Installation Manual |
|
7175000G |
|
|
|
|
||
|
|
|
|
|
S30 - Series Builders Series Sump Pump
*Do not throw away or lose this manual.
Contents
1.) General Information
2.) Sump Pit
3.) Installation
4.) Operation
5.) Maintenance and Troubleshooting
IMPORTANT:
Prior to installation, record Model, Serial Number, and Code Number from pump nameplate for future reference.
MODEL ________________________
SERIAL ______________________
CODE ______________________
INSTALLATION
DATE _______________________
7000 Apple Tree Avenue Bergen, NY 14416 Phone: (800) 543-2550 Fax: (585) 494-1839 www.libertypumps.com
Models
S35M Manual Pump, No Switch
S37 Automatic Pump,
Vertical Switch
S37-P Automatic Pump, Piggy-Back
Vertical Switch
S38 Automatic Pump,
Wide Angle Switch
©Copyright 2016 Liberty Pumps Inc. All rights reserved
1. General Information
Before Installation, read the following instructions carefully. Each Liberty pump is individually factory tested to assure proper performance. By closely following these instructions, potential operating problems should be eliminated, providing years of trouble-free service.
Risk of electric shock. Always disconnect the pump from the power source before handling or making adjustments.
The electrical connections and wiring for a pump installation should only be made by qualified personnel.
This pump is supplied with a grounding conductor and grounding-type attachment plug. To reduce the risk of electric shock, be certain that it is connected only to a properly grounded, grounding-type 15 Amp receptacle.
Always wear rubber boots when water is on the floor and you must unplug the pump.
DO NOT bypass grounding wires or remove ground prong from attachment plugs.
DO NOT use an extension cord.
This pump requires a separate, properly fused and grounded branch circuit. Make sure the power source is properly sized for the voltage and amperage requirements of the pump, as noted on the nameplate.
The electrical outlet shall be within the length limitations of the pump power cord, and at least 4 feet above floor level to minimize possible hazards from flood conditions.
The installation must be in accordance with the National Electric Code, Uniform Plumbing Code, International Plumbing Code, as well as all applicable local codes and ordinances.
Sump and sewage pumps often handle materials which could cause illness or disease. Wear adequate protective clothing when working on a used pump or piping.
Keep clear of suction and discharge openings. To prevent injury, never insert fingers into pump while it is plugged in.
DO NOT use this product for flammable or corrosive liquid.
DO NOT use this product in applications where human contact with the pumped fluid is common (such as swimming pools, fountains, etc.)
NEVER dispose of materials such as paint thinner or other chemicals down drains, as they can chemically attack and damage pump components, potentially causing product malfunction or failure.
DO NOT use pumps in water over 140 F (60 C).
DO NOT use pumps in mud, sand, cement, oil or chemicals.
DO NOT modify the pump in any way.
DO NOT lift or carry pump by power cord.
DO NOT remove any tags from pump or cords.
If pump is installed during construction before power is available, it must be protected from the environment to prevent water from entering through the cord plug end, etc.
2. Sump Pit
A sump pit not less than 14” in diameter is recommended. A larger diameter pit is preferred as it allows for longer pump cycling and reduced switch cycling. The minimum depth of the pit should be 18”.
The bottom of the pit should be a solid level of bricks or concrete. DO NOT place the pump directly on earth, gravel or debris since this can cause excessive wear of the impeller and possible jamming. “The Brick” (sold by Liberty Pumps as part # 4445000) is a pre-molded stable platform designed to fit your submersible pump. It raises the pump 2.75” off the bottom of the pit, reducing the potential for jamming from rocks and debris. Contact your local distributor to order. Remove all debris from the bottom of the sump pit before installation of the pump. A sump pit cover is suggested for safety and to prevent foreign objects from entering the pit.
©Copyright 2016 Liberty Pumps Inc. All rights reserved |
2 |
3. Installation
A.) Removal of the old pump (NOTE: Disconnect pump from power source before handling): Separate the discharge pipe at either the check valve or at the union. If neither a check valve nor a union is part of the existing discharge pipe, cut the pipe with a hacksaw and remove the pump (A union or check valve will need to be installed at this cut).
B.) The discharge size is 1-1/2” NPT Do not reduce the discharge size to less than 1-1/4”, as this will affect pump flow and performance. Schedule 40 PVC pipe is recommended; however, flexible discharge hose kits may be used for temporary installations.
C.) Connect the pipe or the discharge hose to the discharge of the pump. HAND TIGHTEN ONLY, over-tightening can damage the pump discharge.
D.) Install a union or other means of separating the discharge pipe just above the floor to facilitate removal of the pump if necessary. A check valve is recommended just above or in place of the union to prevent the back-flow of water after each pump cycle.
E.) Connect additional pipe as necessary to direct the discharge to the desired location. Discharge should be kept as short as possible with a minimum number of turns.
