Keating Of Chicago 2006 User Manual

SERIES 2006 FRYER MANUAL
Keating’s INCREDIBLE FRYING MACHINE
®
READ AND SAVE THIS MANUAL FOR FUTURE REFERENCE
Record the Model No. and Serial No. of this Incredible Frying Machine®in the space provided below.
Model No. __________________________
Keep these numbers for future reference
IMPORTANT: Keep a copy of your bill of sale. The date on the bill establishes the warranty period should service be required. If service is performed, it is in your interest to obtain and keep all receipts. Keating commercial fryers are intended for other than household use.
1-800-KEATING
www.keatingofchicago.com
CONTENTS:
This Owner’s Guide provides specific operating instructions for your model. Use the Incredible Frying Machine
®
only
as instructed in this Service Guide.
SECTION IV MAINTENANCE
Warranty Repairs............................................................................9
Preventive Maintenance ................................................................9
Oil Breakdown................................................................................9
Thermostat Calibration ..................................................................9
Thermostat Bulb Positioning ....................................................9-10
SECTION V SERVICE DIAGNOSIS
Thermostat Test............................................................................10
Flame Adjustment ........................................................................10
SECTION VI SERVICE
Trouble Shooting Charts ........................................................11-14
SECTION VII PARTS LIST
Ordering Parts ..............................................................................15
Warning and Operating Plates ....................................................15
IFM Gas Fryer Model 2000 Parts List ..........................................15
IFM Gas Fryer Model 2000 Assembly I ......................................16
IFM Gas Fryer Model 2006 Parts List ..........................................17
IFM Gas Fryer Model 2006 Assembly II ......................................18
IFM Gas Fryer Assembly III..........................................................19
IFM Control Panel Parts List ..................................................20-25
IFM Burner Assembly Parts List ..................................................26
Basket Lift Assembly Parts List ..................................................27
SECTION VIII WIRING DIAGRAMS
14IFM Wiring ..........................................................................28-39
Warranty ......................................................................................40
SECTION I INTRODUCTION
General ..........................................................................................1
Standard Features..........................................................................1
Standard Accessories ....................................................................1
Options ..........................................................................................1
Ratings ..........................................................................................1
Model Variations ............................................................................1
Safety Precautions......................................................................1-2
SECTION II INSTALLATION
Damage During Shipment..............................................................3
Installation ......................................................................................3
Leveling ..........................................................................................3
Restraining Devices........................................................................3
Gas Connection ............................................................................4
Electrical Connection ....................................................................4
Gas Leak Testing............................................................................4
Gas Pressure..................................................................................5
SECTION III OPERATING THE FRYER
Filling ..............................................................................................5
Lighting ......................................................................................5-6
Cooking ..........................................................................................6
Shutdown ......................................................................................6
Digital Timers ..............................................................................6-7
Draining ..........................................................................................7
Cleaning and Boil-Out ................................................................7-8
017411 IFM 2006 1108
POST THIS LABEL IN A
PROMINENT LOCATION ON
YOUR UNIT
IMPORTANT
IN THE EVENT A GAS ODOR IS DETECTED,
SHUT DOWN UNITS AT MAIN SHUT OFF VALVE
AND CONTACT THE LOCAL GAS COMPANY OR
GAS SUPPLIER FOR SERVICE.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINI­TY OF THIS OR ANY OTHER APPLIANCE.
*As continuous product improvement occurs, specifications may be changed without notice.
IFM Model 2006 0107 9/07
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, INJURY OR DEATH. READ THE INSTALLATION, OPERATING AND MAIN­TENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS EQUIPMENT.
WARNING
Do not store flammable
liquids near this or any
other appliance.
WARNING
Improper installation can cause damage, injury or death.
INTRODUCTION
Keating’s Incredible Frying Machine®(IFM) are designed to give maximum production efficiency, deliv­ering high quality food products. The following design features are incorporated in Keating’s Incredible Frying Machine
®
(IFM).
