1. THE FOLLOWING SHOULD ALWAYS BE
OBSERVED FOR SAFETY
Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR
•
SAFETY” before installing the air conditioner.
Be sure to observe the cautions specifi ed here as they include important items
•
related to safety.
The indications and meanings are as follows.
•
WARNING
Could lead to death, serious injury, etc.
CAUTION
Could lead to serious injury in particular environments when operated incorrectly.
After reading this manual, be sure to keep it together with the OPERATING
•
INSTRUCTIONS in a handy place on the customer’s site.
WARNING
Q Do not install the unit by yourself (customer).
Incomplete installation could cause injury due to fi re, electric shock, the unit
falling or leakage of water. Consult the dealer from whom you purchased the
unit or special installer.
Install the unit securely in a place which can bear the weight of the unit.
Q
When installed in an insuffi cient strong place, the unit could fall causing injury.
Q Use the specifi ed wires to connect the indoor and outdoor units securely
and attach the wires fi rmly to the terminal block connecting sections so
the stress of the wires is not applied to the sections.
Incomplete connecting and fi xing could cause fi re.
Q Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet.
It could cause a fi re or an electric shock due to defective contact, defective
insulation, exceeding the permissible current, etc.
Q Check that the refrigerant gas do not leak after installation has
completed.
If refrigerant gas leaks indoors, and comes into contact with the fi re of a fan
heater, space heater, stove, etc., harmful substances will be generated.
Q Perform the installation securely referring to the installation manual.
Incomplete installation could cause a personal injury due to fi re, electric shock,
the unit falling or leakage of water.
Q Perform electrical work according to the installation manual and be sure
to use an exclusive circuit.
If the capacity of the power circuit is insuffi cient or there is incomplete electrical
work, it could result in a fi re or an electric shock.
Q Attach the electrical cover to the indoor unit and the service panel to the
outdoor unit securely.
If the electrical cover in the indoor unit and/or the service panel in the outdoor
unit are not attached securely, it could result in a fi re or an electric shock due
to dust, water, etc.
Q Be sure to use the part provided or specifi ed parts for the installation
work.
The use of defective parts could cause an injury or leakage of water due to a
fi re, an electric shock, the unit falling, etc.
Q Be sure to cut off the main power in case of setting up the indoor electronic
control P.C. board or wiring works.
It could cause an electric shock.
Q The appliance shall be installed in accordance with national wiring
regulations.
Q When installing or relocating the unit, make sure that no substance other
than the specifi ed refrigerant (R410A) enters the refrigerant circuit.
Any presence of foreign substance such as air can cause abnormal pressure
rise or an explosion.
HFC
utilized
R410A
Series
When installing an MXZ series
outdoor unit, refer to the MS
and MSH type manual for
indoor unit set up.
Q Earth the unit.
Do not connect the earth to a gas pipe, water pipe, lightning rod or telephone
earth. Defective earthing could cause an electric shock.
Q Do not install the unit in a place where an infl ammable gas leaks.
If gas leak and accumulate in the area surrounding the unit, it could cause an
explosion.
Q Install an earth leakage breaker depending on the installation place (Where
it is humid).
If an earth leakage breaker is not installed, it could cause an electric shock.
Q Perform the drainage/piping work securely according to the installation
manual.
If there is a defect in the drainage/piping work, water could drop from the unit
and household goods could be wet and damaged.
Q Fasten a fl are nut with a torque wrench as specifi ed in this manual.
When fastened too tight, a fl are nut may broken after a long period and cause
a leakage of refrigerant.
IMPORTANT NOTES
TO COMPLY WITH THE REQUIREMENT
OF AUSTRALIAN STANDARD AS/NZS 3000
ELECTRICAL INSTALLATIONS (Wiring Rules),
THE ELECTRICAL WIRING REQUIRED
BETWEEN THE INDOOR AND OUTDOOR
UNITS MUST BE INSTALLED BY A LICENCED
ELECTRICAL CONTRACTOR.
CAUTION
2. SELECTING THE INSTALLATION LOCATION
2-1 INDOOR UNIT
Where airfl ow is not blocked.
•
Where cool air spreads over the entire room.
•
Maximum refrigerant piping length between indoor unit and outdoor unit is 25 m and
•
the difference of height of both units is 10 m.
Rigid wall without vibration.
•
Where it is not exposed to direct sunshine.
•
Where easily drained.
•
At a distance 1 m or more away from your TV and radio. Operation of the air conditioner
•
interferes with radio or TV reception in areas where reception is weak.
An amplifi er may be required for the affected device.
