Keyence BL-180 Series, BL-185, BL-180SO, BL-185SO User Manual

A58-001
No part of this document is to be reproduced or utilized in any form or by any means without the written consent of KEYENCE Corporation.
The contents of this document are subject to revision without notice. If you have any problems or questions regarding this document, please contact
one of the KEYENCE offices listed on the last page of this document. KEYENCE is not responsible for any results of the application of the product. If the document contains incomplete printing, it can be exchanged for a complete
one.
• MS-DOS is a registered trademark of Microsoft U. S. A.
• MS-Windows is a trademark of Microsoft U. S. A.
• Other company names and product names are registered trademarks or trade­marks of the respective companies.
iii
Contents
Introduction ......................................................................................................................vii
Unpacking ........................................................................................................................vii
Safety Precautions ..........................................................................................................vii
Conventions .....................................................................................................................vii
System Configuration ....................................................................................................viii
Parts and Functions .......................................................................................................viii
Chapter 1: Connection and Installation
BL-180 Connections ..........................................................................................................2
Wire colors and signal types ............................................................................................................................2
Power supply wiring .........................................................................................................................................2
Wiring I/O .........................................................................................................................................................2
RS-232C Connections ..................................................................................................................................... 3
Installing the BL-180 Series ..............................................................................................6
Chapter 2: Functions for Reading Operation
Read Operation ................................................................................................................10
Scanning method ...........................................................................................................................................10
Data-send mode ............................................................................................................................................. 11
Read modes .....................................................................................................................12
Single label read mode .................................................................................................................................. 12
Multi-label read mode 1 (Multi 1) .................................................................................................................... 12
Multi-label read mode 2 (Multi 2) .................................................................................................................... 13
Multi-label read mode 3 (Multi 3) .................................................................................................................... 13
Label orientation mode ...................................................................................................16
Test Mode .........................................................................................................................17
STABILITY LEDs ..............................................................................................................19
Preset Function (Compare with:) ...................................................................................20
What is the preset function? ........................................................................................................................... 20
Wildcard symbols (“!” and “?”) ........................................................................................................................20
Additional Information ....................................................................................................21
Max. Code Length (Designated Digit )
Output Function ...............................................................................................................23
Chapter 3: Setup Software
Controlling the BL-180 ....................................................................................................26
Setup Software Requirements .......................................................................................................................26
Operating Procedure .......................................................................................................28
Outline of Operation ....................................................................................................................................... 28
Setup Software Operating Procedure ............................................................................29
File Operation ................................................................................................................................................. 30
Main setting screen ........................................................................................................................................ 32
CODE39 setup ............................................................................................................................................... 33
ITF setup ........................................................................................................................................................ 34
Setup for Industrial 2 of 5 and COOP 2 of 5 .................................................................................................. 34
iv
Codabar setup ............................................................................................................................................... 35
UPC/EAN setup ............................................................................................................................................. 36
CODE128 setup ............................................................................................................................................. 36
Trigger input setting ....................................................................................................................................... 37
Communication setting .................................................................................................................................. 38
Communication strings setup ......................................................................................................................... 38
Other setting .................................................................................................................................................. 39
Sending Settings ............................................................................................................................................ 40
Version Display .............................................................................................................................................. 40
List of Error Messages ................................................................................................... 41
How to Use Terminal Software ...................................................................................... 42
Chapter 4: Serial Communication (RS-232C/RS-422A)
Serial Communication .................................................................................................... 46
Communication Setup .................................................................................................................................... 46
Details on Data Communication .................................................................................... 47
Communication Protocols(Hardware handshaking) ....................................................................................... 47
Capacity of Transmission Buffer .................................................................................................................... 48
Read Data Format ......................................................................................................................................... 48
Read Error Code ............................................................................................................................................ 49
Command Communication ............................................................................................ 50
Setup of Direct Control Commands ............................................................................................................... 50
Explanation of Direct Control Commands ...................................................................................................... 51
Details on Parameter Setting Commands ...................................................................................................... 52
Response Error Code .................................................................................................................................... 53
Description of Parameter Setting Commands ................................................................................................ 53
Appendix
Specifications .................................................................................................................. 62
Reading Range Characteristics (Typical) ..................................................................... 63
Angular Characteristics (Typical) .................................................................................. 64
Dimensions ...................................................................................................................... 65
Example Program for Serial Communication ............................................................... 67
Troubleshooting .............................................................................................................. 6 8
CODE128 Specifications ................................................................................................ 70
ASCII Code Table ............................................................................................................ 71
Default Settings ...............................................................................................................72
BL-U1
Introduction ..................................................................................................................... 78
Conventions ....................................................................................................................78
System Configuration ..................................................................................................... 79
Using the RS-232C and RS-422A ................................................................................................................. 79
Using the RS-485 multidrop link .................................................................................................................... 79
Other Options ................................................................................................................................................. 79
BL-U1 ............................................................................................................................................................. 80
BL-U1 Connections ......................................................................................................... 81
Connecting the AC power supply ................................................................................................................... 81
Connecting the BL-U1 to a BL series ............................................................................................................. 81
v
Setting the BL-U1 DIP switches ..................................................................................................................... 82
Function and wiring on the I/O terminal block ................................................................................................ 83
RS-232C port pin assignment ........................................................................................................................ 84
RS-232C port wiring .......................................................................................................................................85
RS-422A port wiring ....................................................................................................................................... 85
Wiring the RS-485 (multidrop link) .................................................................................................................86
Installation ........................................................................................................................87
Precautions before use ..................................................................................................................................87
Installing the BL-U1 ........................................................................................................................................88
Outline of Multidrop Link ................................................................................................89
Multidrop Link .................................................................................................................................................89
System Configuration .....................................................................................................................................89
Setup and Connection Procedures ................................................................................90
Communication ................................................................................................................91
Outline of Communication types ....................................................................................................................91
Communication Format ..................................................................................................................................91
Details on Data Communication ..................................................................................................................... 93
Details of Command Communication ............................................................................................................. 95
Precautions for Programming ........................................................................................97
BL-U1 Specifications ......................................................................................................98
vi
Introduction
Thank you for choosing the BL-180 series CCD bar-code reader . This User’ s Man­ual describes details on operations and functions of the BL-180. Read this manual carefully to maximize the BL-180 performance.
Unpacking
There are two packages: A BL-180 package and a software package. Each package contains the following components. Be sure to check the items
against the checklist below:
BL-180 package
BL-180 unit 1 Mounting bracket 1 Mounting bracket screw (8 mm) 2 Instruction manual 1
Setup software (BL-18H1E) and user’s manual
Setup software floppy disk (3.5-inch) 1 User’s Manual (this document) 1
The setup software and user’s manual are not included in the BL-180 package. You can order the software package, free of charge, separately.
Safety Precautions
Be sure to observe the following precautions when using this unit:
• Do not use the BL-180 as a controller for equipment which could potentially harm a person.
• Be sure to match the polarities (+ and -) of the power supply when soldering the connections. Reversing the polarities will damage the unit.
• Do not disassemble the BL-180. Doing so may make repair impossible.
• This is a precision instrument. Dropping the unit could damaged it. Exercise caution when moving or installing.
• For shipping, a protective seal covers the optical pickup. Remove this before use.
• Be sure that there is no water, oil or dust on the optical pickup. Such obstruc­tions can cause read errors. Clean the pickup by gently wiping with a soft lens cloth soaked with water.
Conventions
This document uses the following conventions to help you easily recognize impor­tant and useful information.
Important information which must be read to avoid damaging the unit.
Provides information for effective use of the unit. Read as required. Any reference to the BL-180 in this manual refers to information on all products in
the BL-180 series. When refering to specific product information, the product name exclusively will be used.
Note
CAUTION
Note
vii
System Conguration
The 5 VDC power supply unit must be purchased separately. The optional BL-U1 or BL-U2 power supply is also available.
Parts and Functions
BL-180
BL-180/185
RS-232C
OK/NG output
RS-232C null modem cable OP-22149 (1.5 m) + OP-25057 (25- to 9-pin adapter)
IBM PC/AT or compatible
BL-18H1E Setup software
3.5-inch version WINDOWS 3.1
Trigger input
PLC etc.
5VDC
Power-supply unit*
Timing sensor
Note
OK/NG STABILITY
BL-180
OK output: Lights in green. NG output: Lights in red.
STABILITY LED Indicates reading stability (see P. 31).
Cable (2 m)
Light source/optical pickup
Light source LED Lights during reading
viii
Chapter 1
Connection and Installation
1.1 BL-180 Connections
2
1.1 BL-180 Connections
1.1.1
Wire colors and signal types
The following wires extend from the BL-180. Solder the required wires to a con­nector to connect the BL-180 to a computer/controller.
1.1.2
Power supply wiring
• Be sure to match the polarities of the power supply when soldering the con­nections. Reversing the polarities will damage the unit.
• Make sure that the power supply provides a stable 5 VDC ± 5%. If the power supply does not function in the above range, it can damage the unit.
• Do not use a power cable longer that 2 meters. A long power cable can cause a voltage drop, preventing the BL-180 from starting properly.
• If the power supply is UL rated, it must provide Class 2 output.
1.1.3
Wiring I/O
Trigger (TIM) input
The trigger input is used to signal the BL-180 to start reading (Start laser emis­sion). The trigger input is a non-voltage input (TTL input is also available).
Wire Color
Symbol Description Signal Direction
Shield
Shield Connect to ground (SG) ——
Purple RS-
232C
SD (TXD) Send data Output Brown RD (RXD) Receive data Input Pink RS (RTS) Request to send (always on) Output Blue CS (CTS) Request to receive Input
Black GND (SG)
Ground (common ground for respective signals)
——
Yellow TIM Trigger input Input White OK OK output Output Gray NG NG output Output Red + 5V + 5V power supply input Input
5VDC
BL-180
+5V
Red
GND
Black
+
CAUTION
GND
TIM
Yellow
Black
5VDC
10K
4.7 K
BL-180
Internal circuit
With or without relay
1.1 BL-180 Connections
3
OK/NG output
This output signals whether the readout data is the same as the preset data. When no preset data has been registered, the signal indicates bar code read sta­tus. It is an NPN open-collector output.
1.1.4
RS-232C Connections
This BL-180 setup software applies to port 1 and port 2 only. Communication cannot be performed with another port.
When using a D-sub 9-pin connector:
Use a metallic connector housing for the D-sub 9-pin connector. Connect the shielded cable with the connector housing.
When using a D-sub 25-pin connector:
Be sure the BL-180s shielded cable is properly connected. Refer to 1.1.3 Con­necting shielded cables in the Users Manual.
GND
OK/NG
Write/Gray
Black
Load
BL-180
1k
*Rated load: 24 VDC (100 mA) max.
+
Internal circuit
Note
Purple
Shield
Blown
Blue Pink
Black
Red
5VDC
BL-180
SD RD CS RS
GND
+5V
PC
2
3 7
5 4
8
6
RD
Shield Connector case
SD RS CS SG DR ER
D-sub 9-pin (male)
# 4-40 screw
+
Purple
Shield
Blown
Blue Pink
Black
Red
5VDC
BL-180
RD SD CS RS
GND
+5V
PC
2
1
3 4
7 6
5
20
SD
Shield FG
RD RS CS SG DR ER
D-sub 25-pin (male)
M 2..6 screw
+
Note
1.1 BL-180 Connections
4
Hints on correct use
Trigger (TIM) input
Set the trigger input to be long enough to allow the laser beam to cover the entire bar code.
If the trigger input needs to be on for only a short period of time, select one-shot mode.
Influence from mirror surface
If a mirror surface (metallic surface) is near the bar code and the laser beam re­flects off the mirror, the BL-180 may cause a read error. Protect the unit from the influence of a mirror surface by covering the surface or changing the bar code la­bel position.
Bar code pitch
Do not place several bar codes in the field of the laser beam, unless you are in multi-label read mode (Multi 3).
If you use multi-label read mode (multi 3), the BL-180 can simultaneously read 2 to 4 bar codes in the field of the laser beam.
Influence from photoelectric sensor
When using a photoelectric sensor to control trigger, block the sensor beam so it does not enter the BL-180 optical pickup.
The beam from the photoelectric sensor can interfere with the BL-180, deteriorat­ing reading performance. If this case, reposition the photoelectric sensor.
OK/NG STABILITY
BL-180
Optical pickup
Light source
Object
Bar code
OK/NG STABILITY
BL-180
1.1 BL-180 Connections
5
Bar code height
The bar code height must be at least 3 mm. However, adjust any bar code of 3 mm or more height so that it is arranged from one end to the other on the light­receiving axis.
Light­receiving axis
3 mm or more
1.2 Installing the BL-180 Series
6
1.2 Installing the BL-180 Series
Installation method
Use the mounting holes on the side panel to install the unit. To prevent dust from entering the unit, seals have been placed over the screw holes. Remove the seals before mounting.
Using the supplied mounting brackets
Install the BL-180 Series as shown in the figures below. BL-180 pattern 1 BL-180 pattern 2
(BL-185)
Select screws of the proper length by checking the thickness of the plate used for mounting. (The screws provided are for use with the mounting bracket.)
For the mounting hole diameter, see page 65.
Installation with no mounting bracket
(BL-180) (BL-185)
Prepare M3 male screws separately.
Although the mounting holes are on both sides of the unit, only one side should
be mounted.
For the mounting hole diameter, see page 65.