STANDARD FEATURES
• Highly polished stainless steel fryer vessel
• Highly polished stainless steel front
• Highly polished stainless steel heat transfer tubes
• Highly polished stainless steel thermostat bulb
• Highly polished stainless steel Hi-Limit bulb
• Complete stainless steel cabinet
• True Cold Zone for proper sedimentation
• Grid screen over heat transfer tubes
• 1" full port front drain valve
• Patented accurate temperature control system ±2°F
• Ideal 35" working height
• 3/4” NPT gas connection on single fryers
• One pair of split baskets or one full-size basket
• Patented burner design
• Spark Ignition system
• 100% proof of air flow safety shut-off
• 100% proof of flame safety shut off
• Digital timers (2) (where applicable)
• Gas and air adjustments
• Gas pressure test port
• Blower grease filter (easily accessible from front)
• Easy access for servicing from front of fryer
• Burner, blower and Hi-Limit indicating lights
• Insulated fryer vessel
• Heat recirculation for higher efficiency and lower flue temperature
• Black heat tube interiors for optimum heat transfer
• Instant-On
ignition system (where applicable)
• 120 VAC 9' neoprene cord with 3-pronged grounded plug
• Instant recovery to cooking temperature
• High temperature stainless steel flue lining
• 100% factory testing
STANDARD ACCESSORIES
• Keating Klenzer Sample
• Drain clean out rod
OPTIONS
• Natural Gas or Propane
• Automatic Basket-Lift
• Cooking Computer
RATINGS
• 14" fryer vessel - 38 lb. oil capacity
• 18" fryer vessel - 68 lb. oil capacity
• 20" fryer vessel - 100 lb. oil capacity
• 7" W.C. (Natural Gas) or 11” W.C. (Propane) Line Gas Pressure.
• 3" WC (Natural Gas) or 10" WC (Propane) manifold gas pressure.
• 3/4" gas supply pipe recommended
MODEL VARIATIONS
Basket-Lift Model: Basket-Lift Model Fryers come
with all the same features as the standard models. The Basket-Lift mechanism lowers the baskets of food into the oil when the timer button is pressed and raises the baskets when the cooking cycle is complete. Split baskets are required for these models.
CPU Model: CPU Incredible Frying Machine (IFM) have the same input as the standard models. A programmable computer replaces the two timers and thermostat.
SAFETY PRECAUTIONS
THIS SYMBOL WARNS YOU THAT SERIOUS BURNS OR OTHER INJURIES MAY RESULT IF SAFETY INSTRUCTIONS ARE NOT FOLLOWED.
• This service manual should be retained in a safe place for future reference. The installation of your new fryer must conform to local codes or in the absence of local codes, with the current National Fuel Gas Code ANSI Z223.1/NFPA 54 (latest edition), Natural Gas Installation Code CAN/ CGA-B149.1 or Propane Installation Code CAN/ CGA-B149.2.
• Your ventilation hood, when installed, must conform to the current ANSI/NFPA 96 standard (latest edition).
• No frame or restriction shall be constructed around the fryer that will restrict air movement into the fryer’s combustion area or prevent proper ventilation.
• Keating fryers are designed to operate on the gas fuel specified on the serial plate and must not be operated with another gas fuel. They cannot be converted to another gas fuel by turning or engaging a switch.
1
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY APPLIANCE.
You will post, in a prominent location, instructions to be followed in the event the user smells gas. This information shall be obtained from your local gas supplier.
IMPORTANT: IN THE EVENT A GAS ODOR IS DETECTED, SHUT DOWN UNIT AT MAIN SHUT-OFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR EMERGENCY SERVICE.
• Suitable for installation on non combustible floors.
• You must maintain this appliance free and clear from combustibles.
• You must maintain the following minimum clearances from combustible and noncombustible construction:
• You must install this appliance at least 16 inches away from any open flame.
• Adequate clearance for servicing and proper operation must be maintained. Your fryer is designed to be serviced from the front.
• Keating commercial fryers are intended for other
than household use.
• ALWAYS instruct new employees on proper fryer
operation.
• A fryer should be operated ONLY by properly trained
personnel.
• ALWAYS turn fryer off each night.
• ALWAYS disconnect fuel source before servicing.
• NEVER leave a fryer unattended during operation.
• NEVER move a fryer when full of hot oil.
