1. Indication of capacity has been changed.(BTU base ➔kW base)
2. Power supply cord has been removed.
3. Indoor electronic control P.C. board has been changed.
4. Indoor fan motor has been changed. ( AC ➔ DC)
5. Shape of motor band and motor bed have been changed.
6. Symbol on terminal block has been changed (to S1/S2/S3).
TECHNICAL CHANGES
E1E1
E1E1
E1E1
2
2
Grille
(When the grille is opened)
Remote controller
Operation section
Display section
Emergency operation switch
Operation indicator lamp
Air inlet
Remote control
receiving section
Horizontal vane
Vertical vanes
Air cleaning filter (option)
(Anti-allergy enzyme
filter:blue bellows type)
Catechin air filter
Remote control
receiving section
1
2
3
4
5
6
7
Installation plate
Installation plate fixing screw 4 o 25 mm
Remote controller holder
Fixing screw for 3o 3.5 o 1.6 mm (Black)
Battery (AAA) for remote controller
Wireless remote controller
Felt tape (Used for left or left-rear piping)
1
7
1
2
2
1
1
PART NAMES AND FUNCTIONS
MSZ-GA50VA
MSZ-GA60VA
MSZ-GA71VA
ACCESSORIES
3
REMOTE CONTROLLER
ON/OFF
TOO
COOL
TOO
WARM
LONG
Open the front lid.
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
TEMPERATURE buttons
Indication of remote controller
model is on back.
ON-TIMER button
CLOCK SET button
TIME SET buttons
FORWARD button
BACKWARD button
VANE CONTROL button
(Horizontal vane button)
OFF-TIMER button
LONG button
RESET button
WIDE VANE button
(Vertical vane button)
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
MSZ-GA50VA
MSZ-GA60VA
MSZ-GA71VA
4
3
Indoor model
Function
Power supply
Air flow
(High/Med./Low)
Power outlet
Running current
✽1
Power input
✽1
Power factor
✽1
Fan motor current
✽1
Model
Dimensions WOHOD
Weight
Air direction
Sound level(High/Med./Low)
Fan speed(High/Med./Low)
Fan speed regulator
Remote controller model
K /h
A
A
W
%
A
mm
kg
dB
rpm
MSZ-GA50VA
Single phase
230V, 50Hz
852/690/498
20
0.45
50
48
0.45
RC0J56-AA
1,100O325O258
16
5
48/38/31
1,120/940/720
3
KM05C
Cooling
Heating
MSZ-GA60VA
Single phase
230V, 50Hz
20
0.60
60
43
0.60
RC0J56-AA
1,100O325O258
16
5
54/40/32
3
KM05C
Cooling
1,032/768/522
1,310/1030/750
Heating
1,032/786/522
1,310/1050/750
Electrical
data
Fan motor
Special
remarks
Capacity
Indoor model
Function
Power supply
Air flow(High/Med./Low)
Power outlet
Running current
✽1
Power input
✽1
Power factor
✽1
Fan motor current
✽1
Model
Dimensions WOHOD
Weight
Air direction
Sound level(High/Med./Low)
Fan speed(High/Med./Low)
Fan speed regulator
Remote controller model
K /h
A
A
W
%
A
mm
kg
dB
rpm
MSZ-GA71VA
Single phase
230V, 50Hz
20
0.60
60
43
0.60
RC0J56-AA
1,100O325O258
16
5
54/40/33
3
KM05C
Cooling
1,032/798/564
1,310/1,060/800
Heating
1,032/816/564
1,310/1,080/800
Electrical
data
Fan motor
Special
remarks
Capacity
SPECIFICATION
NOTE: Test conditions are based on ISO 5151.
Cooling : IndoorDry-bulb temperature 27°C Wet-bulb temperature 19°C
Heating : IndoorDry-bulb temperature 20°C Wet-bulb temperature 15.5°C
✽1 Measured under rated operating frequency.
