Legrand AL3356-ACTLPB User Manual

Page 1
AL3300 RACEWAY CABLE FILL CAPACITIES FOR DATA/COMMUNICATION
OD W/O Divider W/Offset Divider W/Half Divider
CABLE/WIRE SIZE [In.] [mm] (4.75 sq. in.) (.95 sq. in.) (2.08 sq. in.)
20%* 40%** 20%* 40%** 20%* 40%**
UNSHIELDED 4-pair, 24 AWG, Cat.5 0.220 [5.6] 24 49 4 9 10 21 TWISTED PAIR 4-pair, 24 AWG, Cat.3 0.190 [4.8] 33 67 6 13 14 29
4-pair, 24 AWG, Cat.6 0.250 [6.3] 19 38 3 7 8 16
TELEPHONE 2-pair, 24 AWG 0.140 [3.6] 61 123 12 24 27 54
25-pair, 24 AWG 0.410 [10.4] 7 14 1 2 3 6
COAXIAL RG58/U 0.195 [5.0] 31 63 6 12 13 27
RG59/U 0.242 [6.1] 20 41 4 8 9 18 RG62/U 0.242 [6.1] 20 41 4 8 9 18 RG6/U 0.270 [6.9] 16 33 3 6 14
TWINAXIAL 100 Ohm 0.330 [8.4] 11 22 2 4 4 9
SHIELDED Type 1 0.390 [9.9] 7 15 1 3 3 6 TWISTED PAIR Type 2 0.465 [11.8] 5 11 1 2 2 4
Type 3 0.245 [6.2] 20 40 4 8 8 17
FIBER OPTIC Two Standard (Duplex) 0.190 [4.8] 33 67 6 13 14 29
Multimedia, 62.5/125 um
AL3300 Aluminum Surface Raceway
INSTALLATION INSTRUCTIONS
Installation Instruction No.: INST014 R2 – Updated April 2005
NOTE:* 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict
cross sectional area.
** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.
Wiremold Electrical Systems conform with, and should be installed and properly grounded in compliance with requirement of the current National Electrical Code or codes administered by local authorities.
All electrical products may represent a possible shock or fire hazard if improperly installed or used. Wiremold electrical products are UL list­ed, made for interior use and should be installed by qualified electrical people in conformance with current local and/or the National Electrical Code.
Note: Raceway may be configured in single or multiple channels
to accommodate power or communications wiring.
MAXIMUM CROSS SECTION
2 7/8"
[70mm]
1 7/8"
[48mm]
AL3300 RACEWAY WIRE FILL CAPACITIES FOR POWER
CAPACITY OF CROSS SECTIONAL AREA
WITH OFFSET WITHOUT WITH HALF WITHOUT
DIVIDER OFFSET DIVIDER DIVIDER HALF DIVIDER
WIRE TYPE 6 AWG 10 24 17 33 THWN/THHN 8 AWG 14 33 23 47
10 AWG 28 66 47 95 12 AWG 44 104 74 150 14 AWG 60 140 99 202
Page 2
AL3300B BASE
AL3301 COUPLING
AL3309 GROUND CLAMP
AL3300 SYSTEM PRODUCT APPLICATION
At AL3300B base section butt joints, slide AL3301 Coupling into first base section. Mount next base to surface. Center coupling on joint. Tighten locking screws.
To attach AL3300B Series base sections to mounting surface. Drill 9/32" holes in the base (approx. 48" o.c.). Fasten base with #8 flat head screws.
1. Provide electrical feed through 1/2" or 3/4" trade size K.O.’s in at AL3310B1 end.
2. Attach base section to mounting surface by drilling 9/32" holes in base then fastening with #8 flat head.
3. Secure conductors in place with AL3300WC Wire Clips.
4. Join additional raceway sections with AL3301 Coupling.
5. Close end with either AL3310B or AL3310B1 End Fitting.
6. Snap cover into base to complete installation.
Position AL3309 Ground clamp into rib in AL3300B raceway Base. Tighten locking screw. Attach ground wire using brass cup washer and green hex nut to ground lug.
AL3300 SERIES DEVICE PLATES
AL3300D SERIES DIVIDER
For AL3346 and AL3356 Series Device Plates, install wiring to devices as required. Attach device to plate using #6 screws and "keep" nuts (provided). Snap device plate onto AL3300B raceway base.
Position AL3300D Divider into AL3300B raceway base as shown. See cross sections below and refer to wire fill charts.
48"
[1219mm]
2
1
5
DIVIDER AND DIVIDER
CLIPS (OPTIONAL)
OPTIONAL
DIVIDER
SECTION A-A
DEVICE PLATE
A
A
B
B
C
C
SECTION B-B SECTION C-C
4
3
6
Page 3
OR
Y
Y
X
AL3310B FEED END FITTING AL3310B BLANK END FITTING
K.O. REMOVAL
To remove only 1/2" trade size KO apply pressure or light impact at "X" location. To remove 3/4" trade size KO apply pressure or light impact at "Y" location.
At end of AL3300B raceway run, slide AL3310B Blank End fitting in last base section. Secure in place by tightening two #8-32 screws.
Page 4
AL3311 90° FLAT ELBOW AL3317 INTERNAL ELBOW
AL3315 TEE FITTING
AL3318 EXTERNAL ELBOW
AL3300WC WIRE CLIP
At 90° turn , position AL3311 Flat Elbow at end of AL3300B base. Position next bases section onto other end of AL3311. Center couplings over base joints and tighten screws. Install fitting cover after wiring.
Install AL3317 to raceway base BEFORE mounting raceway base. Fasten base section to surface joints, tighten setscrews. Install fitting cover after wiring.
AL3315 Tee Fitting, position fitting at end of AL3300B base. Install other base section to other end of fitting. Center couplings on joints and tighten screws. Install fitting cover after wiring.
At 90° outside corner, position AL3318 External Elbow at end of the fitting. Center couplings on joints and tighten screws. Install fitting cover after wiring.
For retaining wires in long raceway runs, snap-in AL3300WC Wire Clip approx. 30" apart into AL3300B Base.
Wiremold / Legrand
U.S. and International: 60 Woodlawn Street • West Hartford, CT 06110 1-800-621-0049 • FAX 860-232-2062 • Outside U.S. 860-233-6251 Canada: 570 Applewood Crescent • Vaughan, Ontario L4K 4B4 1-800-723-5175 • FAX 905-738-9721
INST014 R2 – Updated April 2005 – For latest specs visit www.wiremold.com
© Copyright 2005 The Wiremold Company All Rights Reserved
AL3316 CROSS FITTING
AL3316 cross Fitting, position fitting at end of AL3300B base. Install other base sections to other ends of the fitting. Center couplings on joints and tighten screws. Install fitting cover after wiring.
Loading...