• NEVER introduce objects or liquids into fryer, while operational, which are not designed or made for cooking.
• THIS FRYER MAY NOT BE ALTERED, MODIFIED OR CHANGED IN ANY WAY.
The State of California enacted the California Safe drinking water and Toxic Enforcement Act of 1986, (Prop. 65), which “prohibits any person in the course of doing business from knowingly and intentionally
exposing any individual to a chemical known to the State of California to cause cancer or reproductive toxicity without first giving clear and reasonable warning to such individuals.” The Governor’s Scientific Advisory Panel added carbon monoxide
to the list of hazardous
chemicals known to cause reproductive harm.
Carbon monoxide would not be present in concentrations that would pose a “significant risk” to the consumer when the equipment is installed, operated and maintained as follows:
• Installed in accordance with all local codes, or in the absence of local codes, with the current National Fuel Gas Code ANSI Z223.1/NFPA 54 (latest edition).
• Installed under a properly designed operating exhaust hood.
• Connected to the type of gas for which the appliance is manufactured.
• In-line pressure regulator, not supplied by Keating, must be installed outside the appliance to maintain proper incoming gas pressure (7” W.C. Natural, 11” W.C. L.P.).
• The appliance is adjusted for the manifold pressure marked on the serial plate.
• Adequate air supply to the appliance.
• The equipment is operated in the manner intended using the proper utensils.
• Keep the equipment clean and have it checked periodically.
• Burner air adjustments, mechanical maintenance and repairs must be performed by qualified service personnel.
If the equipment is not installed, operated and maintained in accordance with the above, concentrations of carbon monoxide in excess of the established limits could be present in the kitchen environment.
Clearances
Combustible Construction
Noncombustible
Construction
Back 6" 0"
Right Side 6" 0"
Left Side 6" 0"
2
INSTALLATION
This fryer MUST be installed, inspected, calibrated and serviced by qualified and/or certified and/or licensed service personnel - you may void your Keating warranty if installation is not completed per local, national and Keating specifications. Contact your dealer for assistance.
DAMAGE DURING SHIPMENT
The fryer has been assembled, tested and inspected at the factory. Upon arrival, the complete fryer should be checked for any damage that may have occurred during shipment.
The carrier is responsible for all damage in transit whether visible or concealed. Do not pay for the freight bill or sign the Bill of Lading until the fryer has been thoroughly checked for damage. If concealed damage is found later, contact the carrier immediately to file a claim.
What to do if equipment arrives damaged:
VISIBLE LOSS OR DAMAGE - Be certain to note this on the freight or express receipt and have it signed by the delivery person.
FILE CLAIM FOR DAMAGES IMMEDIATELY ­Regardless of extent of damage. This claim must be filed with the carrier.
CONCEALED LOSS OR DAMAGE - If damage is noticed when equipment is unpacked, notify the freight company immediately, and file a “concealed damage claim”. This MUST be done immediately. Be sure to retain the shipping container for inspection.
Keating does not assume responsibility for Loss OR Damage incurred in transit. Keating’s sole responsibility in such cases will be to provide support in determining the extent of the parts, labor, and cost thereof needed to return said equipment to new condition.
INSTALLATION
Installation must conform with local codes or, in absence of local codes, with the current National Fuel Gas Code Z223.1/NFPA 54(latest edition), Natural Gas Installation CAN/CGA - B149.1 or Propane Installation Code CAN/CGA-B149.2. When pressure testing at test pressures less than or equal to 1/2 psig (3.45 KPA), fryer must be isolated from gas supply piping. When pressure testing at test pressures above 1/2 psig (3.45 KPA), fryer must be disconnected from gas supply piping system.
Counter model and floor model fryers must be restrained to prevent tipping when installed in order to avoid splashing, spilling, etc. of hot liquid. The restraining method may be a manner of installation or by separate means.
LEVELING
The fryer will operate at its highest efficiency when properly leveled. Place a level on fryer vessel from side to side. For fryers on legs, the bottom foot of the leg is adjustable. Turn clockwise to decrease height or counter clockwise to increase height until level. For fryers on casters, the casters are adjustable by loosening the jam nut and turning the caster in or out. When the desired level is reached, tighten the jam nut. Adjustments of more than 3/4" are not recommended on any caster. The same procedure should be followed to level the fryer from front to back.
