KROHNE BM 70 A, BM 700, BM 702, BM 70 P Remote Operation Instructions

Page 1
© KROHNE 12/2000
Remote Operation
Instructions
HART Communicator 275
Asset Management Solutions (AMS)
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
1/10
Page 2
Remote Operation Instructions BM 70 A/P, BM 700, BM 702 HART
1 General Information 3
1.1 Configuring Instruments for Multidrop 3
2 IDs and Revision numbers 3
3 Implementation Peculiarities 3
4 HART Communicator 275 (HC275) 4
4.1 Installation 4
4.2 Operating 4
4.3 Known HC275 (4.9) Shortcomings 4
5 Asset Management Solutions (AMS) 4
5.1 Installation 4
5.2 Operating 5
5.3 Known AMS (5.0) Shortcomings 6
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
2/10
Page 3
Remote Operation Instructions BM 70 A/P, BM 700, BM 702 HART
1 General Information
The BM 70 A/P, BM 700, BM 702 are all the two-wire transmitters with 4..20mA current output and HART® capability. General characteristics of the BM70 X HART® interface:
•
Multidrop Mode is supported.
•
Burst Mode is not supported.
Electrical connection (point-to-point or multidrop): refer to sections 4.1 – 4.4 of the
Instructions. BM 70 A/P, BM 700, BM 702“.
„Installation and Operating
1.1 Configuring Instruments for Multidrop
There are differences in configuring instruments for multidrop mode from remote or via device local keypad.
•
If the instrument is entering multidrop via HART® interface (any application can be used), i.e. its bus address is
changed from ‘0’ to any allowed, then all the necessary operation with the instrument current output are done automatically (by the HART® transm itter) .
•
If the instrument local keypad is used, the user must manually carry out the three assignments:
1. Set the desirable bus address (Fct. 3.3.6),
2. Set the current output range to “4 – 20 mA” (Fct. 3.3.2),
3. Switch the current output function to “Off” (Fct. 3.3.1) and store configuration.
2 IDs and Revision numbers
The HART Device Descriptions described in this document have the following IDs and revision numbers: Manufacturer ID: 69 (0x45) Device Type: 249 (0xF9) Device Revision: 11 (0x0B) DD Revision: 2 HART Universal Revision: 5 HC 275 OS Revision: AMS Version:
≥ ≥
4.9
5.0
For information about Transmitter Revisions and related Device Descriptions refer to the KROHNE HART Device List.
3 Implementation Peculiarities
As for all previous BM 70 X DD revisions there are some implementation peculiarities, caused by either restrictions of the DDL / AMS or introduced deliberately – to restrict the usage/access to some device functionality. The list of implementation peculiarities/restrictions follows:
•
The values in the
unchanged in operation. The user should not have access to these values. Therefore the service data is made inaccessible for offline device configuration (it is open for live device provided the user is capable to get authorization as specia list) .
•
The
•
The BM 70 A/P /700 /702 HART® transmitter interacts with the instrument mastering SW via special interface
Conversion Table
functions. Their actual set impose some display-related restrictions: functions of the display) and display submenu (3.2) is left out (i.e. is not maintained by the instrument HART® application layer) – the local instrument user might configure the display settings without any impact on the remote HART® bus master. Hence one important consequence must be pointed out: the units for measurements on HC275 screens/AMS faceplates coincide with the ones for configuration parameters (say, for ‘Level’ measurements – with the units for ‘Tank height’, ‘Block distance’, etc.) but not with the ones that are set via display menu (3.2.2, 3.2.3). If the user
Service
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
menu are generally set by Krohne or possibly by the Service technician, and remain
is excluded from offline data for HC275 whilst for AMS it is possible to configure it offline.
Test Display
Display Firmware
(2.4.2) are not supported by the HART® interface. Besides, the complete
(2.1.2 – tests the HW
3/10
Page 4
Remote Operation Instructions BM 70 A/P, BM 700, BM 702 HART
due to any reason (say, for testing purposes) wants these units to be same, he can either “equalize” them from remote ( configuration tab for AMS) or from the device keypad (functions 3.2.2/3.2.3).
Configuration/Test ➪
Installation ➪
Display ➪ Unit length/Unit conversion
for HC275 or “
Process Input
4 HART Communicator 275 (HC275)
4.1 Installation
The HC275 has to be programmed with the BM 70 A/P /700 /702 HART Device Description. Otherwise the HC275 user will work with the instrument as a generic one thus loosing opportunity for entire instrument control.