F.) Model S37, S37-P and S38: When placing the pump in the basin assure that float switch has adequate clearance in pit and will not interfere with side wall.
G.) For added protection, consider the addition of a back-up pump such as Liberty’s SJ10 SumpJet, as well as an alarm such as Liberty’s ALM-2 in applications where loss of pump function could result in property damage. If an alarm is used, it must be connected to a separate electrical circuit.
4. Operation
A separate branch circuit, properly fused and grounded, should be provided to the pump. Make sure the power source is properly sized for the voltage and amperage requirements of the motor as noted on the pump nameplate. If electrical receptacle is corroded or worn it should be replaced to ensure reliable operation of the pump. The electrical outlet or panel shall be within the length limitations of the pump power cord and at least 4 feet above floor level to minimize possible hazards from flood conditions. Check to make sure installation is in accordance with the National Electric Code and all applicable local codes and ordinances. Wiring extended over greater distances must be in accordance with NEC requirements. DO NOT USE AN EXTENSION CORD.
Models S37 and S37-P have an integrated vertical float switch. The turn off position can be adjusted by sliding a rubber grommet up or down the length of the float rod.
©Copyright 2016 Liberty Pumps Inc. All rights reserved |
3 |
Models S37-P and S38 are automatic pumps which come with two cords - one for the switch and the other for the pump motor. The switch cord has a series (piggyback) plug enabling the pump (motor) cord to be plugged into the back of it. The purpose of this design is to allow manual operation of the pump separate from the switch if necessary.
For automatic operation using the supplied switch, the two cords should be interconnected and plugged into a separately fused, grounded outlet of proper amp capacity for your pump model. Both cords are equipped with 3-prong plugs and must be properly plugged into a properly grounded 3-wire receptacle. DO NOT REMOVE THE GROUND PRONGS.
For manual operation, or in the event of switch failure, the pump cord can be separated and plugged directly into the electrical outlet, bypassing the switch. The unit can be operated by directly plugging the pump cord (from the motor) into an approved electrical outlet. To prevent excessive seal wear and overheating, the pump should not be run dry for extended periods of time. A minimum 2-1/2” water level is recommended.
DON’T |
DO |
TEMPORARY |
|
MANUAL OPERATION |
|||
|
|||
|
|
5. Maintenance and Troubleshooting
WARNING: ALWAYS DISCONNECT THE PUMP FROM THE POWER SOURCE BEFORE HANDLING. The guide on the following page is designed to help identify reasons for potential operating problems. It is not a service guide. Dismantling of the pump voids the warranty. Servicing of the pump other than simple cleaning of the pump inlet or impeller should be referred to the factory or its authorized service centers. NOTE: The manufacturer assumes no responsibility for damage or injury due to disassembly in the field.
©Copyright 2016 Liberty Pumps Inc. All rights reserved |
4 |
Troubleshooting Table:
|
Problem |
|
|
Cause |
|
|
Correction |
|
||
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
||
Pump will not run |
|
Blown fuse or other |
|
If blown, replace with properly sized fuse or reset |
||||||
|
|
interruption of power; improper |
|
|
breaker; if voltage is under 108V, check wiring size. |
|||||
or hum. |
|
|
|
|
||||||
|
|
voltage. |
|
|
Remove extension cord if connected. |
|||||
|
|
|
|
|
|
|
||||
|
|
|
|
Water level in pit may be too |
|
Add more water to the pit. |
||||
|
|
|
|
|
low to activate switch. |
|
|
|
|
|
|
|
|
|
Plug on power cord may not |
|
Check security and connection. If receptacle is |
||||
|
|
|
|
|
be making contact in |
|
|
corroded, have it replaced by a certified electrician. |
||
|
|
|
|
|
receptacle. |
|
|
|
|
|
|
|
|
|
Piggyback plugs may not be |
|
Tighten connection of plugs. |
||||
|
|
|
|
|
connected tightly together. |
|
|
|
|
|
|
|
|
|
Switch is defective Model S38 |
|
Verify that water level is at least 4” above pump. To |
||||
|
|
|
|
|
only. |
|
|
test the switch, plug the power cord directly in to the |
||
|
|
|
|
|
|
|
|
|
electrical receptacle bypassing the piggyback plug. If |
|
|
|
|
|
|
|
|
|
|
pump operates, then the switch needs replacement. |
|
|
|
|
|
|
|
|
|
|
(See Switch-Servicing procedures on page 5). |
|
|
|
|
|
Motor winding may be open. |
|
|
Consult factory. |
|||
|
|
|
|
Float switch obstructed Models |
|
The float must be free to move unobstructed – if |
||||
|
|
|
|
|
S37 and S38. |
|