Figure 2-1
RESTRAINING DEVICES
1.) Adequate means must be provided to limit the
movement of the appliance without depending on the connector and the quick-disconnect device or its| associated piping to limit the appliance movement.
Fryer must also be restrained to prevent tipping when installed so that hot liquid splashing is avoided.
2.) The restraint means must be attached to the rear of
the Keating IFM within 2" of the center line width and approximately 1 5/8" from the bottom of the cabinet back to allow the restraining bolt to be anchored to the cabinet back between the cabinet bottom and inner liner. IF DISCONNECTION OF THE RESTRAINT IS
NECESSARY, IT MUST BE RECONNECTED WHEN THE KEATING IFM IS RETURNED TO ITS ORIGINALLY INSTALLED POSITION.
NOTICE: WHEN THIS APPLIANCE IS INSTALLED WITH CASTERS, IT MUST BE INSTALLED WITH CASTERS SUPPLIED, A CONNECTOR COMPLYING WITH EITHER ANSI Z21.69 OR CAN/CGA - 6.16 AND A QUICK-DISCONNECT DEVICE COMPLYING WITH EITHER ANSI Z21.41 OR CAN1- 6.9. IT MUST ALSO BE INSTALLED WITH RESTRAINING MEANS TO GUARD AGAINST TRANSMISSION OF STRAIN TO THE CONNECTOR, AS SPECIFIED IN THE APPLIANCE MANUFACTURER’S INSTRUCTIONS.
3
INSTALLATION
The installer is responsible for attaching the tipping restraint.
ELECTRICAL CONNECTION
The Keating IFM, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, the National Electrical Code, ANSI/NFPA No. 70. or the Canadian Electrical Code, CSAC-22.2 as applicable. A wiring diagram is located on the last page. In the U.S.A. and Canada, the electrical supply must be 120 VAC, 60 Hz.
The Keating Incredible Frying Machine (IFM) is equipped with a 9' neoprene covered, 3 wire electrical cord with a three-pronged grounded plug for protection against electrical shock. This plug must be placed into a 120V properly grounded three-pronged polarized outlet. For proper grounding procedures see local codes, or in the absence of local codes, the National Electrical Code ANSI/NFPA 70 (latest edition) or Canadian Electrical Code CAN 22.2 (latest edition) as applicable.
Before plugging in the fryer, confirm the outlet is properly polarized and grounded. If the hot and neutral terminals are reversed or the outlet is not properly grounded, the burners may not ignite (burner on light will go out after 2-1/2 seconds and the ignition processes will continue 3 times).
THIS APPLIANCE IS EQUIPPED WITH A THREE-PRONG 120 VOLT NEMA 5-15 (GROUNDING) PLUG FOR YOUR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY GROUNDED AND POLARIZED THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM
THIS PLUG.
IF DISCONNECTION OF THE RESTRAINT IS NECESSARY, IT MUST BE RECONNECTED WHEN THE FRYER IS RETURNED TO ITS ORIGINALLY INSTALLED POSITION.
GAS CONNECTION
• PIPE JOINT COMPOUNDS RESISTANT TO PROPANE GASES MUST BE USED.
• BEFORE OPERATING THIS FRYER, CHECK PIPE JOINTS FOR LEAKS BY USING A SOAP AND WATER SOLUTION ONLY. DO NOT USE AN OPEN FLAME!
Figure 2-3
Main Gas Connection
Connect the fryer to the main gas supply line at the rear of the fryer. The piping should be a minimum of 3/4" NPT supply pipe for a single fryer at the burner mani­fold. Batteries require larger supply lines. Installation must conform to the current local codes and National Fuel Gas Code (U.S.) ANSI Z223. 1/NFPA 54 (latest edition), Natural Gas Installation Code CAN/CGA-B149.1 or Propane Installation Code CAN/CGA-B149.2 (latest edition).
