KROHNE WATERFLUX 3000 Operating Manual

Page 1
Handbook
Handbook
WATERFLUX 3000
WATERFLUX 3000
WATERFLUX 3000WATERFLUX 3000
HandbookHandbook
Electromagnetic flow sensor
The documentation is only complete when used in combination with the relevant documentation for the signal converter.
© KROHNE 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 2
:
IMPRINT
:::::::::::::::::::::::::::::::::::::::
Subject to change without notice.
Copyright 2018 by KROHNE Messtechnik GmbH - Ludwig-Krohne-Str. 5 - 47058 Duisburg (Germany)
2
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 3
WATERFLUX 3000
CONTENTS
1 Safety instructions 5
1.1 Intended use ..................................................................................................................... 5
1.2 Certification ...................................................................................................................... 5
1.3 Safety instructions from the manufacturer ..................................................................... 6
1.3.1 Copyright and data protection ................................................................................................ 6
1.3.2 Disclaimer............................................................................................................................... 6
1.3.3 Product liability and warranty ................................................................................................ 7
1.3.4 Information concerning the documentation........................................................................... 7
1.3.5 Warnings and symbols used................................................................................................... 8
1.4 Safety instructions for the operator................................................................................. 8
2 Device description 9
2.1 Scope of delivery............................................................................................................... 9
2.2 Device description .......................................................................................................... 10
2.3 Nameplate (example) ..................................................................................................... 11
3 Installation 12
3.1 General notes on installation ......................................................................................... 12
3.2 Storage ........................................................................................................................... 12
3.3 Transport ........................................................................................................................ 12
3.4 Pre-installation requirements ....................................................................................... 13
3.5 General requirements.................................................................................................... 13
3.5.1 Vibrations .............................................................................................................................. 13
3.5.2 Magnetic field........................................................................................................................ 13
3.6 Installation conditions ....................................................................................................14
3.6.1 Inlet and outlet...................................................................................................................... 14
3.6.2 T-section ............................................................................................................................... 14
3.6.3 Open discharge ..................................................................................................................... 14
3.6.4 Bends .................................................................................................................................... 15
3.6.5 Pump ..................................................................................................................................... 15
3.6.6 Control valve ......................................................................................................................... 16
3.6.7 Air venting and vacuum forces ............................................................................................. 16
3.6.8 Mounting position.................................................................................................................. 17
3.6.9 Flange deviation.................................................................................................................... 17
3.7 IP 68 ................................................................................................................................ 18
3.8 Mounting......................................................................................................................... 19
3.8.1 Torques and pressures......................................................................................................... 19
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
3
Page 4
CONTENTS
WATERFLUX 3000
4 Electrical connections 22
4.1 Safety instructions.......................................................................................................... 22
4.2 Grounding ....................................................................................................................... 22
4.3 Connection diagrams ..................................................................................................... 22
5 Service 23
5.1 Spare parts availability...................................................................................................23
5.2 Availability of services .................................................................................................... 23
5.3 Returning the device to the manufacturer..................................................................... 23
5.3.1 General information.............................................................................................................. 23
5.3.2 Form (for copying) to accompany a returned device............................................................ 24
5.4 Disposal .......................................................................................................................... 24
6 Technical data 25
6.1 Measuring principle........................................................................................................25
6.2 Technical data................................................................................................................. 26
6.3 Legal metrology.............................................................................................................. 31
6.3.1 MID Annex III (MI-001)........................................................................................................... 31
6.3.2 Verification to MI-001............................................................................................................ 33
6.4 Measurement accuracy.................................................................................................. 34
6.4.1 WATERFLUX 3050, 3100 and 3300 without straight inlet and outlet sections..................... 35
6.5 Dimensions and weights ................................................................................................ 36
6.6 Pressure loss.................................................................................................................. 40
7 Notes 41
4
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 5
WATERFLUX 3000
1.1 Intended use
CAUTION!
Responsibility for the use of the measuring devices with regard to suitability, intended use and corrosion resistance of the used materials against the measured fluid lies solely with the operator.
INFORMATION!
The manufacturer is not liable for any damage resulting from improper use or use for other than the intended purpose.
This electromagnetic flowmeter is designed exclusively to measure the flow of drinking water, raw water and irrigation water.
WARNING!
If the device is not used according to the operating conditions (refer to chapter Technical data), the intended protection could be affected.
1.2 Certification
SAFETY INSTRUCTIONS
1
CE marking
The manufacturer certifies successful testing of the product by applying the CE marking.
This device fulfils the statutory requirements of the relevant EU directives.
For full information of the EU directives and standards and the approved certifications, please refer to the EU Declaration of Conformity or the website of the manufacturer.
Other approvals and standards
Measuring Instruments Directive 2014/32/EU, Annex III (MI-001), Annex VI (MI-004)
NAMUR NE 21/04
For more information, please refer to the dedicated documentation.
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
5
Page 6
1
SAFETY INSTRUCTIONS
1.3 Safety instructions from the manufacturer
1.3.1 Copyright and data protection
The contents of this document have been created with great care. Nevertheless, we provide no guarantee that the contents are correct, complete or up-to-date.
The contents and works in this document are subject to copyright. Contributions from third parties are identified as such. Reproduction, processing, dissemination and any type of use beyond what is permitted under copyright requires written authorisation from the respective author and/or the manufacturer.
