Revision B : |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Indoor heat exchanger of MS-GA80VB - E1 has been changed. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
SPLIT-TYPE, AIR CONDITIONERS |
|
|
• PARTS LIST and RoHS PARTS LIST have been changed. |
||||||||||||||||||||||||||||
|
|
|
|||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Please void OB369 REVISED EDITION-A. |
INDOOR UNIT
SERVICE MANUAL
No. OB369
REVISED EDITION-B
Wireless type
Models
MS-GA50VB - E1
MS-GA60VB - E1
MS-GA80VB - E1
Outdoor unit service manual
MU-GA•VB Series (OB370)
CONTENTS
1.TECHNICAL CHANGES ····································2
2.PART NAMES AND FUNCTIONS······················2
3. SPECIFICATION·················································4
4.NOISE CRITERIA CURVES ·······························5
5.OUTLINES AND DIMENSIONS ·························6
6.WIRING DIAGRAM ············································7
7. REFRIGERANT SYSTEM DIAGRAM ················8
8. SERVICE FUNCTIONS ······································9
9. TROUBLESHOOTING······································11
10. DISASSEMBLY INSTRUCTIONS·····················19
11.PARTS LIST······················································21
12.RoHS PARTS LIST···········································23
13.OPTIONAL PARTS···········································25
NOTE:
This service manual describes technical data of the indoor units.
RoHS compliant products have <G> mark on the spec name plate.
For servicing of RoHS compliant products, refer to the RoHS PARTS LIST (RoHS compliant).
Revision A :
• RoHS PARTS LIST has been added.
Revision B :
• Indoor heat exchanger of MS-GA80VB - E1 has been changed.
• PARTS LIST and RoHS PARTS LIST have been changed.
1 TECHNICAL CHANGES
MS-A18WV - E1 MS-GA50VB - E1
MS-A24WV - E1 MS-GA60VB - E1
MS-A30WV - E1 MS-GA80VB - E1
1.Model name has been changed.
Indication of capacity has been changed. (BTU kW)
2.Grille design has been changed.
3.Unit size has been changed.(W 1,100aoH 325aoD 227a W1,100aoH 325aoD 258a)
2 PART NAMES AND FUNCTIONS
MS-GA50VB MS-GA60VB MS-GA80VB
Air cleaning filter (option) |
Grille |
|
(White bellows type) |
||
|
Air inlet
To breaker Front panel
Power supply cord
Catechin air filter
Remote control receiving section
Vertical vanes
Horizontal vane
Remote controller
Operation section |
Display section |
(When the grille is opened) |
Operation indicator lamp |
|
Emergency operation switch
Remote control receiving section
ACCESSORIES
|
|
MS-GA50VB |
|
|
MS-GA60VB |
|
|
MS-GA80VB |
1 |
Installation plate |
1 |
2 |
Installation plate fixing screw 4 o 25 mm |
7 |
3 |
Remote controller holder |
1 |
4 |
Fixing screw for 3 o 3.5 o 1.6 mm (Black) |
2 |
5 |
Battery (AAA) for remote controller |
2 |
|
|
|
6 |
Wireless remote controller |
1 |
|
|
|
7 |
Felt tape (Used for left or left-rear piping) |
1 |
|
|
|
2
REMOTE CONTROLLER
MS-GA50VB
MS-GA60VB
MS-GA80VB
Signal transmitting section
Operation display section
OPERATE/ STOP (ON/ OFF) button
|
|
PM |
|
|
AM |
ON/OFF |
TOO |
TOO |
|
WARM |
COOL |
TEMPERATURE buttons
Open the front lid. |
VANE button (Horizontal vane button)
OPERATION SELECT button
ECONO COOL button
WIDE VANE button (Vertical vane button)
RESET button
Indication of remote controller model is on back.