NOTE: If more than one gas fryer is on the same supply line, you may require a larger line. Consult your local gas company to assure adequate volume and pressure. Refer to serial plate for proper gas requirements for your particular model.
NOTE: Piping for a battery should be at least 1 1/4” to 1 1/2” IPS, depending on total BTU input. Consult your local gas supplier for appropriate battery piping size.
NOTE: The electrical wiring diagram for the fryer is located on the inside of the fryer door or in the back of this manual.
GAS LEAK TESTING
Prior to lighting your fryer:
1. Make sure all thermostats, switches and safety
valves are in the “OFF” position.
2. Turn main On/Off manual gas valve to the “ON”
position.
3. Have your plumber or gas company check for leaks
with a soap solution. (NEVER check with an open flame!)
4
GAS PRESSURE AT MANIFOLD
NATURAL Gas - 3.0 in. W.C. LP Gas - 10.0 in. W.C.
MAXIMUM INCOMING GAS PRESSURE
NATUARAL Gas - 7.0 in. W.C. LP Gas - 11.0 in. W.C.
NOTE: It is estimated that half of all service calls made on Keating Incredible Frying Machine® (IFM) result from an inadequate gas supply. During installation, have a gas company representative make certain that the fryer is receiving adequate gas pressure and volume (see “Installation” or your serial plate on the fryer door).
PROPANE GAS MAY EVENTUALLY LOSE ITS ODOR AND PRECAUTIONS SHOULD BE TAKEN TO ASSURE THAT IT IS NOT PRESENT EVEN THOUGH YOU DO NOT DETECT AN ODOR. IF THERE IS ANY DOUBT, YOU SHOULD CALL YOUR LOCAL PROPANE GAS SUPPLIER FOR ASSISTANCE.
OPERATING
FILLING
NOTE: Before filling the fryer make certain the fryer
vessel is sanitized, dry and the drain valve is completely closed. Refer to item 13 on page 16, or item 11 on page 18 for location of drain valve.
NOTE: We recommend that solid shortening not be used in an Incredible Frying Machine (IFM) as they are not equipped with a melt cycle. If solid shortening is used, it should be melted prior to filling the fryer vessel. Damage done by melting solid shortening in the fryer vessel will void the warranty.
BE SURE THE HEAT TRANSFER TUBES ARE COMPLETELY COVERED WITH OIL BEFORE SWITCHING THE FRYER ON. IF OIL LEVEL DROPS BELOW TOP OF HEAT TRANSFER TUBES, SEVERE DAMAGE TO FRYER AND INJURY TO OPERATOR MAY RESULT.
DO NOT MIX HOT OIL AND WATER IN ANY FORM.
Oil expands when heated. The “Max” line has been provided to ensure optimum cooking while ensuring the safety of the operator. Do not overfill the fryer vessel.
See Figure 3-1.
Figure 3-1
“Max” Level Line
Fill the fryer vessel with oil or MELTED solid shortening up to the “Max” line.
LIGHTING
BEFORE ATTEMPTING TO LIGHT THE FRYER, MAKE SURE THE GAS CONNECTIONS ARE SECURE AND HAVE BEEN LEAK TESTED AND THE FRYER HAS BEEN PROPERLY FILLED WITH OIL.
Figure 2-4 IFM Control Panel
Control Panel with timers Model 2000
14” Control Panel with timers Model 2006
5
1. Turn on main power switch.
2. Set thermostat to desired setting. (Between 325°F/162.8°C) – (335°F/165.3°C)
3. Once main power switch is on and the thermostat is set, the following occurs:
a. Blower will start and blower indicating light will
come on.
b. After a preset ten second delay, the gas valve
will open and the burner indicating light will come on.
c. The spark module will light the burners auto-
matically.
d. The burner indicating light will be on whenever
the burners are on. The light goes off when the oil has reached the desired temperature. If the burners do not light immediately, the burner light will shut off, the blower light will stay on, and after 6 seconds, the burners will try to light again. This process will repeat 3 times.
NOTE: The fryer cannot be operated during a power failure as the electronic ignition system cannot be operated.