The manufacturer tries always to observe the copyrights of others, and to draw on works created in-house or works in the public domain.
The collection of personal data (such as names, street addresses or e-mail addresses) in the manufacturer's documents is always on a voluntary basis whenever possible. Whenever feasible, it is always possible to make use of the offerings and services without providing any personal data.
WATERFLUX 3000
We draw your attention to the fact that data transmission over the Internet (e.g. when communicating by e-mail) may involve gaps in security. It is not possible to protect such data completely against access by third parties.
We hereby expressly prohibit the use of the contact data published as part of our duty to publish an imprint for the purpose of sending us any advertising or informational materials that we have not expressly requested.
1.3.2 Disclaimer
The manufacturer will not be liable for any damage of any kind by using its product, including, but not limited to direct, indirect or incidental and consequential damages.
This disclaimer does not apply in case the manufacturer has acted on purpose or with gross negligence. In the event any applicable law does not allow such limitations on implied warranties or the exclusion of limitation of certain damages, you may, if such law applies to you, not be subject to some or all of the above disclaimer, exclusions or limitations.
Any product purchased from the manufacturer is warranted in accordance with the relevant product documentation and our Terms and Conditions of Sale.
The manufacturer reserves the right to alter the content of its documents, including this disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable in any way for possible consequences of such changes.
6
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 7
WATERFLUX 3000
1.3.3 Product liability and warranty
The operator shall bear responsibility for the suitability of the device for the specific purpose. The manufacturer accepts no liability for the consequences of misuse by the operator. Improper installation or operation of the devices (systems) will cause the warranty to be void. The respective "Standard Terms and Conditions" which form the basis for the sales contract shall also apply.
1.3.4 Information concerning the documentation
To prevent any injury to the user or damage to the device it is essential that you read the information in this document and observe applicable national standards, safety requirements and accident prevention regulations.
If this document is not in your native language and if you have any problems understanding the text, we advise you to contact your local office for assistance. The manufacturer can not accept responsibility for any damage or injury caused by misunderstanding of the information in this document.
This document is provided to help you establish operating conditions, which will permit safe and efficient use of this device. Special considerations and precautions are also described in the document, which appear in the form of icons as shown below.
SAFETY INSTRUCTIONS
1
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
7
Page 8
1
SAFETY INSTRUCTIONS
1.3.5 Warnings and symbols used
Safety warnings are indicated by the following symbols.
DANGER!
This information refers to the immediate danger when working with electricity.
DANGER!
This warning refers to the immediate danger of burns caused by heat or hot surfaces.
DANGER!
These warnings must be observed without fail. Even partial disregard of this warning can lead to serious health problems and even death. There is also the risk of seriously damaging the device or parts of the operator's plant.
WARNING!
Disregarding this safety warning, even if only in part, poses the risk of serious health problems. There is also the risk of damaging the device or parts of the operator's plant.
WATERFLUX 3000
CAUTION!
Disregarding these instructions can result in damage to the device or to parts of the operator's plant.
INFORMATION!
These instructions contain important information for the handling of the device.
LEGAL NOTICE!
This note contains information on statutory directives and standards.
HANDLING
HANDLING
HANDLINGHANDLING
This symbol designates all instructions for actions to be carried out by the operator in the specified sequence.
i
RESULT
RESULT
RESULTRESULT This symbol refers to all important consequences of the previous actions.
1.4 Safety instructions for the operator
WARNING!
In general, devices from the manufacturer may only be installed, commissioned, operated and maintained by properly trained and authorized personnel. This document is provided to help you establish operating conditions, which will permit safe and efficient use of this device.
8
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 9
WATERFLUX 3000
CAUTION!
The WATERFLUX 3000 can be combined with the mains powered IFC 050, IFC 100 and IFC 300 signal converter and with the battery powered IFC 070 signal converter.
This handbook only describes the combination with the IFC 050, IFC 100 and IFC 300 signal converter.
2.1 Scope of delivery
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Inspect the packaging carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer.
INFORMATION!
The remote version will arrive in two cartons. One carton contains the converter and one carton contains the sensor.
DEVICE DESCRIPTION
2
Figure 2-1: Scope of delivery
1 Ordered flowmeter 2 Product documentation 3 Factory calibration report 4 CD-ROM with product documentation in available languages 5 Signal cable (remote versions only)
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools in compliance with the applicable occupational health and safety directives.
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
9
Page 10
2
DEVICE DESCRIPTION
2.2 Device description
Electromagnetic flowmeters are designed exclusively to measure the flow and conductivity of electrically conductive, liquid media.
Your measuring device is supplied ready for operation. The factory settings for the operating data have been made in accordance with your order specifications.
INFORMATION!
Product specific information and extensive product specification is available using PICK, the Product Information Center KROHNE web-tool. PICK can be found via the service menu button on the KROHNE.com website.
The following versions are available:
Compact version (the signal converter is mounted directly on the measuring sensor)
Remote version (measuring sensor with connection box and a signal converter in a remote
(field) housing)
WATERFLUX 3000
10
Figure 2-2: Device versions
1 Remote version 2 Compact version with signal converter IFC 300 3 Compact version with signal converter IFC 100 (0°) 4 Compact version with signal converter IFC 100 (45°) 5 Compact version with signal converter IFC 100 (10°) Stainless steel 6 Compact version with signal converter IFC 050 (10°)
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 11
WATERFLUX 3000
2.3 Nameplate (example)
INFORMATION!