AM |
ON/OFF |
TOO |
TOO |
|
WARM |
COOL |
|
FAN |
STOP |
FAN SPEED CONTROL button |
|
|
||
I FEEL COOL |
|
|
OFF-TIMER button |
|
VANE |
START |
|
|
|
||
FAN DRY |
|
|
ON-TIMER button |
|
|
|
|
MODE |
WIDE VANE |
HR. |
HR. button |
|
|
|
|
ECONO COOL |
LONG |
MIN. |
MIN. button |
|
|
|
(TIME SET button) |
|
RESET CLOCK |
|
CLOCK SET button |
|
|
|
|
|
|
|
LONG button |
3 SPECIFICATION
|
|
Indoor model |
|
|
|
|
Function |
|
|
|
|
Power supply |
|
|
Capacity Air flow(High/Med./Low) |
K /h |
|||
Electrical |
data |
Power outlet |
A |
|
Power factor |
% |
|||
|
|
Running current |
A |
|
|
|
Power input |
W |
|
|
|
Fan motor current |
A |
|
Fan |
motor |
Model |
|
|
Winding |
" |
|||
|
|
|||
|
|
resistance(at 20:) |
||
|
|
|
||
|
|
Dimensions WOHOD |
mm |
|
|
|
Weight |
kg |
|
|
|
Air direction |
|
|
Special |
remarks |
Sound level(High/Med./Low) |
dB |
|
Fan speed(High/Med./Low) |
rpm |
|||
|
|
|||
|
|
Fan speed regulator |
|
|
|
|
Thermistor RT11(at 25:) |
k" |
|
|
|
Thermistor RT12(at 25:) |
k" |
|
|
|
Remote controller model |
|
|
|
|
Indoor model |
|
|
|
|
Function |
|
|
|
|
Power supply |
|
|
Capacity Air flow(High/Med./Low) |
K /h |
|||
Electrical |
data |
Power outlet |
A |
|
Running current |
A |
|||
|
|
|||
|
|
Power input |
W |
|
|
|
Power factor |
% |
|
|
|
Fan motor current |
A |
|
Fan |
motor |
Model |
|
|
Winding |
" |
|||
|
|
|||
|
|
resistance(at 20:) |
||
|
|
|
||
|
|
Dimensions WOHOD |
mm |
|
|
|
Weight |
kg |
|
|
|
Air direction |
|
|
|
|
Sound level(High/Med./Low) |
dB |
|
Special |
remarks |
Fan speed(High/Med./Low) |
rpm |
|
Thermistor RT11(at 25:) |
k" |
|||
|
|
Fan speed regulator |
|
|
|
|
Thermistor RT12(at 25:) |
k" |
|
|
|
Thermistor RT13(at 25:) |
k" |
|
|
|
Remote controller model |
|
NOTE: Test conditions are based on ISO 5151. Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB(24°C) Indoor-Outdoor piping length : 5m
MS-GA50VB |
MS-GA60VB |
Cooling |
Cooling |
Single phase |
Single phase |
230V, 50Hz |
230V, 50Hz |
768/642/528 |
768/672/588 |
10 |
10 |
0.30 |
0.30 |
60 |
60 |
87 |
87 |
0.30 |
0.30 |
RC4V32-AA |
RC4V32-AA |
WHT-BLK 293 |
WHT-BLK 293 |
BLK-RED 146 |
BLK-RED 146 |
1,100O325O258 |
1,100O325O258 |
16 |
16 |
5 |
5 |
42/38/34 |
45/41/37 |
1,070/920/780 |
1,070/960/850 |
3 |
3 |
10 |
10 |
10 |
10 |
KM04B |
KM04B |
MS-GA80VB
Cooling
Single phase 230V, 50Hz
960/822/684
10
0.34
69
88
0.34
RC4V40-AA
WHT-BLK 138.2
BLK-RED 159.0
1,100O325O258
