Mitsubishi MS-GA50VB-E1, MS-GA60VB-E1, MS-GA80VB-E1 Service Manual

SPLIT-TYPE, AIR CONDITIONERS
Revision B :
• Indoor heat exchanger of MS-GA80VB - has been changed.
• PARTS LIST and RoHS PARTS LIST have been changed. Please void OB369 REVISED EDITION-A.
INDOOR UNIT
SERVICE MANUAL
Wireless type Models
E1
No. OB369
REVISED EDITION-B
MS-GA50VB ­MS-GA60VB ­MS-GA80VB -
E1
E1
E1
Outdoor unit service manual
MU-GA•VB Series (OB370)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················2
3. SPECIFICATION·················································4
4. NOISE CRITERIA CURVES·······························5
5. OUTLINES AND DIMENSIONS·························6
6. WIRING DIAGRAM ············································7
7. REFRIGERANT SYSTEM DIAGRAM················8
9. TROUBLESHOOTING ······································11
10. DISASSEMBLY INSTRUCTIONS·····················19
11. PARTS LIST······················································21
12. RoHS PARTS LIST···········································23
13. OPTIONAL PARTS ···········································25
NOTE:
This service manual describes technical data of the indoor units. RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS PARTS LIST (RoHS compliant).
Grille
(When the grille is opened)
Remote controller
Operation section
Display section
Emergency operation switch
Operation indicator lamp
Air inlet
To breaker
Power supply cord
Remote control
receiving section
Air cleaning filter (option) (White bellows type)
Horizontal vane
Vertical vanes
Catechin air filter
Remote control
receiving section
Catechin air filter
Front panel
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 o 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
1 7 1 2 2 1 1
MS-GA50VB MS-GA60VB MS-GA80VB
Revision A :
RoHS PARTS LIST has been added.
Revision B :
Indoor heat exchanger of MS-GA80VB - has been changed.
PARTS LIST and RoHS PARTS LIST have been changed.
E1
1
MS-A18WV - MS-GA50VB ­MS-A24WV - MS-GA60VB ­MS-A30WV - MS-GA80VB -
1. Model name has been changed. Indication of capacity has been changed. (BTU➔kW)
2. Grille design has been changed.
3. Unit size has been changed.(W 1,100aoH 325aoD 227a W1,100aoH 325aoD 258a)
2
TECHNICAL CHANGES
E1E1
E1E1
E1E1
PART NAMES AND FUNCTIONS
MS-GA50VB MS-GA60VB MS-GA80VB
ACCESSORIES
2
REMOTE CONTROLLER
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
ECONO COOL
STOP
START
HR.
MIN.
WIDE VANE
LONG
I FEEL
COOL
DRY
PM
CLOCK
AM
RESET CLOCK
FAN
Open the front lid.
Signal transmitting section
Operation display section
OPERATE/ STOP (ON/ OFF) button
TEMPERATURE buttons
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
ECONO COOL button
VANE button
(Horizontal vane button)
CLOCK SET button
LONG button
WIDE VANE button
(Vertical vane button)
Indication of remote controller model is on back.
MS-GA50VB MS-GA60VB MS-GA80VB
3
3
Indoor model
Function
Power supply
Air flow
(High/Med./Low) Power outlet Running current Power input Power factor Fan motor current Model Winding resistance(at 20:) Dimensions WOHOD Weight Air direction Sound level(High/Med./Low) Fan speed(High/Med./Low) Fan speed regulator Thermistor RT11(at 25:) Thermistor RT12(at 25:) Remote controller model
K /h
A
A W %
A
"
mm
kg
dB
rpm
k" k"
MS-GA50VB
Cooling
Single phase
230V, 50Hz
768/642/528
10
0.30 60 87
0.30
RC4V32-AA WHT-BLK 293 BLK-RED 146
1,100O325O258
16
5
42/38/34
1,070/920/780
3 10 10
KM04B
MS-GA60VB
Cooling
Single phase
230V, 50Hz
768/672/588
10
0.30 60 87
0.30
RC4V32-AA WHT-BLK 293 BLK-RED 146
1,100O325O258
16
5
45/41/37
1,070/960/850
3 10 10
KM04B
Electrical
data
Fan
motor
Special
remarks
Capacity
Indoor model
Function
Power supply
Air flow
(High/Med./Low) Power outlet Running current Power input Power factor Fan motor current Model Winding resistance(at 20:) Dimensions WOHOD Weight Air direction Sound level(High/Med./Low) Fan speed(High/Med./Low) Fan speed regulator Thermistor RT11(at 25:) Thermistor RT12(at 25:) Thermistor RT13(at 25:) Remote controller model
K /h
A
A W %
A
"
mm
kg
dB
rpm
k" k" k"
MS-GA80VB
Cooling
Single phase
230V, 50Hz
960/822/684
10
0.34 69 88
0.34
RC4V40-AA WHT-BLK 138.2 BLK-RED 159.0 1,100O325O258