Do not insert screws into the BL-180 by 5 mm or deeper. Doing so may damage the unit parts.
Select screws of the proper length by checking the thickness of the plate used for mounting.
M3 screws
M3 screws
M3 screws
CAUTION
1.2 Installing the BL-180 Series
7
Mounting angle and mounting distance
BL-180
Set the angle and reading distance by referring to the read range characteristics and angle characteristics described on page 63 and 64.
The allowable reading distance and angle may vary depending on the narrow bar width of the bar code, the bar code size, and the readability of the bar code. Set these parameters after performing a test read of the required bar code using the unit.
Do not set the unit at an angle at which the light-receiving axis is perpendicular to the surface of the bar code. The beam will be fully reflected into the reader, mak­ing correct reading impossible (see page 64).
Set the angle so that the light-receiving axis will be centered on the bar codes. Bar codes of insufficient height may deviate from the desired position in relation
to the light-receiving axis. Be sure to position the unit carefully. (The bar codes must have a height of at least 3 mm.)
The reading check test mode (see page 17) allows you to set the optimal reading position.
15.3
12.5
10°
BL-180
BL-185
Light-receiving axis
33
Note
1.2 Installing the BL-180 Series
8
Chapter 2
Functions for Reading Operation
2.1 Read Operation
10
2.1 Read Operation
2.1.1
Scanning method
There are two methods for triggering the BL-180 to read bar codes; the “Level sig­nal” method and the “One-shot signal” method. The example given for these two methods uses the “single label read mode” (see page 12), which reads one bar code while trigger input turns on once, and uses the “after read” as the data-send mode (see page 11).
Level signal trigger
When the trigger input turns on, LED emission begins and the the unit begins reading. The LED turns off after reaching the specified decode count. Then, the unit sends the readout data.
1. Set trigger input so that it stays on long enough for the LED beam to cover
the entire bar code.
2. After the trigger input exceeds the preset input time, the LED begins to emit.
3. The communication time can be obtained from the following expression:
4. The length of time that the OK/NG output is on can be changed to between
10 ms and 2.55 s.
5. The OK/NG output turns on 5 ms after the data has been read (or trigger
input turns off in case of reading failure).
Trigger input
Bar code
LED beams
Communication time
OK/NG output OK/NG NG
<Succeed to read> <Fail to read>
*2
*1
*3
*4
*5
Data bits + (1: If parity is used) + Start/stop bit
Baud rate
(code length of data to be sent + Header/ number of characters in delimeter)
X
2.1 Read Operation
11
One-shot signal trigger
The unit detects the rising edge of the trigger input and starts reading bar codes for the preset input time. The LED beam turns off after reaching the specified de­code count and the unit sends the readout data.
The remaining actions are the same as those for level signal trigger.
1. After the trigger input exceeds the preset input times, the LED begins to emit.
The BL-180 can read up to 4 types of bar codes without changing the bar code type setting (see page 32).
For general operation, see "Level signal trigger"
Choose One-shot signal trigger when the trigger input signal is very short or
you want to set the input time.
2.1.2
Data-send mode
In the single label read mode only, you can select from the two data send modes (OK/NG output on trigger) described below: In the multi-label read mode, you can only select the send after reading mode.
Send after read
The unit outputs the communication and OK/NG signals after a sucessful read (trigger output turns on as many times as the preset decode count). This is the same operation as in the time chart described in 1.1 Scanning method. Normal­ly, this is the method you should use.
Send at trigger input
The unit outputs the communication and OK/NG signal when the trigger input turns off (or the preset input time has passed if one-shot signal trigger is selected).
OK/NG NG
<Succeed to read> <Fail to read>
Trigger input
Bar code
*1
Preset input time
Preset input time
LED beams
Communication time
OK/NG output
Note
OK/NG
NG
<Succeed to read>
<Fail to read>
Trigger input
Bar code
LED beams Communication time
OK/NG output
2.2 Read modes
12
2.2 Read modes
The BL-180 provides 4 types of read modes.
2.2.1
Single label read mode
This mode allows the unit to read one bar code during one trigger input signal. The operation and timing chart are described on page 10.
2.2.2
Multi-label read mode 1 (Multi 1)
This mode allows the unit to read several bar codes printed on one label as shown below during one trigger input signal. The unit outputs the readout data sequen­tially.
Multi-label read mode 1 operation
In the multi-label read mode 1, the unit reads several bar codes continuously, and outputs them sequentially as it reads while LED beam remains on and trigger in­put turns on after bar codes have been read (or during the preset input time if one­shot signal trigger is selected).
To prevent the unit from reading the same bar code twice, the time for one bar code to pass across the LED beams field and read, plus the repeat reading time must be set (100 ms to 25.5 s). During the repeat reading time, the unit cannot read the same bar code repeatedly, but can read different bar codes.
A reading error is issued only when the unit cannot read any bar code while the trigger input is on.
For OK/NG output, “OK” turns on every time the unit reads a bar code and “NG” turns on if the unit fails to read a bar code. (Comparison to the preset data is not performed.)
Repeat reading time
OK
NG
<Succeed to read> <Fail to read>
Trigger input
Bar code
LED beams Communication time
OK/NG output
OK OK OK
2.2 Read modes
13
2.2.3
Multi-label read mode 2 (Multi 2)
As with multi 1 mode, this mode allows the unit to read several bar codes contin­uously while the trigger input is on. (The number of bar codes that can be read depends on the buffer capacity. See page 48.) The difference between the two modes is that multi 2 modesends all the readout data at one time after the trigger input turns off.
Multi-label read mode 2 operation
Multi 2 mode allows the unit to read several bar codes while the trigger input is on (or during the preset input time if one-shot signal trigger is selected) and sends all the readout data at one time after the trigger input turns off (or after the preset input time is expired if one-shot signal trigger is selected).
To prevent the unit from reading the same bar code twice, the time for one bar code to pass across the LED lights field and read, plus the repeat reading time must be set. During the repeat reading time, the unit cannot read the same bar code repeatedly, but can read different bar codes.
For OK/NG output, after trigger input turns off, OK turns on if the unit reads at least one bar code and “NG” turns on if the unit fails to read a bar code. (Compar­ison to the preset data is not performed.)
Reading data format
Each data packet is separated by a comma (, : 2CH) (intermediate delimiter). The unit sends as many data packets the number of bar codes read. See page 46 for header string and delimeter.
2.2.4
Multi-label read mode 3 (Multi 3)
As described in multi-label read modes 1 and 2, this mode also allows the unit to read several bar codes (up to 4 codes) while the trigger input is on.
The unit sends the readout data at one time according to a specified sequence after the trigger input turns off. When up to 4 codes are in the LED beams field, the unit can simultaneously reads all of them.
Repeat reading time
12345
12345
OK
NG
<Succeed to read> <Fail to read>
Trigger input
Bar code
LED beams
Communication time
OK/NG output
Header
1st
data
,
2nd
data
,
3rd
data
,
4th
data
, Delimeter
2.2 Read modes
14
Operation of multi-label read mode 3
This mode allows the unit to continuously read each one of 4 bar code types Code 1, Code 2, “Code 3, and Code 4 as specified in the code setup of the setup software (see page 32). If 3 types are specified in the code setup, the unit reads 3 bar codes (each of 3 types). If 2 types are specified, the unit reads 2 bar codes.
The following time chart is given.
The above example chart is with all four codes specified in the code setup of the setup software.
The bar code reading sequence is not xed.
The unit communicates the readout data in the order of Code 1 to Code 4.
After the trigger input turns off, the unit sends all the data at one time.
For OK/NG output, OK turns on if the unit reads all the specied Codes 1 to 4 and NG” turns on if the unit fails to read at least one bar code. (Comparison to the preset data is not performed.)
Reading data format
Each data packet is separated by a comma (, : 2CH) (intermediate delimiter).
If an read error occurs on any one of Codes 1 to 4, or the corresponding bar
code does not exist, ERROR (see page 49 for the reading error codes), instead of the read data is sent.
See page 48 for header string and delimeter.
Example Suppose that the following codes are specified:
Code 1 --- CODE39, 10 digits Code 2 --- EAN/UPC, 13 digits Code 3 --- None Code 4 --- CODE39, 8 digits
When the unit successfully reads all 3 types of codes:
When the unit fails to read Code 1 (CODE39, 10 digits)
When the unit fails to read Code 1 (CODE39, 10 digits) and Code 4 (CODE39, 8 digits)
When the same type of data having the same digits is specified to all Codes 1 to 4, the unit sends the data in the reading order.
OK
Trigger input
Bar Code
LED beams Communication time
OK/NG output
Code 1 Code 2 Code 3 Code 4
Code 1
Code 2
Code 3
Code 4
NG
Header
Data read
from Code
1
,
Data read
from Code
2
,
Data read
from Code
3
,
Data read
from Code
4
, Delimeter
Header ABCDE12345 , 4901234567894 , KEYENCE Delimeter
Header ERROR , 4901234567894 , KEYENCE Delimeter
Header ERROR , 4901234567894 , ERROR Delimeter
2.2 Read modes
15
Example Suppose that the following codes are specified: Code 1 --- CODE39, 7 digits
Code 2 --- CODE39, 7 digits Code 3 --- CODE39, 7 digits Code 4 --- CODE39, 7 digits
The unit cannot read the bar code having the same content twice while trigger in­put turns on once.
Header
ABCD123 , XYZ3333 , 1234567 , KEYENCE , Delimeter
Note
2.3 Label orientation mode
16
2.3 Label orientation mode
As shown below, this mode allows the unit to read bar codes only in the specified orientation when bar code labels are moving both in the forward and reverse ori­entations.
Normally, the unit can read bar codes regardless of the orientation.
An reading error is issued when the unit reads a bar code label running in the ori­entation which is not specified.
The above chart applies to the single label read mode. You can also use this mode together with the desired multi-label read mode. However, in any case, the unit reads bar codes running in the specified orientation only.
You can specify the orientation individually for Codes 1 to 4, such as specifying forward orientation for Code 1, and reverse orientation for Code 2.
4 9000000
4 9000000
Forward orientation Reverse orientation
OK/NG
STABILITY
BL-180
OK/NG
NG
<Specified orientation>
<Non-specified orientation>
Trigger input
Bar code
LED beams Communication time
OK/NG output
2.4 Test Mode
17
2.4 Test Mode
Test mode can be used for the bar code reading test. Because trigger input is not required, this mode allows you to perform a reading test easily. You can select one of the following 3 methods to enter the test mode.
Send the command
Enter test mode by sending the serial command for the test mode (TEST1, TEST2). Commands should be entered in all uppercase characters.
Turning on trigger input
You can use the BL-180 to switch to test mode by turning on the trigger input (see page 35). If you select this method to enter the test mode, trigger input is disabled to ensure normal operation.
Turning on power supply
You can set the BL-180 to enter test mode by turning on the power supply (see page 37).
When you try to enter the test mode by turning on trigger input, you cannot use the serial command to enter the test mode.
The following 2 types of test modes are available:
Reading rate check mode
The unit scans a bar code100 times and analyzes how many times it can decode the scanned data (reading rate). This mode is useful in the following cases:
When adjusting the mounting distance and angle
When verifying the reading stability of the bar code to be used
The analyzed result will be output anytime (every 100 scans) using the follow-
ing format:
m = 0 to 100 (zero-suppressed)
Although an OK/NG signal is not output, the OK/NG LED lights (see page 19).
Tact check mode
In this test mode, the unit counts how many scans can be decoded (the decode count) while reading one bar code.
This mode is useful when testing which line speed can be expected when actually implementing the BL-180 system on the line.
The analyzed data is output using the following format 0.2 seconds after the bar code has passed the LED beams eld.
m = 1 to 999 (zero-suppressed)
The unit continues to read a bar code while the code is in the LED beams field and does not output the result. If the LED beam does not detect a bar code for
0.2 seconds, the unit stops scanning and outputs the result.
If the unit reads the same bar code twice within the 0.2 seconds, the unit can­not separate the bar codes and will add to the read count. However, the unit can continuously reads different bar codes within the 0.2 seconds by recogniz­ing the delimiter.
Note
Delimiter
Readout data
: m %
Delimiter
Readout data
: m
2.4 Test Mode
18
The read count can be up to 9999.
Although an OK/NG signal is not output, the OK/NG LED lights (see page 19).
When the unit is running in test mode, the LED beam remains on, which can shorten the LEDs service life. Select the test mode only when you need to perform a test read.
Avoid long emission times. When using the additional information (see page 21 to 22) in the test mode, the
selected data is added in the same manner as in the normal operation mode. However, only when selecting the reading rate check mode, the decode count and scan count are not added to the analyzed results.
Note
2.5 STABILITY LEDs
19
2.5 STABILITY LEDs
STABILITY LEDs allows you to easily check reading stability. STABILITY LEDs light only when the test mode gets started or the decode count
adding function (see P. 34) is used.
Indication of reading stability
When reading rate check mode is selected
STABILITY LEDs light according to the reading rate shown in the table below. Al­though, in the test mode, the unit does not output an OK/NG singnal, the OK/NG LED lights as below. (Comparison to the preset data is not performed.)
When tact check mode is selected
STABILITY LEDs light according to the scan count (decode count), which indi­cates the number of successful reads, as shown in the table below.
Although, in the test mode, the unit does not output an OK/NG signal, OK/NG LED lights as below. (Comparison to the preset data is not performed.)
When using the decode count adding function
STABILITY LEDs light as shown in the table below according to the decode count.