In a place as far away as possible from fl uorescent and incandescent lights (so the
•
infrared remote control can operate the air conditioner normally).
Where the air fi lter can be removed and replaced easily.
•
2-2 OUTDOOR UNIT
Where it is not exposed to strong wind.
•
Where airfl ow is good and dustless.
•
Where it is not exposed to rain and direct sunshine.
•
Where neighbours are not annoyed by operation sound or hot air.
•
Where rigid wall or support is available to prevent the increase of operation sound
•
or vibration.
Where there is no risk of combustible gas leakage.
•
When installing the unit at a high level, be sure to fi x the unit legs.
•
Where it is at least 3 m away from the antenna of TV set or radio. Operation of the
•
air conditioner interferes with radio or TV reception in areas where reception is weak.
An amplifi er may be required for the affected device.
Install the unit horizontally.
•
Please install it in an area not affected by snowfall or blowing snow. In areas with
•
heavy snow, please install a canopy, a pedestal and/or some baffl e boards.
Note:
It is advisable to make a piping loop near outdoor unit so as to reduce vibration
transmitted from there.
CAUTION
Avoid the following places for installation where air conditioner trouble is liable
to occur.
Where fl ammable gas could leak.
•
Where there is much machine oil.
•
Salty places such as the seaside.
•
Where sulfi de gas is generated such as a hot spring.
•
Where there is high-frequency or wireless equipment.
•
2-3 WIRELESS REMOTE CONTROLLER MOUNTING
Place of mounting
•
• Where it is easy to operate and easily visible.
• Where children can not touch.
Mounting
•
Select a position about 1.2 m above the fl oor, check that signals from the remote
controller are surely received by the indoor unit from that position (‘beep’ or
‘beepbeep’ receiving tone sounds). After that, attach remote controller holder 3 to
a pillar or wall and set the wireless remote controller 6.
In rooms where inverter type fl uorescent lamps are used, the signal from the wireless
remote controller may not be received.
3.
INSTALLATION DIAGRAM & ACCESSORIES
FLARED CONNECTIONS
This unit has fl ared connections on both indoor and outdoor sides.
•
Remove the outdoor units valve cover, then connect the pipe.
•
Refrigerant pipes are used to connect the indoor and outdoor units.
•
Be careful not to crush or bend the pipe in pipe bending.
•
Limits
Pipe length25 m max.
Height difference10 m max.
No. of bends10 max.
Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant
•
(R410A) charge is required.
(The outdoor unit is charged with refrigerant for pipe length up to 7 m.)
Up to 7 mNo additional charge is required.
Pipe length
Refrigerant to
be added
Exceeding 7 m
20 g/m × (refrigerant piping length (m) -7)
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
Installation plate1
1
Installation plate fi xing screw 4 × 25 mm7
2
Remote controller holder1
3
4Fixing screw for 3 3.5 × 16 mm (Black)
Battery (AAA) for remote controller2
5
Wireless remote controller1
6
Felt tape (Used for left or left-rear piping)1
7
Air Cleaning fi lter2
8
Additional charge is required.
(Refer to the table below.)
2
PIPING PREPARATION
1 Specifi cations
Use the refrigerant pipes that meet the following specifi cations.
Pipe
For liquid6.358
For gas12.78
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm.
Never use any pipe with a thickness less than 0.8 mm, as the pressure resistance
is insuffi cient.
2 Ensure that the 2 refrigerant pipes are insulated to prevent condensation.
3 Refrigerant pipe bending radius must be 100 mm or more.
Be sure to use the insulation of specifi ed thickness. Excessive thickness may
cause incorrect installation of the indoor unit and lack of thickness may cause dew
drippage.
1
2
0 mm
or more
72 mm or more
100 mm or more for left and left
back piping (using spacer)
Outside diameter Insulation thickness
mmmm
Insulation material
Heat resisting
foam plastic 0.045
specifi c gravity
CAUTION
Decide the installation position using mark on the installation
plate indicating the indoor unit size as reference.
Be careful the
drain hose is not
raised.
1
PART TO BE PROVIDED AT YOUR SITE
Optional extension pipe
Indoor/outdoor unit connecting wire
A
(2-core 1.0 mm
Extension pipe
B
Wall hole sleeve
C
Wall hole cover
D
Pipe fi xing band
E
(The quantity depends on the pipe length.)
Fixing screw for E 4 × 20 mm
F
(The quantity depends on the pipe length.)
Piping tape
G
Putty
H
Drain hose
I
(or soft PVC. hose, 15 mm inner dia.)