16
5
47/42/37
1,280/1,130/970
3
10
10
10
KM04B
4
4 NOISE CRITERIA CURVES
MS-GA50VB |
MS-GA60VB |
FAN SPEED SPL(dB(A)) |
LINE |
High 42
FAN SPEED SPL(dB(A)) |
LINE |
High 45
Test conditions, |
Test conditions, |
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19: |
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19: |
BAR |
90 |
|
|
|
|
|
|
|
|
BAR |
90 |
|
|
|
|
|
|
|
|
|
|
||
MICRO |
80 |
|
|
|
|
|
|
|
|
MICRO |
80 |
|
|
|
|
|
|
|
|
|
|
||
0.0002 |
70 |
|
|
|
|
|
|
|
NC-70 |
0.0002 |
70 |
|
|
|
|
|
|
|
|
|
|||
dB re |
60 |
|
|
|
|
|
|
|
|
dB re |
60 |
LEVEL, |
|
|
|
|
|
|
|
|
LEVEL, |
||
|
|
|
|
|
|
|
|
NC-60 |
|
||
50 |
|
|
|
|
|
|
|
|
|
||
PRESSURE |
|
|
|
|
|
|
|
|
PRESSURE |
50 |
|
|
|
|
|
|
|
|
|
NC-50 |
|
||
40 |
|
|
|
|
|
|
|
|
40 |
||
|
|
|
|
|
|
|
|
NC-40 |
|
||
SOUND |
|
|
|
|
|
|
|
|
SOUND |
|
|
30 |
|
|
|
|
|
|
|
|
30 |
||
BAND |
|
|
|
|
|
|
|
|
NC-30 |
BAND |
|
20 |
APPROXIMATE |
|
|
|
|
|
|
20 |
|||
OCTAVE |
|
|
|
|
|
|
OCTAVE |
||||
THRESHOLD OF |
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
||||
|
HEARING FOR |
|
|
|
|
|
NC-20 |
|
|||
|
CONTINUOUS |
|
|
|
|
|
|
|
|||
10 |
NOISE |
|
|
|
|
|
|
|
10 |
||
|
63 |
125 |
250 |
500 |
1000 |
2000 |
4000 |
8000 |
|
||
|
|
|
|
|
|
|
|
|
|
|
NC-70 |
|
|
|
|
|
|
|
NC-60 |
|
|
|
|
|
|
|
NC-50 |
|
|
|
|
|
|
|
NC-40 |
|
|
|
|
|
|
|
NC-30 |
APPROXIMATE |
|
|
|
|
|
|
|
THRESHOLD OF |
|
|
|
|
|
|
|
HEARING FOR |
|
|
|
|
|
NC-20 |
|
CONTINUOUS |
|
|
|
|
|
|
|
NOISE |
|
|
|
|
|
|
|
63 |
125 |
250 |
500 |
1000 |
2000 |
4000 |
8000 |
BAND CENTER FREQUENCIES, Hz |
BAND CENTER FREQUENCIES, Hz |
MS-GA80VB
FAN SPEED SPL(dB(A)) |
LINE |
High 47
Test conditions,
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
BAR |
90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MICRO |
80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.0002 |
70 |
|
|
|
|
|
|
|
NC-70 |
|
|
|
|
|
|
|
|
||
dB re |
60 |
|
|
|
|
|
|
|
|
LEVEL, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NC-60 |
|
50 |
|
|
|
|
|
|
|
|
|
PRESSURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NC-50 |
|
40 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NC-40 |
|
SOUND |
|
|
|
|
|
|
|
|
|
30 |
|
|
|
|
|
|
|
|
|
BAND |
|
|
|
|
|
|
|
|
NC-30 |
20 |
APPROXIMATE |
|
|
|
|
|
|
||
OCTAVE |
|
|
|
|
|
|
|||
THRESHOLD OF |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|||
|
HEARING FOR |
|
|
|
|
|
NC-20 |
||
|
CONTINUOUS |
|
|
|
|
|
|
||