OK/NG output (OK/NG LED) turns ON/OFF based on the result of comparison to the preset data.
When you do not use the decode count adding function or use the multi-label read mode 3, STABILITY LEDs do not light.
Reading rate
STABILITY LED OK/NG LED
80 to 100%
Green Green 50 to 79% Orange Green 20 to 49% Red Green
1 to 19% —— Green
0% —— Red
Decode count
STABILITY LED OK/NG LED
50 or more
Green Green (decode counts are
equal to or greater than the preset match count) Red (decode counts are less than the preset match count)
10 to 49 Orange
5 to 9 Red 1 to 4 ——
0 —— Red
Decode count
STABILITY LED
50 or more
Green
10 to 49 Orange
5 to 9 Red
4 or less ——
CAUTION
2.6 Preset Function (Compare with:)
20
2.6 Preset Function (Compare with:)
2.6.1
What is the preset function?
The BL-180 can store one bar codeas preset data. It compares the preset data to the bar code data actually read and outputs an OK/NG signal to whether there is a match.
Using the BL-180 preset function, you can prevent the wrong products from en­tering the line without using a PC.
If no preset data is registered, the unit outputs OK when it successfully reads a bar code and NG when it fails to read a bar code.
See page 10 to 16 for output timing.
Use the setup software and serial command to register the preset data (see
page 39 and page 59).
The bar code actually read can be compared to the preset data only in the sin­gle label read mode.
See page 70 if you want to use CODE128.
2.6.2
Wildcard symbols (“!” and “?”)
Using ! and ? in the preset data allows for flexible settings.
?:
Does not define numeric values (characters) of certain digit(s) of the bar code.
!:
Ignores numeric values and symbols within the dot box and recognizes the bar codes as the same group.
Setting examples
1. “ABC?” ABCD (OK), ABC3 (OK), ABC (NG), ABCDE (NG)
2. “ABC!” ABCD (OK), ABC3 (OK), ABC (OK), ABCDE (OK), AB (NB)
3. “?????” Any 5-digit bar code will be OK.
4. “!CDE” ABCDE (OK), 3CDE (OK), CDE (OK), ABBDE (NG), ADE (NG)
5. “A!E” ABCDE (OK), A3CE (OK), ABCD (NG), AE (OK)
You can use ! only once in the setting.
If you do not register preset data, “!” is automatically registered. Therefore, when the unit sucessfully reads a bar code, “OK” is output; when the unit fails to read, NG is output.
You cannot use the * character as a wild card symbol with the BL series.
Note
4912 3456 4912 5256 4912 AB5 6
4912 3456 4912 C 4912
When using “?” data as “4912??56”, 2 digits positioned in ?? can contain any numeric values (or characters), expanding the allowable range. Iden­tifies all the bar codes to be OK as long as the beginning or ending strings match.
When using ! as 4912!, any bar code which begins with “4912” will be OK. When using ! as !4912, any bar code which ends with 4912 will be OK.
Note
2.7 Additional Information
21
2.7 Additional Information
When sending the bar code data, you can add the following data to the readout data.
Additional information types
Decode match count add function
Adds the number of successful scans during one bar code reading (decode count) to the end of the readout data (up to 9999 count). However, this decode count is never less than the preset decoding match count.
This function can be used to check reading stability and code label quality.
d = [Decoding match count] to 9999: Decode count
The value is zero-suppressed.
When using this function, output turns on at a different time from normal opera­tion.
In single label read mode, output turns on after one bar code has been read (after trigger input turns off). Even if you set the data-send to “after read”, the data is forced sent after trigger input turns off.
In multi-label read mode 1, a bar code passes across the LED beams eld, after repeat read time, and is nally output.
In multi-label read mode 2 or 3, operation is the same as when you do not use the decode match count adding function.
When you use the decode count adding function, STABILITY LEDs light to show reading stability (see P. 31).
Scan count add function (valid only when using the read count add func­tion)
Adds the number of scans, including when no bar code exists, to the end of the decode count (up to 9999).
Code type add function
Adds the bar code type before the readout data .
Delimiter
Readout data
: d
Note
m = 1 to 999 (zero-suppressed)
The value is zero-suppressed.
Delimiters
Readout data
: d / s
t = 0 :Code39
1 :ITF 2 :Industrial 2 of 5 3 :Codabar 4 :EAN/UPC (AE) 5 :CODE 128 6 :COOP 2 of 5 7 :Read error
Delimiter
t
:
Readout data
2.7 Additional Information
22
label orientation add function
Adds the orientation of bar code travel before the readout data.
Order of additional information
If you select to include all the additional information functions, they appear in the following order:
You can change the delimiter as desired (one character), except the delimiter of the scan count.
4 9000000
4 9000000
Forward orientation Reverse orientation
OK/NG
STABILITY
BL-180
r =F :Forward
R :Reverse
If an read error occurs, this information is not added.
Delimiter
r
:
Readout data
Code type
:
label
orientation
: Readout data :
Decode match
count
: Scan count
Note
2.8 Max. Code Length (Designated Digit ) Output Function
23
2.8 Max. Code Length (Designated Digit ) Output Function
This function allows you to output the designated digit(s) as desired from the readout bar code data. For example, from bar code data “49123456”, you can ex­tract 1234 for output.
Setting digits to be output
Set the digits to be output as shown below. Individually set the digits for codes 1 to 4.
1. Set the direction to designate. Set from which direction you want to start counting.
2. Set from which digit you want to begin designation (destination start digit).
3. Set how many digits you want to designate for output starting from the desig­nation start digit in (2) (designation effective digits).
Example Designating and outputting 34 from bar codes 158423421 and 58423421
Designate 2 digits starting from 3rd digit by counting reversely.
Regardless of the designated direction, the data is output forward in the com-
munication application.
When the bar code group includes those having different digits, take special
care on the designated direction when setting the digits to be output.
When comparing to the preset data, all the digits of the bar code are used.
4 9 1 2 3 4 5 6
Forward Reverse
4 9 1 2 3 4 5 6
5th digit by counting forward
4 9 1 2 3 4 5 6
3 digits starting from 5th digit by counting forward
1 5 8 4 2 3 4 2 1
5 8 4 2 3 4 2 1
Note
2.8 Max. Code Length (Designated Digit ) Output Function
24
Chapter 3
Setup Software
3.1 Controlling the BL-180
26
3.1 Controlling the BL-180
The BL-180 can be controlled by computer using an RS-232C serial communica­tion with Windows™ Terminal software or using BL-180 Setup Software. This chapter describes how to set the BL-180 using the BL-180 setup software. For more information on using the serial communication, see “Chapter 4” on page 45.
3.1.1
Setup Software Requirements
The BL-180 Setup Software for Windows operates in the following environments:
Personal Computer
IBM PC/AT or compatible model (100% compatible) CPU: 80386 or higher Memory: 4 MB or more Floppy drive: One or more 3.5 inch drives RS-232C: One serial port (COM 1 or COM 2) DOS: Windows 3.1
* The BL-180 Setup Software applies to COM 1 only.
Starting the setup software
1. Prepare the following items before starting.
• BL-180
• Power supply unit for BL-180 (5 VDC) or the BL-U1
• RS-232C cable described on p. 2 to 4 in this manual
• Setup software
• Personal computer
• Mouse
2. Connect the PC with the BL-180 or BL-U1 using the RS-232C cable.
3. Set the DIP switches on the BL-U1 to RS-232C when you use the BL-U1.
4. Install the setup software. Turn the PC’s power switch ON to start Windows.
5. Insert the setup software into the floppy disk drive.
6. Select File - Run on the menu bar of the program manager.
7. When the following screen appears, type the name of the floppy disk drive and the name of the installed file “SETUP” in the “Command Line”. After typ­ing the above, click on the OK button.
Example When the floppy drive is drive A, type as follows:
A:\SETUP
Then, the target directory for installation is displayed.
“C:\BL180”
is displayed.
3.1 Controlling the BL-180
27
8. To accept the directory name, click on the OK button.
9. To change the directory name, click on the column displying the directory name, type a desired directory name using the keyboard, and click on the
OK
buttonAfter the installation is completed, the “KEYENCE Barcode
Reader” window is created in the program manager. In this window, icon “BL18WIN” is created.
10. To start the setup software, double-click on the “BL18WIN” icon.
11. After the setup software gets started, the following screen appears:
When using a monochrome display on a laptop PC, the display appears in re­verse video. To make the display clearer, set the laptop’s display to reverse video and then restart the setup software.
Note
3.2 Operating Procedure
28
3.2 Operating Procedure
3.2.1
Outline of Operation
To operate the setup software, place the mouse pointer on the item to be changed, and click the left button of the mouse.
Use the Down Arrow button to select an item from a list. Place the mouse pointer on a desired item, and click on the item.
Click on the Option button to select one of several items.
In the above settings, Read mode is set to “Single” and Data-send is set for “At trigger input.”
The Check Box is used to enable special functions. An “X” in the Check Box indi­cates that a function has been enabled.
In the above settings, “Inspect check-digit[Modulus43]” is enabled. To enter characters or a value in a field, insert the mouse pointer over the field.
The pointer will change to a cursor. Click inside the field and type in the desired value.
If the specified value exceeds the setting range, an error message will appear
To shift to a different screen, click the mouse cursor one of the buttons in the win­dow. For example to return to the previous screen, click on the button.
3.3 Setup Software Operating Procedure
29
3.3 Setup Software Operating Procedure
After the setup software is started, the following screen (main setting screen) is displayed.
The function of each display is as follows.
The setup software provides the following setting screens according to the pa­rameters.
Main setting [Main]
• Type of the bar code to be read
• Read mode and its setup
• Decoding match count
• Additional information
Setting details for the specified code type [Code setup]
• Setting No. of bar code length, inspection of check-digit, etc.
Trigger input setup [Setup Trigger input]
• Setting the operation mode and the trigger input
• Selecting the test mode starting method
• Setting characters for the trigger ON/OFF command
Communication parameters [Setup comm]
• Setting the baud rate, data bits, stop bit and parity
• Setting the protocol
• Setting the Communication strings (header string, delimiter, read error code,
etc.)
Utility [Utility]
• Setting the beeper
• Duration of OK/NG output
• Registration of preset data
For the operating procedure, see “Setup Software Operating Procedure” on page 29.
For the error messages displayed during operation, see page 41.
Title (Name of the current setting screen)
Current file name The initial file name is “Untitled. CFG”.
Menu bar (*)
Parameter
Setting screen selector buttons
3.3 Setup Software Operating Procedure
30
Menu Bar
The following operations can be performed using the menu bar.
File Menu (Alt+F)
Specifies a file name/Saves a file. Exits the setup software.
Send Settings (Alt+S)
Sends settings to the BL-180.
Info (Alt+I)
Indicates the version number of this software.
3.3.1
File Operation
The following is the procedure for specifying a file name, saving a file or exiting the setup software.
Click on File in the menu bar. The following menu appears.
New
Cancels the current setting file and calls the initial setting.
Open
Calls the previously stored file.
Save As
Saves a file with a specified file name.
Save
Saves a file.
Exit
Exits the setup software.
New
1. Click on New. The following message appears.
2. To cancel the current settings and call the initial setting, click on the OK but­ton. If you wish not to execute this operation, click on Cancel
.
3.3 Setup Software Operating Procedure
31
Open
1. Click on Open .
2. The following screen is displayed for selection of the file to be read.
Select a desired file from those listed in the file selection column, and click on the OK button.
If you wish to cancel this operation, click on the Cancel button. To change the directory or drive, select a desired directory or drive in the di-
rectory/drive selection column.
3. When you click on the OK button on the above screen, the following mes­sage appears.
To cancel the current setting and call a new file, click on the OK button. If you wish not to execute this operation, click on the Cancel button.
Save As
1. Click on Save As .
2. The “Save As” screen appears.
3. Click in the file name entry field and type a file name using the keyboard. Type a file name of up to 8 characters. Be sure to add extension “CFG” to the file name.
3.3 Setup Software Operating Procedure
32
Example When the file name is “TEST”:
1. Click on the file name entry column.
2. Enter “TEST. CFG” as the file name .
3. Click on the OK button. If you wish cancel this operation, click on the Cancel button. To change the directory or drive, select a desired directory or drive in the directory/drive selection column.
4. If the specified file name has already been stored, the following message will appear.
To save the setting by overwriting the existing file, click on the OK button. If you wish not to save the setting, click on the Cancel button.
Save
A file name must be entered before the file can be saved
1. Click on Save . The file will be saved.
Exit
1. Click on Exit . The following message appears.
2. To e xit the setup softw are, clic k on the OK button. If y ou wish cancel, clic k on
Cancel .
Save the current settings before exiting the setup software.
3.3.2
Main setting screen
1. Place the mouse cursor at the item to be changed and click it, or move to the target item by pressing [TAB] . Then, change the setting using [Space] .
2. To codes 1 to 4, specify the types of bar codes to be read. If you specify 4 different types of bar codes, the BL-180 can read them with­out changing the settings.
3. To set the code length or the inspect for check-digit, click Setup or press
[ENTER] to move to the setup screen for each code (see page 33 to 36).
3.3 Setup Software Operating Procedure
33
4. When selecting Single for Read mode, the following appears on the screen:
When selecting Multi 1 or Multi 2, the following appears on the screen:
Set the time within the range from 1 to 255 (100 ms to 25.5 s). When selecting Multi 3, none of the above information appears.
