting operation
during heating emergency operation. (5) Cool emergency operation must be within 10 hours at most. It may cause heat exchanger frosting in the indoor unit. (6) After completing the emergency operation, return the switch setting, etc. in former state.
3. How to operate the emergency operation (1) Turn off the main power supply. (2) Turn on the emergency switch (SWE) in the indoor controller board. (3) Short-circuit the CN31 (emergency operation connector) in the outdoor controller board. (4) Set the operation mode (COOL or HEAT) with the SW4-2 in the outdoor controller board.
(SW4-1 cannot be used.) (5) Turn on the main power supply. (6) The emergency operation starts and be sure of blinking the operation mode display.
4. Emergency operation details (1) Operate with the operation mode which has set (COOL or HEAT) by the SW4-2. (2) In the fan operation conditions, the fan is always operated by 100 percent. (3) The operation mode display blinks at intervals of 1 second.
5. How to release the emergency operation (1) Turn off the main power supply. (2) Turn off the emergency switch (SWE) in the indoor controller board. (3) Open the CN31 (emergency operation connector) in the outdoor controller board. (4) Set the SW4-2 on the outdoor controller board as in the right.
Unit operation during emergency operation
54
Page 55
Switch
Signal
SW1 1
2
No.
Function Effective timing
Action by the switch operation
Compulsory defrosting w1 Start Normal Heat compressor operating
~
3 6
Abnormal history clear
Refrigerant address setting When power supply ON
Clear Normal off or operating
SW4 1
2
Trial run ON/OFF ON OFF
OFF
Trial run mode setting Heat Cool
SW5 1
2
Fan 100% fix 100% fix Normal
Outdoor LEV opening fix w2 Fix Normal 3 4
No function No function No function No function No function No function
off or operating off or operating
– –
ON OFF
123
0123
456ON123456ON123456ON123456
ON
123
4567
456ON123456ON123456ON123456
ON
123
891011
456ON123456ON123456ON123456
ON
123
12 13 14 15
456ON123456ON123456ON123456
ON
10-9. FUNCTION OF SWITCHS, CONNECTORS AND JUMPERS
Outdoor switch for a new freon function table
w1 Compulsory defrosting should be done as follows.
1Change the DIP SW1-1 in the outdoor controller board OFF➔ ON (compulsory defrosting start). According to the 1 operation,
• Heat mode setting • Compressor operating • The defrosting starts when the piping temperature is 8˚C and below.
• When the stated condition is satisfied, the defrosting operation will be completed.
w2 Ignore the change of LEV opening, which is subject to change of subcooling, and fix DIP SW 5-2 in the on position. Then
LEV opening is fixed. When air conditioner is overloaded for some reasons, ignore the change of subcooling and adjust the LEV opening in accordance with overload condition.
55
Page 56
Function of switches
Note : Do not use CN33.
Type of switches
DIP SW SW2
1 2 3 4 5 6
Switch Function
Changing of LED display <Self-diagnosis>
Operation monitor Operation monitor
Under operation or suspension
No.
ON
OFF
Action by the switch operation
Effective timing
Jumper connector function table
Switch
Signal
J1
J2
J3
J4
J5
J6
CN31
No.
Function Effective timing
Action by the switch operation
Switch of single phase and
3 phase power supply
Switch of cooling
only/cooling and heat pump
When power supply ON
When power supply ON
Single phase3 phase
When power supply ON
Cooling and heat pumpCooling only
Capacity switch
Emergency operation Emergency operation Normal When power supply ON
ON OFF
Model
Setting
J3 J4 J5 J6
:Short :Open
P25 P35 P50 P60 P71 P100 P125 P140
10-10. Optional parts
A-control Service Tool [ PAC-SK52ST ]
56
Page 57
Outdoor unit operation monitor function
1ON23456
1ON23456
1 second
interval
Display Operation mode
The tens digit : Operation mode The units digit : Relay output
O C H
d
Display
0 1 2 3 4 5 6 7
Compressor 4-way valve
Bypass solenoid valve
— — —
— ON ON ON ON
— ON ON
— ON ON
ON
ON
ON
ON
OFF
COOL
HEAT
DEFROSTING
Display
Inspection unit 0 1 2 3 4
Outdoor unit Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4
1 second
interval
<Abnormal unit number> <Abnormal code>
Operation indicator SW2 : Indicator change of self diagnosis
SW2 setting
<Digital indicator LED1 working details>
· Lighting (Normal operation) : Indicating the operation mode.
(Be sure the 1 to 6 in the SW2 are set to OFF)
(1) Display when the power supply ON.
When the power supply ON, blinking displays by turns. Wait for 4 minutes at the longest.
(2) When the display lights. (Normal operation)
1Operation mode display.
Display detail
(Lighting)
LED1
Explanation for display Unit
Code
indication
SW2
(Initial setting)
2Error postponing display
(Compressor stop by the protection device
working) : Display the postponement code.
Postponement code is display during the error
postponing.
(3) When the display blinks (Operation stop by the protection device working) : Display the inspection code.
An error unit number and code are displayed by turns.
(4) When 7SEG display lights up (Protective device stops compressor operating.):
The screen displays the corresponding code when abnormality is being recorded.
57
Page 58
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456 1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
Display detail
Piping temperature. (TH3) – 40~90
Explanation for display Unit
– 40~90 (When the coil thermistor is 0:or below, “–” and
temperature displays by turns.) (Example) When -10:
One second interval – 10
:
Discharge temperature. (TH4) 0~216
FAN output step. 0~16
The number of ON / OFF times. 0~9999
Compressor integrating operation times. 0~9999
0~216 (When the discharge thermistor is 100 or more, the
hundreds digit and tens, units digit are displayed by turns.)
(Example) When 150:
One second interval 1 50
0~16
0~9999 (When the number of times is 100 or more, the
hundreds digit and tens, units digit are displayed by turns.)
(Example) When 42500 times
One second interval 4 25
0~9999 (When the time is 100 or more, the hundreds digit
and tens, units digit are displayed by turns.)
(Example) When 2450 hours
One second interval 2 45
:
Step
100 times
10 hours
Compressor operating current. 0~40
LEV opening. 0~440
New error postponement code. New outdoor unit error postponement display.
Operation mode on error occurring. Operation mode on error stop.
0~40
Output pulse is displayed by one fifth of actual value. (Example) When the display shows 300
300 5 = 1500 pulse 1500 pulse is the actual output pulse
No postponement code is “00”.
SW2 setting is displayed at below code.
(SW2)
58
A
Pulse
Code
display
Code
display
Page 59
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
Display detail
Piping temperature (TH3) on error occurring – 40~90
Explanation for display Unit
– 40~90 (When the coil thermistor is 0:and less, “–” and
temperature are displayed by turns)
(Example) When –15:
One second interval – 15
:
Compressor temperature (TH4) or discharge temperature (TH4) on error occurring. 0~216
Compressor operating current on error occurring. 0~40
Error code history (1) (latest) Alternate display of abnormal unit number and code.
Error code history (2) Alternate display of error unit number and code.
0~216 (When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 130:
One second interval 1 30
0~40
When no error history, “ 0 ” and “– –” and displayed by turns.
When no error history, “ 0 ” and “– –” and displayed by turns.
:
A
Code
display
Code
display
Thermistor ON time . 0~999
Trial run elapsed time. 0~120
The number of connected indoor unit. 0~4
0~999 (When the time is 100 or more, the hundreds digit
and tens, units digit are displayed by turns.)
(Example) When 245 minutes
One second interval 2 45
0~120 (When the time is 100 or more, the hundreds digit
and tens, units digit are displayed by turns.)
(Example) When 105 minutes
One second interval 1 05
0~4
59
Minute
Minute
Unit
Page 60
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
Capacity
P25 P35 P50 P60
P71 P100 P125 P140
Code
6 9
10
11 14 20 25 28
Setting details
The tens digit (Total display for applied setting)
The units digit
H·P /
Cooling only
Single phase / Three phase
Display details
0 : H·P 1 : Cooling only 0 :
Single phase
2 :
Three phase
Setting details
Defrosting switch
Display details
0 :
Normal
1 :
High humidity region
1ON23456
1ON23456
Display detail
Capacity setting display
Outdoor unit setting advice
Indoor unit piping temperature / LIQUID (TH2) Indoor 1 – 39~88
Explanation for display
Display as an outdoor capacity code
(Example) When switching cooing and heat pump,
three phase, defrosting (normal)
“20”
– 39~88 (When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
Unit
Code
display
Code
display
:
Indoor unit piping temperature / LIQUID (TH2) Indoor 2 – 39~88
Indoor unit piping temperature / LIQUID (TH2) Indoor 3 – 39~88
Indoor unit piping temperature / LIQUID (TH2) Indoor 4 – 39~88
Indoor room temperature (TH1) 8~39
– 39~88 (When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
:
When no indoor unit, “00” is displayed.
– 39~88 (When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
:
When no indoor unit, “00” is displayed.
– 39~88 (When the temperature is 0: or less, “–” and
temperature are displayed by turns)
:
When no indoor unit, “00” is displayed.
8~39
:
60
Page 61
SW2 setting
1ON23456
1ON23456 1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
Display detail
Indoor setting temperature 17~30
Explanation for display Unit
17~30
:
Outdoor piping temperature/Cond./Eva. (TH6) – 39~88
Discharge super heat. SHd 0~255
Cool = TH4-TH6 Heat = TH4-TH5
Sub cool. SC 0~130
Cool = TH6-TH3 Heat = TH5-TH2
Communication demanded capacity. 0~255
When air conditioners are connected to M-NET and under central control.