Check the device nameplate to ensure that the device is delivered according to your order. Additional information (e.g. correct supply voltage), can be found in the documentation of the signal converter.
Figure 2-3: Example of nameplate
1 Name and address of manufacturer 2 Type designation of the flowmeter and CE sign with number(s) of notified body / bodies 3 Meter constant, diameter, wetted materials, protection class
DEVICE DESCRIPTION
2
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
11
Page 12
3
INSTALLATION
3.1 General notes on installation
INFORMATION!
Inspect the packaging carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate.
3.2 Storage
Store the device in a dry, dust-free location.
Avoid continuous direct sunlight.
Store the device in its original packaging.
Storage temperature: -50...+70°C / -58...+158°F
WATERFLUX 3000
3.3 Transport
Signal converter
No special requirements.
Compact version
Do not lift the device by the signal converter housing.
Do not use lifting chains.
To transport flange devices, use lifting straps. Wrap these around both process connections.
12
Figure 3-1: Transport
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 13
WATERFLUX 3000
3.4 Pre-installation requirements
Make sure that you have all necessary tools available:
Allen key (4 mm)
Small screwdriver
Wrench for cable glands
Wrench for wall mounting bracket (remote version only)
Torque wrench for installing flowmeter in pipeline
3.5 General requirements
INFORMATION!
The following precautions must be taken to ensure reliable installation.
Make sure that there is adequate space to the sides.
Protect the signal converter from direct sunlight and install a sun shade if necessary.
Signal converters installed in control cabinets require adequate cooling, e.g. by fan or heat exchanger.
Do not expose the signal converter to intense vibration. The flowmeters are tested for a vibration level in accordance with IEC 68-2-64.
INSTALLATION
3
3.5.1 Vibrations
Figure 3-2: Avoid vibrations
3.5.2 Magnetic field
Figure 3-3: Avoid magnetic field
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
13
Page 14
3
INSTALLATION
3.6 Installation conditions
CAUTION!
To prevent damage to the Rilsan carefully. Take precautions during transport and installation to protect the in- and outlet of the sensor.
3.6.1 Inlet and outlet
WATERFLUX 3000
®
coating, the WATERFLUX 3000 sensor must be installed
Figure 3-4: Minimal inlet and outlet
1 Inlet: t 0 DN 2 Outlet: t 0 DN
3.6.2 T-section
Figure 3-5: Distance behind a T-section
1 t 0 DN
3.6.3 Open discharge
14
Figure 3-6: Installation in front of an open discharge
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 15
WATERFLUX 3000
3.6.4 Bends
Figure 3-7: Installation in bending pipes
INSTALLATION
3
3.6.5 Pump
Figure 3-8: Installation in bending pipes
Figure 3-9: Installation behind a pump
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
15
Page 16
3
INSTALLATION
3.6.6 Control valve
Figure 3-10: Installation in front of a control valve
3.6.7 Air venting and vacuum forces
WATERFLUX 3000
Figure 3-11: Air venting
1 t 5 m 2 Air ventilation point
Figure 3-12: Vacuum
1 t 5 m
16
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 17
WATERFLUX 3000
3.6.8 Mounting position
Figure 3-13: Mounting position
Install flow sensor in line with the pipe axis.
Pipe flange faces must be parallel to each other.
INSTALLATION
3
3.6.9 Flange deviation
CAUTION!
Max. permissible deviation of pipe flange faces:
- L
L
max
Figure 3-14: Flange deviation
1 L
max
2 L
min
d 0.5 mm / 0.02"
min
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
17
Page 18
3
INSTALLATION
3.7 IP 68
The WATERFLUX 3000 flow sensor is rated IP68 (NEMA 4X/6P). It is suitable for submersion in flooded measurement chambers and for subsurface installation.
WATERFLUX 3000
Figure 3-15: IP68 versions
1 Submersible 2 Buried
1
2
18
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 19
WATERFLUX 3000
3.8 Mounting
3.8.1 Torques and pressures
The maximum pressure and torque values for the flowmeter are theoretical and calculated for optimum conditions and use with carbon steel flanges.
INSTALLATION
3
Figure 3-16: Tightening of bolts
Tightening of bolts
Always tighten the bolts uniformly and in diagonally opposite sequence.
Do not exceed the maximum torque value.
Step 1: Apply approx. 50% of max. torque given in table.
Step 2: Apply approx. 80% of max. torque given in table.
Step 3: Apply 100% of max. torque given in table.
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
19
Page 20
3
INSTALLATION
WATERFLUX 3000
Nominal size
DN [mm]
25 PN 16 4 x M 12 12
40 PN 16 4 x M 16 30
50 PN 16 4 x M 16 36
65 PN 16 8 x M 16 50
80 PN 16 8 x M 16 30
100 PN 16 8 x M 16 32
125 PN 16 8 x M 16 40
150 PN 10 8 x M 20 55
150 PN 16 8 x M 20 55
200 PN 10 8 x M 20 85
200 PN 16 12 x M 20 57
250 PN 10 12 x M 20 80
250 PN 16 12 x M 24 100
300 PN 10 12 x M 20 95
300 PN 16 12 x M 24 136
350 PN 10 16 x M 20 96
400 PN 10 16 x M 24 130
450 PN 10 20 x M 24 116
500 PN 10 20 x M 24 134
600 PN 10 20 x M 27 173
1 The torque values also depend on variables (temperature, bolt material, gasket material, lubricants, etc.)
outside the control of the manufacturer. Therefore these values should be regarded as indicative only.