16
5
47/42/37
1,280/1,130/970
3 10 10 10
KM04B
Electrical
data
Fan
motor
Special
remarks
Capacity
SPECIFICATION
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB(24°C)
Indoor-Outdoor piping length : 5m
4
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
47
SPL(dB(A)) LINE
High
FAN SPEED
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
42
SPL(dB(A)) LINE
High
FAN SPEED
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
45
SPL(dB(A)) LINE
High
FAN SPEED
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
INDOOR UNIT
WALL
MICROPHONE
0.8m
1m
NOISE CRITERIA CURVES
MS-GA50VB MS-GA60VB
MS-GA80VB
5
5
258
162
19
58
47
7.5
315
255.547
2.5
98
173
98 173414.5 414.5
5
253
791
56
1068
1100
325
Air out
Air in
Insulation [28
Drain hose [16 (Connected part O.D)
Installation plate
Wall hole [75
Wireless remote controller
Installation plate
Indoor unit
{
Liquid line [ 6.35-0.5m Gas line [ 12-0.43m Insulation [ 50 O.D
[ 32 I.D
{
Liquid line [ 9.52-0.5m Gas line [ 12-0.43m Insulation [ 50 O.D
[ 32 I.D
for MS-GA50/60VB
for MS-GA80VB
Power supply cord Lead to right 2.0m Lead to left 1.0m
OUTLINES AND DIMENSIONS
MS-GA50VB MS-GA60VB MS-GA80VB
Unit: mm
6
6
12V
BLK GRY YLW BRN WHT RED
3
SR141
4
3
1
CN
121
C11
HIC1
MV1
2 1
CN112
151
CN
MV2
15
RT12
RT11
111
CN
CN211
NR11
ELECTRONIC CONTROL P. C. BOARD
F11
L
BRN
1
2
3
CN201
MV2
CN
101
CN
102
DISPLAY P. C. BOARD
RECEIVER P. C. BOARD
REMOTE CONTROLLER
33
TAB12
GRN/YLW
N
TB
2
1 2
1
CN202
TO OUTDOOR UNIT CONNECTING
BLK WHT
BLU
BRN BLU
1.About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Connector
: Terminal block
NOTES:
SYMBOL
C11 F11
HIC1
MF
NAME INDOOR FAN CAPACITOR FUSE (3.15A) DC/DC CONVERTER INDOOR FAN MOTOR (INNER FUSE)
SYMBOL
MV1
MV2 NR11 RT11
NAME VANE MOTOR (HORIZONTAL) VANE MOTOR (VERTICAL) VARISTOR ROOM TEMPERATURE THERMISTOR
SYMBOL
RT12
SR141
TB
NAME INDOOR COIL THERMISTOR SOLID STATE RELAY TERMINAL BLOCK
MF
1 2 3 4 5 6
PE
CIRCUIT BREAKER
POWER SUPPLY CORD ~/N 230V 50Hz
12V
TO OUTDOOR UNIT CONNECTING
BRN BLU
GRN/YLW
BLK GRY YLW BRN WHT RED
MF
3
SR141
4
3
1
CN
121
C11
HIC1
MV1
RT13
4 3 2 1
CN112
151
CN
MV2
15
RT12
RT11
111
CN
CN211
NR11
ELECTRONIC CONTROL P. C. BOARD
F11
3 N L
BRN
1
2
3
CN201
MV2
BLU
RED
CN
101
CN
102
DISPLAY P. C. BOARD
RECEIVER P. C. BOARD
REMOTE CONTROLLER
33
TAB12
TB
PE
CIRCUIT BREAKER
POWER SUPPLY CORD ~/N 230V 50Hz
1.About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Connector
: Terminal block
NOTES:
SYMBOL
SR141
TB
SYMBOL
MV2 NR11 RT11 RT12 RT13
SYMBOL
C11
F11
HIC1
MF
MV1
NAME
NAME NAME INDOOR FAN CAPACITOR FUSE(3.15A) DC/DC CONVERTER INDOOR FAN MOTOR(INNER PROTECTOR) VANE MOTOR(HORIZONTAL)
VANE MOTOR(VERTICAL) VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB)
SOLID STATE RELAY TERMINAL BLOCK
WIRING DIAGRAM
MS-GA50VB MS-GA60VB
MS-GA80VB
7
7
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Flared connection
Refrigerant pipe [15.88 (with heat insulator)
Refrigerant pipe [9.52 (with heat insulator)
Indoor coil thermistor RT12(main)
Strainer
#50
REFRIGERANT SYSTEM DIAGRAM
MS-GA50VB
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Distributor
Refrigerant pipe [12.7 (with heat insulator)
Flared connection
Flared connection
MS-GA60VB
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Distributor
Unit:mm
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
MS-GA80VB
Refrigerant pipe [6.35 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Refrigerant flow in cooling
8
8
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
SERVICE FUNCTIONS
MS-GA50VB MS-GA60VB MS-GA80VB
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board. The time will be shortened as follows.
Set time : 1 minute 1-second Set time : 3 minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For modification, take out the bat-
teries and press the OPERATE/ STOP (ON/ OFF) button 2 or 3 times at first. After modification, put back the batteries then press the RESET button.
J1
J2
The P.C. board has the print J1 and J2. Solder J1 and J2 according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
Table 1
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned OFF, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
9