5. In the Additional information field, you can select one or more items. How­ever, the scan count is given only when the decode count is selected.
Read mode --> Page 12 Data-send --> Page 11 Repeating-reading time --> Page 12 Decoding match count --> Page 10 Additional information --> Page 21
3.3.3
CODE39 setup
When setting CODE39 to any one of codes 1 to 4 and trying to set details, this setting screen appears.
1. Place the mouse cursor at the item to be changed and click it, or move to the target item by pressing [TAB] . Then, change the setting using [Space] .
2. Setting Max code length and Min code length allows the BL-180 to read bar codes having the specified range of digits. If you want to read bar codes with the specific code length, set the same value to both Max code length and Min code length.
The allowable setting range is 3 to 32 digits including the start/stop character.
3. When you select Send start/stop character, * is added to the data when being sent.
Note
3.3 Setup Software Operating Procedure
34
4. When you select Inspect check-digit, the following information appears:
The above setting sends the data together with the check-digit. Modulus 43 is used to calculate the check-digit.
5. When you select Max code length output, the following information appears:
Set Effective and Starting from 1 to 32.
6. When you select Specify label orientation, the following information appears:
7. Click the Return button or press [ENTER] to return to the main setting screen.
Max. code length output --> Page 23 Specify label orientation --> Page 16
3.3.4
ITF setup
1. Setup is the same as the CODE39 setup. However, ITF does not have Start/ stop character.
2. Set code length using a even value within the range from 2 to 32.
3. Modulus 10/Weight3 is used to calculate the check-digit.
When reading the standard distribution code (bar code on the corrugated fiber­board box), set the code length to 14 or 16 and select the Inspect check-digit.
3.3.5
Setup for Industrial 2 of 5 and COOP 2 of 5
1. Setup is the same as the CODE39 setup. However, a start/stop character and Inspect check-digit are not provided.
2. Set code length within the range from 1 to 32.
Note
Note
3.3 Setup Software Operating Procedure
35
3.3.6
Codabar setup
1. Set code length from 3 to 32 including the start/stop character.
2. When you select Send start/stop character, A, B, C, and D are added to the data to be sent.
In this case, the following information appears:
You can select lowercase or uppercase for the start/stop character.
3. When you select Inspect check-digit, the following information appears:
Specify the check-digit calculation method and whether or not the check-digit is sent.
4. Set the other parameters in the same manner as for CODE39.
3.3 Setup Software Operating Procedure
36
3.3.7
UPC/EAN setup
1. Select Read EAN 8 code, Read UPC-A[EAN13] code or Read UPC-E to enable to read.
If you select Read UPC-A[EAN13] code, the following information appears, asking you to select which digits you want to output on UPC-A.
If you select Read UPC-E, the following information appears, asking if you want to send data with the leading zero-suppressed.
2. Y ou can use the same setting procedure as f or CODE39 f or Max code length output and Specify label orientation. However, the setting range of Effective and Starting in Max code length output is limited to the code length of the readout UPC/E code.
• Although the check-digit parameter is not provided on the screen, the system
internally calculates it using modulus 10/Weight3. (The calculated data is sent.)
3.3.8
CODE128 setup
1. The setting range of code length depends on the start character type CODE­A to C (see page 70).
• CODE-A and B --- 1 to 32
• CODE-C --- 2 to 64 The code length does not include the start/stop character or check-digit. Also, FNC1 to 4 (function codes), SHIFT, and CODE-A to C are excluded from the code length.
3.3 Setup Software Operating Procedure
37
2. Check that the double-character start pattern is regulated in the UPC/EAN­128 standard. It means the combination of start character (CODE-C) and FNC1 (function code 1). The standard specifies that the UPC/EAN-128 bar codes should start with the double character start pattern.
Using this parameter, you can specify that reading will not start without the double character start pattern.
3. Y ou can use the same setting procedure as f or CODE39 f or Max code length output and Direction. However, the setting range of Effective and Starting in Max code length output is 1 to 64 if the start character is CODE-C.
• Although the check-digit parameter is not shown on the screen, the system
internally calculates it using modulus 10/Weight3. (The calculated data is not sent.)
3.3.9 Trigger input setting
1. Place the mouse cursor at the item to be changed and click it, or move to the target item by pressing [TAB]. Then, change the setting using [Space].
2. Select Level synchronization or One-shot synchronization as the scanning method. When you select One-shot, the following information appears, ask­ing you to set the scanning time:
Set the scanning time within the range from 1 to 255 (100 ms to 25.5 s).
3. When you select “Test mode initiated with trigger input ON” or “Test mode ini­tiated at startup,” the following information appears, asking you which test mode you want to start:
If you select both “Test mode initiated with trigger input ON” and “Test mode initiated upon power-up,” “Test mode initiated with trigger input ON” is used.
4. In the Command for trigger input parameter, you can freely change the char­acters for the Trigger ON/OFF command (within 8 characters).
Normally, you should use the default setting (Lon, LOff).
5. Click the Return button or press [ENTER] to return to the main setting screen.
Scanning method --> Page 10 Starting the test mode --> Page 17 Trigger ON/OFF command --> Page 51
Note
3.3 Setup Software Operating Procedure
38
3.3.10 Communication setting
1. Place the mouse cursor at the item to be changed and click it, or move to the target item by pressing [TAB]. Then, change the setting using [Space].
2. When setting the header string, delimeter, and read error, click [Communica­tion strings] or press [ENTER] to move to the communication strings setting screen.
3. Click the Return button or press [ENTER] to return to the main setting screen.
(Communication) protocol --> Page 47 The setup software does not allow you to set the baud rate to 19200 to 38400 bit/
s. If you want to set the baud rate within this range, use the serial commands (see page 58).
3.3.11 Communication strings setup
1. Place the mouse cursor at the item to be changed and click it, or move to the target item by pressing [TAB]. Then, change the setting using [Space].
2. Select appropriate values for Header string and Delimiter from among the displayed items. When you select Custom, the following appears:
Then, you can enter the desired value from the keyboard (within 5 charac­ters).
Note
3.3 Setup Software Operating Procedure
39
3. When you select Default[:] for Partition mark and Intermediate delimiter, these parameters are set as below:
When you select Custom, the following appears:
Then, you can enter the desired value from the keyboard (using one character for the partition mark and 5 characters or less for the intermediate delimiter).
4. Input the Read error using the keyboard. You can change the code as desired (within 8 characters).
Normally, you should use the default setting (ERROR). You can chose not to send the read error by selecting a null value for the read error.
5. Click the Return button or press [ENTER] to return to the communication setting screen.
Header string, delimeter --> Page 48 Partition mark --> Page 21 Intermediate delimiter --> Page 13 Read error --> Page 48
3.3.12 Other setting
1. Place the mouse cursor at the item to be changed and click it, or move to the target item by pressing [TAB]. Then, change the setting using [Space].
2. By setting Bepper for OK/NG output, the beeper beeps to indicate reading stability during the normal reading operation.
3. To set OK/NG output duration, enter the appropriate numeric value from the keyboard. The setting range is from 1 to 255 (10 ms to 2.55 s).
4. To set Compare with, enter the preset data to be registered from the key­board.
Usually, specify the data within 32 characters. If you are using CODE128 and the start character is CODE-C, you can set the data using up to 64 characters.
5. Click the Return button or press [ENTER] to return to the main setting screen.
STABILITY LED --> Page 19 OK/NG output duration --> Page 10 Preset data --> Page 20
Note
Note
3.3 Setup Software Operating Procedure
40
3.3.13 Sending Settings
1. Choose Send from the menu bar. The following screen appears.
2. Set the baud rate, data bits, stop bit and parity according the BL-180’s set­tings. The BL-180’s default settings are shown above.
3. Specify whether the parameter settings are to be saved in the EEPROM or not. If the current settings are not saved in the EEPROM, the setup software will start with the previous settings when the power is turned on again.
4. After setting the communication parameters, click on OK. Data transmission will begin. If a communication error occurs, the following message will appear.
If you are not sure of the communication parameter settings of the BL-180, turn ON the BL-180’s power switch before executing data transmission, and set the communication parameters as shown in step 1.
* The BL-180’s communication parameters are set as shown above for 5 seconds after the power is turned ON. (see page 46.)(See p. 58 of the Users’ Manual.)
5. If the setup software is normally exited, it will return to the main setting screen.
3.3.14 Version Display
1. Click on Info on the manu bar.
2. The following screen appears, where you can confirm the version of this setup software.
3.4 List of Error Messages
41
3.4 List of Error Messages
If an error occurs, the following messages will appear on the screen. Click on OK and delete the error message. Then, take the necessary corrective
action.
Error message Cause of error
Error during file operation
File not found. The file specified for Open Setting does not exist.
Drive is not ready. The specified disk is not prepared.
Write protected. Overwrite protection is set to the disk.
Insufficient disk space.
The remaining disk capacity is insufficient. Replace the disk.
Illegal filename (must be in format of xxxxxxxx.CFG.)
The file name does not have extension CFG. Enter the file name correctly.
Illegal file. Use a correct file name.
Path not found. The pass for the specified file is invalid.
Device not ready. The specified drive is invalid.
Insufficient memory. The main memory capacity is insufficient.
Device I/O error The disk may be damaged or unformatted.
This is not BL-180 setting file.
The stored file data are incorrect. Specify a correct file name. Data of the BL-180 setup file are different from that of the BL-180. These files are not for common use.
Error in detailed code data.
The stored file data are damaged. Specify a ne w file name.
Error during setup
Communication error
An error occurred during communication. The parameter settings (e.g. baud rate) may not be matched, or the connection may be incorrect.
Value out of range.
The specified value is exceeding the setting range. Enter a correct value.
Min. code length is set larger than Max. code length.
The minimum code length is set larger than the maximum code length. Enter a correct number.
Device is unavailable.
The serial port is being used for a device other than the BL or else “Terminal” is running.
3.5 How to Use Terminal Software
42
3.5 How to Use Terminal Software
The terminal software allows bar code data to be displayed on a Windows-based personal computer and allows serial commands to be sent to the BL-180.
You can use the standard terminal software included in Windows Ver. 3.1. This section describes how to use the terminal software to confirm the operation of the BL-180.
For more information on the terminal software and its functions, please refer to theWindows manual.
1. Double-click on the Terminal icon in the Accessory Group.
The terminal software starts up.
2. When the terminal software is started, the following screen appears.
3. First, set the terminal software. When you click on Settings, the following menu appears.
3.5 How to Use Terminal Software
43
4. When you click on Terminal Preferences, the setting screen is displayed. Set the displayed parameters as shown below. After setting the parameters, click on OK.
5. Then, Click on Settings then Communications. The following screen appears.
After setting “Connector” to COM1 or COM2, set the baud rate, data bits, stop bits and parity according to the BL-180’s settings. When the data bits is set to “8 bits”, the parity can only be set to “None.”
After setting the communication parameters, click on [OK].
6. When the BL-180 reads a bar code, the read data is displayed on the screen. (When the BL-180’s delimiter is set to CR, data will be displayed with car­riage returns. Control codes cannot be displayed.)
7. To send a command, type TEST1/TEST2 using the keyboard, and then press [ENTER]. All commands should be in entered in all uppercase charac­ters. Refer to pages 51 to 52 for available commands and for descriptions of each commnad. In read rate display test mode (TEST 1 mode), the entered command is diffi­cult to see on the screen because the BL-180 is displaying the read data. However, the command will be correctly sent.
8. To exit the terminal software, click on F
ile then Exit.
Multi drop link commands cannot be sent. RTS/CTS protocol commands cannot be confirmed.
When you start up “Terminal”, you cannot send the setting to BL using SETUP software. Quit on close “Terminal” before you send the setting.
Note
3.5 How to Use Terminal Software
44
Chapter 4
Serial Communication (RS-232C/RS-422A)
4.1 Serial Communication
46
4.1 Serial Communication
The BL-180 communicates with the PC via the RS-232C serial port. This enables you to change the BL-180’s settings from your PC.
Communication T ypes
The BL-180 provides the following two communication types:
Data communication
Sends read bar code data from the BL-180 to the PC.
Command communication
Changes the BL-180s settings by sending a command from the PC to the BL-
180. All communication is performed using ASCII codes.
4.1.1
Communication Setup
Configure the setup for BL-180 and the PC before attempting serial communica­tion.
Setup of BL-180
Set the following parameters for the BL-180 using the setup software. Baud rate, Data bits, Parity, Stop bit, Communication protocol, Header/Delimiter,
Read error code
PC setup
Based on the BL-180s settings, set the communication parameters on the PC us­ing the Ports setting in the Windows Control Panel.
The following communication parameters are the default settings for the BL-180: Baud rate: 9600 bps
Data bits: 7 bits Parity: Even Stop bit: 1 bit
Set the PC according to the above settings before attempting communication. The BL-180 is set, temporarily, to the default settings for 5 seconds after the pow-
er switch is turned on. When the current settings of BL-180 is not certain, send the command SSET
and a [CR] to the BL-180 from your PC with 5 seconds after power-up. This caus­es the BL-180 to remain at its default settings and you can communicate with the BL-180 at the default settings.
For information on checking the BL-180s current settings, see Details on Param­eter Setting Commands on page 52. For information on changing the above communication parameters see Description of Parameter Setting Commands on page 53.
Data communication can be performed with the current parameter settings even for 5 seconds after the power is turned on.
All commands should be entered in all uppercase characters. The BL cannot ac­cept lowercase characters.