When no communication demanded
setting, “100” is displayed.
Error thermistor display
Fan step on error occurring. 0~16
– 39~88 (When the temperature is 0: or less, “–” and
temperature are displayed by turns)
0~255 (When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) 115 :
One second interval. 1 15
0~130 (When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
0~255 (When the capacity is 100 or more, the hundreds
digit and tens, units digit are displayed by turns)
(Example) When 100
One second interval. 1 00
3: Outdoor liquid piping thermistor (TH3) 6: Outdoor condenser thermistor (TH6)
When no error thermistor, “–” is
displayed.
0~16
:
:
:
%
Code
Step
LEV opening on error occurring 0~440 Display by scaled 1/5 to actual opening
Outdoor piping temperature/Cond./Eva. on error occurring. (TH6) – 39~88
Discharge super heat on error occurring. SHd 0~255
Cool = TH4-TH6 Heat = TH4-TH5
Sub cool on error occurring. SC 0~130
Cool = TH6-TH3 Heat = TH5-TH2
0~440 (When the pulse is 100 or more, the hundreds digit
and tens, units digit are displayed by turns)
(Example) When the display shows 300.
300
5 = 1500 pulse
– 39~88 (When the thermistor is 0:and less, “–” and
temperature are displayed by turns.)
(Example) When –15:
One second interval – 15
0~255 (When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 150:
One second interval 1 50
0~130 (When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 115:
One second interval 1 15
61
Pulse
:
:
:
Page 62
SW2 setting
1ON23456
1ON23456
1ON23456
1ON23456
1ON23456
Display detail
Thermo-on time to error stop. 0~999
Indoor unit piping temperature / cond. / Eva. (TH5) indoor 1 –39~88
Explanation for display Unit
0~999 (When the time is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 415 minutes
One second interval 4 15
–39~88 (When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Minute
°C
Indoor unit piping temperature / cond. / Eva. (TH5) indoor 2 –39~88
–39~88 (When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
°C
When no indoor unit, “00” is displayed.
Indoor unit piping temperature / cond. / Eva. (TH5) indoor 3 –39~88
–39~88 (When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
°C
When no indoor unit, “00” is displayed.
Indoor unit piping temperature / cond. / Eva. (TH5) indoor 4 –39~88
–39~88 (When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
°C
When no indoor unit, “00” is displayed.
For A-control Service Tool [ PAC-SK52ST ]
[Operation for A-control Service Tool]
1. By operating the dip switch SW2 on A-control Service Tool, the digital display of light-emitting diode (LED1) indicates the operation mode and types of inspection with a tow-digit number and symbol.
2. After the inspection, A-control Service Tool shall be removed out of outdoor unit control board.
62
Page 63
1 blink
2 blinks
LED1
(Green)
LED2 (Red)
1 blink
2 blinks
1 blink
2 blinks
3 blinks
4 blinks
•Negative Phase detection
•The wires of power supply and connecting wires of indoor / outdoor units are crossed with one another.
•51CM connector open
•Start-up time is up
•Indoor / outdoor unit connector mis-wiring
•Excessive numbers of indoor units per an outdoor unit (five or more)
•Mis-wiring of indoor / outdoor unit connection wires (crossed wiring or disconnection)
•Indoor / outdoor unit transmission error (Transmitting error: Outdoor controller side)
•Indoor / outdoor unit transmission error (Signal receiving error: Indoor controller side)
•Indoor / outdoor unit transmission error (Transmitting error: Indoor controller side)
•Indoor / outdoor unit transmission error (Signal receiving error :Outdoor controller side)
•Remote controller transmission error (Transmitting error: Indoor controller side)
•Undefined error code
•Remote controller transmission error (Signal receiving error: Remote controller side)
•Remote controller transmission error (Transmitting error: Remote controller side)
•Remote controller transmission error (Signal receiving error: Indoor controller side)
1 Check if the wires of power supply are connected to their corresponding terminals on TB1. 2 Check if the wirings are correct on power supply (TB1) and outdoor power supply board (TB2).
1 Check if the wirings are correct on the connecting wires of indoor / outdoor units. 2 Check if a single outdoor unit connects five or more indoor units.
1 Check if the connectors of 51CM (51C) on outdoor controller board are disconnected. 2 Check the continuity of connector 51CM (51C) by using a tester.
•63L connector open
1 Check connection of 63L(63L) connector on outdoor
controller board.
2 Check the 63L side of connecting wire. 3 Check refrigerant pressure.
Charge additional refrigerant. Check continuity by tester. Replace outdoor controller board.
4 Replace outdoor controller board.
1 Check if the wirings are correct on indoor units or remote
controllers. 2 Check if there is noise on the transmission lines of remote controllers.
3 Turn the power off and let the units operate again to confirm.
1 Check if there is noise on the transmission lines of remote
controllers. 2 Check if there is noise on the connecting wires of indoor/outdoor units. 3 Turn the power off and let the units operate again to confirm.
To be continued on the next page.
1 Check if the wirings are correct on the connecting wires of indoor / outdoor units. 2 Check if there is noise on the wires of power supply and connecting wires of indoor / outdoor units. 3 Check if there is noise on both indoor and outdoor controller board. 4 Turn the power off and let the units operate again to confirm.
Indication (O.B)
Error Name Inspection method
LED1 (Green)
LED2 (Red)
<Display function of inspection for outdoor unit>
• The blinking patterns of two LEDs—LED1(Green) and LED2(Red)—show the diagnoses of troubles in case of malfunction.
• By 7SEG indicator board indicates the operation mode and inspection types.
63
Page 64
From the preceding page.
Indication (O.B)
LED1
(Green)
3 blinks
4 blinks
LED2
(Red)
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
1 blinks
2 blinks
3 blinks
•Abnormal high discharge temperature(TH4)
•Abnormal high pressure (High pressure switch 63H worked)
•Abnormal low pressure (Low pressure switch 63L worked)
•Protection from overheat operation (TH3)
•Compressor's overcurrent (Overload)
•Thermal relay (51C) has been tripped
•Overcurrent has locked the operation of compressor in start-up.
•Open / short circuit of discharge thermistor (TH4)
•Open / short circuit of liquid pipe thermistor (TH3)
•Open / short circuit of EVA / COND pipe thermistor (TH6)
•Abnormality of room temperature thermistor (Indoor unit side: TH1)
•Abnormality of Liquid pipe thermistor (Indoor unit side:TH2)
•Abnormality of EVA / COND pipe thermistor (Indoor unit side: TH5)
•Abnormality of drain sensor (Indoor unit side : (DS))
•Malfunction of drain-up machine
•Abnormality of pipe temperature
Error Name Inspection method
1 Check if ball valves are open. 2 Check the continuity of connector (TH4) on outdoor controller
board by using a tester. 3 Check if the unit fills the refrigerant at the same amount as specified. 1 Check if indoor / outdoor units have a short cycle on their air ducts. 2 Check if the connector of 52C (63H) on outdoor controller board is disconnected. 3 Check if the units get their heat exchanger and filter dirty and clogged. 4 Measure resistance values among terminals on linear expansion valve by using a tester.
1 Check stop valve. 234 Put the power off and on again to check if F3 is displayed
on restarting. If F3 is displayed, follow the F3 processing direction.
5 Correct to proper amount of refrigerant. 6 Check linear expansion valve. Refer to 10-6. 1 Check if outdoor unit has a short cycle on its air duct. 2 Check if the connector of TH3 on outdoor controller board is
disconnected.
1 Check if ball valves are open. 2 Measure resistance values among terminals on compressor
by using a tester.
3 Check if outdoor unit has a short cycle on its air duct. 4 Check if the connector of 51CM (51C) on outdoor controller
board is disconnected. 5 Check if the units get their heat exchanger and filter dirty and clogged. 1 Check if the connectors of TH4, TH3, and TH6 on outdoor controller board are disconnected. 2 Measure the resistance values of each thermistor (TH4, TH3, and TH6). 1 Check if the connectors of CN20, CN21, and CN29 on outdoor controller board are disconnected. 2 Measure the resistance values of each thermistor (TH1, TH2, and TH5).
1 Check if the connector of CN31 on outdoor controller board is disconnected.
2 Measure the resistance value of drain sensor. 3 Measure resistance values among terminals on drain-up
machine by using a tester. 1 Check if the connectors of CN20, CN21, and CN29 on outdoor controller board are disconnected.
2 Check if ball valves are open. 3 Check if the wirings are correct on the connecting wires of
indoor / outdoor units.
64
Page 65
11 FUNCTION SETTING
11-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1.
<Table 1> Function selections
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
W1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
Function
Power failure automatic recovery Indoor temperature detecting
LOSSNAY connectivity
Power supply voltage Frost prevention temperature Humidifier control
Change of defrosting control Thermo differential setting
Settings
OFF ON Operating indoor units (The average is considered as indoor temperature.) Indoor unit with remote controller Remote controller's internal sensor Not supported Supported (indoor unit not equipped with outdoor air intake) Supported (indoor unit equipped with outdoor air intake) 240V 220V,230V 2: (Normal) 3: When the compressor operates, the humidifier also operates. When the fan operates, the humidifier also operates. Standard For high humidity Normal 5: 10:
Mode No.
01
02
03
04 15 16 17
19
Setting No.
1 2
1 2
3 1 2 3 1 2 1 2 1 2 1 2 1 2 3
Initial setting
(when sent from the factory)
Remarks
The setting is applied to all the units in the same refrigerant system.