Refrigeration oil
J
Power supply cord (See the table in 5
INDOOR/OUTDOOR WIRE CONNECTION
K
AND OUTDOOR POWER SUPPLY CORD
CONNECTION for the cord size.)
mm
0
9
2
2
-2.0 mm2)
850mm
Air outlet
500mm
mm01
Slot
4-10 mm × 21 mm
Note:
When operating the air conditioner in low outside temperature,
be sure to follow the instructions described below.
Never install the outdoor unit in a place where its air inlet/outlet
•
side may be exposed directly to wind.
To prevent exposure to wind, install the outdoor unit with its
•
air inlet side facing the wall.
To prevent exposure to wind, it is recommended to install a
•
baffl e board on the air outlet side of the outdoor unit.
1
1
1
1
2 to 5
2 to 5
1
1
1
1
1
mm
8
1
mm013
mm81
8
5
1
00 mm or more
2
00 mm or m
5
6
4
ore
Note: Do not obstruct
the air outlet.
7 mm or more
3
00 mm or more
100 mm or more
1
7
200 mm or more
D
H
C
Piping can be directed towards rear,
right, downward, left or left-rear
directions.
Rear side
Right
Rear
DownwardLeft-rear
Lock the catch.
from the fl oor
1800 mm or more
Front
Left
B
G
Separate the 2 connecting pipes and
F
E
A
K
I
350 mm or more
apply insulation individually.
8 mm thickness thermal insulation
plastic
When the piping is to be attached to
a wall containing metals (tin plated)
or metal netting, use a chemically
treated wooden piece 20 mm or
thicker between the wall and the piping
or wrap 7 to 8 turns of insulation vinyl
tape around the piping.
Units should be installed by licensed contractor according
to local code requirement.
4. INDOOR UNIT INSTALLATION
4-1 FIXING OF INSTALLATION PLATE
Find a structural material (such as a stud) in the wall and fi x installation plate
•
horizontally.
Bind the line to the center hole.
0 mm or more
12
(off the wall)
Installation
plate fi xing
screw 2
4 × 25 mm
To prevent the installation plate from vibrating, be sure to fi x the holes
as indicated by the arrows .
Installation
plate 1
Plumb
When bolts recessed in the concrete wall are to be utilized, secure the installation plate
1 using 11 × 20 · 11 × 26 oval hole (450 mm pitch).
If the recessed bolt is too long, change it for a shorter one available in the market.
4-2 WALL HOLE DRILLING
1 Determine the wall hole position.
2 Drill a 75 mm hole so that outside can be lower than inside.
3 Insert the wall hole sleeve C.
Positioning of the holes on the wall
Installation plate 1
Insert the scale.
Align the scale with the line.
Repeat the same procedure for the left hole.
Wall hole
75 mm dia.
(Indoor side)
(Wall hole cross section)
Be sure to use wall hole sleeve C to prevent the outdoor connecting wires from
contacting with metal part in the wall and to prevent damage by rat in case the wall
is hollow.
Wall hole sealing and fi xing pipe to wall
Wall hole cover D
Seal the wall hole
gap with putty H.
Fix the pipe to wall with
pipe fi xing band E.
100 mm
Hole of dia.
75 mm
Wall thickness
Wall hole sleeve C
72 mm or more
100 mm or more for left
and left back piping (using
spacer)
00 mm or more
2
the wall)
(off
1800 mm or more
from the fl oor
Align the plumb line
with the mark .
One scale
Cut with 1 extra
scale length.
Cut off the
extra length. Pipe fi xing
band E
4-3 CONNECTING WIRE SPECIFICATIONS
Use special room air conditioning circuit.
•
Power supply cord length
(Lead to left/Lead to right)
Indoor/outdoor unit connecting
wire Specifi cation
Take out power supply cord from the left or right bottom corner of the indoor unit.
•
Cable 2-core 1.0 mm
Design 60245 IEC 57.
1 m/2 m
2
, in conformity with
Connect to the power switch which has a gap of 3 mm or more when open to
interrupt the source power phase.
(When the power switch is shut off, it must interrupt all phases.)
(Rated Voltage/Frequency : 230 V/50 Hz)
(Input capacity Main switch/Fuse : 10 A)
(This plug has to be the one meets the Standards.)
WARNING
Never cut the indoor and outdoor unit connecting wire and connect it to other wires.
It may cause a fi re.
Do not bundle the spare wire, but put it as shown below.
4-4 INDOOR AND OUTDOOR CONNECTING WIRE
CONNECTION
You can connect indoor/outdoor lead wire without removing the front panel.
1 Open the front panel.
2 Remove one screw holding the electrical cover, then remove the cover.
3 Remove the VA clamp and the cord clamp.
4 Pass the indoor/outdoor unit connecting wire from the back of the indoor unit and
process the end of the wire, then connect it to the terminal block.