Pressure
rating
Bolts Max. torque
1
[Nm]
20
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 21
WATERFLUX 3000
INSTALLATION
3
Nominal size
[inch]
1 150 4 x 1/2" 4
1½ 150 4 x 1/2" 11
2 150 4 x 5/8" 18
2.5 150 8 x 5/8" 27
3 150 4 x 5/8" 33
4 150 8 x 5/8" 22
5 150 8 x 3/4" 33
6 150 8 x 3/4" 48
8 150 8 x 3/4" 66
10 150 12 x 7/8" 74
12 150 12 x 7/8" 106 14 150 2 12 x 1" 87 16 150 2 16 x 1" 84 18 150 2 16 x 1 1/8" 131 20 150 2 20 x 1 1/8" 118 24 150 2 20 x 1 1/4" 166
1 The torque values also depend on variables (temperature, bolt material, gasket material, lubricants, etc.)
outside the control of the manufacturer. Therefore these values should be regarded as indicative only.
2 No full rating (max. 150 psi / 10 bar).
Flange class
[lb]
Bolts Max. torque
[lbs.ft]
1
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
21
Page 22
4
ELECTRICAL CONNECTIONS
4.1 Safety instructions
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take note of the voltage data on the nameplate!
DANGER!
Observe the national regulations for electrical installations!
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the electrical components of the measuring device may only be carried out by properly trained specialists.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate.
WATERFLUX 3000
4.2 Grounding
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel against electric shocks.
Figure 4-1: Grounding
INFORMATION!
Grounding without grounding rings. The flow sensor is equipped with a reference electrode.
4.3 Connection diagrams
22
INFORMATION!
For the connection diagrams please refer to the documentation of the applicable signal converter.
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 23
WATERFLUX 3000
5.1 Spare parts availability
The manufacturer adheres to the basic principle that functionally adequate spare parts for each device or each important accessory part will be kept available for a period of 3 years after delivery of the last production run for the device.
This regulation only applies to spare parts which are subject to wear and tear under normal operating conditions.
5.2 Availability of services
The manufacturer offers a range of services to support the customer after expiration of the warranty. These include repair, maintenance, technical support and training.
INFORMATION!
For more precise information, please contact your local sales office.
5.3 Returning the device to the manufacturer
SERVICE
5
5.3.1 General information
This device has been carefully manufactured and tested. If installed and operated in accordance with these operating instructions, it will rarely present any problems.
WARNING!
Should you nevertheless need to return a device for inspection or repair, please pay strict attention to the following points:
Due to statutory regulations on environmental protection and safeguarding the health and safety of the personnel, the manufacturer may only handle, test and repair returned devices that have been in contact with products without risk to personnel and environment.
This means that the manufacturer can only service this device if it is accompanied by the following certificate (see next section) confirming that the device is safe to handle.
WARNING!
If the device has been operated with toxic, caustic, radioactive, flammable or water-endangering products, you are kindly requested:
to check and ensure, if necessary by rinsing or neutralising, that all cavities are free from such dangerous substances,
to enclose a certificate with the device confirming that it is safe to handle and stating the product used.
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
23
Page 24
5
SERVICE
5.3.2 Form (for copying) to accompany a returned device
CAUTION!
To avoid any risk for our service personnel, this form has to be accessible from outside of the packaging with the returned device.
Company: Address:
Department: Name:
Tel. no.: Fax no. and/or Email address:
Manufacturer's order no. or serial no.:
The device has been operated with the following medium:
This medium is: radioactive
water-hazardous
toxic
caustic
flammable
We checked that all cavities in the device are free from such substances.
We have flushed out and neutralized all cavities in the device.
WATERFLUX 3000
We hereby confirm that there is no risk to persons or the environment through any residual media contained in the device when it is returned.
Date: Signature:
Stamp:
5.4 Disposal
LEGAL NOTICE!
Disposal must be carried out in accordance with legislation applicable in your country.
Separate collection of WEEE (Waste Electrical and Electronic Equipment) in the European Union:
Separate collection of WEEE (Waste Electrical and Electronic Equipment) in the European Union:
Separate collection of WEEE (Waste Electrical and Electronic Equipment) in the European Union:Separate collection of WEEE (Waste Electrical and Electronic Equipment) in the European Union:
According to the directive 2012/19/EU, the monitoring and control instruments marked with the WEEE symbol and reaching their end-of-life must not be disposed of with other waste The user must dispose of the WEEE to a designated collection point for the recycling of WEEE or send them back to our local organisation or authorised representative.
must not be disposed of with other waste.
must not be disposed of with other wastemust not be disposed of with other waste
24
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 25
WATERFLUX 3000
6.1 Measuring principle
An electrically conductive fluid flows inside an electrically insulated pipe through a magnetic field. This magnetic field is generated by a current, flowing through a pair of field coils. Inside of the fluid, a voltage U is generated: U = v * k * B * D
U = v * k * B * D
U = v * k * B * DU = v * k * B * D
in which: v = mean flow velocity k = factor correcting for geometry B = magnetic field strength D = inner diameter of flowmeter
The signal voltage U is picked off by electrodes and is proportional to the mean flow velocity v and thus the flow rate Q. A signal converter is used to amplify the signal voltage, filter it and convert it into signals for totalizing, recording and output processing.