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the indoor unit number.
• When setting functions for a simultaneous- Twin Triple indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin Triple-indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to 4 setting the indoor unit number.
Initial setting (Factory setting
Mode
Setting
Function Settings
Filter sign 100Hr 1
Air flow Quiet Standard 1 - - - ­(
No.of air outlets 4 directions 1 - - - - -
Optional high efficiency filter Supported Vane setting
Energy saving air Disabled flow (Heating mode Optional humidifier Not supported ( Vane differential setting No.1 setting (TH5: 24-28: in heating mode No.2 setting (Standard, TH5:28-32: ( Swing Not available
Set temperature in heating Available mode (4 deg up Fan speed when the Extra low 1 heating thermostat is OFF
Quiet operation mode Disabled (Standard of PLA-AA(Fan speed Fan speed when the cooling thermostat is OFF Stop Detection of abnormality of Available the pipe temperature (P8)Not available
)
Fan speed
PLA-AA only
cold wind prevention
)
)
)
2500Hr 07 2 No filter sign indicator
Standard High ceiling
3 directions 09 2 - - - - ­2 directions Not supported
No vanes (Vane No.3 setting : PLA, PLH only Vane No.1 setting Vane No.2 setting
Enabled
Supported
)
No.3 setting (TH5: 32-38:
Available
Not available Stop
Set fan speed
)
Enabled (Quiet operation mode Set fan speed
High ceiling1 High ceiling2
)
PLA, PLH
}
)
)
)
)
No.
08 2 - - - -
10
)
11 2 - - - -
12
13
14 2 - - -
23
24
25 2
26
27
28
4-Way
No.
cassette
PLA-AA
PLH-AAH
3
3----
3----­1 2
1----
3---­1 2 1 2
1-- -
3-- ­1 2 1 2
3 1 2 1 2 1 2
Ceiling
concealed
PEAD-EA
PEHD-EAH
PEAD-GA
----
----
----
----
-----
-----
---
---
-----
-----
- : Not available
Ceiling suspended
PCA-GA
PCH-GAH
PCA-HA
)
Wall
mounted
PKA-GAL
PKH-GALH
PKA-FAL
PKH-FALH
Floor
standing
PSA-GA
PSH-GAH
1-Way
Casette
PMH-BA
-
-
-
-
-
-
-
-
-
-
-
-
-
-
65
Page 66
11-1-1. Selecting functions using the wired remote controller
First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room temperature detection position is given. For actual operations, refer to steps 1 to 0 .
Modes 01 to 13 can be activated by pressing buttons
A
and
B
simultaneously, and modes 15 to 28 by pressing buttons
B
and J.
The above procedure must be carried out only if changes are necessary.
Mode number
F
E
G
Selecting functions using the wired remote controller
1
Check the function selection setting.
2
Switch to function setting mode.
(Press
A
with the remote controller stopped.)
Setting number
C
Refrigerant address Unit number
and B at the same time
D
For modes 15 and higher,
J
and B at the same time.
press
I
A
B
J
3
Specify refrigerant address 00 (outdoor unit)
4
Specify unit No. 00. (indoor unit)
(Use
C
and D.)
5
Enter the setting.
(Press
6
Select mode No. 02
E
.)
(Specified indoor unit: BLOW operation)
(room temperature detection position).
7
Select setting No. 03 (remote controller fixed).
(Use
F
and G.)
8
Enter the setting.
(Press
E
.)
Finished
Example: Selecting room temperature detection position
NO
YES
0
Function selection end screen
(Press
A
and B at the same time.)
NO
YES
Change refrigerant address unit No.
9
66
Page 67
[Operating Procedure]
1 Check the setting items provided by function selection.
If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2 to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual.
2 Switch off the remote controller.
A Hold down the
least two seconds. display content will change as shown below.
* If the unit stops after
Check to see if there are any sources of noise or interference near the transmission path. Note
If you have made operational mistakes during this procedure, exit function selection (see step 0 ), and then restart from step 2 .
4 Set the indoor unit number.
D Press the
area.
ON/OFF
and B
FILTER
FUNCTION
will start to flash, and then the remote controller's
SELECTION
Refrigerant address display section
FUNCTION
flashed for two seconds or "88" flashes in the room temperature display area for two seconds, a transmission error may have occurred.
SELECTION
button so that " - -" flashes in the unit number display
Unit number display section
buttons simultaneously for at
TEST
3 Set the outdoor unit's refrigerant address.
C Press the [ CLOCK] buttons ( and ) to select the desired
refrigerant address. The refrigerant address changes from "00" to "15". (This operation is not possible for single refrigerant systems.)
C Press the [
of the indoor unit for which you want to perform function selection. The unit number changes to "00", "01", "02","03",04" and "AL" each time a button is pressed.
CLOCK] buttons ( and ) to select the unit number
* To set modes 01 to 06 or 15 to 22 select unit number "00". * To set modes 07 to 14 or 23 to 28 carry out as follows:
• To set each indoor unit individually, select "01" to "04".
• To set all the indoor units collectively, select "AL".
5 Confirm the refrigerant address and unit number.
E Press the
number. After a while, "- - " will start to flash in the mode number display area.
Mode number display section
* "88" will flash in the room temperature display area if the selected refrigerant
address does not exist in the system. Furthermore, if refrigerant address display area also flashes, there are no units that corre­spond to the selected unit number. In this case, the refrigerant address and unit number may be incorrect, so repeat steps 2 and 3 to set the correct ones.
6 Select the mode number.
F Press the [
number. (Only the selectable mode numbers can be selected.)
7 Select the setting content for the selected mode.
G Press the
flash, so check the currently set content.
8 Register the settings you have made in steps 3 to 7 .
E Press the
to flash and registration starts.
button to confirm the refrigerant address and unit
MODE
"F"
appears and flashes in the unit number display area and the
TEMP] buttons ( and ) to set the desired mode
button. The currently selected setting number will
MENU
Setting number display section
button. The mode number and setting number will start
MODE
Setting number 1 = Indoor unit operating average
E When the refrigerant address and unit number are confirmed by pressing the
button, the corresponding indoor unit will start fan operation. This
MODE
helps you find the location of the indoor unit for which you want to perform function selection. However, if "00" or "AL" is selected as the unit number, all the indoor units corresponding to the specified refrigerant address will start fan operation.
Example) When the refrigerant address is set to 00 and the unit number is 02.
00 refrigerant address
Outdoor unit
Indoor unit
Designate operation
* When grouping different refrigerant systems, if an indoor unit other than the
one to which the refrigerant address has been set performs fan operation, there may be another refrigerant address that is the same as the specified one. In this case, check the DIP switch of the outdoor unit to see whether such a refrigerant address exists.
Mode number display section
F Press the [
number.
The mode number and setting number will stop flashing and remain lit, indicating the end of registration.
Unit number 01 Unit number 02
Remote controller
Mode number 02 = Indoor tempreture detection
TEMP] buttons ( and ) to select the desired setting
Setting number 3 = Remote controller built-in sensor
Fan draft
Unit number 03
* If " - - - " is displayed for both the mode number and setting number and "
Check to see if there are any sources of noise or interference near the transmission path. 9 If you wish to continue to select other functions, repeat steps 3 to 8 . 0 Complete function selection.
A Hold down the
two seconds. After a while, the function selection screen will disappear and the air condi­tioner OFF screen will reappear.
Note If a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check" column of Table 1 to indicate the change.
FILTER
and
TEST
" flashes in the room temperature display area, a transmission error may have occurred.
buttons simultaneously for at least
* Do not operate the remote controller for at least 30 seconds after completing
function selection. (No operations will be accepted even if they are made.)
67
Page 68
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESET
SET
CLOCK
h
CHECK
min
h
The flow of the function selection procedure is shown below. This example shows how to turn off the function that raises the set temperature by 4 degrees during HEAT operation . The procedure is given after the flow chart.
1 Check the function selection setting. 2 Switch to function selection mode.
(Enter address "50" in troubleshooting mode, then press the HOUR button.)
Troubleshooting mode is the mode entered when you press the INSPECT button twice to display "INSPECT".
3 Specify unit No. "01" (since the function applies to unit 01).
(Set address "01" while still in troubleshooting mode, then press the MINUTE button.)
Note: You can't specify the refrigerant address. 4
Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation). (Set address "24" while still in troubleshooting mode, then press the HOUR button.)
6
Finished
8 End function selection mode.
(End troubleshooting mode.)
YES
NO
Note: When you switch to function selection mode
on the wireless remote controller's operation area, the unit ends function selection mode automatically if nothing is input for 10 minutes or longer.
5 Select setting No. "02" (OFF).
(Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change unit No.
YES
NO
7
11-1-2. Selecting functions using the wireless remote controller (Type C)
h
min
Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refriger­ant system with wireless function. Refrigerant address cannot be specified by the wireless remote controller.
[Flow of function selection procedure]
[Operating instructions]
1 Check the function settings. 2 Press the button twice continuously. CHECK is lit and “00” blinks.
Press the temp button once to set “50”. Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
3 Set the unit number.
Press the temp button to set the unit number. (Press “01” to specify the indoor unit whose unit number is 01.) Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
By setting unit number with the button, specified indoor unit starts performing fan operation. Detect which unit is assigned to which number using this function. If unit number is set to AL, all the indoor units in same refrigerant system start performing fan operation simultaneously.
* If a unit number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the unit number
setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the unit number
setting.