Note
Note
4.2 Details on Data Communication
47
4.2 Details on Data Communication
4.2.1
Communication Protocols(Hardware handshaking)
The BL-180 supports the following four handshaking protocols.
No Handshaking
The BL-180 sends read data to the PC without using any handshaking protocol.
PASS/RTRY Handshaking
After sending the read data, the BL-180 waits for a response from the PC. The response is either a PASS command or a RTRY command.
The PASS command (quit) indicates that the PC has successfully received one data packet. The BL-180 then prepares for the next data transmission.
The RTRY command (request to re-send) indicates that the data was not trans­mitted successfully. The command is a request to the BL-180 to re-send the data. The BL-180 sends the same data again and then waits for the response.
After the BL-180 once receives PASS, the BL-180 sends back no data even if RTRY is sent to the BL-180.
The BL-180 can continue to read while waiting for the PASS command. The data is stored in the BL-180s transmission buffer (For the capacity of the transmission buffer, see page 48).
If the amount of stored data exceeds the capacity of the transmission buffer, the BL-180 sends back <Header> OVER <Delimiter> to the PC, and clears all data stored in the transmission buffer. For more information, see Capacity of Trans­mission Buffer on page 48.
The BL-180 can receives other commands while waiting for the PASS command. In this case, the BL-180 sends back an immediate response (e.g. OK).
When the SSET command (see 4.3.3 on page 52) is sent to the BL-180 while the BL-180 is waiting for the PASS command, the BL-180 clears the data stored in the transmission buffer, and enters the setting mode.
ACK/NAK Handshaking
The ACK/NAK handshaking uses ACK (06H) and NAK (15H) instead of PASS and RTRY used in the PASS/RTRY handshaking, respectively. With these proto­cols, the BL-180 sends back different characters, but performs the same opera­tion.
Read data
(PASS , RTRY )
C
R
C
R
Read data
Response
Note
4.2 Details on Data Communication
48
RTS/CTS Handshaking
When the PCs RTS (BL-180s CTS) signal turns off, the BL-180 becomes ready for data transmission. When the PCs RTS signal turns on, the BL-180 starts data transmission.
When the PCs RTS signal is off, the BL-180 can still read. In this case, data is stored in the BL-180s transmission buffer (see 4.2.2 below).
If the amount of stored data exceeds the capacity of the transmission buffer, the BL-180 sends back <Header>OVER<Delimiter> to the PC, and clears all data stored in the transmission buffer.
The RTS/CTS handshaking cannot be used for RS-422A communication. The RTS/CTS protocol can be used together with other handshaking protocols. When the PCs RTS signal is off, the BL-180 does not sends back a response to
the PC.
4.2.2
Capacity of Transmission Buffer
The BL-180 s transmission buffer can store 400 bytes (400 characters). The number of characters stored in the transmission buffer for each data packet
is the number of characters in the data (including additional data such as the num­ber of decoding match count) plus an additional five characters indicating the da­tas attributes.
When multi label reading mode 2 or 3 is used, these five attribute characters are added to each data packet.
Example 1
When the number of bar code digits is 10 (with no additional data) 400 ÷ (10 + 5) = 26 The transmission buffer can store 26 pieces of data.
Example 2
When the number of bar code digits is 20 (with no additional data) 400 ÷ (20 + 5) = 16 The transmission buffer can store 16 pieces of data.
4.2.3
Read Data Format
Set the data format of the Header and Delimiter, respectively.
With the setup software, the following formats can be selected. Other than the fol­lowing formats, you can freely set up to 5 characters.
Header
ESC (1BH)/STX (02H)/None
Delimiter
CR (ODH)/CR (ODH) LF (OAH)/ETX (O3H)
Note
Header Read data Delimiter
4.2 Details on Data Communication
49
4.2.4
Read Error Code
If the BL-180 fails to read a bar code, the B-500 sends back a read error code. The initial setting of the read error code is as follows:
The read error code can freely be changed (within 8 characters). The BL-180 can be set to send no error code (see page 38).
Header
ERROR Delimiter
4.3 Command Communication
50
4.3 Command Communication
The BL-180 includes commands to directly operate the BL-180 (direct control commands) and the commands used to change or confirm the BL-180s settings (parameter setting commands).
4.3.1
Setup of Direct Control Commands
Communication procedure
1. Send a direct control command from the PC to the BL-180.
2. After receiving the command, the BL-180 sends back an OK response and executes the required operation. When the read operation control command or test mode control command is sent to the BL-180, the BL-180 sends back no response.
3. When an incorrect command is sent to the BL-180, the BL-180 sends back no response.
LF
can be added after the command being sent. In this case, however, LF is not
added to the response data. When ESC is inserted before the command being sent, characters in the BL-
180s command receiving buffer are cleared. If the BL-180s command receiving buffer contains erroneous characters due to
data transmission error during communication, add ESC to the command being sent.
For command communication, set the time duration between transmission of each character (byte) to up to 30 seconds. If this duration exceeds 30 seconds, the BL-180 cancels the received characters.
Command
Response
Note
Note
4.3 Command Communication
51
4.3.2
Explanation of Direct Control Commands
The following describe direct control commands in details.
Read operation control
This command specifies the data read timing.
[LON] Trigger on
Command: LON Response: None
[LOFF] Trigger off
Command: LOFF Response: None
Even when the read operation is controlled with these commands, the BL-180 performs the same operation as with the trigger input (see page 10 to 12).
•“Trigger input: on corresponds to LON , and trigger input: off corresponds to
LOFF .
The BL-180 starts read operation on receipt of LON and stops it on receipt of
LOFF .
When a bar code can be correctly read and the read data has already been set, you need not send LOFF .
The command characters can be freely changed (within 8 characters).
Test mode control
Starts or quits the test mode.
[TEST1] Reading rate check
Command: TEST1 Response: None
[TEST2] Tact check
Command: TEST2 Response: None
[QUIT] Resetting test
Command: QUIT Response: None
After using the test mode, be sure to reset it.
OK/NG output control
Directly turns on/off the OK/NG output. This enables you to easily check wiring.
[OKON] Turning the OK output on
Command: OKON Response: OK
[NGON] Turning the NG output on
Command: NGON Response: OK
[ALLOFF] Turning the OK/NG outputs off
Command: ALLOFF Response: OK
4.3 Command Communication
52
Clearing transmission buffer
[BCLR] Clears data stored in the transmission buffer.
Command: BCLR Response: OK
Shift to setting mode
[SSET] Enters the setting mode (see page 51).
Command: SSET Response: OK
4.3.3
Details on Parameter Setting Commands
The following describes how to change the BL-180s settings through command communication.
You can use the setup software to change the BL-180s settings instead of these commands.
Communication Details
1. Send the direct control command SSET to the BL-180. The BL-180 will shift to setting mode. After successfully executing the command, the BL-180 sends back an OK .
2. After the BL-180 shifts to setting mode, send the command (setting change command) corresponding to the item to be changed to the BL-180. After successfully executing the command, the BL-180 sends back an OK .
If an error occurs with this command, the BL-180 sends back ERR
nn
. (nn
sttands for error code numbers.)
3. To conrm the current settings, send a setting conrmation command. After successfully executing the command, the BL-180 sends back an OK .
If an error occurs with this command, the BL-180 sends back ERR
nn
.
4. To save the current settings in the EEP-ROM, send SAVE to the BL-180. Once you save the settings in the EEP-R OM, the BL-180 will start with these settings when the BL-180 is turned on next. After successfully executing the command, the BL-180 sends back an OK .
If an error occurs with this command, the BL-180 sends back ERR
nn
.
5. To quit the setting mode and perform the normal bar code reading, send
SEND to the BL-180.
After successfully executing the command, the BL-180 sends back an OK . If an error occurs with this command, the BL-180 sends back ERR
nn
.
Note [LF] can be added at the end of the command being sent. In this case, however,
[LF] is not added to the response data. When [ESC] is added before the command being sent, characters in the BL-180’s
command receiving buffer are cleared. If the BL-180s command receiving buffer contains erroneous characters due to a
data transmission error during communication, add [ESC] to the command being sent.
For command communication, set the time duration between transmission of each character (byte) to up to 30 seconds. If this duration exceeds 30 seconds, the BL-180 cancels the received characters.
Note
4.3 Command Communication
53
4.3.4 Response Error Code
When an incorrect command is sent to set parameters, the BL-180 sends back data indicating the cause of the error (error code). For the commands correspond­ing to the error codes, see the error code column given in the table on the follow­ing pages.
4.3.5 Description of Parameter Setting Commands
Saving/Initializing Settings/Quitting Setting Mode
Error code Cause of error
00 Undened command. 01 Command format is incorrect. 02 Nothing corresponds to the number in the command. 03 m value (codes 1 to 4) is other than 0 to 3.
04
Bar code type setting command was not sent rst. Sending No. of readable digits setting command is invalid
for JAN code. 05 The number in the command is too long. 06 hhh...” data is too short. 07 n value is not 0 or 1. 08 n value is exceeding the setting range. 09 nnn or nn” value is exceeding the setting range. 10 hhh...” is not specified in HEX (hexadecimal) code. 11 hhh...=FF cannot be set.
12
hhh...” or aaa...” contains more than the specied number
of characters. 13 Characters of aaa...” are invalid.
14
Data in the EEPROM may be damaged. Perform initial
setup. 15
Error in the area storing initial settings.
Settings are automatically initialized. 17 \ is not followed by !, ? or \ in preset data. (See page 70.) 18 Two !s exist in preset data. (See page 20.) 99 The BL-180 may malfunction. Contact KEYENCE.
Function Command being sent
Respons
e
Description
Error
Code
Saves settings in the EEP­ROM.
SAVE OK See page 51. -
Initializes settings. DFLT OK Returns to the default-settings, and saves the set-
tings in the EEP-ROM.
00,05 14,15
Quits the setting mode. SEND OK See page 51. -
4.3 Command Communication
54
Setting Bar Code Type and Number of Readable Digits for Codes 1 to 4
The following describes the parameter setting commands for Codes 1 to 4. Be sure to send Bar code type setting command first before setting other param-
eters.
When “Bar code type setting command” is newly sent, all other parameters for the specified code will return to the default settings.
In this case, set all other parameters again. Setting change commands and setting confirmation commands are described on
the following pages.
Note
Function command being sent
Respons
e
Description
Error
Code
Setting bar code type for codes 1 to 4.
Change CODEm=n OK m= 0 to 3:Codes 1 to 4
n= 0:CODE 39
1:ITF 2:Industrial2-of-5 3: Codabar 4: UPC/EAN 5: CODE128 6: COOP2-of-5 7: None
00, 01 03, 05 08, 14
Confirm CODEm mn
Setting Max. No. of readable digits
Change MAXm=nn OK m= 0 to 3: Codes 1 to 4
nn= 01 to 32 * For CODE39, Codabar: 03 to 32 * For ITF: 02 to 32 * For CODE128: 01 to 64 Note: With EAN code, this command causes error.
00, 01 03, 04 05, 09 14
Confirm MAXm mnn
Setting Min. No. of readable digits
Change MINm=nn OK Confirm MINm mnn
Sending start/stop character.
Change WCm00n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
00, 02 03, 04 05, 07 14
Confirm RCm00 00n
Inspection of check digit (Modulus 43)
Change WCm01n OK
m= 0 to 3: Codes 1 to 4 n= 0: Disable
1: Enable
Confirm RCm01 01n
Function Command being sent
Respons
e
Description
Error Code
Sending check digit.
Change WCm02n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
00, 02 03, 04 05, 07 14
Confirm RCm02 02n
Inspection of check digit (Modulus 10)
Change WCm10n OK
m= 0 to 3: Codes 1 to 4 n= 0: Disable
1: Enable
Confirm WCm10 10n
Sending check digit.
Change WCm11n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
Confirm RCm11 11n
Sending start/stop character.
Change WCm30n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
Confirm RCm30 30n
Start/Stop character type
Change WCm31n OK m= 0 to 3: Codes 1 to 4
n= 0: Lower case
1: Upper case
Confirm RCm31 31n
Inspection of check digit
Change WCm32n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
Confirm RCm32 32n
Sending check digit
Change WCm33n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
Confirm RCm33 33n
CODE39
CODE39
CODE39
ITF
ITF
Codabar
Codabar
Codabar
Codabar
4.3 Command Communication
55
Setting check digit type
Change WCm34n OK m= 0 to 3: Codes 1 to 4
n= 0: Mudulus16
1: Modulus 11 2: Modulus 10/Wait 2 3: Modulus 10/Wait 3 4: 7 Check DR 5: Modulus 11-A 6: Modulus 10/Wait 2-A
00, 02 03, 04 05, 08 14
Confirm RCm34 34n
Reading UPC-E
Change WCm40n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
00, 02 03, 04 05, 07 14
Confirm RCm40 40n
Reading EAN 8 digits
Change WCm41n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
Confirm RCm41 41n
Function Command being sent
Respons
e
Description
Error Code
Codabar
UPC(A-E)/EAN
UPC(A-E)/EAN
Function Command being sent
Respons
e
Description
Error Code
Reading JAN 13 digits
Change WCm42n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
00, 02 03, 04 05, 07 14
Confirm WCm42 42n
No. of UPC-A output digits
Change WCm43n OK m= 0 to 3: Codes 1 to 4
n= 0:Output in 13 digits
1:Output in 12 digits
Confirm RCm43 43n
Adding “0” to UPC-E system code
Change WCm44n OK
m= 0 to 3: Codes 1 to 4 n= 0: Disable
1: Enable
Confirm RCm44 44n
Checking double character start pattern (See p. 34.)