COOKING
Keating Incredible Frying Machine
®
Gas Fryers (IFM) are designed to provide maximum production efficiency and deliver high quality food products. Low- temperature cooking, highly polished stainless steel and a true COLD ZONE mean extended oil life. Follow cooking procedures below for your model.
• OPERATION OF THIS FRYER SHOULD BE LIMIT-
ED TO PERSONNEL WHO HAVE BEEN THOR­OUGHLY TRAINED IN OPERATING PROCE­DURES.
• USE ONLY KEATING APPROVED BASKETS IN
YOUR FRYER. NEVER OVERFILL FRY BASKETS. DO NOT BANG BASKETS ON BASKET HANG­ERS OR ON FRYER VESSEL.
• CARE SHOULD BE TAKEN WHEN LOWERING
BASKETS INTO FRYER TO PREVENT SPLASH­ING HOT OIL FROM FRYER VESSEL.
• NEVER LIFT BASKETS DIRECTLY OUT OF THE
FRYER VESSEL WITHOUT DRAINING, AS SEVERE INJURY MAY RESULT.
1. Set thermostat to the desired frying temperature
(between 325°F - 335°F).
2. When the oil reaches the desired temperature,
burner indicating light will go off.
3. Set timer(s) to desired cooking time and fill bas­ket(s) to proper level (if applicable).
4. Lower filled basket(s) slowly into oil. For fryers with automatic basket lift, place basket(s) on upper bas­ket hanger rods on splashback of fryer.
5. Push “T1”, “T2” or “T3” button of electronic timer(s). This simultaneously activates the Instant-On™ systems (if applicable). For fryers with automatic basket lift, basket(s) will lower into fryer vessel.
6. When timer(s) sounds, carefully lift basket(s) out of hot oil (if applicable). For fryers with automatic bas­ket lift, a buzzer will sound and the basket(s) will rise automatically. Allow oil to drain before remov­ing.
7. Place basket(s) on basket hanger rods on splash­back of fryer and allow to drain.
SHUT DOWN
Turn off main power switch.
DIGITAL TIMER (PART # 030834)
RESETTING TO MINUTES : SECONDS
STEP 1
Make certain power to the timer has been OFF for at least 30 seconds. Then PRESS and hold down the UP arrow button while turning the rocker power switch to the ON position. The timer will turn ON and the display will now be indicating
OR
The BEEPER will BEEP 4 times.
If STEP 1 was OK, proceed to STEP 2. If not, retry Step 1 making sure the power was OFF for at least 30 seconds or more.
6
– – – – – –:– –
STEP 2 PRESS all 3 buttons in sequence: left-center-
right. The BEEPER will BEEP. If BEEPER does not BEEP, the timer is defective. STOP TESTING. Reset procedure is completed when 1:00 appears on the digital display.
DIGITAL TIMER (PART # 030834)
PROGRAMMING
To program the timers, the unit must be in the idle mode. Press and hold the set but­ton for approximately two seconds. The display will show “SEt”. Press the button
for the channel to be programmed. The display will show the current setting for that channel. Use the up or down button to increment or decrement the setting. When the setting is correct, press and hold the set button again for approximately two seconds. The display will show "StO" for approximately two sec­onds and the timer will return to normal operation. Repeat the process as necessary for the other timers.
OPERATING LOGIC
When the timer is powered up, the display will show the time setting for the channel that was operated last and the relay output contacts will be open. To start a cycle, press the desired channel button (1-3). The display will begin to countdown from the preset time setting and the relay output contacts will close. During the countdown the colon will flash at a one-second rate. When the countdown has reached "00:00" the relay output contacts will open, the display will flash, and the audible alarm will sound. To cancel the audible alarm, press any button.
PAUSE FEATURE
To pause a cycle in progress, press any button. The relay output contacts will open, the display will flash, and the countdown will pause. To resume the countdown, press any button. The display will resume the normal countdown and the relay output contacts will close.
CANCELING A CYCLE
To cancel a cycle in progress press and hold any button for approximately two seconds. The relay output contacts will open and the display will show the time setting for the channel last used.