4 Select a mode.
Press the temp button to set a mode. Press “24” to turn on the function that raises the set temperature by 4 degree during heat operation. Direct the wireless remote controller toward the sensor of the indoor unit and press the button. The sensor-operation indicator will flash and beeps will be heard to indicate the current setting number. Current setting number: 1 = 1 beep (one second)
* If a mode number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the mode
number.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the mode
number.
5 Select the setting number.
Press the temp button to select the setting number. (02: Not available) Direct the wireless remote controller toward the receiver of the indoor unit and press the button. The sensor-operation indicator will flash and beeps will be heard to indicate the the setting number.
Setting number: 1 = 2 beeps (0.4 seconds each)
* If a setting number that cannot be recognized by the unit is entered, the setting will turn back to the original setting. * If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the setting number.
6 Repeat steps 4 and 5 to make an additional setting without changing unit number. 7 Repeat steps 3 to 5 to change unit number and make function settings on it. 8 Complete the function settings
Press button.
* Do not use the wireless remote controller for 30 seconds after completing the function setting.
2 = 2 beeps (one second each) 3 = 3 beeps (one second each)
2 = 2 beeps (0.4 seconds each, repeated twice) 3 = 2 beeps (0.4 seconds each, repeated three times)
68
Page 69
11-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1.Change Language ("CHANGE LANGUAGE")
2.Function limit ("FUNCTION SELECTION")
3.Mode selection ("MODE SELECTION")
4.Display change ("DISP MODE SETTING")
Item 3 (Setting content)
• Display in multiple languages is possible.
• Setting the range of operation limit (operation lock)
• Setting the use or non-use of "automatic" operation mode
• Setting the temperature adjustable range (maximum, minimum)
• Selecting main or sub remote controller *
When two remote controllers are connected to one group, one controller must be set to sub.
• Setting the use or non-use of clock function
• Setting the timer type
• Contact number display in case of error
• Setting the telephone number
• Setting the temperature unit (: or °F) to display
• Setting the use or non-use of the display of indoor (suction) air temperature
• Setting the use or non-use of the display of "Cooling" or "Heating" display during
operation with automatic mode
Item 2
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
(1)
Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
(2) Use of clock setting ("CLOCK") (3) Timer function setting ("WEEKLY TIMER") (4) Contact number setting for error situation ("CALL.")
(1) Temperature display :/°F setting ("TEMP MODE :/°F") (2)
Suction air temperature display setting ("ROOM TEMP DISP SELECT")
(3)
Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
[Function selection flowchart] Refer to next page. [1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting. (Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔
[Detailed setting] [4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
• Press the [
MENU] button to change the language.
1 Japanese (JP), 2 English (GB), 3 German (D), 4 Spanish (E), 5 Russian (RU), 6 Italian (I), 7Chinese (CH),8 French (F)
[4] -2. Function limit (1) Operation function limit setting (operation lock)
• To switch the setting, press the [ ON/OFF] button. 1 no1: Operation lock setting is made on all buttons other than
the [
ON/OFF] button.
2 no2: Operation lock setting is made on all buttons. 3 OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER] and [ ON/OFF] buttons at the same time for two seconds.) on the normal screen after the above setting is made..
(2) Use of automatic mode setting When the remote controller is connected to the unit that has auto­matic operation mode, the following settings can be made.
• To switch the setting, press the [ ON/OFF] button. 1 ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.
2 OFF : The automatic mode is not display
when the operation mode is selected.
[4] -3. Mode selection setting (1) Remote controller main/sub setting
• To switch the setting, press the [ ON/OFF] button.
1 Main : The controller will be the main controller. 2 Sub : The controller will be the sub controller.
(2) Use of clock setting
• To switch the setting, press the [ ON/OFF] button.
1 ON :The clock function can be used. 2 OFF:The clock function cannot be used.
(3) Timer function setting
• To switch the setting, press the [ ON/OFF] button (Choose one of the followings.).
1 WEEKLY TIMER (initial setting on MA deluxe):
The weekly timer can be used.
2 AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER (Default setting on MA smooth):
The simple timer can be used.
4
3
TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF, the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation
• To switch the setting, press the [ ON/OFF] button.
1 CALL OFF:
The set contact numbers are not displayed in case of error.
2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
(3) Temperature range limit setting After this setting is made, the temperature can be changed within the set range.
• To switch the setting, press the [ ON/OFF] button. 1 LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
2 LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
3 LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode. 4 OFF (initial setting) : The temperature range limit is not active. *
When the setting, other than OFF, is made, the temperature range limit setting on cooling, heating and automatic mode is made at the same time. However the range cannot be limited when the set temperature range has not changed.
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
To switch the upper limit setting and the lower limit setting, press the
[ ]
button. The selected setting will flash and the temperature can be set.
• Settable range
Cooling/Dry mode : Lower limit: 19 : ~ 30: Upper limit: 30 : ~ 19: Heating mode : Lower limit: 17 : ~ 28: Upper limit: 28 : ~ 17: Automatic mode : Lower limit: 19 : ~ 28: Upper limit: 28 : ~ 19:
CALL_ : The contact number can be set when the display is as
shown on the left.
• Setting the contact numbers To set the contact numbers, follow the following procedures. Move the flashing cursor to set numbers. Press the [
TEMP. ( ) and
(
)] button to move the cursor to the right (left). Press the [ CLOCK
(
) and ( )] button to set the numbers.
[4] -4. Display change setting (1) Temperature display :/ F setting
• To switch the setting, press the [ ON/OFF] button.
1 : : The temperature unit : is used. 2 F: The temperature unit
°
°°
F is used.
(2) Suction air temperature display setting
• To switch the setting, press the [ ON/OFF] button.
1 ON :The suction air temperature is displayed. 2 OFF:The suction air temperature is not displayed.
(3) Automatic cooling/heating display setting
• To switch the setting, press the [ ON/OFF] button. 1 ON : One of "Automatic cooling" and "A utomatic heating" is displa yed
under the automatic mode is running.
2 OFF:Only "Automatic" is displayed under the automatic mode.
69
Page 70
Flowchart of Function Setting
Setting language (English)
Normal display (Display when the air condition is not running)
Hold down the E button and press the D button for 2 seconds.
Remote controller function selection mode
Item1 Item2
Change Language
E
Function selection
E
E
Hold down the E button and press the D button for 2 seconds.
E Press the operation mode button. G Press the TIMER MENU button. D Press the TIMER ON/OFF button.
G
EN
Dot display
GE
ES
RU
G
IT
ZH
FR
JA
G
G
G
G
Item3
D
OFF
on1
D
on2
D
ON
OFF
D
D
OFF
D
Operation lock setting is not used. (Initial setting value)
D
Operation lock setting is except On/Off buttons.
Operation lock setting is All buttons.
The automatic mode is displayed when the operation mode is selected. (Initial setting value)
D
The automatic mode is not displayed when the operation mode is selected.
The temperature range limit is not active. (Initial setting value)
D
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
F
TEMP.
E
G
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
CLOCK
ON/OFF
OPERATION
ON/OFF
I
FILTER
A
CHECK
TEST
CLEAR
B
H
D
C
Mode selection
Display mode setting
The temperature range can be changed on automatic mode.
G
G
E
G
G
G
G
G
G
G
D
D
D
ON
OFF
D
D
The remote controller will be the main controller. (Initial setting value)
D
The remote controller will be the sub controller.
The clock function can be used. (Initial setting value)
D
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
D
Auto off timer can be used.
D
D
OFF
D
CALL-
D
:
°F
D
D
ON
OFF
D
D
ON
OFF
D
Simple timer can be used.
Timer mode can not be used.
The set contact numbers are not displayed in case of error. (Initial setting value)
D
The set contact numbers are displayed in case of error.
The temperature unit : is used. (Initial setting value)
D
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
D
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayed under the automatic mode is running. (Initial setting value)
D
Only "Automatic" is displayed under the automatic mode.
70
Page 71
12 DISASSEMBLY PROCEDURE
PUH-P125YGAA.UK PUH-P140YGAA.UK
OPERATING PROCEDURE PHOTOS
1. Removing the Service panel and Top panel
(1) Remove the 3 service panel fixing screws (5 15) and
slide the hook to remove the service panel.
(2) Remove the screws (3 for front, 2 for rear/5 15) of the
top panel and remove it. <When the rear screws of the top panel are not possible
to remove> Remove the 3 front screws (5 15) of the top panel and lift the front side of the top panel.
2. Removing the Fan and Fan motor
(1) Remove the 6 fan guard screws (5 15) to remove it.
(See Photo 1) (2) Remove the propeller nut (M8) and propeller fan. (3) Remove the 3 fan motor screws (5 16) to remove the
fan motor.
Note : PU(H)-P25-71 : Nut (M6)
Photo 1
Fan guard
Photo 2
Top panel screws
Fan guard screws
Top panel
Service panel
Service panel screws
Fan motor screws
3. Removing the Electrical box
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the Bypass valve, Crankcase heater, Pressure
switch<for high pressure>, Liquid temperature thermistor,
Discharge temperature thermistor, condenser/evaporator
temperature thermistor and 4-way valve from the connector
housing on the controller board,then disconnect the fan
motor lead wire from the housing mentioned before and the
condenser lead wire for the fan from the electrical box.
<Diagram symbol in the connector housing>
Bypass valve solenoid coil (SV) · Crankcase heater (CH) Pressure switch <for high pressure> (63H) Liquid temperature thermistor (TH3) Discharge temperature thermistor (TH4) Condenser/evaporator temperature thermistor (TH6) 4-way valve solenoid coil (21S4) · Fan motor (MF3, MF4)
(4) Remove the terminal cover and disconnect the compressor
lead wire and inner thermal device terminal. (5) Remove the electrical box screw (4 10) and lift the
box to remove it. The electric box cover is hooked at 2
points on the left and 1 point on the right.
