This Servise Manual OB207 deals with MSH-07/09/12/18/24NV-E1,
MUH-07/09/12/18/24NV-E1, MSH-18NV-E2, and MUH-18NV-E2 in
OB176 REVISED EDITION-A issued in July in1997.
Therefore, please refer to OB207, not to OB176 REVISED
EDITION-A, for the above models.
MSH-07NV -(Serial number 7000201T~)MSH-09NV -(Serial number 7000201T~)
MSH-12NV -(Serial number 7000001T~)MSH-24NV MSH-07NV -MSH-09NV MSH-12NV -MSH-18NV -(Serial number 7000001T~)
MSH-24NV -MSH-18NV -
E1E1
E1E1
E2E2
E2E2
E3E2
5
3
Capacity
Electrical data
Compressor
Indoor
fan motor
Outdoor
fan motor
Dimensions
Weight
Special remarks
Model
Function
Power supply
Coefficient of performance(C.O.P)
Capacity
Dehumidification
Air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding resistance(at20:)
Model
Winding resistance(at20:)
Model
Winding resistance(at20:)
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
Fan speed
(Hi)
Fan speed
regulator
Refrigerant filling capacity(R-22)
Thermistor
Width
Height
Depth
Width
Height
Depth
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Dehumidification
Air flow
Power outlet
Running current
Power input
Auxiliary heater
Electrical data
Power factor
Starting current
Compressor motor current
Fan motor current
Coefficient of performance(C.O.P)
Model
Compressor
Output
Winding resistance(at20:)
Indoor
fan motor
Outdoor
fan motor
Model
Winding resistance(at20:)
Model
Winding resistance(at20:)
Indoor unit
Dimensions
Outdoor unit
Weight
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
Fan speed
(Hi)
Special remarks
Fan speed
regulator
Refrigerant filling capacity(R-22)
Thermistor
Width
Height
Depth
Width
Height
Depth
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
RT11(at25:)
RT12(at25:)
RT61(at0:)
MSH-12NV -
Cooling
E1 E2
Heating
Single phase,220-240V,50Hz
kW
R/h
K /h
A
A
W
A(kW)
%
A
A
A
3.4
1.6
INDOOR 558 OUTDOOR 2130-2244
10
5.75-5.90
1220-1300
5.95-6.10
1260-1350
—
96-92
96-92
35
5.21-5.36
5.41-5.56
INDOOR 0.17 OUTDOOR 0.37
2.78-2.61
3.17-2.96
RH-231VHAT
W
"
1100
C-R2.1 C-S3.9
RC4V19-AA
"
WHT-BLK292 BLK-RED324
"
mm
mm
mm
mm
mm
mm
kg
kg
RA6V40-EC or EE
WHT-BLK130 BLK-RED134.6
815
275
183
850
605
290
8
43
5
dB
dB
rpm
rpm
42
50
1230
780-820
4
1
kg
k"
k"
k"
1.15
10
10
33.18
4.0
—
—
MSH-18NV -
Cooling
E1 E2 E3
Heating
Single phase,220-240V,50Hz
5.1
2.5
5.4
—
INDOOR 756 OUTDOOR 2142
15
9.4-9.2
2030-2120
—
98-96
9.2-9.0
1980-2070
—
98-96
52-58
8.76-8.56
8.56-8.36
INDOOR 0.25 OUTDOOR 0.39
2.51-2.41
2.73-2.61
NH-36VMDT
1700
C-R1.2 C-S2.7
RA4V27-EA
WHT-BLK183.8 BLK-RED250.5
RA6V50-OD or OF
WHT-BLK116.4 BLK-RED111.0
1015
320
190
850
605
290
14
59
5
42
52
1180
810-845
4
1
1.8
10
10
33.18
NOTE:Test conditions
Cooling : Indoor DB27°C / WB19°C
Outdoor DB35°C / WB24°C
Heating : Indoor DB20°C /WB15°.5C
Outdoor DB 7°C / WB 6°C
7
Capacity
Electrical data
Compressor
Indoor
fan motor
Outdoor
fan motor
Dimensions
Weight
Special remarks
Model
Function
Power supply
Coefficient of performance(C.O.P)
Capacity
Dehumidification
Air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding resistance(at20:)
Model
Winding resistance(at20:)
Model
Winding resistance(at20:)
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
Fan speed
(Hi)
Fan speed
regulator
Refrigerant filling capacity(R-22)
Thermistor
Width
Height
Depth
Width
Height
Depth
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
RT11(at25:)
RT12(at25:)
RT61(at0:)
kW
R/h
K /h
A
A
W
A(kW)
%
A
A
A
W
"
"
"
mm
mm
mm
mm
mm
mm
kg
kg
dB
dB
rpm
rpm
kg
k"
k"
k"
MSH-24NV -
E1 E2
Cooling Heating
Single phase,220-240V,50Hz
6.0 6.2
3.1 —
816
25
12.6-11.7 11.5-11.0
2720-2750 2470-2580
—
98
59
11.73-10.83 10.63-10.13
INDOOR 0.29 OUTDOOR 0.58
2.21-2.18 2.51-2.40
NH-47VMDT
2200
C-R 0.96 C-S 2.07
RA4V27-EC
WHT-BLK183.8 BLK-RED250.5
RA6V85-AA
WHT-BLK62.7 BLK-YLW30.2 YLW-RED62.9
1015
320
190
870
850
295
14
72
5
45
53
1,260
720-750
4
2
2.4
10
10
33.18
NOTE:Test conditions
Cooling : Indoor DB27°C / WB19°C
Outdoor DB35°C / WB24°C
Heating : Indoor DB20°C /WB15.5°C
Outdoor DB 7°C / WB 6°C
8
Refer to the Service Manual OB185 when MSH-07/09/12NV-, MSH-07/09/12/18NV-, and MSH-18NV-are
connected with MXZ-32NV-as multi system units.