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature(24°C)
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
Indoor-Outdoor piping length 5m
5
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
Test conditions
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
48
SPL(dB(A))LINE
High
FAN SPEED
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15.5:
Fuse
Vane motor
Varistor
Terminal block
(F11)
(MV1/ MV2)
(NR11)
(TB)
T3.15AL 250V
MP20/MP20
ERZV14D471
4P
Specifications and rating conditions of main electric parts
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
Test conditions
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
54
SPL(dB(A))LINE
High
FAN SPEED
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15.5:
INDOORUNIT
WALL
MICROPHONE
0.8m
1m
4
NOISE CRITERIA CURVES
MSZ-GA50VAMSZ-GA60VA
MSZ-GA71VA
6
5
258
159
19
58
47
7.5
315
255.547
2.5
98
173
98173414.5414.5
5
253
791
56
1068
1100
325
Air out
Air in
Insulation [28
Drain hose [16
(Connected part O.D)
Installation plate
Wall hole [75
Wireless remote controller
Installation plate
Indoor unit
{
Liquid line [ 6.35-0.5m
Gas line [ 12-0.43m
Insulation [ 50 O.D
[ 32 I.D
{
Liquid line [ 9.52-0.5m
Gas line [ 12-0.43m
Insulation [ 50 O.D
[ 32 I.D
for MSZ-GA50/60VA
for MSZ-GA71VA
OUTLINES AND DIMENSIONS
MSZ-GA50VA
MSZ-GA60VA
MSZ-GA71VA
Unit: mm
7
6
MV2MV2
55
152
CN
3
CN
101
BLU
CN211
6
5
3
1
RT12
RT11
MF
BLK
YLW
112
CN
CN
111
WHT
RED
RT13
2
4
5
1
2
3
4
GRN
S1
T111
CN
151
1
2
CN201
LD104
12-24V
105(T)
LD
2
F11
NR11
DB111
TAB3
TB
S3
RED
BLK
TO OUTDOOR
UNIT
CONNECTING
MV1
5
RECEIVER
P.C.BOARD
SW P.C.
BOARD
INDOOR ELECTRONIC
CONTROL P.C. BOARD
BLU
230V~
3
POWER MONITOR
P.C.BOARD
S2
REMOTE
CONTROLLER
SYMBOL
RT13
T111
TB
SYMBOL
MV2
NR11
RT11
RT12
SYMBOL
DB111
F11
MF
MV1
DIODE STACK
FUSE (3.15A)
INDOOR FAN MOTOR
VANE MOTOR (HORIZONTAL)
VANE MOTOR (VERTICAL)
VARISTOR
ROOM TEMPERATURE THERMIST OR
INDOOR COIL THERMISTOR (MAIN)
1.About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate.
: Connector
: Terminal block
NOTES:
WIRING DIAGRAM
MSZ-GA50VA
MSZ-GA60VA
MSZ-GA71VA
8
7
Indoor
heat
exchanger
Flared connection
Room temperature
thermistor
RT11
Indoor coil
thermistor
RT13(sub)
Flared connection
Refrigerant pipe [15.88
(with heat insulator)
Refrigerant pipe [9.52
(with heat insulator)
Indoor coil
thermistor
RT12(main)
Strainer
#50
REFRIGERANT SYSTEM DIAGRAM
MSZ-GA50VA
Indoor
heat
exchanger
Indoor coil
thermistor
RT13(sub)
Room temperature
thermistor
RT11
Indoor coil
thermistor
RT12(main)
Distributor
Refrigerant pipe [12.7
(with heat insulator)
Flared connection
Flared connection
MSZ-GA60VA
Indoor
heat
exchanger
Indoor coil
thermistor
RT13(sub)
Room temperature
thermistor
RT11
Indoor coil
thermistor
RT12(main)
Distributor
Unit:mm
Refrigerant pipe [15.88
(with heat insulator)
Flared connection
Flared connection
MSZ-GA71VA
Refrigerant pipe[6.35
(with heat insulator)
Refrigerant pipe [6.35
(with heat insulator)
Refrigerant flow in cooling
Refrigerant flow in heating
9
8
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
–
–
–
2 units operation
Same as at left
Solder J1
–
–
3 units operation
Same as at left
Same as at left
Solder J2
–
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
SERVICE FUNCTIONS
MSZ-GA50VA
MSZ-GA60VA
MSZ-GA71VA
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.
The time will be shortened as follows.
Set time : 1 minute ➔ 1-second
Set time : 3 minute ➔ 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
NOTE : For modification, take out
the batteries and press the
OPERATE/STOP(ON/OFF)
button twice or 3 times at first.
After finish modification,
put back the batteries then
press the RESET button.
J1
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
J2
Table 1
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the
remote controller for the indoor unit.
The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are
set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are
memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power
has restored after power failure. Then, the unit will restart automatically.
10