TECHNICAL DATA
6
Figure 6-1: Measuring principle
1 Field coils 2 Magnetic field 3 Electrodes 4 Induced voltage (proportional to flow velocity) 5 Rectangular cross section
Rectangular cross section
Rectangular cross section
Rectangular cross sectionRectangular cross section
The minimal height of the measuring tube decreases the distance between the field coils (1), resulting in a stronger and more homogeneous magnetic field (2). In addition, the mean flow velocity v increases due to the rectangular and reduced cross section. The large electrode spacing (D) and the increased flow velocity results in a higher magnetic signal voltage, also in the presence of a low flow rate.
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
25
Page 26
6
TECHNICAL DATA
6.2 Technical data
INFORMATION!
The following data is provided for general applications. If you require data that is more relevant to your specific application, please contact us or your local sales office.
Additional information (certificates, special tools, software,...) and complete product documentation can be downloaded free of charge from the website (Downloadcenter).
Measuring system
Measuring principle Faraday's law of induction
Application range Electrically conductive fluids
Measured value
Measured value
Measured valueMeasured value
Primary measured value Flow velocity
Secondary measured value
Design
Features Unique rectangular flow tube design providing improved flow profile and
WATERFLUX 3000
Volume flow
signal to noise ratio resulting in highest accuracy and large turndown ratio
Rilsan® polymer coated flow tube approved for drinking water
No internal or moving parts
Built-in reference electrode
Modular construction The measurement system consists of a flow sensor and a signal converter.
Compact version With IFC 050 converter: WATERFLUX 3050 C
Remote version In wall (W)mount version with IFC 050 converter: WATERFLUX 3050 W
Nominal diameter DN25...600 / 1...24" ; Rectangular bore
It is available as compact and as separate version. More information about the signal converter can be found in the relevant documentation.
With IFC 100 converter: WATERFLUX 3100 C
With IFC 300 converter: WATERFLUX 3300 C
In wall (W)mount version with IFC 100 converter: WATERFLUX 3100 W
In field (F), wall (W) or rack ( R) mount version with IFC 300 converter: WATERFLUX 3300 F, W or R
26
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 27
WATERFLUX 3000
Measuring accuracy
Maximum measuring error
Repeatability DN25...300 / 1...12" ; ±0.1% (v >0.5m/s / 1.5 ft/s)
Calibration / Verification Standard:
MID Annex MI-001 (Directive 2014/32/EU)
TECHNICAL DATA
IFC 050: down to 0.5% of the measured value ±1 mm/s
IFC 100: down to 0.3% of the measured value ±1 mm/s
IFC 300: down to 0.2% of the measured value ±1 mm/s
The maximum measuring error depends on the installation conditions.
For detailed information refer to
DN350...600 / 14...24"; ±0.2% (v >0.5m/s / 1.5 ft/s)
Standard:
Standard:Standard:
2 point calibration by a direct volume comparison.
Option (for DN25...600):
Option (for DN25...600):
Option (for DN25...600):Option (for DN25...600):
Verification to Measurement Instrument Directive (MID), Annex MI-001. Standard: Verification at Ratio (Q3/Q1) = 80, Q3 t 2 m/s / 6.6 ft/s Optional: Verification at Ratio (Q3/Q1) > 80
Only in combination with the IFC 300 signal converter
EC-Type examination certificate to MID Annex MI-001
EC-Type examination certificate to MID Annex MI-001
EC-Type examination certificate to MID Annex MI-001EC-Type examination certificate to MID Annex MI-001
Only in combination with the IFC 300 signal converter
Diameter range: DN25...600 / 1...24"
Minimum straight inlet flow: 0 DN
Minimum straight outlet flow: 0 DN
Forward and reverse (bi-directional) flow
Orientation: any
Ratio (Q3/Q1) up to 640
Liquid temperature range: +0.1°C / 50°C
Maximum operating pressure: d DN200 / 8" : 16 bar / 232 psi, t DN250 / 10": 10 bar / 145 psi
For detailed information refer to
Measurement accuracy
Legal metrology
on page 31.
on page 34.
6
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
27
Page 28
6
TECHNICAL DATA
Operating conditions
Temperature
Temperature
TemperatureTemperature
Process temperature -5...+70°C / +23...+158°F
Ambient temperature Standard
Protect electronics against self-heating at ambient temperatures above 55°C / 131°F
Storage temperature -50+70°C / -58+158°F
Measurement range
Measurement range -12...+12 m/s / -40...+40 ft/s
Measurement rangeMeasurement range
Pressure
Pressure
PressurePressure
Operating pressure Up to 16 bar / 232 psi for DN25...00 / 1...12"
Vacuum load 0 mbar / 0 psi absolute
Pressure loss For detailed information refer
Chemical properties
Chemical properties
Chemical propertiesChemical properties
Physical condition Water: drinking water, raw water, irrigation water.
Electrical conductivity t 20 PS/cm
WATERFLUX 3000
Standard: DN25...200: remote or compact version with aluminium converter
StandardStandard housing and with stainless steel flanges:
-40+65°C / -40+149°F compact version with stainless steel converter housing and with stainless steel flanges
-40+55°C / -40+130°F
Standard
Standard, DN250...600: remote version with stainless steel converter
StandardStandard housing and with carbon steel flanges:
-20+65°C / -4+149°F compact version with stainless steel converter housing and with carbon steel flanges
-20+55°C / -4+130°F
Option
Option, DN250...600 with low temperature carbon steel or stainless steel
OptionOption flanges :
-40+65°C / -40+130°F .