Capacity
Capacity
Electrical data
Coefficient of performance(C.O.P)
Compressor
Indoor
fan motor
Outdoor
fan motor
Dimensions
Weight
Special remarks
NOTE:Test conditions
Dehumidification
Air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding resistance(at20:)
Model
Winding resistance(at20:)
Model
Winding resistance(at20:)
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
Fan speed
(Hi)
Fan speed
regulator
Refrigerant filling capacity(R-22)
Thermistor
E1
Model
Function
Power supply
Width
Height
Depth
Width
Height
Depth
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
RT11(at25:)
RT12(at25:)
RT61(at0:)
MSH-07NV- (INDOOR UNIT)
E1 E2 E1 E2
Cooling Heating
Single phase,220-240V,50Hz
kW
R/h
K /h
A
A
W
A(kW)
%
A
A
A
— —
— —
492
10
0.17
35
—
94-86
—
—
0.17
—
—
W
"
—
—
RC4V19-AA
"
WHT-BLK292 BLK-RED324
"
mm
mm
mm
mm
mm
mm
kg
kg
—
—
815
275
183
—
—
—
8
—
5
dB
dB
rpm
rpm
37
—
1,100
—
4
—
kg
k"
k"
k"
—
10
10
—
Please refer to Service manual OB185 for capacity.
MSH-09NV- (INDOOR UNIT)
Cooling Heating
Single phase,220-240V,50Hz
— —
— —
492
10
0.17
35
—
94-86
—
—
0.17
—
—
—
—
RC4V19-AA
WHT-BLK292 BLK-RED324
—
—
815
275
183
—
—
—
8
—
5
37
—
1,100
—
4
—
—
10
10
—
E3E2E1
Cooling : Indoor DB27°C / WB19°C
Outdoor DB35°C / WB24°C
Heating : Indoor DB20°C /WB15.5°C
Outdoor DB 7°C / WB 6°C
9
Capacity
Electrical data
Compressor
Indoor
fan motor
Outdoor
fan motor
Dimensions
Weight
Special remarks
Model
Function
Power supply
Coefficient of performance(C.O.P)
Capacity
Dehumidification
Air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding resistance(at20:)
Model
Winding resistance(at20:)
Model
Winding resistance(at20:)
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Air direction
Sound level
(Hi)
Fan speed
(Hi)
Fan speed
regulator
Refrigerant filling capacity(R-22)
Thermistor
Width
Height
Depth
Width
Height
Depth
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
RT11(at25:)
RT12(at25:)
RT61(at0:)
kW
R/h
K /h
A
A
W
A(kW)
%
A
A
A
W
"
"
"
mm
mm
mm
mm
mm
mm
kg
kg
dB
dB
rpm
rpm
kg
k"
k"
k"
MSH-12NV- (INDOOR UNIT)
Cooling Heating
Single phase,220-240V,50Hz
— —
—
558
10
0.17
35
—
94-86
—
—
0.17
—
—
—
—
RA4V19-AA
WHT-BLK292 BLK-RED324
—
—
815
275
183
—
—
—
8
—
5
42
—
1,230
—
4
—
—
10
10
—
MSH-18NV- (INDOOR UNIT)
Cooling Heating
Single phase,220-240V,50Hz
— —
—
756
10
0.28
60
—
97-89
—
—
0.25
—
—
—
—
RA4V27-EA
WHT-BLK184 BLK-RED251
—
—
1015
320
190
—
—
—
14
—
5
42
—
1,180
—
4
—
—
10
10
—
Please refer to Service manual OB185 for capacity.
E1 E2 E2 E3
Refer to the Service Manual OB185 when MSH-07/09/12NV-, MSH-07/09/12/18NV-, and MSH-18NV-are
connected with MXZ-32NV-as multi system units.
E1
E3E2E1
NOTE:Test conditions
Cooling : Indoor DB27°C / WB19°C
Outdoor DB35°C / WB24°C
Heating : Indoor DB20°C /WB15.5°C
Outdoor DB 7°C / WB 6°C
10
4
OUTLINES AND DIMENSIONS
MSH-07NV -MSH-09NV -MSH-07NV -MSH-09NV -
INDOOR UNIT
Unit: mm
E2E2E1E1
MUH-07NV -MUH-09NV -MUH-07NV -MUH-09NV -
OUTDOOR UNIT
E2E2E1E1
11
MSH-12NV -MSH-12NV -
INDOOR UNIT
E2E1
Unit: mm
9.52
MUH-12NV -MUH-12NV -
OUTDOOR UNIT
E2E1
If the right/left sides or
back side is vacant,the
front has only to be 50cm
unobstructed.
NOTE:1. Use copper conductors only.(For field wiring)
2. “❈”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate.
: Terminal block, : Connector
16
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
MSH-18NV -
E1
MODEL WIRING DIAGRAM
INDOOR UNIT
❈
❈
❈
❈
SYMBOL
C11
F12
F11
MF
MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR
FUSE(93:)
FUSE(3.15A)
INDOOR FAN MOTOR
VANE MOTOR