Change WCm51n OK
m= 0 to 3: Codes 1 to 4 n= 0: Disable
1: Enable
Confirm RCm51 51n
Setting max. code length out­put function
Change WCm83n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
Confirm RCm83 83n
Setting direction for max. code length output
Change WCm84n OK m= 0 to 3: Codes 1 to 4
n= 0: Forward
1: Reverse
Confirm RCm84 84n
Setting effective digits for max. code length output
Change WCm85nn OK
m= 0 to 3: Codes 1 to 4 nn= 01 to 32: Effective digits
00, 02 03, 04 05, 09 14
Confirm RCm85 85nn
Setting starting digit for max. code length output
Change WCm86nn OK m= 0 to 3: Codes 1 to 4
nn= 01 to 32:
Starting digit
Confirm RCm86 86nn
Setting label orientation speci­fied reading
Change WCm81n OK m= 0 to 3: Codes 1 to 4
n= 0: Disable
1: Enable
00, 02 03, 04 05, 07 14
Confirm RCm81 81n
Setting orientation for orienta­tion- specified reading
Change WCm82n OK m= 0 to 3: Codes 1 to 4
n= 0: Forward
1: Reverse
Confirm RCm82 82n
UPC(A-E)/EAN
UPC(A-E)/EAN
UPC(A-E)/EAN
CODE128
4.3 Command Communication
56
Setting Reading Mode/Data Addition Functions
Function Command being sent
Respons
e
Description
Error Code
Setting reading mode Change WP12n OK n= 0: Single label
1: Multi label 1 2: Multi label 2 3: Multi label 3
00, 02 05, 08 14
Confirm RP12 12n
Setting data send timing Change WP13n OK
N= 0: Sends data after reading
1: Sends after timing input turns off
00, 02 05, 07 14
Confirm RP13 13n
Setting repeat-read time in multi label reading mode 1 or 2
Change WP41nnn OK
nnn=001 to 225 (by 100 ms step)
00, 02 05, 09 14
Confirm RP41 41nnn
Setting decoding match count Change WP43nnn OK
nnn=001 to 225
Confirm RP43 43nnn
Setting decoding match count in additional information
Change WP10n OK
n= 0: No addition
1: Add
00, 02 05, 07 14
Confirm RP10 10n
Setting scans in additional information
Change WP11n OK n= 0: No addition
1: Add Note: Effective only when No. of decodings are added.
Confirm RP11 11n
Setting label orientation in additional information
Change WP14n OK
n= 0: No addition
1: Add
Confirm RP14 14n
Setting code type in additional information
Change WP17n OK
n= 0: No addition
1: Add
Confirm RP17 17n
4.3 Command Communication
57
Setting Trigger Input (Starting Test Mode)
To set characters of the trigger on/Off command, send the following command. Example 1: Change the trigger on command to S.
Function Command being sent
Respons
e
Description Error
Code
Setting signal type Change WP05n OK
n= 0: Level
1: One-shot
00, 02 05, 07 14
Confirm RP05 05n
Setting one-shot input time Change WP42nnn OK
nnn=001 to 225
(by 100 ms step)
Confirm RP42 42nnn
Setting time constant of trig­ger input
Change WP04n OK
n= 0: 2 ms
1: 10 ms
Confirm RP04 04n
Setting state of trigger input Change WP03n OK
n= 0: Normal-open
1: Normal-close
Confirm RP03 03n
Starting test mode when trig­ger input turns on. (To specify the test mode, use the command below.)
Change WP06n OK
n= 0: Disable
1: Enable
Confirm RP06 06n
Specifying the test mode to be started when trigger input turns on.
Change TRGTn OK
N= 1: Reading rate check mode
2: Tact check mode
00, 02 05, 08 14
Confirm TRGT TRGTn
Starting test mode when power is turned on.
Change TESTn OK n= 0: Reset
1: Reading rate check mode 2: Tact check mode
Confirm TEST TESTn
Setting characters of trigger on command
Change WP56hhh... OK
hhh...=Trigger on command (Up to 8 characters) * Specify characters in HEX (hexadecimal) code.
00, 02 05, 11 14
Confirm RP56 56hhh...
Setting characters of trigger off command
Change WP57hhh... OK
hhh...=Trigger off command (Up to 8 characters) * Specify characters in HEX (hexadecimal) code.
Confirm RP57 57hhh...
Note
WP5653CR
S
S=53h
4.3 Command Communication
58
Setting Communication Parameters
Function command being sent Respons
e
Description Error
Code
Setting baud rate Change WP35n OK N= 0: 9600 bps
1: 4800 bps 2: 2400 bps 3: 1200 bps 4: 600 bps 5: 38400 bps 6: 31250 bps 7: 19200 bps
00, 02 05, 08 14
Confirm RP35 035n
Setting data bit length Change WP30n OK
n= 0: 7 bits
1: 8 bits
00, 02 05, 07 14
Confirm RP30 30n
Setting parity check * To set the parity type, use the command below.
Change WP31n OK
n= 0: Disable
1: Enable
Confirm RP31 31n
Setting parity type Change WP32n OK
n= 0: Even
1: Odd
Confirm RP32 32n
Setting Stop bit Change WP33n OK
n= 0:1 bit
1: 2 bits
Confirm RP33 33n
Setting handshaking protocol 1 * To specify the protocol, use the command below.
Change WP07n OK
n= 0: No protocol
1: Set protocol
Confirm RP07 07n
Setting handshaking protocol 2 Change WP08n OK
n= 0: PASS/RTRY handshaking
1: ACK/NAK handshaking
Confirm RP08 08n
Setting RTS/CTS handshaking Change WP22n OK
n= 0: Disable
1: Enable
Confirm RP22 22n
4.3 Command Communication
59
Setting Communication strings
To set communication strings, send the following command. Example 1: Set the communication data format to SOH 01 Bar Code Data ACR .
Example 2: Set the read error code to BR.
Example 3: Set no read error code.
Utility Setting (Buzzer, OK/NG output duration, Preset data for compare)
To register the preset data, send the following command. Example: Register ABC123 as preset data.
WP68ABC123CR
Function command being sent Response Description
Error Code
Setting header Change WP51hhh... OK hhh...= Header (Up to 5 characters)
* Specify characters in HEX (hexadecimal) code. * To set no header, hhh...=FF.
00, 02 05, 06 10, 12 14
Confirm RP51 51hhh...
Setting delimiter Change WP52hhh... OK hhh...= Delimiter (Up to 5 characters)
* Specify characters in HEX (hexadecimal) code. * To set no delimiter, hhh...=FF.
Confirm RP52 52hhh...
Setting partition mark when additional information is used.
Change WP50hh OK hh= Partition mark(1 character)
* Specify the mark in HEX (hexadecimal) code. * To set no mark, hh=FF.
Confirm RP50 50hh
Setting intermediate delimiter when multi label reading mode 2 or 3 is used.
Change WP54hhh... OK hhh...=Intermediate delimiter (Up to 5 charac-
ters) * Specify characters in HEX (hexadecimal) code. * To set no intermediate delimiter, hhh...=FF.
Confirm RP54 54hhh...
Setting read error code Change WP55hhh... OK hhh...= Read error code (Up to 8 characters)
* Specify characters in HEX (hexadecimal) code. * To set no read error code, hhh...=FF.
Confirm RP55 55hhh...
Note
WP51013031CR
00SOH
WP52410DCR
CRA
SOH=01h, 0=30h, 1=31h, A=41h, CR=0Dh
WP554252CR
RB
B=42h, R=52h
WP55FFCR
Function command being sent Response Description
Error Code
Setting buzzer Change WP15n OK n= 0: on
1: on when OK output turns on. 2: on when NG output turns on. 3: off
00, 02 05, 07 14
Confirm RP15 15n
Setting OK/NG output duration Change WP40nnn OK nnn= 001 to 255
(by 10 ms step)
00, 02 05, 09 14
Confirm RP40 40nnn
Registration of preset data for compare
Change WP68aaa... OK aaa...= Preset data (Up to 32 characters)
* For CODE128, see page 70. * To delete the preset data, send WP68.
00, 02 05, 12 13, 14 17, 18
Confirm RP68 68aaa...
Note
4.3 Command Communication
60
APPENDIX
A.1 Specifications
62
A.1 Specifications
BL-180/185
The internal settings of the BL-180 series are stored in the EEPROM. (Rewritable up to 10,000 times)
Model
BL-180 BL-185 Model (with connector) BL-180SO(7030) BL-185SO(7031) Scanning direction
Front Side
Light source/Light receiving element
LED/CCD image sensor
Scanning distance
33 mm ± 10 mm
1
(Using narrow bars of at least 0.19
mm in width)
Readable bar width
0.125 to 1.0 mm
2
Maximum label width
80 mm
3
(Using narrow bars of at least 0.19 mm in
width)
PCS
0.45 or more (Reflectance of white part: 75% or more)
Scanning rate
500 scans/sec
Target code
CODE39, ITF, Industrial2-of-5, COOP2-of-5, Codabar,
CODE128, EAN/UPC(A-E)
No. of readable digits
32 digits
Trigger input
Non-voltage input (contact or solid-state) TTL input is
also possible.
Rated load
24 VDC, 100 mA
Ambient light
Sunlight, Incandescent lamp: 10,000 lux,
Fluorescent lanp: 3,000 lux.
Current consumption
300 mA max.
Weight
Approx. 165 g Approx. 180 g
1. 33
±
5 mm when the narrowest bar is less than 0.19 mm.
2. Readable bar width indicates the range of the narrowest readable bar.
3. 60 mm when the narrowest bar is less than 0.19 mm.
OK/NG output
Output type
NPN open collector output
Leakage current (at off)
0.1 mA max.
Residual voltage (at on)
0.5 V max.
Ambient temperature
0 to 40°C
Relative humidity
35 to 85%
Vibration
10 to 55 Hz, Double amplitude in X, Y and Z directions, 2 hours
respectively
Power supply voltage
5 VDC±5%
1
Serial interface
Applied standard
EIA RS-232C port
Synchronization
Start-stop
Transmission code
ASCII
Baud rate
600 to 38,400 bps
Data length
7 bits/8 bits
Parity check
None/even/odd
Stop bit
1/2 bit
1. Use a stable power supply of 5 VDC
±
5%. The BL-U1 Special Power Unit is available as an option.
Note
A.2 Reading Range Characteristics (Typical)
63
A.2 Reading Range Characteristics (Typical)
Mount the BL-180 referring to the figure below. (The BL-185 provides the same characteristics as the BL-180.)
* The readable label width means the bar code length including the bar code mar­gins (quiet zones).
The above range may be reduced depending on the bar code quality. Set the op­timum reading position based on enough reading tests.
OK/NG STABILITY
BL-180
10
55
10
33
80
60
Reading distance (mm)
•••Reading range when narrow bar width is not less than 0.125, less than 0.19 mm.
•••Reading range when narrow bar width is 0.19 to 1.0 mm.
(Measuring conditions)
•The KEYENCE standard bar code is used.
•Skew :-10°
•Pitch : 0°
•Tilt : 0°
Readable label width (mm)
Narrow bar width Reading distance Maximum readable label width
0.125 to 0.19 mm (less than 0.19 mm)
33 ±5 mm 60 mm
0.19 to 1.0 mm 33 ±10 mm 80 mm
CAUTION
A.3 Angular Characteristics (Typical)
64
A.3 Angular Characteristics (Typical)
Mount the BL-180 referring to the data given below. (The BL-185 provides the same characteristics as the BL-180.)
(Measuring conditions)
• The KEYENCE standard bar code is used.
• Reading distance: 33 mm
The skew angles of -5° to +10° are the specular reflection range (dead angles). In this range, bar codes cannot be read, or reading error may occur. Avoid mount­ing the BL-180 series at the above skew angles.
Skew Pitch
Tilt
Narrow bar width
Skew Pitch Tilt
0.125 to 0.19 mm(less than 0.19 mm)
-40° to -5°, +10° to +40° ±15° ±10°
0.19 to 1.0 mm -40° to -5°, +10° to +40° ±15° ±15°
CAUTION
0°
Receiver axis
_
+
OK/NG STABILITY
0°
+
+
0°
Receiver axis
_
A.4 Dimensions
65
A.4 Dimensions
BL-180
BL-185
4
10
4
55
5
10
29
ø10
26 17
2 x 2-M3 Depth: 5 mm or less
Receiver axis
ø4.5 Cable length: 1.8 m
47 20
80
26 17
15.3
33 10
Readable
width
4
6
6
4
55
5
12.5
37
ø10
15 36
55
20
80
3615
33
10
2 x 2-M3 Depth: 5 mm or less
Receiver axis
ø4.5 Cable length: 1.8 m
Readable
width
A.4 Dimensions
66
BL-180 (with mounting bracket)
BL-185 (with mounting bracket)
820
80 (Readable width)
55
9
31
16
33 47
33
7
31
(36)
t=1.6
23.3
10°
55
9
31
16
80 (Readable width)
33 47
33
7
31
(38)
15.7
Receiver axis
10°
1120
Receiver axis
820
80 (Readable width)
55
9
31
16
33 47
7
31
t=1.6
10°
Receiver axis
33
8
(37)
12.5
4.4
4
Note: Detail of slot
A.5 Example Program for Serial Communication
67
A.5 Example Program for Serial Communication
The following is a example program that allows data communication and com­mand communication. Type in a command and press [Enter] to send the data to the BL-180.