DRAINING
ALWAYS SHUT THE FRYER OFF COMPLETELY BEFORE DRAINING. THE FRYER SHOULD BE DRAINED ONLY UNDER THE SUPERVISION OF PROPERLY TRAINED PERSONNEL. A DRAIN PIPE AND COVERED CONTAINER SUITABLE FOR USE WITH HOT OIL SHOULD BE USED TO ENSURE THE SAFETY OF THE OPERATOR.
1. Operator should be outfitted with proper attire including:
–Oil and heat resistant gloves –Oil and heat resistant apron –Safety goggles –Oil and heat resistant footwear
Figure 3-2
2. Turn off the fryer and open the door.
3. Put suitable container under drain valve (for Safe & Easy models, slide filter onto rails inside of fryer or filter cabinet).
4. • Front Drain: Drain oil from fryer by slowly
turning handle. The drain will be completely open after 1/4 turn.
• Rear Drain: Pull black knob forward slowly.
5. After fryer drains, close the drain valve.
6. Filtering may be done at this step - refer to filter manual.
CLEANING AND BOIL-OUT
When cleaning and boiling out your fryer use Keating Sea Powder and Keating Klenzer to keep your fryer in top condition. Keating Sea Powder dissolves any grease build up — even carbonized grease in fryer vessels — one of the leading causes of premature oil breakdown. Once your fryer vessel is clean, use Keating Klenzer, the finest dry stainless steel polish available, to restore your Keating Incredible Frying Machine
®
’s (IFM) exterior to its
original luster.
7
11:: 0000
Side view of Safe & Easy Filter
Figure 3-4
Keating Klenzer and Sea Powder
1. Put on safety attire. See Draining.
2. Turn the fryer off
3. Drain oil from fryer, see draining steps 2-4 above.
4. Remove oil container to a secure area to prevent accidental spillage.
5. Fill fryer vessel to “Max” line with water.
UNDER NO CIRCUMSTANCES SHOULD THE FRYER BE LEFT UNATTENDED DURING BOIL-OUT. TRAINED PERSONNEL MUST BE PRESENT DURING THE PROCEDURE TO PREVENT BOIL OVER OR TO TURN OFF THE POWER IF WATER DROPS BELOW HEAT TRANSFER TUBES.
6. Set thermostat and turn fryer on to bring water to a gentle boil.
7. Once boil has been reached, turn fryer off.
8. Dissolve
2
/
3 cup of Keating Sea Powder for every
five gallons of water and let soak for
1
/2
hour. If there is a large build-up of carbonized grease, allow fryer to soak overnight.
CAUTION: When soaking overnight, make sure the fyer is turned off.
CAUTION: Do not damage or reposition thermostat probe as this may affect the accuracy of the fryer.
9. While soaking, a natural fiber brush may be used to scrub the tubes and inside walls of fryer.
10. Drain the water and Sea Powder into a dry suitable receptacle and remove from cooking area.
NOTE: DO NOT pump water through the filter machine.
11. Spread Keating Klenzer liberally on tubes and sides of fryer vessel.
12. A non-abrasive scouring pad may be used to remove the now softened carbonized grease.
13. Thoroughly rinse fryer vessel with potable water to remove all Klenzer.
14. Prior to refilling with oil, wipe the inside of the fryer vessel making sure all water and Klenzer has been removed.
DO NOT MIX HOT OIL AND WATER IN ANY FORM.
15. Close drain valve.
FAILURE TO CLOSE DRAIN VALVE BEFORE REFILLING THE FRYER MAY RESULT IN SERIOUS INJURY.
16. Check thermostat bulb positioning – see page 9.
17. Refill the fryer with new oil.
8
MAINTENANCE
WARRANTY REPAIRS
Keating’s warranty begins with the date of installation (or ship date if we are not notified of an installation date).
In the event that your fryer, under warranty, needs repairs other than routine maintenance or cleaning, you are required to contact Keating of Chicago (at 1-800-KEATING) before calling a local service company. Failure to do so may void your warranty.
PREVENTIVE MAINTENANCE
Preventive maintenance should be done in daily, week­ly, monthly and yearly intervals as necessary. Following preventive maintenance procedures will help keep your fryer working efficiently. Proper care and servicing will lead to years of quality performance.