4.2 Operating
Refer to the BM 70 A/P /700 /702 Menu Tree HC275 (Attachment A). The online help of each parameter contains its function number as a reference to the device’s local display and the “Installation and Operating Instructions”. Parameter protection via passwords (Entry Code, Service Code) is the same as on local display. Please refer to the online help for valid symbols according to device’s keypad. The BM 70 X operation via HC275 is made quite close to the manual instrument control via keypad. The differences follows:
•
The instrument write protection (parameters “Entry Code 1”, “Code 1”, menu items 3.4.2, 3.4.3 of the
and Operation Instructions. BM 70 A/P, BM 700, BM 702”
(item 3 ➪ 1 of the HC275 Menu Tree).
•
To “open” service functionality the user has to register as specialist. To do this, one should invoke the “Service
Code” method (item 3 ➪ 2 of the HC275 Menu Tree) and enter the correct service password. After the HC275 is switched off (or the same method is invoked with improper service password) specialist authorization is lost, and all service parameters/functions (trim PV current DAC zero/gain) again become inaccessible.
•
For additional details refer to the
Transmitter-Specific Command Specification“.
While saving “Standard” configuration to HC275 from connected instrument, some crucial service variables (refer to section 3) are also stored. Hence in the offline mode their values cannot be changed (and will not be sent to device), but are shown to HC275 user and control assignments for maintenance data. In case “Full (for PC)” configuration is stored in Communicator, only the maintenance parameters (refer to section 3) can be edited via HC275 in offline mode. However, when such configuration is changed offline (within the maintenance part) and stored in Communicator, it is possible to transfer it (later on) complete (with service data!) to AMS (excluding conversion table - refer to section 3).
“HART® Smart Communications Protocol. BM70 A/P /700 /702 Level Radar.
) is changed via invocation of “Entry Code” method
„Installation
”
4.3 Known HC275 (4.9) Shortcomings
•
When the “Save” operation is activated with the “Full (for PC)” data type chosen, HC275 loops forever attempting
to retrieve instrument Service Data. The loop can be avoided if the user has registered as specialist in advance. With alternative data type (“Standard”) such preliminary registration is not necessary.
•
The same is true when the “Send” option is selected for “Full (for PC)” configuration. After such data “transfer” is
cancelled by disconnection of Communicator (no other way is possible), the preserved configuration might be damaged (then the HC275 user is prompted ‘No configurations stored’ in case ‘twas the sole configuration in Communicator).
5 Asset Management Solutions (AMS)
5.1 Installation
If the BM 70 A/P /700 /702 Device Description is not already installed on the AMS System a so called
BM 70 A/P /700 /702 HART AMS
Internet page).
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
is needed (available on floppy disk from KROHNE or as download from KROHNE
Installation Kit
4/10
Page 5
Remote Operation Instructions BM 70 A/P, BM 700, BM 702 HART
For installing the DD with the Installation Kit refer to the
“Adding new Device Types to AMS”
“Install Device Types Manually”
/
“AMS User's Guide”
.
section 3:
”Managing HART Devices”
/
5.2 Operating
Refer to the BM70 A/P /700 /702 Menu Tree AMS (Attachment B). Due to AMS requirements and conventions the BM 70 X operation differs a little from operation with HC275 and via local keypad. The online help of each parameter contains its function number as a reference to the device’s local display and the “Installation and Operating Instructions”. Parameter protection via passwords (Entry Code, Service Code) is the same as on local display. Please refer to the online help for valid symbols according to device’s keypad.
Some additional comments follow:
•
To “open” service functionality the user has to register as specialist. To do this, one should invoke the
Code”
method from the
Connection View
is reopen (or the same method is invoked with improper service password) specialist
Device Context Menu
and enter the correct service password. Note, that after the
authorization is lost, and all service parameters/functions (trim PV current DAC zero/gain) again become inaccessible.