5 Replace the fi xture and electrical cover securely.
Indoor
terminal block
Indoor/outdoor unit connecting wire A
VA clamp
Never fail to hook the left claw on
the wire fi xture to secure indoor/
outdoor unit connecting wire A.
Securely push the wire into
the terminal block until no
part of its core is appeared.
WARNING
O
Use the indoor/outdoor unit connecting wire that meets the Standards to connect
the indoor and outdoor units and fi x the wire to the terminal block securely so
that no external force is conveyed to the connecting section of the terminal block.
Incomplete connection or fi xing of the wire could result in a fi re.
O
Attach the VA clamp securely. If it is attached incorrectly, it could result in a fi re
or an electric shock due to dust, water, etc.
ELECTRICAL COVER
Fixing screws
Indoor unit
Wall hole
sleeve C
Fixing screw F
MSH type
Loosen terminal
screw.
Terminal
block
15 mm
<Connection details>
35 mm
Lead wire
3 N
3
N
Indoor terminal block
Indoor/outdoor unit
connecting wire A
2-core 1.0 mm
Outdoor terminal block
2
MS type
Loosen terminal
screw.
15 mm
35 mm
Terminal
block
<Connection details>
O
Be careful not to make mis-wiring.
O
Firmly tighten the terminal screws to prevent them from loosening.
O
After tightening, pull the wires lightly to confi rm that they do not move.
O
If the connecting wire is incorrectly connected to the terminal block, the unit does
not operate normally.
O
If an earth is incorrect, it may cause an electric shock.
O
Make earth wire a little longer than the others. (more than 35 mm)
Lead wire
CAUTION
Indoor terminal block
Indoor/outdoor unit
connecting wire A
2-core 1.0 mm
Outdoor terminal block
2
4-5 AUTO RESTART FUNCTION
These models are equipped with an auto restart function. If you do not want to use
•
this function, please consult the service representative because the setting of the unit
needs to be changed.
When the indoor unit is controlled with the remote controller, the operation mode, the
•
set temperature, and the fan speed are memorized by the indoor electronic control P.C.
board. The auto restart function sets to work the moment the power has restored after
power failure, then, the unit will restart automatically. If the unit is operated in “I FEEL...”
or “AUTO” mode before power failure, the operation mode (COOL, DRY or HEAT) is not
stored in the memory. When the main power is turned on, the unit decides the operation
mode by the initial room temperature at restart and starts operation again.
Insert the piping and the drain hose into the wall hole sleeve C, and hook the upper
•
part of the indoor unit on the installation plate 1.
Check if the indoor unit is hooked securely on the installation plate 1 by moving the
•
unit to left and right.
Thrust the lower part of the indoor unit into the installation plate 1.
•
FOR LEFT OR LEFT-REAR PIPING
Pipe arrangement
•
Put the refrigerant piping and the drain hose together, then apply felt tape 7 to them.
Be careful drain
hose is not heaved.
Felt tape 7
Firmly apply felt tape 7 from the end.
(Felt tape 7 overlap width should be 1/3
the tape width.)
REATTACHING DRAIN HOSE
Be sure to reattach the drain hose and the drain cap in case of left or left-rear piping.
Otherwise, it could cause drops of water to drip down from the drain hose.
Cut off in case of left piping.
Use a bandage stopper at
the end of felt tape 7.
Operation
1 If the main power (230V AC) has been cut, the operation settings remain.
2 When three minutes have passed after power was restored, the unit will restart
automatically according to the memory.
Notes:
• The operation settings are memorized when 10 seconds have passed after the remote
controller was operated.
• If the main power is turned off or a power failure occurs while AUTO START/STOP timer
is active, the timer setting is cancelled. As these models are equipped with an auto
restart function, the air conditioner starts operating with timer cancelled at the same
time that power is restored.
• If the unit has been off with the remote controller before power failure, the auto restart
function does not work as the power button of the remote controller is off.
• To prevent breaker off due to the rush of starting current, systematize other home
appliances not to turn on at the same time.
4-6 PIPE FORMING
Place the drain hose below the refrigerant piping.
•
Make sure that the drain hose is not heaved or snaked.
•
Do not pull the hose to apply the tape.
•
When the drain hose passes the room, be sure to wrap insulation material (obtainable
•
at a store) around it.
Wrap the felt tape 7 around the pipe and the drain hose, then put the pipe in the back
•
space of the indoor unit.