Up to 10 bar / 150 psi for DN50...600 / 14...24"
Pressure loss
For salt water please contact the factory.
to on page 40.
Installation conditions
Installation Assure that the flow sensor is always fully filled.
For detailed information refer to
Flow direction Forward and reverse
Arrow on flow sensor indicates forward flow direction.
Inlet run t 0 DN
For detailed information refer to
Outlet run t 0 DN
For detailed information refer to
Dimensions and weights For detailed information refer to
Installation
Measurement accuracy
Measurement accuracy Dimensions and weights
on page 12.
on page 34.
on page 34.
on page 36.
28
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 29
WATERFLUX 3000
Materials
Sensor housing Sheet steel
Measuring tube DN25...200 / 1...8" : metallic alloy
Flanges DN25...600 / 1...24" : steel 1.0460 / 1.0038 (RSt37-2)
Liner
Protective coating On exterior of the meter: flanges, housing, signal converter (compact
Connection box Only for remote versions
Measuring electrodes Standard: stainless steel 1.4301 / AISI 304
Reference electrode Standard: stainless steel 1.4301 / AISI 304
TECHNICAL DATA
DN250...600 / 10...24" : stainless steel
DN25...200 / 1...8" : ; stainless steel 3.04 (optionally 3.16)
®
Rilsan
version) and/or connection box (field version)
Standard: polysiloxane
Option: subsoil or offshore coating
Standard: stainless steel
Option: Hastelloy® C
6
Option: Hastelloy® C
Grounding rings Grounding rings can be omitted when the reference electrode is used.
Process connections
Flange
Flange
FlangeFlange
EN 1092-1 Standard:
ASME 1"...12": 150 lb RF (232 psi / 16 bar rated)
JIS DN25...300 / 1"...12": 10 K
AS 4087 DN25...600 / 1"...24": Class 16: on request
AS 2129 DN25...600 / 1"...24": Table D & E: on request
Other connections
Other connections
Other connectionsOther connections
Thread DN25 / 1" : G1" thread connection on request
Other Weld-on, clamp, oval flanges: on request
Standard:
Standard:Standard:
DN25...200 / 1...8" : : PN 16
DN250...600 / 10...24" : PN 10
Optional:
Optional:
Optional:Optional:
DN250...600 / 10...24" : PN16 (DN350...600 / 14...24" : 10 bar rated)
14"...24": 150 lb (150 psi / 10 bar rated)
DN350...600 / 14"...24": 7.5 K
(DN350...600 / 14"...24": 10 bar rated)
(DN350...600 / 14"...24": 10 bar rated)
For detailed information of nominal flange pressure and nominal diameter refer to
DN40 / 1½" : G1.5" & G2" thread connection on request
Dimensions and weights
on page 36.
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
29
Page 30
6
TECHNICAL DATA
Electrical connections
Signal cable
Signal cable (remote versions only)
Signal cableSignal cable
Type A (DS) In combination with the IFC 050, IFC 100 and the IFC 300 signal converter
Type B (BTS) Only in combination with the IFC 300 signal converter
I/O For full details of I/O options, including data streams and protocols, see
WATERFLUX 3000
For detailed information refer to the documentation of the relevant signal converter.
In combination with the IFC 050, IFC 100 and the IFC 300 signal converter
In combination with the IFC 050, IFC 100 and the IFC 300 signal converterIn combination with the IFC 050, IFC 100 and the IFC 300 signal converter
Standard cable, double shielded. Max. length: 600 m / 1950 ft (depends on electrical conductivity and measuring sensor).
For detailed information refer to the documentation of the relevant signal converter.
Only in combination with the IFC 300 signal converter
Only in combination with the IFC 300 signal converterOnly in combination with the IFC 300 signal converter
Optional cable, triple shielded. Max. length: 600 m / 1950 ft (depends on electrical conductivity and measuring sensor).
For detailed information refer to the documentation of the relevant signal converter.
technical datasheet of the relevant converter.
Approvals and certificates
CE
CE
CECE
This device fulfils the statutory requirements of the EU directives. The manufacturer certifies successful testing of the product by applying the CE mark
For full information of the EU directives & standards and the approved certifications, please refer to the EU Declaration of Conformity or the manufacturer website.
Custody transfer Only in combination with the IFC 300 signal converter.
Directive:2014/32/EU MID Annex III (MI-001) and MID Annex VI (MI-004) type examination certificate ( DN25...600 / 1...24")
OIML R49 edition 2006 certificate of conformity ( DN25...600 / 1...24")
Innerstaatliche Bauartzulassung als Kältezähler (For Germany, Switzerland and Austria)
Other approvals and standards
Other approvals and standards
Other approvals and standardsOther approvals and standards
Drinking water approvals ACS, DVGW W270, NSF / ANSI Standard 61, TZW, KIWA (ATA), KTW, WRAS
Protection category acc. to IEC 60529
Corrosion protection class acc. to ISO 12944-2
Shock test IEC 68-2-27
Vibration test IEC 68-2-64
Standard:
Standard:
Standard:Standard:
IP66 / 67 (NEMA 4/4X/6)
Option:
Option:
Option:Option:
IP68 factory (NEMA 6P)
IP68 field (NEMA 6P)
IP68 is only available for separate design
Standard: C3 medium
Option: off-shore paint C5-I high - C5-M high
30 g for 18 ms
f = 20...2000 Hz, rms = 4.5 g, t = 30 min
30
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 31
WATERFLUX 3000
6.3 Legal metrology
INFORMATION!