|
bound remove debris or position pump to prevent |
||
|
|
|
|
|
|
|
|
|
float from rubbing on side wall of sump. |
|
Pump runs or |
|
Check valve may be installed |
|
Make sure it’s installed properly and flapper in valve |
||||||
|
|
backwards or is defective. |
|
|
is free to move. |
|||||
hums but does |
|
|
|
|
||||||
not remove |
|
|
Discharge line may be blocked |
|
Make sure line doesn’t pass through cold areas or |
|||||
water. |
|
|
or frozen. |
|
|
isn’t blocked. |
||||
|
|
|
|
Vertical lift is beyond pump’s |
|
If possible, try to reduce the discharge head to a |
||||
|
|
|
|
|
capability. |
|
|
lower height. |
||
|
|
|
|
Inlet screen of pump is |
|
Remove the pump screen and clean inlet and |
||||
|
|
|
|
|
plugged or the impeller is |
|
|
impeller. |
||
|
|
|
|
|
jammed. |
|
|
|
|
|
Pump runs and |
|
Switch is defective or |
|
Make sure switch is free from obstruction or replace |
||||||
|
|
obstructed. |
|
|
switch. |
|||||
removes water |
|
|
|
|
||||||
but does not shut |
|
|
Pump has met or exceeded its |
|
|
Route discharge piping to a lower level. If this isn’t |
||||
off. |
|
|
maximum lift. |
|
|
possible then a larger pump may be required. |
||||
Pump runs but |
|
Vertical lift is approaching |
|
If possible, try to reduce the discharge head to a |
||||||
|
|
pump’s maximum lift capability |
|
|
lower height. |
|||||
removes very |
|
|
|
|
||||||
|
|
of 27’. |
|
|
|
|
||||
little water. |
|
|
|
|
|
|
||||
|
|
|
|
|
Pump’s inlet is partially |
|
Remove volute and make sure inlet is clear of debris. |
|||
|
|
|
|
|
blocked. |
|
|
|
|
|
|
|
|
|
Discharge line is partially |
|
|
Remove blockage. |
|||
|
|
|
|
|
blocked. |
|
|
|
|
|
|
|
|
|
Check valve is not opening all |
|
Remove blockage or make sure check valve is not |
||||
|
|
|
|
|
the way. |
|
|
defective. |
||
Circuit breaker |
|
Fuse or breaker is too small. |
|
A 15-amp breaker should be used. |
||||||
|
|
|
|
|
|
|
|
|||
trips or fuse |
|
|
|
|
|
|
|
|
||
|
|
Other major appliance is on |
|
Pump should be on its own circuit. |
||||||
blows when |
|
|
||||||||
|
|
the same circuit. |
|
|
|
|
||||
pump starts. |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|||
|
|
Pump is connected to an |
|
Have an electrician check for proper wiring. |
||||||
|
|
|
|
|
||||||
|
|
|
|
|
extension cord or wiring is |
|
|
|
|
|
|
|
|
|
|
inadequate. |
|
|
|
|
|
|
|
|
|
Defective motor or switch. |
|
|
Consult factory. |
|||
|
|
|
|
|
|
|
|
|
|
|
©Copyright 2016 Liberty Pumps Inc. All rights reserved |
5 |
6.3 Year Limited Warranty
Liberty Pumps, Inc. warrants that pumps of its manufacture are free from all factory defects in material and workmanship for a period of 3 years from the date of purchase. The date of purchase shall be determined by a dated sales receipt noting the model and serial number of the pump. The dated sales receipt must accompany the returned pump if the date of return is more than 3 years from the "CODE" (date of manufacture) number noted on the pump nameplate.
The manufacturer's obligation under this Warranty shall be limited to the repair or replacement of any parts found by the manufacturer to be defective, provided the part or assembly is returned freight prepaid to the manufacturer or its authorized service center, and provided that none of the following warranty-voiding characteristics are evident.
The manufacturer shall not be liable under this Warranty if the product has not been properly installed; if it has been disassembled, modified, abused or tampered with; if the electrical cord has been cut, damaged or spliced; if the pump discharge has been reduced in size; if the pump has been used in water temperatures above the advertised rating, or water containing sand, lime, cement, gravel or other abrasives; if the product has been used to pump chemicals or hydrocarbons; if a non-submersible motor has been subjected to excessive moisture; or if the label bearing the serial, model and code number has been removed. Liberty Pumps, Inc. shall not be liable for any loss, damage or expenses resulting from installation or use of its products, or for consequential damages, including costs of removal, reinstallation or transportation.
There is no other express warranty. All implied warranties, including those of merchantability and fitness for a particular purpose, are limited to three years from the date of purchase.
This Warranty contains the exclusive remedy of the purchaser, and, where permitted, liability for consequential or incidental damages under any and all warranties are excluded.
7000 Apple Tree Avenue
Bergen, NY 14416 Phone: (800) 543-2550 Fax: (585) 494-1839 www.libertypumps.com
©Copyright 2016 Liberty Pumps Inc. All rights reserved |