Liquid pipe
Gas pipe
Indoor/outdoor unit
connecting wire A
Felt tape 7
Drain cap
1
Pull out the drain cap at the rear right of the indoor unit.
Hold the convex section at the end and pull the drain cap.
Drain cap
2
Pull out the drain hose at the rear left of the indoor unit.
Hold the claw marked by the arrow and pull out the drain hose forward.
Drain hose
FOR REAR, RIGHT OR DOWNWARD PIPING
Pipe arrangement
•
Put the refrigerant piping and the drain hose together, then apply felt tape
Be careful drain
hose is not heaved.
Cut off in case of left piping.
Cut off in case of downward piping.
Firmly apply piping tape G
from the end.
G to them.
3
Put the drain cap into the section to which the drain hose is to be
attached at the rear of the indoor unit.
Insert the screwdriver, etc. (not sharp-edged tool) into the hole at the end of the cap
and insert the cap fully into the drain pan.
Drain cap
4
Insert the drain hose into the section to which the drain hose is
to be attached at the rear right of the indoor unit.
Insert the drain hose fully into the drain pan. Check if the hose is hooked securely to
the projection of its inserting part at the drain pan.
Drain hose
INDOOR UNIT INSTALLATION
Insert the drain hose into the wall hole sleeve C, and hook the upper part of indoor
•
unit on the installation plate 1. Then, move the unit to the very edge of the left side
for putting the piping easily in the back space of the indoor unit. After that, cut the part
of packing material (spacer assembly) to hook it on the back rib and lift the indoor
unit as shown in the fi gure below.
Cut part of packing material (spacer assembly) to
hook it on the back rib.
Spacer assembly
Securely attach the spacer assembly
in the concave part of the rib, taking
care its direction is correct as shown
in the fi gure right.
Connect the refrigerant piping with the extension pipe B.
•
Thrust the lower part of the indoor unit into the installation plate 1.
•
Spacer
4-7 DRAIN PIPING
The drain hose should point downward for easy drain fl ow. (Fig. 1)
•
Do not make drain piping as shown in Fig. 2 to 5.
If the extension drain hose has to pass through a room, be sure to wrap it with
•
commercially sold insulation.
Downward
slope
Do not raise.
Accumulated
drain water
Air
5. OUTDOOR UNIT INSTALLATION
INDOOR/OUTDOOR UNIT CONNECTING WIRE CONNECTION AND OUTDOOR POWER SUPPLY CORD CONNECTION
Connect the indoor/outdoor unit connecting wire A from the indoor unit correctly on
•
the terminal block.
For future servicing, give extra length to connecting wire.
•
Rated
Voltage
230 V15 A
O
When too long, or connected by cutting off the middle,
peel off power supply wire to the size as shown in the
O
O
(more than 35 mm)
For the power supply cord and the indoor/outdoor unit connecting wires, be sure to
•
Be sure to push the core until it is hidden and pull each cable to make sure that it is
•
Power supply cord
Specifi cation
Indoor and Outdoor
connecting wire
Specifi cation
Indoor
terminal
block
Outdoor
terminal
block
Breaker
capacity
Connect to the supply terminals and leave a contact
separation of at least 3 mm at each pole to disconnect the
source power pole. (When the power switch is shut off, it
must disconnect all poles.)
Peel off both ends of connecting wire (extension wire).
right.
Be careful not to contact connecting wire with piping.
Make earth wire a little longer than the others.
15 mm
35 mm
use the ones in compliance with the standards.
not pulled up incomplete insertion may cause a risk of burning the terminal blocks.
2
3-core 1.5 mm
in conformity with Design 60245 IEC 57.
3-core 2.5 mm
in conformity with Design 60245 IEC 57.
Cable 2-core 1.0 mm
or more,
2
or more,
10 m or less
15 m or less
2
,
in conformity with Design 60245 IEC 57.
WARNING
O A means for disconnection of the supply with an isolation switch, or similar
device, in all active conductors shall be incorporated in the fi xed wiring.
O Never cut the power cord and connect it to other wires.
It may cause a fi re.
MS typeMSH type
221
1
Indoor/outdoor unit
connecting wire A
2-core 1.0 mm
NL
Indoor
terminal
block
Outdoor
terminal
block
3 N
3
N
Indoor/outdoor unit
connecting wire A
2-core 1.0 mm
NL
Water
leakage
(Fig. 1) (Fig. 2) (Fig. 3)
Tip of drain
hose dipped
in water.
Water
leakage
(Fig. 4) (Fig. 5)
If the drain hose provided with the indoor unit is too short, connect it with drain hose
•
I that should be provided at your site. (Fig. 6)
When connecting the drain hose to the hard vinyl chloride pipe, be sure to insert it
•
securely into the pipe. (Fig. 7)
(Fig. 6) (Fig. 7)
Ditch
Less than
50 mm gap
Drain
hose
Soft hose
I.D.