MID Annex MI-001 is only
6.3.1 MID Annex III (MI-001)
All new designs of water meters that are to be used for legal purposes in Europe require certification under the Measurement Instrument Directive (MID) 2014/32/EU. Annex III (MI-001) of the MID applies to water meters intended for the measurement of the volume of clean, cold or heated water in residential, commercial, and light industrial use. An EC­type examination certificate is valid in all countries of the European Union.
The WATERFLUX 3300 has an EC-type examination certificate and can be verified to the MID Annex III (MI-001) for water meters with diameter DN25...DN600. The conformity assessment procedure followed for the WATERFLUX 3300 is Module B (Type Examination) and Module D (Quality Assurance of the Production Process).
The maximum permissible error on volumes delivered between Q2 (transitional) flow rate and Q4 (overload) flow rate is ±2%. The maximum permissible error on volumes delivered between Q1 (minimum) flow rate and Q2 (transitional) flow rate is ±5%.
TECHNICAL DATA
only available in combination with the IFC 300 signal converter!
onlyonly
6
Q1 = Q3 / R
Q2 = Q1 * 1.6
Q3 = Q1 * R
Q4 = Q3 * 1.25
Figure 6-2: ISO flow rates added to figure as comparison towards MID X:
X: Flow rate
X:X: Y [%]:
Y [%]: Maximum measuring error
Y [%]:Y [%]:
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
31
Page 32
6
TECHNICAL DATA
MI-001 certified flow characteristics
WATERFLUX 3000
DN Span (R)
Flow rate [m3/h]
Q3 / Q1
Minimum Q1 Transitional Q2 Permanent Q3 Overload Q4
25 640 0.025 0.040 16 20.0
40 640 0.0625 0.100 40 50.0
50 630 0.100 0.160 63 78.75
65 635 0.1575 0.252 100 125.0
80 640 0.25 0.400 160 200.0
100 625 0.40 0.640 250 312.5
125 640 0.625 1.00 400 500.0
150 630 1.00 1.60 630 787.5
200 508 1.575 2.52 800 1000
250 400 2.50 4.00 1000 1250
300 400 4.00 6.40 1600 2000
350 160 15.625 25.0 2500 3125
400 160 25.00 40.0 4000 5000
450 160 25.00 40.0 4000 5000
500 160 39.375 63.0 6300 7875
600 100 63.00 100.8 6300 7875
32
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 33
WATERFLUX 3000
6.3.2 Verification to MI-001
INFORMATION!
Verification to MI-001 , standard at the following values for R, Q1, Q2 and Q3. Verification at other values for R and Q3 available on request.
Verification to MID Annex III (MI-001)
TECHNICAL DATA
6
DN Span (R)
Flow rate [m3/h]
Q1 Q2 Q3
25 80 0.050 0.08 4
40 80 0.125 0.20 10
50 80 0.200 0.32 16
65 80 0.313 0.50 25
80 80 0.500 0.80 40
100 80 0.788 1.26 63
125 80 1.250 2.00 100
150 80 2.000 3.20 160
200 80 3.125 5.00 250
250 80 5.000 8.00 400
300 80 7.875 12.60 630
350 80 20.00 32.0 1600
400 80 31.25 50.0 2500
450 80 31.25 50.0 2500
500 80 50.00 80.0 4000
600 80 78.75 126 6300
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
33
Page 34
6
TECHNICAL DATA
6.4 Measurement accuracy
Every electromagnetic flowmeter is calibrated by direct volume comparison. The wet calibration validates the performance of the flowmeter under reference conditions against accuracy limits.
The accuracy limits of electromagnetic flowmeters are typically the result of the combined effect of linearity, zero point stability and calibration uncertainty.
Reference conditions
Medium: water
Temperature: +5...35°C / +41...95°F
Operating pressure: 0.1...5 barg / 1.5...72.5 psig
Inlet section: t 3 DN
Outlet section: t 1 DN
WATERFLUX 3000
34
Figure 6-3: Flow velocity vs. accuracy XXXX [m/s]: flow velocity YYYY [%]: deviation from the actual measured value
Converter type Accuracy Curve
IFC 050 0.5% of mv +1 mm/s 3 IFC 100 0.3% of mv +1 mm/s 2 IFC 300 0.2% of mv +1 mm/s 1
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 35
WATERFLUX 3000
TECHNICAL DATA
6.4.1 WATERFLUX 3050, 3100 and 3300 without straight inlet and outlet sections
Disturbed flow profiles, such as those that occur behind elbows, tee pieces, reducers or valves installed in front of a flowmeter, affect the measuring performance. Therefore it is usually recommended to fit a straight inlet length in front of and straight outlet length behind a flowmeter.
As a result of the unique WATERFLUX flow sensor design, whereby the mean flow velocity and flow profile are optimized within the rectangular and reduced cross section, the additional uncertainty for upstream disturbances are drastically reduced. Therefore the requirements for straight length and in front of and behind a meter are reduced.