•
Opposed to the HC275, handling of Conversion Table via AMS is carried out directly from the three configuration
displays. Due to transmitter implementation peculiarities some steps should be sequentially undertaken to create or change the table. The matter is that all the changes in table elements are initially accumulated in instrument RAM. The trigger event that launches the table’s burning into EEPROM, is Command #141 (Write Conversion Table Point Number) that deals with a single parameter, being the ‘ display “
Strap Table, 1-20
”). Just this command initiates the check of complete table and in case ‘twas successful
Number of points
’ variable (configuration
– activates the burning procedure. Worth noting that as soon as every table point depends on the ‘
points
’ variable (in terms of VALIDITY clause), the latter is always written to instrument before the points’ set. Hence while augmenting table the user can be prompted “Error ‘Table not monotonous’ happened writing ‘Number of points’”. Only after this response the table (changed elements) is copied to the instrument RAM. To burn it into EEPROM one have to “change” again the number (say, 10 to 10, or 4 to 4) and press ‘Apply’ again. All the commentaries above can be summarized as follows:
1. If the number of points is changed (with or without changes of the table contents), the user should ignore the first possible error response after pressing ‘Apply’ (‘Table not monotonous’ happened writing ‘Number of points’), “change” the number of points again to desirable one (i.e. reenter exactly the same value) and again press ‘Apply’.
2. If the number of points is preserved but some table items are changed, the user should press ‘Apply’ (thus transferring changed items to device), then reenter the number of points (as above) and press ‘Apply’ again ­otherwise the updated point(s) will be “in play” until the first power reset.
•
While transferring configurations (various transfer types are possible here - between live instruments; some
stored configuration and live device; two offline configurations – say, between HC275 and AMS; etc.) one should bear in mind that the ‘Transfer the device configuration’ buttons on the reconcile views (the “<<”, “>>” buttons to the left of “OK”-button) are available only in case the devices/configurations are in one and the same transmitter mode (refer to Attachment C). Otherwise the buttons are grayed and display the mode of corresponding configuration (say, “/0”, “/6” will imply that the left-hand configuration was stored (or corresponds to connected instrument) when device was in ‘0’ mode whilst the right-hand – in ‘6’th. In case of different configurations’ modes only partial transfer is possible when the accessible (not grayed) parameters are transferred individually. Worth noting that “relocatable” parameter set depends on how severe corresponding modes differ. Moreover – the mode-driven restrictions might have some intermediate/secondary effect: say, transfer of enumerator of some “wide” configuration (e.g. any corresponding to BM 70 A) to a “narrow” one (e.g. any of BM 702) can lead to a so­called ‘Unknown enumerator’ situation (when transferred value is replaced with ‘**********’ in configuration­“receiver” due to restrictions of any kind – e.g. “Agitator” setting for ‘
Tank type’
is possible only for BM 70 A but not for any other device type/modes). Such wrong enumerators will be (for sure) rejected being applied to a live instrument (i.e. when configuration-receiver is connected device), but are accepted by some preserved configuration (in
User Configurations
view, etc.). Hence it is recommended for the user to use the online help for
every transferred parameter in case the two configurations represent different transmitter modes!
•
The Dynamic Variables mapping (to the sole/primary current output and the three logical slots) can be controlled
for this revision from the
“Device/HART”
configuration tab. One note should be mentioned here: when the
“Service
Device
Number of
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
5/10
Page 6
Remote Operation Instructions BM 70 A/P, BM 700, BM 702 HART
instrument is in multidrop, changing of the digital value (and corresponding settings) whilst the current output function (
‘PV is’
value (Primary Variable code) affects only Primary Variable
‘Function I’
on the
“Analog Output”
tab) remains switched “Off”. Otherwise - when the instrument has the ‘0’ bus address – changes in Primary Variable assignment are traced at analog output and its function. And vise versa – when the
‘Function I’
parameter is changed, Primary Variable code is correspondingly changed. The only exclusion here is when the
‘Function I’
is set to “Off” – then the last meaningful assignment for PV (process variable or status data) is
retained.
5.3 Known AMS (5.0) Shortcomings
There are several insignificant shortcomings (all having workarounds) found during trials with AMS. Some of them pertained also to the previous AMS versions, one (last mentioned) is new.
•
Losing of the “Service Code”. If after registration as specialist (refer to section 4.2), the user does not open the
“Configuration Properties”
the correct service code), and the user will have to undertake the same actions (4.2) to re-establish access rights. In case if any window is already open before the happen.
•
Getting/releasing specialist access initiates a re-read process of the Service data package. And if the service
access rights are being changed when the “Error reading <parameter label>: Wrong service password” for every service parameter available on the tab (number depends on device implementation and some additional mutual parameters’ dependencies). No boring messages are presented to the user, if any other window (except
•
In case the instrument mode is changed (say,
does not reflect/trace the new mode (opposed to configuration tabs) and must be closed/reopen.