Photo 3
Fan motor
Fan guard
Compressor
Electric parts box
Outdoor unit controller board
Electrical box fixing screw
Terminal cover
Cover panel
Cover panel fixing screw
71
Page 72
OPERATING PROCEDURE PHOTOS
4. Removing the liquid temperature thermistor, discharge temperature thermistor and condenser/evaporator temperature thermistor
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1)
(When the top panel removing is not possible, remove
the electric parts box. Refer to 3.)
w When removing liquid temperature thermistor and the
discharge temperature thermistor, it unnecessary to remove the top panel. (See Photo 5)
(3) Disconnect the lead wire of the liquid temperature thermistor,
discharge temperature thermistor and condenser/evaporator temperature thermistor from the housing (TH3, TH4, TH6)
on the controller board. (4) Loosen the 1 lead wire clamps on the electrical box. (5) Pull out the thermistor from the sensor holder.
5. Removing the bypass valve solenoid coil (SV)
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1)
(When the top panel removing is not possible, remove
the electrical box. Refer to 3. )
(3) Remove coil fixing screw (M4 8) and disconnect the
lead wire of the bypass valve solenoid coil (SV) from on
the controller board.
6. Removing the bypass valve
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the bypass valve solenoid coil. (See Photo 4) (4) Recover gas from the refrigerant circuit. (5) Remove the braze at the intake and outlet of the bypass
valve.
Note :
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
When installing the bypass valve, cover it with a wet cloth to
prevent it from heating, then braze the pipes.
7. Removing the 4-way valve solenoid coil (21S4)
(1) Remove the service panel. (See Photo 1) (2) Remove 4-way valve solenoid coil fixing screw (M5 6)
and disconnect the
lead wire of the 4-way valve solenoid coil (21S4) from the controller board.
8. Removing the 4-way valve
(1) Remove the service panel. (See Photo 1) (2) Remove the 4-way valve solenoid coil. (See Photo 5) (3) Recover gas from the refrigerant circuit. (4) Remove the braze pipe of the 4-way valve.
2
(0 MPa).
Note :
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
When installing the 4-way valve, cover it with a wet cloth to
prevent it from heating, then braze the pipes.
2
(0 MPa).
Photo 4
Electrical box
Rear panel
Photo 5
Liquid temperature thermistor
Clamp
Linear expansion valve coil
Pressure switch <High>
Condenser/evaporator temperature thermistor
Bypass valve solenoid coil
Bypass valve solenoid coil fixing screw
4-way valve
4-way valve solenoid coil fixing screw
4-way valve solenoid coil
Discharge temperature thermistor
72
Page 73
OPERATING PROCEDURE PHOTOS
9. Removing the high pressure switch
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical box. (See Photo 3) (4) Disconnect the lead wire of the pressure switch.
(See Photo 6)
(5) Remove the braze part of the pressure switch. Note : When installing the pressure switch, cover the pressure
switch with a wet cloth to prevent the pressure switch from heating, then braze it.
10. Removing the low pressure switch
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical box. (See Photo 3) (4) Disconnect the lead wire of the pressure switch.
(See Photo 7)
(5) Remove the braze part of the pressure switch.
Photo 6
Photo 7
Electrical box
Lead wire
Lead wire
Capillary tube
Pressure switch <High>
Valve bed fixing screws
Note : When installing the pressure switch, cover the pressure
switch with a wet cloth to prevent the pressure switch from heating, then braze it.
11. Removing the linear expansion valve
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical box. (See Photo 3) (4) Recover gas from the refrigerant circuit. (5) Remove the linear expansion valve coil. (See Photo 8) (6) Remove the braze pipes of the linear expansion valve.
Note 1: When installing the linear expansion valve, remove
its coil and cover the valve with a wet cloth so as to prevent it from heating, then braze the pipes.
Note 2: By detaching the rear panel, the brazed parts will
easily become separated.
Note 3:
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
2
(0 MPa).
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
Photo 8
Accumulator
Bypass valve solenoid coil
Pressure switch <Low>
Bypass valve
Linear expansion valve coil
Linear expansion valve
73
Page 74
OPERATING PROCEDURE PHOTOS
12. Removing the Bell mouth
(1) Remove the 6 fan guard fixing screws (5 15) to
remove it. (See Photo 1) (2) Remove the top panel. (3) Remove a bell mouth fixing screw (5 15) to remove it.
13. Removing the compressor
(1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electric parts box. (See Photo 3) (4) Remove the bell mouth. (See Photo 9) (5) Remove the 3 valve bed fixing screws (4 10) and the
4 ball valve fixing screws(5 16) to remove the valve bed. (6) Remove the 3 rear panel fixing screws (5 15) to the panel. (7) Remove the cover panel fixing screw (5 15) to remove
the front side of cover panel. (8) Recover gas from the refrigerant circuit. (9) Remove the 3 points of the compressor fixing nut with a
monkey wrench.
(10) Remove the brazed pipe of compressor intake and outlet
to remove the compressor
Photo 9
Photo 10
Bell mouth fixing screw
Accumulator
<Reference>
w When the power supply terminal block of the compressor
is fixed with the screws, the tightening torque is from
1.4 to 1.7 N.m.
NOTE
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
14. Removing the accumulator.
(1) Recover gas from the refrigerant circuit. (2) Remove the compressor or remove the rear panel. (3) Remove the brazed pipe of accumulator intake and outlet
to remove the accumulator
NOTE :
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
2
(0 MPa).
2
(0 MPa).
Compressor
Compressor fixing nuts
74
Page 75
13 PARTS LIST
STRUCTURAL PARTS PUH-P25VGAA.UK PUH-P35VGAA.UK PUH-P35YGAA.UK PU-P35VGAA.UK PU-P35YGAA.UK
1 2 3
4
5 6
17
161415
13
No.
10 11 12 13 14 15
16
17
Part No.
1
S70 30L 641
2
S71 000 051
3
S70 30L 613
4
S70 23T 614
5
S70 30L 119
6
S70 E01 675
7
S70 E01 686
8
S70 K02 130
9
S70 001 699 S70 31L 658 S70 30L 658 S70 E00 682 S70 30L 655 S70 K01 661 S70 K02 661 S70 K03 661 S70 K02 663 S70 30L 698
Part Name
TOP PANEL F.ST SCREW REAR SUPPORT FRONT SUPPORT BELL MOUTH WIRE GRILL - S SEPARATOR ASSY BASE MOTOR SUPPORT VALVE BED ASSY LABEL (MITSUBISHI) COVER PANEL 1 COVER PANEL 2 REAR PANEL PANEL HANDLE SERVICE PANEL SERVICE PANEL SERVICE PANEL SERVICE PANEL REAR GUARD
78 11
Specification
(515)
9 10
Q,ty/set
PUH-P
GAA.UK
25.35V
35Y 35V 35Y
1
1
16
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PU-P GAA.UK
1
1
16
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
1
Remarks
(Drawing No.)
(RG00R045G06)
(RG00R048G01)
Wiring
Diagram
Symbol
Recom-
mended
Q,ty
Unit
12
Price
Amount
75
Page 76
STRUCTURAL PARTS PUH-P50VGAA.UK PUH-P60VGAA.UK PUH-P50YGAA.UK PUH-P60YGAA.UK PU-P50VGAA.UK PU-P60VGAA.UK PU-P50YGAA.UK PU-P60YGAA.UK
1 2
3
4
5
6
17
161415
13
No.
Part No. Part Name
1
S70 30L 641
2
S71 000 051
3
S70 97W 613
4
S70 E00 614
5
S70 36L 119
6
S70 E02 675
7
S70 K03 130 8 9
10
S70 E02 686
11
S70 30L 655
12
S70 31L 658
13
S70 30L 658
14
S70 E01 682
15
S70 001 699
S70 K05 661
S70 K06 661
16
S70 K07 661
S70 K08 661
17
S70 31L 698
— —
78 1112
TOP PANEL F.ST SCREW REAR SUPPORT FRONT SUPPORT BELL MOUTH WIRE GRILL-M MOTOR SUPPORT SEPARATOR ASSY VALVE BED ASSY BASE PANEL HANDLE COVER PANEL-1 COVER PANEL-2 REAR PANEL LABEL (MITSUBISHI) SERVICE PANEL SERVICE PANEL SERVICE PANEL SERVICE PANEL REAR GUARD
9 10
Specificatio
(515)
Q,ty/set
PUH-P
GAA.UK 50,60V
50,60Y 50,60V 50,60Y
1
1
16
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1 1
1
1
1
PU-P
GAA.UK
1
1
16
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1 1
1
Remarks
(Drawing No.)
(RG00R045G07) (RG00R048G01)
Wiring
Diagram
Symbol
Recom­mended
Q,ty
Unit
Price
Amount
76
Page 77
STRUCTURAL PARTS PUH-P71VGAA.UK PUH-P71YGAA.UK PU-P71VGAA.UK PU-P71YGAA.UK
1 2
3 4
5
6
17
161415
13
Part No. Part Name
No.