Only the QUIT command can be sent by pressing [Q] . Set the BL-180 as follows:
• Header: [STX] Delimiter: [ETX]
• Handshaking protocol: No handshaking or PASS/RTRY handshaking
100 ‘***BL-180 SAMPLE PROGRAM********************************************* 110 CLS 3 120 DAT$=””:RD$=””:CM$=”” 130 OPEN “COM1:” AS #1 140 *BUFFCLR :’***CLEAR BUFFER******************************************** 150 A=LOC(1) 160 IF A<>0 THEN R$=INPUT$(1,#1) :GOTO *BUFFCLR 200 ‘ 210 *MAIN :’***MAIN ROUTINE*********************************************** 220 K$=INKEY$ 230 IF K$<>”” THEN GOSUB *COMMAND 240 A=LOC(1) 250 IF A<>0 THEN GOSUB *RECEIVE 260 GOTO *MAIN 300 ‘ 310 *Receive :’***RECEIVE DATA 320 RD$=INPUT$(1,#1) 330 IF RD$=CHR$(&H02) THEN RD$=”” :’RECEIVE STX 340 IF RD$=CHR$($H03) THEN GOSUB *BARCODE :RETURN :’RECEIVE ETX 350 IF RD$=CHR$($H0D) THEN GOSUB *RESPONSE :RETURN :’RECEIVE CR 360 DAT$=DAT$+RD$ 370 RETURN 400 ‘ 410 *COMMAND :’***SEND COMMAND******************************************** 420 IF K$=CHR$(&H0D) THEN *SEND 430 IF K$=”Q” AND CM$=”” THEN CM$=”QUIT”:GOTO *SEND 440 PRINT K$; 450 CM$=CM$+K$ 460 RETURN 470 *SEND 480 PRINT #1, CM$;CHR$(&H0D); :’SEND COMMAND 490 PRINT:PRINT CM$;”COMMAND IS SENT” 500 CM$=”” 510 RETURN 600 ‘ 610 *RESPONSE :’***DISPLAY RESPONSE DATA TO THE COMMAND******************* 620 PRINT DAT$ ;”IS SENT BACK” 630 DAT$=”” 640 RETURN 700 ‘ 710 *BARCODE :’***DISPLAY BAR CODE DATA*********************************** 720 PRINT DAT$ ;”IS READ” 730 DAT$$=”” 740 RETURN
A.6 Troubleshooting
68
A.6 Troubleshooting
If a problem occurs during operation, please check the following troubleshooting notes first. If you cannot fix the problem, contact KEYENCE or your nearest deal­er.
Bar codes cannot be read.
Check whether the light source LED is ON.
When using a power supply other than the BL-U1 special power supply unit, con­firm that the power supply voltage and capacity is within 5 VDC±5% and 300 mA. Check the wiring of the power supply unit and the timing input terminal (see p. 11).
Connecting the power supply unit with the reverse polarity may damage the BL series. If the BL-180 does not operate, contact KEYENCE.
Check the bar code setting (type, No. of digits).
Check the following parameters using the setup software.
• Bar code type, No. of digits.
• Setting of the check digit inspection (enabled or disabled)
• Setting of the label orientation-specified reading
when using CODE39 or Codabar, include the start/stop characters and check dig­it in the number of digits.
For Code128, see page 70.
Check the distance and angle between the BL-180 and bar code.
Check the distance and angle while referring to “Mounting angle and mounting distance” on page 7.
Check the bar code margins (quiet zones).
A bar code requires the right and left margins to be at least 10 times wider than the narrow bar width.
If the bar code margins are too narrow, it may not be read.
Check the bar code label length.
The bar code label length is the lateral length of a bar code including the right and left margins (quiet zones).
When the narrow bar width (the minimum bar width) is 0.125 to 0.19 mm (less than 0.19 mm), the readable label length is up to 60 mm length. When the narrow bar width is 0.19 to 1.0 mm, the readable label length is up to 80 mm.
Check the bar code.
A bar code with blurred sections, defects or stains may not be read correctly. Bar codes printed with dot matrix or ink jet printers are prone to such problems.
CAUTION
Note
A.6 Troubleshooting
69
Check whether the transmitter (light source) and the receiver (optical pickup) are clean.
If moisture, oil or dust adheres to the transmitter or the receiver, wipe the units using a soft cloth and a mild plastic cleaner.
Check whether the protective label is attached to the transmitter or the receiver.
Remove the protective label before using the BL series. Check whether the protective label is attached to the transmitter or the receiver.
Check the environmental conditions.
See “Hints on correct use” on page 4.
Reading rate check mode is not 100%.
Check the previous item “Bar codes cannot be read”.
The Read rate indicates the number of acceptable decodings (reads) during 10 scans of a bar code. When a bar code has stains or defects, the read rate is re­duced.
However, even when the read rate is 20%, 2 decodings are possible during 10 scans. Therefore, if the number of decode matches is 2, the bar code can be read.
If the trigger input can be set enough long, the read operation is not affected.
Initial settings cannot be sent to the BL-180 series using the setup software.
• Check whether the communication parameters such as baud rate and data length conform to the settings of the BL-180.
• Check whether the pin assignment of RS-232C cable conforms to those of the BL-180 and the PC. Check that the cable isn’t disconnected. Also check the BL-U1’s connection.
• Check whether the BL-180’s or BL-U1’s power switch is on.
• Check whether the PC’s RS-232C interface is “enabled”.
• If you are using the BL-U1, check that its DIP switches are set to RS-232C.
Note
A.7 CODE128 Specifications
70
A.7 CODE128 Specications
Setting No. of Digits
• The start/stop character and check digit are not included in the number of dig­its.
• FNC1 to 4 (Function codes), SHIFT, and CODE-A to -C should not be added to the number of digits.
• The number of digits setting range varies depending on the start character (CODE-A to -C).
CODE-A, B: 1 to 32
CODE-C: 2 to 64
One digit of CODE-A or CODE-B represents two digits of CODE-C.
Data T ransmission
• The start/stop character and check digit cannot be sent.
• FNC1 to 4 (Function codes), SHIFT, and CODE-A to -C cannot be sent.
• Control codes are sent.
Registration of Preset Data
The number of characters that can be registered as preset data is up to 32 digits for CODE-A or CODE-B, and up to 64 digits for CODE-C, as described above.
When ! or ? is registered as preset data, it functions as the Preset “!” “?” Function, as described on page 20 .
Since CODE128 can represent all ASCII codes as bar code data, ! or ? can also be represented as bar code data.
To register ! or ? as preset data, send \! or \? to differentiate it from the Preset “!” “?” function.
To register \ as preset data, send \\.
Example: To register 123 \!?ABC as preset data, send the following command (see
page 57). WP68123 \\\!\?ABC Control codes (00h to 2Fh of the ASCII code table, such as and <STX>), start/
stop character, check digit, FNC1 to 4 (function codes), SHIFT or CODE-A to-C cannot be registered as preset data. (Data comparison is also impossible.)
A.8 ASCII Code Table
71
A.8 ASCII Code Table
Upper 4 bits
HEX
0
1 2 3 4 5 6 7
Binary 0000
0001 0010 0011 0100 0101 0110 0111
Lower
4 bits
0
0000 DLE (SP) 0 @ P p 1 0001 SOH DC1 ! 1 A Q a q 2 0010 STX DC2 2 B R b r 3 0011 ETX DC3 # 3 C S c s 4 0100 EOT DC4 $ 4 D T d t 5 0101 ENQ NAK % 5 E U e u 6 0110 ACK SYN & 6 F V f v 7 0111 BEL ETB 7 G W g w 8 1000 BS CAN ( 8 H X h x 9 1001 HT EM ) 9 I Y i y
A 1010 LF SUB * : J Z j z B 1011 HM ESC + ; K [ k { C 1100 CL
,
< L \ l |
D 1101 CR
-
= M ] m }
E 1110 SO
.
> N ^ n ~
F 1111 SI
/
? O _ o del
A.9 Default Settings
72
A.9 Default Settings
In the main setting screen, the default bar code selections for the four bar code fields are as shown below.
Bar Code Default Settings
Below are the default settings for each bar code setting screen.
CODE 39
ITF
A.9 Default Settings
73
2of5
Codabar
UPC-EAN
A.9 Default Settings
74
COOP 2opf5
CODE 128
Read Mode/Data Addition Functions default settings
A.9 Default Settings
75
Trigger input default settings
Communication Parameters default settings
Communication strings default settings
A.9 Default Settings
76
Utility default settings
BL-U1
Power Supply
Introduction
This User’s Manual describes the operation and functions of the BL-U1. Read this manual carefully to ensure safe use and maximum performance from your BL-U1.
Note: No part of this document is to be reproduced or utilized in any form or by any
means without the written consent of KEYENCE Corporation. The contents of this document are subject to revision without notice. If you have any problems or questions regarding this document, please contact one of the KEYENCE offices listed on the last page of this document. KEYENCE is not responsible for any results of the application of the product. If the document contains incomplete printing, it can be exchanged for a complete one.
• MS-DOS is a registered trademark of Microsoft U. S. A.
• MS-Windows is a trademark of Microsoft U. S. A.
• Other company names and product names are registered trademarks or trade­marks of the respective companies.
Conventions
This document uses the following conventions to help you easily recognize impor­tant and useful information.
Important information which must be read to avoid damaging the unit.
Provides information for effective use of the unit. Read as required.
CAUTION
Note
79
System Configuration
Using the RS-232C and RS-422A
• If not using the BL-U1, prepare an equivalent 5 VDC power supply unit sepa­rately.
• To communicate through the RS-422A, you need a BL-U1 in your system.
Using the RS-485 multidrop link
• To communicate through the RS-485, you need a BL-U1 in your system.
• Prepare a RS-485/RS-232C convertor separately.
• When using the RS-485 multidrop link, you cannot use the Windows™ Setup software.
Other Options
OP-22149
RS-232C null modem cable with D-sub 25-pin connector (1.5 m). To connect the BL-U1 to a IMB PC/AT compatible using the RS-232C port, use a 25- to 9-pin adapter (OP-25057).
BL series
RS-232C
BL-U1 Power supply unit
RS-422A
OK/NG output
BL-18H1E Setup software
3.5-inch version WINDOWS 3.1
Trigger input
PLC etc.
Equipment with
RS-422A*
Timing sensor
RS-232C null modem cable OP-22149 (1.5 m) + OP-25057 (25- to 9-pin adapter)
IBM PC/AT or compatible
BL series
L-U1
RS-485
RS-232C
Maximum number of connected units: 31 Maximum extension distance: 1.2 km
RS-485/RS-232C convertor
PC
80
BL-U1
123
OK/NG LED OK output: Lights in green. NG output: Lights in red.
TIMING LED Lights when trigger input turns ON.
POWER LED
Communication status indicator LEDs Indicate the communication status of each communication signal line. Each LED lights when the corresponding signal turns ON. Show SD, RD, RS, and CS from the top.
I/O terminal block Contains I/O terminals and RS-422A/RS-485 terminals.
DIP switches
Power switch Power cable (2 m) Use 100 to 240 VAC (50/60 Hz).
RS-232C port Connects to a PC.
READER port Connects to a bar-code reader
Power Supply BL-U1
83
1 BL-U1 Connections
1.1
Connecting the AC power supply
Plug the BL-U1 power cable into the power receptacle. At the same time, ground the frame ground wire.
Make sure that the power supply provides 100 to 240 VAC ± 10%.
1.2
Connecting the BL-U1 to a BL series
Use the READER port on the BL-U1. The pin assignment is shown in the table below:
UL-U1 READER port pin assignment
FG line
CAUTION
21345
6789
D-sub 9-pin (male) DCE specification (defined as modem) #4-40 screw (female)
Pin No. Symbol Description
Signal
direction
1
TIM
Trigger input
Output
2 RD (RXD)
Send data through RS-232C
Output
3 SD (TXD)
Receive data through RS-232C
Input
4 OK
OK uotput
Input
5 GND (SG)
Ground (common ground for respective sig­nals)
——
6
NG
NG uutput
Input
7 RS (RTS)
Enable to send data through RS-232C (always ON)
Input
8 CS (CTS)
Request to send data through RS-232C (control method can be selected by DIP switches)
Output
9 +5V
+ 5VDC power supply
Output
Power Supply BL-U1
84
Prepare the BL series for connection to the BL-U1 by soldering a D-sub 9-pin con­nector to the BL series cable. Then connect the cable to READER port of the BL­U1.
Prepare the D-sub 9-pin connector and its connector case separately.
Take special care when soldering pin 5 (GND) and pin 9 (+5VDC). A wrong con­nection will damage the unit.
Do not use a power cable over 2 meters long. A long power cable can cause a drop in voltage, preventing the BL series from starting up properly.
1.3
Setting the BL-U1 DIP switches
According to the selected interface and timing input, change the DIP switch set­tings.
Shield
Yellow
Blown
Purple
White
Black Gray
BL series
1 2
-
3
5 6
4
7
Connector case TIM RD SD OK GND NG RS
Pink Blue Red
8 9
CS +5VDC
D-sub 9-pin (female)
#4-40 screw
READER port
BL-U1
Use a metallic connector case for the D-sub 9-pin connector and connect the shielded line to the connector case. This allows connection to the earth ground of the AC power cable.