“Process Variables”
or
window, AMS will lose soon access to service functionality (i.e.
“Service”
configuration tab is active, the user is get prompted with the
Conversion Table
“Service Code”
method is invoked, such loss doesn’t
“Service”
configuration tab) is active.
is removed), the faceplate (in case it was open)
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
6/10
Page 7
Attachment A
g
1 Process Variables
2 Configuration Menu
3 Access Rights
4 View Erros/ Warns
5 HART Variables
Met
Remote Operation Instructions BM 70 A/P, BM 700, BM 702 HART
BM 70 A/P /700 /702 Menu Tree HC275
1 Measurements
2 Input/Outputs
1 Test
2 Installation
3 Service
1 Signal Control
2 General
3 Current Output I
4 User Data
1 Entry Code 2 Service Code
1 Tag 2 Manufacturer Id 3 Model 4 Hardware rev 5 Software rev 6 Message 7 Descriptor 8 Date 9 Final assembly num 10 PV is 11 SV is 12 TV is 13 QV is 14 Num resp preams 15 Pollin
Met
Met
address
1 Level 2 Distance 3 Conversion 4 Reflection
Opt
1 PV current 2 PV percent of range 3 Relay state
Opt
1 Min Peak 2 OF Threshold 3 HP Filter 4 LP Filter 5 Sweep
Opt
Opt
6 Empty spec. type 7 Min Window
1 Offset 2 Corr. Factor 3 Max Tankheight 4 Fct digital input
1 I Calibrate 1 2 I Calibrate 2
Met Met
1 Serial No 2 Option 1 3 Option 2
Opt
1 Hardware 2 Test I 3 SW Output S
Met
Met
Met
4 Master Firmware
1 Basis Parameters
2 Display
3 Signal Output
4 User Data
5 Application
6 Relay Output R
7 Conversion Table
1 Interface Option 2 Firmware version 3 Firmware ident.nr.
1 Tank height 2 Block distance 3 Antenna 4 Antenna extension 5 Distance piece 6 Stillwell 7 ID Stillwell 8 Reference offset 9 Tank bottom offset
1 Unit length 2 Length format 3 Unit conversion 4 Convers. format
Loc
Loc
1 Function I 2 Range I 3 Scale 20 mA 4 Scale 4 mA 5 Baudrate 6 Protocol
1 Tag
1 Auto tankheight 2 Empty spectrum
Met
Met
3 Time constant 4 Tracing velocity 5 Mult. reflections 6 BD Detect 7 Function FTB 8 Epsilon R 9 Tank type
1 Function R 2 Type R 3 Threshold 4 Hysteresis
Opt
Opt
Opt
Opt
1 Level unit 2 Volume unit 3 Input table 4 Delete table
Met
Met
Designations:
Opt
– Optional item, depends on device implementation;
Loc
– Local HC275 variable, that is not read/written to instrument;
Met
– Method is invoked to retrieve/change data.
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
KROHNE BM 70 A/P /700 /702 45f9 0b02
7/10
Page 8
Attachment B
y
Remote Operation Instructions BM 70 A/P, BM 700, BM 702 HART
BM 70 A/P /700 /702 Menu Tree AMS
• Level
• Distance
• Conversion
• Reflection
• Analog Output
• PV Percent of Range
• Rela
State
Opt
Opt
Process Variables Status
Scan Device
-----------------------------------
Diagnostics and Test Calibrate
----------------------------------­Master reset Entry Code Service Code
----------------------------------­Audit Trail Drawing Notes ... Help ...
----------------------------------­Clear Offline Configuration Compare Configurations
Configuration Properties
Overview
• Primary variable out of limits
• Non-primary variable out of limits
• Primary variable analog output saturated
• Primary variable analog output fixed
• Cold start
• Configuration changed
• Field device malfunction
Critical
Hardware Failures
• CPU error
• ROM checksum error
Configuration Errors
• Calibration data error
• Configuration error
• RAM read/write error
• Interrupt Controller error
• Timer error
• EEPROM Error
Informational
Warnings
• Signal low
• Signal too strong
• Poor spectrum
• Sweep low
• Empty Spectrum bad
• Measured value old
Miscellaneous
• Tank bottom
• Measurement frozen
• Tank overfilled
• Relay in test mode
• Current set to error
• Relay set to error
Runtime/Measuring Errors
• Signal down
• No measurement value
• VCO error
Opt
Opt
Designations:
Opt
– Optional, depends on device implementation;
– refer to the next page.