1
S70 30L 641
2
S71 000 051
3
S70 97W 613
4
S70 E00 614
5
S70 36L 119
6
S70 E02 675
7
S70 K03 130 8 9
10 11 12 13 14 15
16
17
— S70 E02 686 S70 30L 655 S70 31L 658 S70 30L 658 S70 E02 682 S70 001 699 S70 K05 661 S70 K06 661 S70 K07 661 S70 K08 661 S70 31L 698
78 1112
TOP PANEL F.ST SCREW REAR SUPPORT FRONT SUPPORT BELL MOUTH WIRE GRILL-M MOTOR SUPPORT SEPARATOR ASSY VALVE BED ASSY BASE PANEL HANDLE COVER PANEL-1 COVER PANEL-2 REAR PANEL LABEL (MITSUBISHI) SERVICE PANEL SERVICE PANEL SERVICE PANEL SERVICE PANEL REAR GUARD
9 10
Specificatio
(515)
Q,ty/set PUH-P71 .UK VGAA YGAA VGAA YGAA
1
16
1 1 1 1 1 1 1 1 2 1 1 1 1 1
1
PU-P71 .UK
1
16
16
1 1 1 1 1 1 1 1 2 1 1 1 1
1
1
1
1
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1 1
1
Remarks
(Drawing No.)
(RG00R045G08) (RG00R048G01)
Wiring
Diagram
Symbol
Recom-
mended
Q,ty
Unit
Price
Amount
77
Page 78
STRUCTURAL PARTS PUH-P100VGAA.UK PU-P100VGAA.UK PUH-P100YGAA.UK PU-P100YGAA.UK
61615
5
Part No. Part Name
No.
1
S70 30L 641
2
S71 000 051
3
S70 98W 613
4
S70 E01 614
5
S70 41L 119
6
S70 E03 675
7
S70 30L 119
8
S70 42L 130
9 10 11 12 13 14 15 16
17
18
— S70 E03 686 S70 30L 655 S70 31L 658 S70 30L 658 S70 E03 682 S70 001 699 S70 K09 661 S70 K10 661 S70 K11 661 S70 K12 661 S70 30L 698
7
TOP PANEL F.ST SCREW REAR SUPPORT FRONT SUPPORT BELL MOUTH WIRE GRILL - L BELL MOUTH MOTOR SUPPORT SEPARATOR ASSY VALVE BED ASSY BASE PANEL HANDLE COVER PANEL-1 COVER PANEL-2 REAR PANEL LABEL (MITSUBISHI) SERVICE PANEL SERVICE PANEL SERVICE PANEL SERVICE PANEL REAR GUARD
131824
8 9 10 11 12 13
Q,ty/set
Specification
(515)
PUH-P100 .UK
VGAA YGAA VGAA YGAA
1
18
1 1 1 1 1 1 1 1 1 2 1 1 1 1 1
2
PU-P100 .UK
1
18
18
1 1 1 1 1 1 1 1 1 2 1 1 1 1
1
2
1
1
18
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1 2
2
17
Remarks
(Drawing No.)
(RG00R045G09) (RG00R048G01)
Wiring
Diagram
Symbol
Recom­mended
Q,ty
14
Unit
Price
Amount
78
Page 79
STRUCTURAL PARTS PUH-P125YGAA.UK PUH-P140YGAA.UK PU-P125YGAA.UK PU-P140YGAA.UK
1 2 3
4 5
19
18
17 16
Part No. Part Name
No.
1
S70 17T 641
2
S71 000 051
3
S70 98W 613
4
S70 17T 614
5
S70 41L 119
6
S70 E03 675
7
S70 30L 119
8
S70 42L 130
9 10 11 12 13 14 15 16 17
18
19
S70 A04 529
— S70 H13 686 S70 30L 655 S70 31L 658 S70 30L 658 S70 E04 682 S70 001 699 S70 K13 661 S70 K14 661 S70 17T 698
6
TOP PANEL F.ST SCREW REAR SUPPORT FRONT SUPPORT BELL MOUTH WIRE GRILL - L BELL MOUTH MOTOR SUPPORT SEPARATOR ASSY ACCUMULATOR DRAIN PAN VALVE BED ASSY BASE PANEL HANDLE COVER PANEL-1 COVER PANEL-2 REAR PANEL LABEL(MITSUBISHI) SERVICE PANEL SERVICE PANEL REAR GUARD
714
Specification
(515)
8
PUH-P125, 140 YGAA.UK YGAA.UK
9
Q,ty/set
1
18
1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1
2
10
PU-P125, 140
11
1
18
1 1 1 1 1 1
(RG00R046G03)
1 1
(RG00R048G03)
1 1 2 1 1 1 1
1 2
12 13
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q,ty
Unit
15
Price
Amount
79
Page 80
FUNCTIONAL PARTS PUH-P25VGAA.UK PUH-P35VGAA.UK PU-P35VGAA.UK
25
24
FUSE
21
2223
20
19
1
18
2
17
3
4
16
5
6
15
14
13
12
7 8 9 10 11
80
Page 81
Part No. Part Name Specification
No.
1
S70 249 708
2
S70 E03 716
3
S70 E04 716
4
S70 K05 763
5
S70 K04 115
6
S70 K01 097
7
S70 E16 202
8
S70 E00 467
9
S70 E00 413 S70 400 418
10
S70 200 418 S70 061 400
11
S70 062 400
12
S70 E02 236
13
S70 E02 440 S70 E01 411
14
S70 E03 411 S70 66L 450
15
S70 E03 401
16
S70 350 242
17
S70 E01 403
18
S70 E15 202
19
S70 E99 408
20
S70 E00 408 S70 E00 208
21
S70 31L 315
22
S70 520 239
23
S70 30L 255
24
S70 E00 723
25
S70 E01 723
CONTACTOR TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN MOTOR PROPELLER FAN 4 NUT THERMISTOR (DISCHARGE) MUFFLER CHARGE PLUG STOP VALVE(LIQUID) STOP VALVE(LIQUID) COMPRESSOR COMPRESSOR CRANKCASE HEATER ACCUMULATOR BALL VALVE BALL VALVE STRAINER LINEAR EXPANSION VALVE 4-WAY VALVE SOLENOID COIL 4-WAY VALVE (REVERSING) THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR ) HEAT EXCHANGER HEAT EXCHANGER HIGH PRESSURE SWITCH OUTDOOR CONTROLLER BOARD FUSE OUTDOOR FAN CAPACITOR COMPRESSOR CAPACITOR COMPRESSOR CAPACITOR
PUH-P PU-P
25VGAA .UK
S-U12 240V 2P(L,N) 3P(S1,S2,S3) YDK75-6U
1 1 1 1 1
M6
1 1 1 2
1/4˝
1 3/8˝ RE189VHSMT
1 RE277VHSMT 240V / 30W
1
1 1/2˝
1 5/8˝ #50-12
1
1
1
1
1
1
OFF:3.3MPa ON:2.6MPa
1
1
6.3A
2.2+ 440V 30+ 420V
4
1
1 40+ 400V
Q,ty/set
35VGAA .UK
1 1 1 1 1 1 1 1 2
1
1 1 1
1 1 1 1 1 1
1 1 1 4 1
1
35VGAA .UK
1 1 1 1 1 1 1
2
1
1 1 1
1 1 1
1
1 1 1
Remarks
4
(PART OF BOARD)
1
1
Wiring
Diagram
Symbol
52C TB1 TB2
MF
TH4
MC MC CH
LEV
21S4
TH3, TH6
63H
O.B
FUSE
C3 C5 C5
Recom­mended
Q,ty
Unit
Price
Amount
81
Page 82
FUNCTIONAL PARTS PUH-P35YGAA.UK PU-P35YGAA.UK
24
FUSE
2223
2021
19
1
18
2
17
3
4
16
5
6
15
14
13
12
7 8 9 10 11
82
Page 83
Part No. Part Name SpecificationNo.
1
S70 250 708
2
S70 E10 716
3
S70 E04 716
4
S70 K05 763
5
S70 K04 115
6
S70 K01 097
7
S70 E16 202
8
S70 E00 467
9
S70 E00 413
10
S70 200 418
11
S70 063 400
12
S70 E02 236
13
S70 E02 440
14
S70 E03 411
15
S70 66L 450
16
S70 E03 401
17
S70 350 242 S70 E01 403
18
S70 E15 202
19
S70 E00 408
20
S70 E00 208
21
S70 32L 315
22
S70 520 239
23
S70 30L 255
24
CONTACTOR TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN MOTOR
MSO-N11 4P(L1,L2,L3,N) 3P(S1,S2,S3)
YDK75-6U PROPELLER FAN 4 NUT
M6 THERMISTOR (DISCHARGE) MUFFLER CHARGE PLUG STOP VALVE(LIQUID) COMPRESSOR CRANKCASE HEATER
3/8˝
RE277YFKM
240V / 30W ACCUMULATOR BALL VALVE STRAINER
5/8˝
#50-12 LINEAR EXPANSION VALVE 4-WAY VALVE SOLENOID COIL 4-WAY VALVE (REVERSING) THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR ) HEAT EXCHANGER HIGH PRESSURE SWITCH
OFF:3.3MPa ON:2.6MPa OUTDOOR CONTROLLER BOARD FUSE OUTDOOR FAN CAPACITOR
6.3A
2.2+ 440V
Q,ty/set
PUH-P35Y
GAA.UK
1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1
PU-P35Y
GAA.UK
1 1 1 1 1 1 1
2 1 1 1 1 1 1 1
1 1 1 1 4 1
Wining
Remarks
Diagram
Symbol
51C,52C
TB1 TB2
MF
TH4
MC CH
LEV
21S4
TH3, TH6
63H O.B
(PART OF BOARD)
FUSE
C3
Recom­mended
Q,ty
Unit
Price
Amount
83
Page 84
FUNCTIONAL PARTS PUH-P50VGAA.UK PUH-P60VGAA.UK PU-P50VGAA.UK PU-P60VGAA.UK
1
FUSE
20212225 2324
19
2
18 17
3 4
16
5
6
15
14
13
12
78 91011
84
Page 85
Part No. Part Name SpecificationNo.