CAUTION
OFF
ON
123456
The switch settings at left are the factory default settings.
DIP switch setting
1 2 3 4 5 6
Interface select
RS-232C ON OFF OFF RS-422A OFF ON OFF RS-485 multidrop OFF OFF ON
RS-422A terminator (terminal resistance 100
)
OFF OFF ON ON
RS-485 terminator (terminal resistance 100
)
OFF OFF ON ON
READER port CS control method select
Reect ON/OFF of CS at RS-232C port
OFF
Always ON ON
Power Supply BL-U1
85
1.4
Function and wiring on the I/O terminal block
The above list starts from the left edge terminal on the terminal block and sequen­tially goes to the right.
M 3.0 screws are used on the terminal block.
Use the clips shown below when wiring.
Wiring the trigger input
The trigger input signals the BL series to start reading. Turn on the trigger input by supplying 8.5 to 30 VDC between the trigger input ter-
minals. You can use the power supply for sensors terminals of the BL-U1 as the input
power supply.
Symbol
Description Signal Direction
TIM
Timing input
Input
Input
+12V OUT
Power supply for sensors (+) (+12 VDC, 300 mA)
Output
Power supply for sensors (-) (0 V)
Output
COM
Common for OK/NG output
——
OK
OK output
Output
NG
NG output
Output
SDA
Send RS-422A data (+)/RS-485 (+)
Output/Input and output
SDB
Send RS-422A data (-)/RS-485 (-)
Output/Input and output
SG
Signal ground
——
RDA
Receive RS-422A data (+)
Input
RDB
Receive RS-422A data (-)
Input
TIM +12V OUT– COM OK NG SDA SDB SG RDA RDB
Trigger
input
Power supply
for sensors
(12 VDC, 300 mA)
OK/NG output
RS-422A/RS-485
6.0 mm or less
Round-shape
6.0 mm or less
Fork-shape
TIM +12V OUT–
8.5~30VDC
+
+
Contact or non-contact
Power Supply BL-U1
86
Wiring the OK/NG output
Use this output to determine OK/NG status by comparing the readout data with the preset data. It is NPN open-collector output.
Input/output circuit diagram
Input circuit Output circuit
1.5
RS-232C port pin assignment
COM OK NG
Load
Load
+
*Rated load: 30 V max. (100 mA)
TIM
2.4 K
3.3K
Internal circuit
Load
OK/NG
COM
+
Internal circuit
Pin No.
Symbol Description
Signal
direction
1
Shield
Shield
——
2
SD (TXD)
Send data through RS-232C
Output
3 RD (RXD)
Receive data through RS-232C
Input
4 RS(RTS)
Request to send data through RS-232C (Always ON)
Output
5 CS(CTS)
Enable to send to RS-232C
Input
6 DR(DSR)
Connect to pin 20 internally
Input
7 GND(SG)
Signal Ground ——
20
ER(DTR)
Connect to pin 6 internally
Output
13
25
1
14
D-sub 25-pin connector (female) DTE specification (defined as terminal) N 2.6 screw (female)
Power Supply BL-U1
87
1.6
RS-232C port wiring
When you want to connect the BL-U1 to a PC through the RS-232C port, the wir­ing is as shown below.
You can use the optional OP-22149 cable (1.5 m) and OP-25057 (25- to 9-pin adapter).
1.7
RS-422A port wiring
When you want to communicate using the RS-422A port, the wiring is as shown below. Use the BL-U1 input/output terminal block.
Set both terminators (terminal resistance 100 Ω ) of the BL-U1 and external unit to ON (see P. 13).
The extended cable length must be within 1.2 km.
You can prepare an equivalent cable which meets the following specifications:
1 2 3 4 5 7 6
20
BL-U1
SD RD RS CS
GND
DR ER
1 2 3 4 5 7 6
20
PC/AT
Shield SD RD RS CS SG DR ER
D-sub 25-pin (male)
M 2.6 screw
D-sub 25-pin (male)
M 2.6 screw
Item
Specification
Cable type
Shielded cable Logarithm 3P Conductor resistance (20°C) 88.0 Ω /km or less Insulator resistance 10,000 M Ω .km or more Withdraw voltage 500 VDC/minute Static capacity (1 kHz) 60 nF/km or less (average) Characteristic impedance (100 kHz) 110 ± 10 Ω
SDA SDB RDA RDB GND
BL-U1
RDA RDB SDA SDB
SG
Shield
Twisted pair cable
External unit
Power Supply BL-U1
88
1.8
Wiring the RS-485 (multidrop link)
Multidrop link is a method to connect multiple BL series units to a single PC. See P. 82 of this document for details. Use the terminal blocks SDA and SDB.
Twisted pair cable
Up to 31 BL-U1 (BL series) units can be connected in multidrop link.
The extended cable length must be within 1.2 km.
Connect the BL-U1 (BL series) to a PC using a commercially available RS-
485/RS-232C convertor.
For units between the RS-485 (those marked with * in the above gure), turn ON the terminator.
You can turn the BL-U1 terminator on and off using DIP switch 5. For the ter­minator of the RS-485/RS-232C convertor, see the instruction manual for the convertor.
Do not connect the RS-485 cable through the terminal block.
Do not connect the multidrop link cables together with the power cable.
Avoid connection including branch of the BL-U1 and RS-485/RS-232C conver-
tor as shown below.
SDA SDB
SDA SDB
SDA SDB
SD/RD+
SD/RD-
RS-232C
PC
*
*
BL-U1 BL-U1 BL-U1
RS-485/RS-232C convertor
GND
SGSG
SG
Twisted
Shielded cable
CAUTION
BL
BL BL
Convertor
BL
BL BL
Convertor
**
Not applicable
(Connection with branch)
Applicable
(Connection without branch)
Terminator ON
Power Supply BL-U1
89
2 Installation
2.1
Precautions before use
Operating environ­ment
The BL-U1 is a precision instrument. Be sure to install the unit in the proper op­erating environment, and avoid using the unit under any of the following condi­tions.
Exposed to direct sunlight, or where the ambient temperature is below 0°C or above 50°C for the BL-U1.
Where the relative humidity is below 35% or above 85%, or where the temper­ature changes drastically, causing condensation.
Where corrosive gases, ammable gases, dust, salt, iron particles or oily smoke may be present.
Where shock or vibration may occur to the BL unit.
Where water, oil or chemicals may be spilled or splashed.
Near any strong magnetic eld.
Installing the BL-U1
When installing the BL-U1 at the site, consider the following points:
Reserve sufcient ventilation space at the site.
If the ambient temperature rises above 50°C during operation, be sure to
install a ventilation fan or cooler.
Avoid installing the BL-U1 near any high-voltage equipment.
Keep the BL-U1 away from the power cable.
Power Supply BL-U1
90
2.2
Installing the BL-U1
There are two methods for installing the BL-U1:
When installing the BL-U1 directly
Pull out the four screw slots on the rear panel and screw them to the base.
When installing the BL-U1 to the DIN rail
1. Hook the BL-U1 to the DIN rail groove from its top. Push the BL-U1 bottom against the DIN rail until you hear a click.
2. Check that the DIN rail mounting notch is shaped like notch A below. If not, push the BL-U1 further.
3. To remov e the BL-U1 from the DIN rail, pull out the notch until its shape turns from Fig. B to Fig. A. Then, disengage the BL-U1 from the DIN rail.
4. When you want to re-install the BL-U1 to the DIN rail, return the notch from that of Fig. A to Fig. B.
4-ø5
150
98
OK Insufficient
Fig. A Fig. B
Power Supply BL-U1
91
3 Outline of Multidrop Link
3.1
Multidrop Link
The multidrop link is a communication method to control several BL series read­ers simultaneously with one host computer as shown in the system configuration on page 79. Using the RS-485 cable as the communication path, the multidrop link offers high noise immunity and enables long-distance transmission. The multidrop link allows easy wiring using twisted-pair cables (2-wire).
3.2
System Conguration
To use the multidrop link, a BL series reader plus the following equipment is re­quired.
BL-U1
To use the multidrop link, be sure to use this power supply unit.
RS-485/RS-232C converter
To connect a BL series reader to the host computer, the RS-485 signal must be converted into an RS-232C signal.
Host computer
Use a personal computer with an RS-232C interface. When several BL readers are reading several bar codes, the amount of data to
be processed may exceed the host computers capacity. To prevent this, reduce the number of the BLs connected to the host computer,
or replace the host computer with another one which provides higher data throughput (including processing of the programming language).
2-wire twisted-pair cable for the RS-485 interface.
Prepare the specified cable (see page 88).
RS-232 cable
Cable used to connect the host computer to the RS-485/RS-232C converter. Use a cable whose pin assignment conforms to those of the RS-232C connector of the host computer and the RS-485/RS-232C converter.
Power Supply BL-U1
92
4 Setup and Connection Procedures
1. BL series setup Using the Setup software, set the BL series as described below:
Set the multidrop link to Enable”.
Assign ID number 1 to 31 to the connected BL series. Do not assign the
same ID number to different BL series.
Set the baud rate, data length, parity and stop bit length.
2. RS-485/RS-232C converter setup Referring to the instruction manual of your RS-485/RS-232C converter, set
the following parameters.
Example
Baud rate: Conforms to the setting of the BL series. Driver active: AUTO Terminater: See p. 17. DTE/DCE selector switch: DTE
3. PC setup Set the baud rate, data length, parity and stop bit length according to the BL
series settings.
4. Connection between the BL series (BL-U1) and the RS-485/RS-232C con­verter.
To connect the equipment, use the specified cable (see page 88).
5. Connection between the RS-485/RS-232C converter and the host computer Use a cable whose pin assignment conforms to those of the RS-232C con-
nector of the host computer and the RS-485/RS-232C converter.
Example
When the host computer is an IBM PC/AT compatible, use the KEYENCE OP-22149 cable (1.5 m).
6. Conrmation of operation Send a command to the BL series to confirm its operation.
Power Supply BL-U1
93
5 Communication
5.1 Outline of Communication types
You can perform all multidrop link communication by sending commands from the host computer to the BL series.
The communication of the multidrop link is classified into the following two types:
Data communication
For sending read data from the BL-series to the host computer. When data re­ceive commands (polling commands) are sequentially sent to each BL series con­nected to the host computer, the read data is sent to the host computer. The read data is stored in the BL series transmission buffer, and the data stored in the transmission buffer is called using the polling command.
Command communication
Using serial communication commands allows direct control of the BL series or change/confirmation of the BL series settings.
5.2 Communication Format
All multidrop link communication is done in the following format. Send any com­mand in this format and the BL Series will respond in the format shown below.
<Communication format>
Detail of each data: 1, 6 Delimiter: All the data should start with [STX](02h) and should end with
[ETX](03h). This cannot be changed.
2 mmm/No. of data: Total number of characters of above data 2 to 5
should be entered. (Do not count [STX] and [ETX].) When you send [STX][mmm][03][SSET][cc][ETX], for example, the num­ber of characters will be; 3+2+4+2=11Thus, [mmm] is 011.
3 nn/ID No.: Specify the ID No. of the BL Series reader you want to send/
receive. ID Nos. should be from 01 to 31.
4 Data/Command/Response: Two commands can be used for multidrop
link communication. [P] for polling and [C] for clearing data.
5 cc/Checksum: Add the checksum when you send the data. When the re-
sponse is returned from BL, the checksum follows the data. Determine the checksum by calculating the Exclusive OR of each data from 2 to 4 as follows.
STX mmm nn Data/Command/Response cc ETX
Delimiter No. of data ID No. Contents of data Checksum Delimiter
1 2 3 4 5 6
Name Command Response Description
Polling com­mand
P
Data is returned if any data is stored.
[e] is returned if no data is stored.
[OVER] is returned if the buffer is full.
Command to ask whether the BL series transmission buffer con­tains any data.
Data clear command
C
[OK] is returned if the data is cleared.
[NG] is returned if the data has been already cleared.
This command clears one piece of the sent data, and completes a series of data communi­cation.
Power Supply BL-U1
94
Examples To send
cc = 7A To send
cc = 4B To send
cc = 7E.
Point Exclusive OR calculation formula
Calculate each bit using the following formula.
Conversion form hexadecimal number into binary number
Convert ASCII codes into binary numbers referring to the following table.
Example: Data to send is [STX][008][01][P][cc][ETX]
0 0 8 0 1 P
1. Convert each data bit to ASCII code (Hex).
30h 30h 38h 30h 31h 50h
2. Convert the ASCII code to 8-bit binary.
0011 0000 0011 0000 0011 1000 0011 0000 0011 0000 0101 0000
3. Calculate Exclusive OR of each data bit.
0011 0000 0011 0000 0011 1000 0011 0000 0011 0000 0101 0000 Exclusiv
e OR
0110 1001
4. Convert the 8-bit binary to hexadecimal data.
0110 1001
69h
5. Enter the result as [cc]. [cc] = 69
[STX] 008 01 C cc [ETX].
[STX] 013 11 ABC876 cc [ETX].
[STX] 010 31 LON cc [ETX].
Hexadecimal 0 1 2 3 4 5 6 7 Binary 0000 0001 0010 0011 0100 0101 0110 0111 Hexadecimal 8 9 A B C D E F Binary 1000 1001 1010 1011 1100 1101 1110
1111
0 , 0 =0 0 , 1 =1 1 , 0 =1 1 , 1 =0
, Exclusive OR operator
Loading...