10 |
NOISE |
|
|
|
|
|
|
|
|
|
63 |
125 |
250 |
500 |
1000 |
2000 |
4000 |
8000 |
|
|
|
BAND CENTER FREQUENCIES, Hz
INDOOR UNIT
WALL
1m
0.8m
MICROPHONE
5
5 OUTLINES AND DIMENSIONS
MS-GA50VB
MS-GA60VB
MS-GA80VB
1068
1100
325
56 |
791 |
58 |
19 |
162 |
|
Wireless remote controller
Unit: mm
Installation plate |
Indoor unit |
|
|
|
|
98 |
|
|
173 |
|
7.5 |
|
|
|
|
|
|
|
|
|
|
255.5 |
315 |
47 |
414.5 |
414.5 |
2.5 |
47 |
|
98 |
173 |
|
|
Wall hole [75
Air in
253
Air out
258 5
{Liquid line [ 6.35- 0.5m
Installation plate Gas line [ 12-0.43m Insulation [ 50 O.D
[ 32 I.D for MS-GA50/60VB
{Liquid line [ 9.52- 0.5m Gas line [ 12-0.43m Insulation [ 50 O.D
[ 32 I.D for MS-GA80VB
Drain hose [16 (Connected part O.D)
Insulation [28
Power supply cord Lead to right 2.0m Lead to left 1.0m
6
6 |
WIRING DIAGRAM |
|
|
|
|
|
|
|
|
||
MS-GA50VB |
|
|
|
|
|
|
|
|
|
|
|
MS-GA60VB |
|
|
|
|
|
|
|
|
|
|
|
TO OUTDOOR UNIT |
|
|
CN202 |
|
|
|
|
|
|
||
CONNECTING |
1TB |
BLK |
|
HIC1 |
2 |
|
|
|
|
||
|
1 |
|
RT12 |
|
|||||||
|
|
WHT |
|
|
|
||||||
|
|
|
|
2 |
|
1 |
|
|
|
|
|
|
|
|
|
|
CN112 |
|
BLK |
|
|
||
|
12V |
2 |
|
|
CN201 |
3 |
1 |
|
|||
|
|
|
NR11 |
|
GRY |
|
|||||
|
|
|
|
|
3 |
CN |
2 |
|
|||
|
|
|
|
|
|
|
|||||
|
|
N |
BLU |
|
2 |
|
121 |
|
YLW |
3 |
MF |
|
|
|
|
|
|
BRN |
|||||
|
|
|
|
|
1 |
C11 |
1 |
|
4 |
||
|
POWER |
L |
BRN |
|
TAB12 |
F11 SR141 |
3 |
|
WHT |
5 |
|
|
|
4 |
|
RED |
6 |
|
|||||
|
SUPPLY |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
ELECTRONIC CONTROL CN211 |
|
|
|
|
||
|
CORD |
|
CN |
CN |
CN |
|
|
|
|
||
|
~/N 230V |
|
P. C. BOARD |
CN |
|
RT11 |
|
||||
|
50Hz |
BRN |
151 |
102 |
101 |
111 |
|
|
|||
|
|
15 |
|
|
|
|
|
|
|
|
|
|
|
BLU |
3 |
|
3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
PE
CIRCUIT BREAKER
GRN/YLW
MV2 MV2 MV1 |
DISPLAY |
RECEIVER |
|
P. C. BOARD |
P. C. BOARD |
REMOTE
CONTROLLER
SYMBOL |
NAME |
SYMBOL |
NAME |
SYMBOL |
NAME |
|
|
|
|
|
|
C11 |
INDOOR FAN CAPACITOR |
MV1 |
VANE MOTOR (HORIZONTAL) |
RT12 |
INDOOR COIL THERMISTOR |
|
|
|
|
|
|
F11 |
FUSE (3.15A) |
MV2 |
VANE MOTOR (VERTICAL) |
SR141 |
SOLID STATE RELAY |
|
|
|
|
|
|
HIC1 |
DC/DC CONVERTER |
NR11 |
VARISTOR |
TB |
TERMINAL BLOCK |
|
|
|
|
|
|
MF |
INDOOR FAN MOTOR (INNER FUSE) |
RT11 |
ROOM TEMPERATURE THERMISTOR |
|
|
|
|
|
|
|
|
NOTES: 1.About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing. 2.Use copper conductors only. (For field wiring)
3.Symbols below indicate.