S70 330 708
1
S70 E03 716
2
S70 E04 716
3
S70 K05 763
4 5
S70 K04 115
6
S70 K01 097
7
S70 E16 202
8
S70 36L 467
9
S70 E00 413
10
S70 300 418 S70 064 400
11
S70 066 400
12
S70 E04 236 S70 E04 440
13
S70 E03 440
14
S70 E04 411
15
S70 36L 450
16
S70 350 242
17
S70 A00 403
18
S70 E15 202
19
S70 E02 401 S70 E02 408
20
S70 E01 408
21
S70 E00 208
22
S70 31L 315
23
S70 520 239
24
S70 30L 255 S70 100 723
25
S70 869 723
CONTACTOR TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN MOTOR
S-N18EX 2P(L,N) 3P(S1,S2,S3)
YDK75-6U PROPELLER FAN 4 NUT
M6 THERMISTOR (DISCHARGE) MUFFLER CHARGE PLUG STOP VALVE (LIQUID) COMPRESSOR COMPRESSOR CRANKCASE HEATER
3/8˝
NE36VMJMT
NE41VMJMT
240V / 38W ACCUMULATOR ACCUMULATOR BALL VALVE STRAINER
5/8˝
#50-16 4-WAY VALVE SOLENOID COIL 4-WAY VALVE (REVERSING) THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) LINEAR EXPANSION VALVE HEAT EXCHANGER HEAT EXCHANGER HIGH PRESSURE SWITCH
OFF:3.3MPa ON:2.6MPa OUTDOOR CONTROLLER BOARD FUSE OUTDOOR FAN CAPACITOR COMPRESSOR CAPACITOR COMPRESSOR CAPACITOR
6.3A
2.2+ 440V
50+ 420V
45+ 440V
Q,ty/set
PUH-P•VGAA.UK
PU-P•VGAA.UK
50 60 50 60
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
4
4
1
1
1
1
1
1
Remarks
1 1 1 1 1 1 1
2 1
1 1
1 1 1
1 1
1 1 1
(PART OF BOARD)
4 1
1
Wiring Diagram Symbol
52C TB1 TB2
MF
TH4
MC MC
CH
21S4
TH3, TH6
LEV
63H
O.B
FUSE
C3 C5 C5
Recom-
mended
Q,ty
Unit
Price
Amount
85
Page 86
FUNCTIONAL PARTS PUH-P50YGAA.UK PUH-P50YGAA.UK PU-P60YGAA.UK PU-P60YGAA.UK
1
FUSE
2021222324
19
2
3 4
18 17
16
5
6
15
14
13
12
78 91011
86
Page 87
Part No. Part Name SpecificationNo.
S70 332 708
1
S70 333 708
2
S70 E10 716
3
S70 E04 716
4
S70 K05 763
5
S70 K04 115
6
S70 K01 097
7
S70 E16 202
8
S70 36L 467
9
S70 E00 413
10
S70 300 418 S70 065 400
11
S70 067 400
12
S70 E04 236 S70 E04 440
13
S70 E03 440
14
S70 E04 411
15
S70 36L 450
16
S70 350 242
17
S70 A00 403
18
S70 E15 202
19
S70 E02 401 S70 E02 408
20
S70 E01 408
21
S70 E00 208
22
S70 32L 315
23
S70 520 239
24
S70 30L 255
CONTACTOR CONTACTOR TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN MOTOR
MSO-N11 MSO-N11 4P(L1,L2,L3,N) 3P(S1,S2,S3)
YDK75-6U PROPELLER FAN 4 NUT
M6 THERMISTOR (DISCHARGE) MUFFLER CHARGE PLUG STOP VALVE (LIQUID) COMPRESSOR COMPRESSOR CRANKCASE HEATER
3/8˝
NE36YEKMT
NE41YEKMT
240V 38W ACCUMULATOR ACCUMULATOR BALL VALVE STRAINER
5/8˝
#50-16 4-WAY VALVE SOLENOID COIL 4-WAY VALVE (REVERSING) THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) LINEAR EXPANSION VALVE HEAT EXCHANGER HEAT EXCHANGER HIGH PRESSURE SWITCH
OFF:3.3MPa ON:2.6MPa OUTDOOR CONTROLLER BOARD FUSE OUTDOOR FAN CAPACITOR
6.3A
2.2+ 440V
Q,ty/set
PUH-P•YGAA.UK
PU-P•YGAA.UK
50 60 50 60
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
4
4
1
1
1
Remarks
1 1 1 1 1 1 1
2 1
1 1
1 1 1
1 1
1 1 1
(PART OF BOARD)
4 1
Wiring
Diagram
Symbol
51C,52C 51C,52C
TB1 TB2
MF
TH4
MC MC CH
21S4
TH3, TH6
LEV
63H O.B
FUSE
C3
Recom­mended
Q,ty
Unit
Price
Amount
87
Page 88
FUNCTIONAL PARTS PUH-P71VGAA.UK PU-P71VGAA.UK
1
FUSE
20212225 2324
19
2
18 17
3 4
16
5
6
15
14
13
12
78 91011
88
Page 89
Part No. Part Name SpecificationNo.
S70 330 708
1
S70 E03 716
2
S70 E04 716
3
S70 K05 763
4
S70 K04 115
5
S70 K01 097
6
S70 E16 202
7
S70 36L 467
8
S70 E00 413
9
S70 300 418
10
S70 068 400
11
S70 E04 236
12
S70 E03 440
13
S70 E04 411
14
S70 36L 450
15
S70 350 242
16
S70 A00 403
17
S70 E15 202
18
S70 E02 401
19
S70 E03 408
20
S70 E00 208
21
S70 31L 315
22
S70 520 239
23
S70 30L 255
24
S70 976 723
25
CONTACTOR TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN MOTOR
S-N18EX
2P(L,N)
3P(S1,S2,S3)
YDK75-6U PROPELLER FAN 4 NUT
M6 THERMISTOR (DISCHARGE) MUFFLER CHARGE PLUG STOP VALVE (LIQUID) COMPRESSOR CRANKCASE HEATER
3/8˝
NE52VNJMT
240V / 38W ACCUMULATOR BALL VALVE STRAINER
5/8˝
#50-16 4-WAY VALVE SOLENOID COIL 4-WAY VALVE (REVERSING) THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) LINEAR EXPANSION VALVE HEAT EXCHANGER HIGH PRESSURE SWITCH
OFF:3.3MPa ON:2.6MPa OUTDOOR CONTROLLER BOARD FUSE OUTDOOR FAN CAPACITOR COMPRESSOR CAPACITOR
6.3A
2.2+ 440V
60+ 450V
Q,ty/set
PUH-P71V PU-P71V
GAA.UK GAA.UK
1 1 1 1 1 1 1
1 1 1 1 1 1
1 1 2 1 1 1 1 1 1
2
1
1
1
1
1
1 1 1 1 1 1 1 1 4 1 1
1
1
1
1
1
4
1
1
Wiring
Remarks
Diagram Symbol
52C TB1 TB2
MF
TH4
MC
CH
21S4
TH3, TH6
LEV
63H
O.B
(PART OF BOARD)
FUSE
C3 C5
Recom-
mended
Q,ty
Unit
Price
Amount
89
Page 90
FUNCTIONAL PARTS PUH-P71YGAA.UK PU-P71YGAA.UK
1
FUSE
2021222324
19
2
3 4
18 17
16
5
6
15
14
13
12
78 91011
90
Page 91
Part No. Part Name SpecificationNo.
Wiring
Diagram
Symbol
Recom-
mended
Q,ty
Unit
Amount
Remarks
Q,ty/set
GAA.UK GAA.UK MSO-N11 4P(L1,L2,L3,N) 3P(S1,S2,S3) YDK75-6U
M6
3/8˝ NE52YDKMT 240V / 38W
5/8˝ #50-16
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ 440V
(PART OF BOARD)
1 2 3 4 5 6 7 8 9
10
11 12 13 14 15 16 17 18 19 20 21 22 23 24
51C,52C
TB1 TB2
MF
TH4
MC CH
21S4
TH3, TH6
LEV
63H
O.B
FUSE
C3
S70 331 708 S70 E10 716 S70 E04 716 S70 K05 763 S70 K04 115 S70 K01 097 S70 E16 202 S70 36L 467 S70 E00 413 S70 300 418 S70 069 400 S70 E04 236 S70 E03 440 S70 E04 411 S70 36L 450 S70 350 242 S70 A00 403 S70 E15 202 S70 E02 401 S70 E03 408 S70 E00 208 S70 32L 315 S70 520 239 S70 30L 255
CONTACTOR TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN MOTOR PROPELLER FAN 4 NUT THERMISTOR (DISCHARGE) MUFFLER CHARGE PLUG STOP VALVE (LIQUID) COMPRESSOR CRANKCASE HEATER ACCUMULATOR BALL VALVE STRAINER 4-WAY VALVE SOLENOID COIL 4-WAY VALVE (REVERSING)
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE HEAT EXCHANGER HIGH PRESSURE SWITCH OUTDOOR CONTROLLER BOARD FUSE OUTDOOR FAN CAPACITOR
PUH-P71Y PU-P71Y
Price
1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1
1 1 1 1 1 1 1
2 1 1 1 1 1 1
1 1 1 1 1 4 1
91
Page 92
FUNCTIONAL PARTS PUH-P100VGAA.UK PU-P100VGAA.UK
1
2
28
26 2527 2324
FUSE
22
18
21
20 19
18
3
17 16
4
15 14
13
12
5
79 111086
92
Page 93
Part number that are circled are not shown in the figure.
