Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Ceilling Concealed Duct
MFL67206507
Rev.06_111419
www.lghvac.com
www.lg.com
Copyright © 2013 - 2019 LG Electronics Inc. All Rights Reserved.
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
ENGLISH
TIPS FOR SAVING ENERGY
2
TIPS FOR SAVING ENERGY
3
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation of all field wiring and components MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code 70 and the National Building Construction and Safety Code or Canadian Electrical code and National Building Code of Canada.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Always perform grounding. - Otherwise, it may cause electrical shock.
• For installation of the product, always contact the service center or a professional installation agency. -
Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board. - No installation may cause a fire and
electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner. - Otherwise, it may cause a
fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly. - It will cause a fire or electrical shock.
• Do not install the product at a place that there is concern of falling down. - Otherwise, it may result in
personal injury.
• Use caution when unpacking and installing. - Sharp edges may cause injury.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or
Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion. There is the risk of death, injury, fire or explosion.
!
ENGLISH
SAFETY INSTRUCTIONS
WARNING
This indicates that the failure to follow the instructions can cause serious injury or death.
CAUTION
This indicates that the failure to follow the instructions can cause the minor injury or damage to the product.
This symbol is displayed to indicate matters and operations that can cause risk. Read the part with this symbol carefully and follow the instructions in order to avoid risk.
!
!
!
SAFETY INSTRUCTIONS
The following safety guidelines are intended to prevent unforeseen risks or damage from unsafe or incorrect operation of the appliance. The guidelines are separated into ‘WARNING’ and ‘CAUTION’ as described below.
• Consult your lacal dealer regarding what to do in case of refrigerant leakage. When the air conditioner is to be installed in a small room, it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage. Otherwise, this may lead to an accident due to oxygen depletion.
• Carry out the specified installation work after taking into account earthquakes. Failure to do so during installation work may result in the unit falling and causing accidents.
• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws and regulations and this installation manual. An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
• Be sure to switch off the unit before touching any electrical parts.
• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal connections or wires.
• If refrigerant gas leaks during installation, ventilate the area immediately. Toxic gas may be produced if the refrigerant gas comes into contact with fire.
• Make sure to be materials in a compartment handling air for circulation through a duct supplying only one room.
Operation
• Unplug the unit if strange sounds, smell, or smoke comes from it. - Otherwise, it may cause electrical shock or a fire.
• Keep the flames away. - Otherwise, it may cause a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands. ­Otherwise, it may cause a fire or electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation. - Otherwise, it may electrical shock and failure.
• Do not allow water to run into electrical parts. - Otherwise, it may cause the failure of machine or electrical shock.
• Never touch the metal parts of the unit when removing the filter. - They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it. - It may cause an injury through dropping of the unit or falling down.
• When the product is submerged into water, always contact the service center. - Otherwise, it may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit. - Otherwise, children may be seriously injured due to falling down.
CAUTION
Installation
• Install the drain hose to ensure that drain can be securely done. - Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors. - Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product. - Otherwise, it may cause the failure of product.
• Keep level parallel in installing the product. - Otherwise, it may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes. - Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent. - The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles. - Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet. - Otherwise, it may cause the failure of appliance or an accident.
!
ENGLISH
SAFETY INSTRUCTIONS
4
ENGLISH
5
2 TIPS FOR SAVING ENERGY 3 SAFETY INSTRUCTIONS 6 INSTALLATION PARTS 7 INSTALLATION
8 Ceiling dimension and hanging bolt location 9 Indoor Unit Installation 11 Air Filter 12 Checking the Drainage 13 Indoor Unit Drain Piping 14 Combination indoor units 15 Flaring work 16 Connection of piping - Indoor, Outdoor, BD Unit 17 Plumbing materials and storage methods 19 Indoor Unit Drain Piping 19 Drain test 20 Heat insulation 20 Wiring Connection 20 Connection method of the connecting cable(Example)
24 REMOTE CONTROLLER INSTALLATION
26 Wired remote controller installation
27 HOW TO SET E.S.P?
27 Installer Setting - E.S.P.
29 SELF-DIAGNOSIS FUNCTION 29 DIP SWITCH SETTING
TABLE OF CONTENTS
TABLE OF CONTENTS
6
ENGLISH
INSTALLATION PARTS
INSTALLATION PARTS
* Screws for fixing panels are attached to decoration panel.
Air outlet vents
Air filters
Control box
Air intake vents
Air filters
Air intake vents
Air outlet vents
Remote Controller
Air inlet vents
Air outlet vents
(Accessory)
Name Drain hose Clamp metal
Washer for
hanging bracket
Clamp
(Tie Wrap)
Insulation for
fitting
Quantity 1 EA 2 EA 8 EA 4 EA 1 set
Shape
for gas pipe
for liquid pipe
ENGLISH
7
INSTALLATION
Install the air conditioner in the location that satisfies the following conditions.
- The place shall easily bear a load exceeding four times the indoor unit’s weight.
- The place shall be able to inspect the unit as the figure.
- The place where the unit shall be leveled.
- The place shall easily connect with the outdoor unit.
- The place where the unit is not affected by an electrical noise.
- The place where air circulation in the room will be good .
- There should not be any heat source or steam near the unit
Confirm the positional relationship between the unit and suspension bolts.
- Installation the ceiling opening to clean the filter or service under the product.
[Unit:mm(inch)]
A(Min)
Ceiling
Service Space
A
B
B(Min)
H=20 (25/32) or more
• Suitable dimension "H" is necessary to get a slope to drain as shown in the figure
Side view [Unit: mm(inch)]
Air outlet
Inspection hole
600 x 600
(23-5/8 x 23-5/8)
Control box
600
(23-5/8)
600
(23-5/8)
Top view [Unit: mm(inch)]
Air outlet
Indoor unit
Capacity (kBtu/h)
A B
9
800 (31-1/2) 800 (31-1/2)
12/18
800 (31-1/2) 1 000 (39-3/8)
INSTALLATION
Make sure to be materials in a compartment handling air for circulation through a duct supplying only one room.