15 mm
70 cm or
more
Differentdiameter joint
Water
leakage
Waving
Drain hose
Hard vinyl
chloride pipe
I.D. 30 mm
Be sure to insert
the drian hose
securely into the
pipe.
Power supply cord K
Power supply cord K
CAUTION
O Use care not to make mis-wiring.
O Firmly tighten the terminal screws to prevent them from loosening.
O After tightening, pull the wires lightly to confi rm that they do not move.
O If the connecting wire is incorrectly connected to the terminal block, the unit
does not operate normally.
Be sure to fi x the indoor/outdoor unit
connecting wire A and power supply cord K
using this cord clamp.
Be sure to put the left portion
into the square hole of the
service panel.
Fixing screws
K
A
Service panel
Remove two fi xing
screws to open the
service panel.
WARNING
Be sure to attach the service panel of the outdoor unit securely. If it is not attached
correctly, it could result in a fi re or an electric shock due to dust, water, etc.
6. INDOOR/OUTDOOR UNIT CONNECTION
FINISHING AND TEST RUN
INSTALLATION INFORMATION FOR THE AIR
CONDITIONER WITH R410A REFRIGERANT
This room air conditioner adopts an HFC refrigerant (R410A) which will never destroy
•
the ozone layer.
Pay particular attention to the following points, though the basic installation
•
procedure is same as that for R22 air conditioners.
1 As R410A has a working pressure approx. 1.6 times as high as that of R22, some
special tools and piping parts / materials are required. (Refer to the table below.)
2 Take suffi cient care not to allow water and other contaminations to enter the
R410A refrigerant during storage and installation, since it is more susceptible to
contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts / materials specifi cally
designed for R410A. (Refer to 2. Refrigerant piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When
charging, charge liquid refrigerant to prevent composition change.
6-1 Tools dedicated for the air conditioner with R410A
refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be
substituted for R410A tools.
The diameter of the service port on the stop valve in outdoor unit has been changed to
prevent any other refrigerant being charged into the unit. (Cap size has been changed
from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.)
R410A tools
Gauge manifoldNo
Charge hoseNo
Gas leak detectorNoDedicated for HFC refrigerant.
Torque wrench
Flare toolYes
Flare gaugeNew
Vacuum pump
adaptor
Electronic scale
for refrigerant
charging
No: Not substitutable for R410A Yes: Substitutable for R410A
Can R22 tools
be used?
Yes1/4
No1/2
New
New
Description
R410A has high pressures beyond the
measurement range of existing gauges.
Port diameters have been changed to prevent
any other refrigerant from being charged into
the unit.
Hose material and cap size have been changed
to improve the pressure resistance.
Clamp bar hole has been enlarged to reinforce
the spring strength in the tool.
Provided for fl aring work (to be used with R22
fl are tool).
Provided to prevent the back fl ow of oil. This
adapter enables you to use existing vacuum
pumps.
It is diffi cult to measure R410A with a charging
cylinder because the refrigerant bubbles due to
high pressure and high-speed vaporization.
6-2 FLARING WORK
Main cause of gas leakage is defect in fl aring work.
•
Carry out correct fl aring work in the following procedure.
1
Pipe cutting
• Cut the copper pipe correctly with pipe cutter.
Good
Copper pipe
2
Burrs removal
• Completely remove all burrs from the cut cross section of pipe.
• Put the end of the copper pipe to downward direction as you remove burrs in order to
avoid to let burrs drop in the piping.
Burr
3
Putting nut on
• Remove fl are nuts attached to indoor and outdoor
units, then put them on pipe having completed
burr removal.
(not possible to put them on after fl aring work)
• Flare nut for R410A pipe differs from R22 pipe.
Refer to the following table for detail.
mmInchR410AR22
ø6.351/41717
ø12.71/22624
4
Flaring work
• Carry out fl aring work using fl aring tool as shown below.
Flaring tool
Wing nut typeClutch type
Outside diameter
ø6.35 mm0 to 0.51.0 to 1.51.5 to 2.0
ø12.7 mm0 to 0.51.0 to 1.52.0 to 2.5
• Firmly hold copper pipe in a die in the dimension shown in the table above.
5
Check
• Compare the fl ared work with fi gure below.
• If fl are is noted to be defective, cut off the fl ared section and do fl aring work again.