EC-type certificate according MID Annex III (MI-001)
In combination with the signal converter IFC 300
Diameter range DN25...600
Minimum straight inlet and outlet pipe length of 0 DN
Bi-directional flow
6
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
35
Page 36
6
TECHNICAL DATA
WATERFLUX 3000
6.5 Dimensions and weights
Remote version
Remote version a = 88 mm / 3.5"
Remote versionRemote version
b = 139 mm / 5.5"
c = 106 mm / 4.2"
Total height = H + a
Compact version with :
Compact version with :
Compact version with :Compact version with : IFC 300
IFC 300
IFC 300IFC 300
a = 155 mm / 6,1"
b = 230 mm / 9.1"
c = 260 mm / 10.2"
Total height = H + a
1
1
36
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 37
WATERFLUX 3000
Compact version with:
Compact version with:
Compact version with:Compact version with: IFC 100 (0
IFC 100 (0°))))
IFC 100 (0IFC 100 (0
Compact version with:
Compact version with:
Compact version with:Compact version with: IFC 100 (45
IFC 100 (45°))))
IFC 100 (45IFC 100 (45
TECHNICAL DATA
a = 82 mm / 3.2"
b = 161 mm / 6.3"
c = 257 mm / 10.1"
Total height = H + a
a = 186 mm / 7.3"
b = 161 mm / 6.3"
c = 184 mm / 2.7"
Total height = H + a
1
1
6
Compact version with:
Compact version with:
Compact version with:Compact version with: stainless steel IFC 100 (10
stainless steel IFC 100 (10°))))
stainless steel IFC 100 (10stainless steel IFC 100 (10
Compact version with:
Compact version with:
Compact version with:Compact version with: IFC 050 (10
IFC 050 (10°))))
IFC 050 (10IFC 050 (10
1 The value may vary depending on the used cable glands.
a = 100 mm / 4"
b = 187 mm / 7.36"
c = 270 mm / 10.63"
Total height = H + a
a = 101 mm / 3.98"
b = 157 mm / 6.18"
c = 260 mm / 10.24"
Total height = H + a
1
1
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
37
Page 38
6
TECHNICAL DATA
INFORMATION!
All data given in the following tables are based on standard versions of the flow sensor only.
Especially for smaller nominal sizes of the flow sensor, the signal converter can be bigger than the flow sensor.
Note that for other pressure ratings than mentioned, the dimensions may be different.
For full information on signal converter dimensions see relevant documentation.
EN 1092-1
WATERFLUX 3000
Nominal size
DN [mm]
100 250 237 220 17
125 250 266 250 21
150 300 300 285 29
200 350 361 340 36
250 400 408 395 50
300 500 458 445 60
350 500 510 505 85
400 600 568 565 110
450 600 618 615 125
500 600 671 670 120
600 600 781 780 180
Dimensions [mm] Approx. weight
[kg]
L H W
25 150 151 115 5
40 150 166 150 6
50 200 186 165 13
65 200 200 185 11
80 200 209 200 17
38
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 39
WATERFLUX 3000
ASME B16.5 / 150 lb
TECHNICAL DATA
6
Nominal size
[inches]
Dimensions [inches] Approx. weight
[lb]
L H W
1 5.91 5.83 4.3 18
1½ 5.91 6 4.9 21
2 7.87 7.05 5.9 34
3 7.87 8.03 7.5 42
4 9.84 9.49 9.0 56
5 9.84 10.55 10.0 65
6 11.81 11.69 11.0 80
8 13.78 14.25 13.5 100
10 15.75 16.3 16.0 148
12 19.7 18.8 19.0 210
14 27.6 20.7 21 290
16 31.5 22.9 23.5 370
18 31.5 24.7 25 420
20 31.5 27 27.5 500
24 31.5 31.4 32 680
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
39
Page 40
6
TECHNICAL DATA
6.6 Pressure loss
Figure 6-4: Pressure loss between 1...9 m/s / 3.3...30 ft/s for DN25...150 / 1...6"
1 DN25 / 1" 2 DN40 / 1½" 3 DN50 / 2" 4 DN65 / 2½" 5 DN80 / 3" 6 DN100 / 4" 7 DN125 / 5" 8 DN150 / 6"
WATERFLUX 3000
40
Figure 6-5: Pressure loss between 1...9 m/s / 3.3...30 ft/s for DN200...600 / 8...24"
1 DN200 / 8" 2 DN250 / 10" 3 DN300 / 12" 4 DN350 / 14" 5 DN400 / 16" 6 DN450 / 18" 7 DN500 / 20" 8 DN600 / 24"
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 41
WATERFLUX 3000
NOTES
7
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
41
Page 42
7
NOTES
WATERFLUX 3000
42
www.krohne.com 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
Page 43
WATERFLUX 3000
NOTES
7
www.krohne.com07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en
43
Page 44
KROHNE – Process instrumentation and measurement solutions
Flow
Level
Temperature
Pressure
Process Analysis
Services
Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Str. 5 47058 Duisburg (Germany) Tel.: +49 203 301 0 Fax: +49 203 301 10389 info@krohne.com
© KROHNE 07/2018 - 4001626605 - HB WATERFLUX 3000 R06 en - Subject to change without notice.
The current list of all KROHNE contacts and addresses can be found at: www.krohne.com