KROHNE BM 70 A/P /700 /702 45f9 0b02
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
8/10
Page 9
Attachment B
g
(continued f rom the previous page)
Remote Operation Instructions BM 70 A/P, BM 700, BM 702 HART
BM 70 A/P /700 /702 Menu Tree AMS
Designations:
Opt
– Optional, depends on device implementation;
Rd
– Read-only variable;
Loc
– Local AMS variable, affects on l y AMS fac eplates and
confi
uration tabs and is not read/written from/to instrument.
Process Variables Status
Scan Device
----------------------------------­Diagnostics and Test Calibrate
----------------------------------­Master reset Entry Code Service Code
----------------------------------­Audit Trail Drawing Notes ... Help ...
----------------------------------­Clear Offline Configuration Compare Configurations
Configuration Properties
Analog Output
• Function I
• Range I
• Scale 20 mA
• Scale 4 mA
Application
• Empty spectrum
• Time constant
• Tracing velocity
• Mult. Reflections
• BD Detect
• Function FTB
• Epsilon R
• Tank type
Hardware test Loop test Test relay
Basic Setup
• Model
Opt
Rd
• Tag
--------------------------------
• Tank height
• Tank type
• Block distance
• Antenna
• Antenna Extension
--------------------------------
• Time constant
--------------------------------
• Function I
• Scale 20 mA
• Scale 4 mA
--------------------------------
• Function S
Relay Output
• Function S
• Type S
• Threshold
• Hysteresis
Opt
Opt
Opt
Opt Opt
Strap Table , 1-20
• Number of points
First 20 pairs Level " Volume
Strap Table, 21-40
Next 20 pairs Level " Volume
Strap Table, 41-50
Last 10 pairs Level " Volume
Calibration Management
----------------------------------­D/A low trim D/A high trim Apply values
----------------------------------­Autodetect tank height Record tank empty spectrum
Basis Parameters
• Tank height
• Block distance
• Antenna
• Distance piece
--------------------------------
• Stillwell
• ID Stillwell
--------------------------------
• Reference offset
• Tank bottom offset
Device/HART
• Model
• Manufacturer
• Field device revision
• Software revision
• Hardware revision
• Firmware version
• Firmware ident.nr.
• Write protect
Rd
Rd
Rd
Rd
Rd
Rd
Rd
Rd
--------------------------------
• Tag
• Polling address
• Device ID
• Universal revision
• Num request preams
Rd
Rd
Rd
• Num response preams
• Final asmby num
• Date
• Descriptor
• Message
--------------------------------
• PV is
• SV is
• TV is
•
Process Input
--Measurements/Cfg data--
• Length unit
• Length fo rmat
• Conversion unit
• Conversion format
Loc
Loc
----- Strap Table ------------
• Level unit
• Level format
• Volume unit
• Volume format
Loc
Loc
---------------------------------
• Time constant
Service
• Min Peak
• OF Threshold
• HP Filter
• LP Filter
• Sweep
Opt
Opt
• Empty spect. Type
• Min Window
--------------------------------
• Offset
• Corr. Factor
• Max Tankheight
• Fct digital input
Opt
--------------------------------
• Serial No
• Option 1
• Option 2
KROHNE BM 70 A/P /700 /702 45f9 0b02
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
9/10
Page 10
Attachment C
Remote Operation Instructions BM 70 A/P, BM 700, BM 702 HART
AMS Transmitter Modes
AMS device mode number
Hardware Setting of “PV is”
(Primary Variable code)
“Number of Points”
(in conversion table) 0 BM70 A, BM70 P any, except “SW Output S” > 1 1 BM70 A, BM70 P only “SW Output S” > 1 2 BM70 A, BM70 P any, except “SW Output S” < 2 3 BM70 A, BM70 P only “SW Output S” < 2 4 BM700, BM 702 Any > 1 6 BM700, BM 702 Any < 2
NOTE: modes with indices 5 and 7 are never used/invoked for 0x0b02 revision and are therefore excluded from the table.
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ! D-47058 Duisburg Tel.: 0203-301 0 ! Fax: 0203-301 389 · e-mail: [email protected]
10/10