Flare tool for R410A
Smooth all around
Even length
all around
Copper pipe
Die
clutch type
o
90
Spare
reamer
Pipe
cutter
Copper pipe
Clutch typeWing nut type
Inside is shining without any scratches.
No good
Tilted Uneven Burred
Flare nut
A
Flare nut
A (mm)
Conventional fl are tool
Copper pipe
Yor k
Die
Copper pipe
6-3 PIPE CONNECTION
Note:
Fasten a fl are nut with a torque wrench as specifi ed in the table below.
When fastened too tight, a fl are nut may broken after a long period and cause a leakage
of refrigerant.
1 Indoor unit connection
Connect both liquid and gas pipings to indoor unit.
Apply a thin coat of refrigeration oil J on the seat surface of pipe.
•
For connection fi rst align the center, then tighten the fi rst 3 to 4 turns of fl are nut.
•
Use tightening torque table below as a guideline for indoor unit side union joint section,
•
and tighten using two wrenches. Excessive tightening damages the fl are section.
Pipe diameterTightening torque
mmN·mkgf·cm
ø6.3513.7 to 17.7140 to 180
ø12.749.0 to 56.4500 to 575
2 Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied for
indoor unit.
For tightening, use a torque wrench or spanner and use the same tightening torque
•
applied for indoor unit.
INSULATION AND TAPING
1 Cover piping joints with pipe cover.
2 For outdoor unit side, surely insulate every piping including valves.
3 Using piping tape G, apply taping starting from the entry of outdoor unit.
Stop the end of piping tape G with tape (with adhesive agent attached).
•
When piping have to be arranged through above ceiling, closet or where the temperature
•
and humidity are high, wind additional commercially sold insulation for prevention of
condensation.
6-4 PURGING PROCEDURES·LEAK TEST
PURGING PROCEDURES
Connect the refrigerant pipes (both liquid pipe and the gas pipe) between the indoor
and the outdoor unit.
Remove the service port cap of the stop valve on the side of the outdoor unit gas
pipe. (The stop valve will not work in it initial state fresh out of the factory (totally
closed with cap on).)
Connect the gauge manifold valve and the vacuum pump to the service port of the
stop valve on the gas pipe side of the outdoor unit.
Run the vacuum pump. (Vacuumize for more than 15 minutes.)
Check the vacuum with the gauge manifold valve, then close the gauge manifold
valve, and stop the vacuum pump.
Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve
remains in the same position. Confi rm that the pressure gauge shows–0.101 Mpa
[Gauge] (–760 mmHg).
Stop valve
Close
Open
Hexagonal wrench
Precautions when using the control valve
Control Valve
Remove the gauge manifold valve quickly from the service port of the stop valve.
After refrigerant pipes are connected and evacuated, fully open all stop valves on
both sides of gas pipe and liquid pipe.
Operating without fully opening lowers the performance and this causes trouble.
A
Open
Close
Body
Pipe length up to 7 m
No gas charge is needed.
Tighten the cap to the service port to obtain the initial status.
Stop valve
Service port
Charge hose
Gauge manifold valve
Charge
hose
When attaching the control valve to the service port,
valve core may deform or loosen if excess pressure
is applied. This may cause gas leak.
When attaching the control valve to the service port,
make sure that the valve core is in closed position, and
then tighten part A. Do not tighten part A or turn the body
when valve core is in open position.
Retighten the cap.
Leak test
Vacuum pump
Pipe length exceeding 7 m
Charge the prescribed amount
of gas. (refer to 3)
Liquid pipe
Hexagonal
wrench
Stop valve
Service port
Gas pipe
Caps
Tightening torque
N·mkgf·cm
Cap for service port13.7 to 17.7140 to 180
Cap for stop valve19.6 to 29.4200 to 300
6-5 TEST RUN
MS type
• Before performing the test run, recheck for any wrong wiring.
Wrong wiring prevents normal operation or results in blown fuse disabling operation.
• The test run can be started by pressing EMERGENCY OPERATION switch. When
the EMERGENCY OPERATION switch is once pressed, the unit will start the test run
(continuous operation) for 30 minutes.
A thermostat does not work during this time. After 30 minutes the unit will start the
EMERGENCY OPERATION at a fi xed temperature setting of 24°C in COOL MODE.
• Perform test run in the following procedure.
PROCEDURE
• Press the EMERGENCY OPERATION switch.
1 Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE
starts.
2 Press it once more, and the operation stops.
(The operation mode alternates between 1 and 2 every time the EMERGENCY
OPERATION switch is pressed.)
Operation Indicator lamp
Mode
COOL
1
(Light) (Off)
STOP
2
(Off) (Off)
EMERGENCY
OPERATION switch
MSH type
• Before performing the test run, recheck any wrong wiring.