Part No. Part Name SpecificationNo.
1
S70 E03 763
2
S70 30L 115
3
S70 30L 097
4
S70 E05 408
5
S70 E04 763
6
S70 E00 208
7
S70 42L 467
8
S70 E18 202
9
S70 E00 413
10
S70 071 400
11
S70 300 418
12
S70 E05 236
13
S70 E05 411
14
S70 E05 440
15
S70 42L 450
16
S70 E01 425
17
S70 E02 425
18
S70 E14 202
19
S70 E05 401
20
S70 350 242
21
S70 260 403
22
S70 31L 315
23
S70 520 239
24
S70 30L 255
25
S70 E04 716
26
S70 E03 716
27
S70 330 708
28
S70 E04 408
29
S70 976 723
OUTDOOR FAN MOTOR PROPELLER FAN 4 NUT HEAT EXCHANGER OUTDOOR FAN MOTOR HIGH PRESSURE SWITCH MUFFLER THERMISTOR (DISCHARGE) CHARGE PLUG COMPRESSOR STOP VALVE (LIQUID) CRANKCASE HEATER BALL VALVE ACCUMULATOR STRAINER CAPILLARY TUBE CAPILLARY TUBE
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE 4-WAY VALVE SOLENOID COIL 4-WAY VALVE (REVERSING) OUTDOOR CONTROLLER BOARD FUSE OUTDOOR FAN CAPACITOR TERMINAL BLOCK TERMINAL BLOCK CONTACTOR HEAT EXCHANGER COMPRESSOR CAPACITOR
N026P72MT
M8
N02A672MT OFF:3.3MPa ON:2.6MPa
NE56VNJMT 3/8˝ 240V / 38W 3/4˝
#50-19.1
[4.0 [3.0 350mm [4.0 [3.0 350mm
6.3A
2.2+ 440V 3P(S1,S2,S3) 2P(L,N) S-N18EX
60+ 450V
Q,ty/set
PUH-P100V
PU-P100V
GAA.UK GAA.UK
1 2 2 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 4 2 1 1 1 1 1
Remarks
1 2 2 1 1 1
1 2 1 1 1 1 1 1 1 1 1 1
1
(PART OF BOARD)
4 2 1 1 1 1 1
Wiring
mended
Diagram Symbol
MF
MF
63H
TH4
MC
CH
TH3, TH6
LEV
21S4
O.B FUSE C3, C4
TB2 TB1
52C
C5
Recom-
Q,ty
Unit
Price
Amount
93
Page 94
FUNCTIONAL PARTS PUH-P100YGAA.UK PU-P100YGAA.UK
1
2
28
26 2527 2324
FUSE
22
18
21
20 19
18
3
17 16
4
15 14
13
12
5
79 111086
94
Page 95
Part No. Part Name SpecificationNo.
1
S70 E03 763
2
S70 30L 115
3
S70 30L 097
4
S70 E05 408
5
S70 E04 763
6
S70 E00 208
7
S70 42L 467
8
S70 E18 202
9
S70 E00 413
10
S70 070 400
11
S70 300 418
12
S70 E05 236
13
S70 E05 411
14
S70 E05 440
15
S70 42L 450
16
S70 E01 425
17
S70 E02 425
18
S70 E14 202
19
S70 E05 401
20
S70 350 242
21
S70 260 403
22
S70 32L 315
23
S70 520 239
24
S70 30L 255
25
S70 E04 716
26
S70 E10 716
27
S70 331 708
28
S70 E04 408
Q,ty/set
PUH-100Y PU-P100Y
GAA.UK GAA.UK
OUTDOOR FAN MOTOR
N026P72MT PROPELLER FAN 4 NUT
M8 HEAT EXCHANGER OUTDOOR FAN MOTOR HIGH PRESSURE SWITCH
N02A672MT
OFF:3.3MPa ON:2.6MPa MUFFLER THERMISTOR (DISCHARGE) CHARGE PLUG COMPRESSOR STOP VALVE (LIQUID) CRANKCASE HEATER BALL VALVE
NE56YDKMT
3/8˝
240V / 38W
3/4˝ ACCUMULATOR STRAINER CAPILLARY TUBE CAPILLARY TUBE
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
#50-19.1
[4.0 [3.0 350mm
[4.0 [3.0 350mm
LINEAR EXPANSION VALVE 4-WAY VALVE SOLENOID COIL 4-WAY VALVE (REVERSING) OUTDOOR CONTROLLER BOARD FUSE OUTDOOR FAN CAPACITOR TERMINAL BLOCK TERMINAL BLOCK CONTACTOR
6.3A
2.2+ 440V
3P(S1,S2,S3)
4P(L1,L2,L3,N)
MSO-N11 HEAT EXCHANGER
1 2 2 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 4 2 1 1 1 1
Remarks
1 2 2 1 1 1
1 2 1 1 1 1 1 1 1 1 1 1
1
(PART OF BOARD)
4 2 1 1 1 1
Wining
mended
Diagram Symbol
MF
MF
63H
TH4
MC
CH
TH3, TH6
LEV
21S4
O.B
FUSE
C3, C4
TB2 TB1
51C, 52C
Recom-
Q,ty
Unit
Price
Amount
95
Page 96
FUNCTIONAL PARTS PUH-P125YGAA.UK PUH-P140YGAA.UK PU-P125YGAA.UK PU-P140YGAA.UK
33
32 2931
1
30
FUSE
28 27
12
26
25 24
23
2
22
21 20
19
18
3
17 16
4
15 14
13 12
11
5
68
9
7
10
96
Page 97
Part number that is circled is not shown in the figure.
Part No. Part Name SpecificationNo.
1
S70 E03 763
2
S70 30L 115
3
S70 30L 097
4
S70 E07 408
5
S70 E04 763
6
S70 E19 202
7
S70 E06 401 S70 H10 400
8
S70 H60 400
9
S70 300 418
10
S70 E05 411
11
S70 H40 236
12
S70 E17 202
13
S70 42L 450
14
S70 42H 467
15
S70 E00 208
16
S70 E01 413
17
S70 251 242
18
S70 E02 403
19
S70 E05 425
20
S70 E06 425 S70 E03 425
21
S70 E04 425
22
S70 A14 428
23
S70 351 242
24
S70 H20 209
25
S70 E06 440
26
S70 E00 413
27
S70 33H 315
28
S70 520 239
29
S70 17T 255
30
S70 E04 716
31
S70 E10 716
32
S70 334 708
33
S70 H12 408
34
S70 30L 450
35
S70 H30 450
OUTDOOR FAN MOTOR
N026P72MT PROPELLER FAN 4 NUT
M8 HEAT EXCHANGER (UNDER) OUTDOOR FAN MOTOR
N02A672MT THERMISTOR (DISCHARGE) LINEAR EXPANSION VALVE COMPRESSOR COMPRESSOR STOP VALVE (LIQUID) BALL VALVE CRANKCASE HEATER
BE82YADMT
BE96YADMT
3/8"
3/4"
240V / 38W THERMISTOR(LIQUID, CONDENSER/EVAPORATOR) STRAINER
#50-19.1 MUFFLER HIGH PRESSURE SWITCH
OFF:3.3MPa
ON :2.6MPa
CHARGE PLUG 4-WAY VALVE SOLENOID COIL 4-WAY VALVE (REVERSING) CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE
[4.0 [3.0 200mm
[4.0 [3.0 200mm
[4.0 [2.0 400mm
[4.0 [3.0 450mm
BYPASS VALVE BYPASS VALVE SOLENOID COIL LOW PRESSURE SWITCH
OFF:-0.03MPa
ON :0.05MPa
ACCUMULATOR CHARGE PLUG OUTDOOR CONTROLLER BOARD FUSE FAN MOTOR CAPACITOR TERMINAL BLOCK TERMINAL BLOCK CONTACTOR
6.3A
3.5+ 440V
3P(S1,S2,S3)
4P(L1,L2,L3,N)
MSO-N20 HEAT EXCHANGER (TOP)
STRAINER
#50-9.52 STRAINER ASSY
Q,ty/set
PUH-P•YGAA.UK
PU-P•YGAA.UK
125 140 125 140
1
1 2 2 1 1 1 1 1
1
2
2
2
2
1
1
1
1
1
1
1
1
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1
1 1
1 1
1 1 1
1 1
1 1 1 1
1 1
1
1
1 1
1
1
1
1
1 1 1 1 4 2 1 1 1 1 1 1
1 1
1 1
1 1
1 4
4 2
2 1
1 1
1 1
1 1
1 1
1 1
1
Remarks
1 2 2 1 1 1 1
1 1 1 1 1 1
1 1
1 1
1 1 1 1 4
(PART OF BOARD) 2 1 1 1 1 1 1
Wiring
Diagram
mended
Symbol
MF
MF TH4 LEV
MC MC
CH
TH3, TH6
63H
21S4
SV
63L
O.B
FUSE
C3, C4
TB2 TB1
51C, 52C
Recom-
Q,ty
Unit
Price
Amount
97
Page 98
TM
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Aug. 2005 No.OC336 PDF 8 Made in Japan.
New publication, effective Aug. 2005. Specifications subject to change without notice.
Loading...