WARNING
!
Top view
Inspection hole
600(23-5/8) X 600(23-5/8)
Control box
600(23-5/8) 600(23-5/8)
Front view
(unit: mm(inch))
1 000
(39-3/8)
Front
20(25/32) or more
8
INSTALLATION
ENGLISH
Ceiling dimension and hanging bolt location
Installation of Unit Install the unit above the ceiling correctly.
- Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
- Apply a filter Accessory at air return hole.
<TYPE A/D> <TYPE B/C>
[Unit:mm(inch)]
C
E
G
D
F
I
A
J
B
H
Drainage hole
9 k 12 k / 18 k 24 k / 36 k 24 k 36 k 24 k 36 k
Model
AMNW**GL*A*
(TYPE A)
AMNW**GBGA0
(TYPE B)
ABNH**GGLA2
(TYPE C)
AMNW**GM*A0
(TYPE D)
A
733 (28-17/20) 933 (36-37/50) 1 232 (48-1/2) 1 232 (48.5) 1 290(50.8) 933.4 (36-3/4)
1 283.4 (50-17/32)
B
772 (30-2/5) 972 (38-13/50) 1 182 (46-17/32) 1 182 (46.5) 1 230(48.4) 971.6 (38-1/4) 1 321.6 (52-1/32)
C
628 (24-18/25) 628 (24-18/25) 355 (13-31/32) 355 (14) 477(18.8) 619.2 (24-3/8) 619.2 (24-3/8)
D
700 (27-11/20) 700 (27-11/20) 45.5 (1-25/32) 45.5 (1.8) 56(2.2) 700 (27-9/16) 700 (27-9/16)
E
36 (1-2/5) 36 (1-2/5) 450 (17-23/32) 450 (17.7) 590(23.2) 30 (1-3/16) 30 (1-3/16)
F
190 (7-12/25) 190 (7-12/25) 30 (1-3/16) 30 (1.2) 30(1.2) 270 (10-5/8) 270 (10-5/8)
G
20 (25/32) 20 (25/32) 87 (3-7/16) 87 (3.4) 120(4.7) 15.2 (19/32) 15.2 (19/32)
H
660 (25-49/50) 860 (33-17/20) 830 (32-11/16) 830 (32.7) 1 006(39.6) 858 (33-25/32) 1 208 (47-9/16)
I
155 (6-1/10) 155 (6-1/10) 186 (7-5/16) 186 (7.3) 294(11.6) 201.4 (7-15/16) 201.4 (7-15/16)
J
700 (27-11/20) 900 (35-11/25) 298 (11-23/32) 298 (11.7) 380(15) 900 (35-7/16) 1 250 (49-7/32)
Capacity (kBtu/h)
Dimension
POSITION OF SUSPENSION BOLT
h Install the unit leaning to a drainage hole side as a figure for easy water drainage.
Drainage hole
A
B
CD
(G)
EF
Inspection Port
Indoor Unit
Ceiling
Canvas Duct
Air Intake Port
Ceiling Board
Ceiling Board
Air Discharge Port
Discharge Duct
Intake Duct
body
filter
Joint canvas Main duct
H
I
J
INSTALLATION
ENGLISH
9
Indoor Unit Installation
M10 Nut
M10 washer
X 4
X 4
M10 Nut
M10 washer
X 4
X 8
- A place where the unit will be leveled and that can support the weight of the unit.
- A place where the unit can withstand its vibration.
- A place where service can be easily performed.
POSITION OF CONSOLE BOLT
1 Set anchor
Old building New building
2 Plate washer 3 Spring washer
4 Nut
5 Suspension bolts
- Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
- Mount the suspension bolts to the set anchor firmly.
- Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
- Select and mark the position for fixing bolts.
- Drill the hole for set anchor on the face of ceiling.
• Local supply
Set anchorPlate washer - M10Spring washer - M10Nut - W3/8 or M10Suspension bolt - W3/8 or M10
CAUTION
Tighten the nut and bolt to prevent unit falling.
!
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local supply)
X 4
<TYPE A/D>
<TYPE B/C>
10
INSTALLATION
ENGLISH
1 Install declination of the indoor unit is very important for the drain of the duct type air
conditioner.
2 Minimum thickness of the insulation for the connecting pipe shall be 5 mm(3/16 inch).
• Always lay the drain with downward inclination (1/100 to 1/50). Prevent any upward flow or reverse flow in any part.
• 10 mm or thicker formed thermal insulator shall always be provided for the drain pipe.
• Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.
• Upward routing not allowed
Lay the drain hose with a downward inclination so water will drain out.
• The unit must be declined to the drain hose connected when finished installation.
Front of view
CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING
Ceiling
1/100~1/50
Drainage hole
Drainage hole
CORRECT
INCORRECT
Drainage holeMake sure to be closed.
Unit
Drainage pipe (Local supply)
Thermal insulator
(Local supply)
CORRECT
INCORRECT
Applied U-Trap Dimension
CAUTION
!
U-Trap
B
C
A ≥ 70 mm(2-3/4 inch) B ≥ 2C C ≥ 2 x SP SP = External Pressure
(mmAq(inAq))
Ex) External Pressure
= 10 mmAq (0.39 inAq) A ≥ 70 mm(2-3/4 inch)
40 mm(1-9/16 inch) 20 mm(25/32 inch)
B ≥ C ≥
A