Wrong wiring prevents normal operation or results in blown fuse disabling operation.
• The test run can be started by pressing EMERGENCY OPERATION switch. When
the EMERGENCY OPERATION switch is once pressed, the unit will start the test run
(continuous operation) for 30 minutes.
A thermostat does not work during this time. After 30 minutes the unit will start the
EMERGENCY OPERATION at a fi xed temperature setting of 24°C in COOL MODE or
HEAT MODE.
• Perform test run in the following procedure.
PROCEDURE
• Press the EMERGENCY OPERATION switch.
1 Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE
starts.
If the left side lamp of the operation indicator blinks every 0.5 seconds, inspect the
indoor/outdoor unit connecting wire A for mis-wiring.
2 Press it once more, and the EMERGENCY HEAT MODE starts.
3 Press it once more, and the operation stops.
(The operation mode changes in order of 1 ~ 3 every time the EMERGENCY
OPERATION switch is pressed.)
Operation Indicator lamp
Mode
COOL
1
2
3
• In starting the heating operation, indoor unit fan may not operate to prevent blowing
cool air. Please wait for a few minutes until the temperature of heat exchanger rises
and warm air blows out.
(Light) (Off)
HEAT
(Off) (Light)
STOP
(Off) (Off)
EMERGENCY
OPERATION switch
MS type and MSH type
Checking the remote (infrared) signal reception
Press the ON/OFF button on the remote controller and check that an electronic sound is
heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.
If the indoor unit is operated with the remote controller, both the test
run and the emergency operation are released by commands from
the remote controller.
• Once the compressor stops, the restart preventive device operates so the compressor
will not operate for three minutes to protect the air conditioner.
6-6 EXPLANATION TO THE CUSTOMER
• Using the OPERATING INSTRUCTIONS, explain the following to the customer, how
to control temperature, how to remove the air fi lters, how to remove or put the remote
controller in the remote controller holder, how to clean, precautions for operation, etc.
• Recommend the customer to read the OPERATING INSTRUCTIONS carefully.
7. FOR MOVEMENT AND MAINTENANCE
7-1
REMOVING AND REINSTALLING THE FRONT PANEL
FRONT PANEL REMOVAL
4 Release the hooks.
Hold this concave section and pull the bottom
1 Remove the screw caps.
2 Remove three screws.
FRONT PANEL REINSTALLATION
Note:
Do not open the front panel up beyond the level position.
The panel may come off in order to prevent it from being damaged.
1 Set the horizontal vane to the position as below before reinstalling the front
panel.
1 Point the
horizontal
vane slightly
downward.
2 Attach the bottom of the front panel under the horizontal vane.
3 Fit in the top of the front panel.
4 Fit in the bottom of the front panel and tighten it using screws.
5 Push the section of the front panel marked by the arrow and fi t the panel into the
air conditioner.
forward to remove the front panel.
3 Pull the bottom.
5 Push
Horizontal vane
3
24
7-3 GAS CHARGE
1 Connect gas cylinder to the service port of stop valve (3-way).
2 Execute air purge of the pipe (or hose) coming from refrigerant gas cylinder.
3 Replenish specifi ed amount of the refrigerant, while operating the air conditioner
for cooling.
Note:
In case of adding refrigerant, comply with the quantity specifi ed for the refrigerating
cycle.
CAUTION
O
Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation,
reinstallation, or repairs to the refrigerant circuit.
O
When charging the refrigerant system with additional refrigerant, be sure
to use liquid refrigerant.
Adding gas refrigerant may change the composition of the refrigerant in the
system and affect normal operation of the air conditioner. Also, charge the
system slowly, otherwise the compressor will be locked.
To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm
water (under 40°C) during cold season. But never use naked fi re or steam.
Indoor unit
Refrigerant gas
cylinder
operating valve
Union
Liquid pipe
Gas pipe
Gauge manifold
valve (for R410A)
Charge hose (for R410A)
Refrigerant gas cylinder
for R410A with siphon
Refrigerant (liquid)
Electronic scale for
refrigerant charging
Stop valve
Outdoor unit
Service port
7-2 REMOVING THE INDOOR UNIT
Remove the bottom of the indoor unit from the installation plate.
1 Remove the front panel. (See FRONT PANEL REMOVAL shown above.)
2 Insert fl at screwdrivers into the square holes at the left and right bottom of the indoor
unit and push them up; the bottom of the indoor unit goes down and the hooks are
released.
Push
Go down
Square hole
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODAKU, TOKYO
100-8310, JAPAN
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.