: Terminal block
MS-GA80VB
TO OUTDOOR
UNIT
CONNECTING 3TB
12V |
N |
|
|
POWER |
L |
SUPPLY |
|
CORD |
|
~/N 230V |
|
50Hz |
BRN |
|
|
|
BLU |
PE |
GRN/YLW |
CIRCUIT |
|
BREAKER |
|
: Connector
|
|
|
|
|
|
4 |
RT13 |
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|
|
|
|
|
|
HIC1 |
|
|
2 |
RT12 |
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
RED |
CN201 |
|
|
|
CN112 |
BLK |
|
3 |
|
|
NR11 |
|
CN 3 |
GRY |
|
|
|
|
|
||||
|
2 |
|
|
|
|
121 |
YLW |
BLU |
|
|
|
|
|
||
1 |
|
|
C11 |
1 |
BRN MF |
||
|
|
|
|
WHT |
|||
BRN |
TAB12 |
|
F11 |
SR141 |
|
3 |
|
|
|
RED |
|||||
|
|
4 |
|||||
|
|
|
|
|
|
|
|
CN |
CN |
CN ELECTRONIC CONTROL |
CN211 |
|
|||
151 |
102 |
101 |
P. C. BOARD |
|
|
CN |
RT11 |
|
|
111 |
|||||
|
|
|
|
|
|
||
15 |
3 |
|
3 |
|
|
|
|
|
|
|
|
|
|
||
MV2 MV2 MV1 |
DISPLAY |
RECEIVER |
|
|
|
|
|
|
P. C. BOARD |
P. C. BOARD |
|
|
|
|
REMOTE
CONTROLLER
SYMBOL |
NAME |
SYMBOL |
NAME |
SYMBOL |
NAME |
|
C11 |
INDOOR FAN CAPACITOR |
MV2 |
VANE MOTOR(VERTICAL) |
SR141 |
SOLID STATE RELAY |
|
F11 |
FUSE(3.15A) |
|
NR11 |
VARISTOR |
TB |
TERMINAL BLOCK |
HIC1 |
DC/DC CONVERTER |
RT11 |
ROOM TEMPERATURE THERMISTOR |
|
|
|
MF |
INDOOR FAN MOTOR(INNER PROTECTOR) |
RT12 |
INDOOR COIL THERMISTOR (MAIN) |
|
|
|
MV1 |
VANE MOTOR(HORIZONTAL) |
RT13 |
INDOOR COIL THERMISTOR (SUB) |
|
|
|
NOTES: 1.About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing. |
|
|
||||
2.Use copper conductors only. (For field wiring) |
|
|
|
|||
3.Symbols below indicate. |
|
|
|
|
|
|
|
: Terminal block |
: Connector |
|
|
|
|
|
|
|
|
7 |
|
|
7 REFRIGERANT SYSTEM DIAGRAM
MS-GA50VB |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MS-GA60VB |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit:mm |
|||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Refrigerant pipe [12.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Refrigerant pipe [15.88 |
|||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(with heat insulator) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(with heat insulator) |
|||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Indoor coil |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Indoor coil |
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
Indoor |
|
|
thermistor |
|
|
|
|
Indoor |
|
|
|
thermistor |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
heat |
|
|
RT12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
heat |
|
|
|
RT12 |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
exchanger |
|
|
Distributor |
|
|
|
|
exchanger |
|
|
|
Distributor |
|
|
Flared connection |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Flared connection |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Room temperature thermistor
Room temperature
RT11
thermistor RT11
Flared connection |
Flared connection |
Refrigerant pipe [6.35 |
Refrigerant pipe [6.35 |
(with heat insulator) |
(with heat insulator) |
MS-GA80VB |
|
|
|
|
|
Refrigerant pipe [15.88 |
|
|
|
(with heat insulator) |
|
Indoor |
Indoor coil |
|
|
heat |
thermistor |
|
|
exchanger |
RT12(main) |
Flared connection |
|
|
Indoor coil |
|
|
|
thermistor |
|
|
|
RT13(sub) |
|
|
Room temperature |
|
|
|
thermistor |
|
|
|
RT11 |
|
|
|
|
Strainer |
|
|
|
#50 |
|
|
|
|
Flared connection |
|
|
|
Refrigerant pipe [9.52 |
|
|
|
(with heat insulator) |
Refrigerant flow in cooling |
|
|
|
8
8 SERVICE FUNCTIONS
MS-GA50VB
MS-GA60VB
MS-GA80VB
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board. The time will be shortened as follows.
Set time : 1 minute 1-second
Set time : 3 minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For modification, take out the batteries and press the OPERATE/ STOP (ON/ OFF) button 2 or 3 times at first.
After modification, put back the batteries then press the RESET button.
J1 J2
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
Table 1
|
1 unit operation |
2 units operation |
3 units operation |
4 units operation |
|
|
|
|
|
No. 1 unit |
No modification |
Same as at left |
Same as at left |
Same as at left |
|
|
|
|
|
No. 2 unit |
– |
Solder J1 |
Same as at left |
Same as at left |
|
|
|
|
|
No. 3 unit |
– |
– |
Solder J2 |
Same as at left |
|
|
|
|
|
No. 4 unit |
– |
– |
– |
Solder both J1 and J2 |
|
|
|
|
|
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit.
The indoor unit only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned OFF, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
9