A. Oil Breakdown
As part of a “Preventive Maintenance Program”, the oil in your fryer needs to be filtered regularly to avoid breakdown. The initial investment in the frying system is less than the total overall costs of oil during the life of the fryer, and with regular filtering, you can realize sub­stantial savings in oil costs, as well as maintenance charges.
B. Thermostat Calibration
You will need:
One screwdriver with 1/8" wide flat blade One accurate fryer thermometer
1. Set thermostat to desired frying temperature.
2. Allow fryer to cycle three times.
3. Place an accurate thermometer in the oil at the tip of the thermostat bulb.
Figure 4-1
Dial Plate with knob removed
NOTE: Locate thermometer in same position for every
calibration.
4. If calibration of fryer is found to be less than 25°F off, simply loosen the four retaining screws holding the dial plate in place. Reset the dial plate to match the thermometer reading. If the fryer is found to be more than 25°F off, a qualified service company must be contacted to have the fryer properly calibrated.
Do NOT adjust set screw on thermostat.
C. Thermostat Bulb Positioning
BEFORE REPLACING, TEST THERMOSTATS:
Operational problems can easily be corrected by thermostat bulb positioning.
Keating’s patented thermostat application is accurate within 2°F of the dial setting between 250°F – 350°F. This accuracy is attained only if the thermostat bulb is placed properly against the heat transfer tube. To quickly and accurately test for proper bulb placement, a single thickness of writing paper should be pulled through between the tube and the bulb with medium resistance.*
1. *For gas fryers 14":
The end of thermostat bulb should touch the burn­er tube.
2. For gas fryers 18" & up:
If the bulb is too loose, the paper will slip through with little or no resistance. A fryer with a thermo­stat bulb that is too loose will overshoot.
Overshoot: The thermostat takes a long time to cycle and then misses its preset temperature by 20°F - 40°F yielding a poor quality product.
If the bulb is too tight, the paper will either not pull through or it will tear. A fryer with a thermostat bulb that is too tight will short cycle.
9
PREVENTIVE MAINTENANCE CHART
TIME
FRAME
OPERATOR/OWNER SECTION
Daily*
• Check lights and controls
• Check that the oil is up to “Max” line.
• Clean all baskets
• Drain, strain or filter shortening.
III
Weekly*
• Drain and clean fryer
• Boil-out fryer
III & VI
Monthly*
• Verify thermostat settings.
• Test Hi-Limit control.
III
IV & V
Yearly*
QUALIFIED SERVICE PER­SONNEL ONLY
• Check burner flame color and adjust air shutters.
V
* High production facilities should be checked more often.
Short Cycle: The thermostat will cycle rapidly while the fryer is in the idle mode; the temperature will be erratic.
Thermostat Bulb Positioning 18
" & up Fryer Gas
SERVICE
ALL HI-LIMIT CONTROLS ARE PRESET AT THE FACTORY FOR A SPECIFIC TEMPERATURE. DO NOT
ATTEMPT TO CHANGE THE SETTING OF THE HI-LIMIT. IF THE HI-LIMIT FAILS TO SHUT OFF BETWEEN 425°F AND 450°F DURING TESTING, IT MUST BE REPLACED.
FLAME ADJUSTMENT
A. Gas Pressure
1. At gas valve, remove adjustment port cover, rotate
adjustment screw with screwdriver and replace port cover.
2. To check the gas pressure (3" WC for natural gas
or 10" WC for Propane at the manifold), use an allen wrench to remove the gas pressure test port, located in the center of the manifold.
3. Line pressure (incoming pressure) is critical for
proper ignition of the IFM. Incoming pressure must be : Natural - 7” W.C.
Propane - 11” W.C.
B. Air Flow
1. To determine the proper gas/air mixture, look into
the viewing window for each burner, located just to the left of each burner air hose where the hose is connected to the burner assembly. (See figure below).
bright red/orange with proper mixture – orange “glow” around burner tube
too much gas – orange “haze” around burner tube (showing incomplete combustion)
too little gas – blue at front of burner, or totally blue
REQUIRED TEST THERMOSTAT
Multimeter (for testing continuity)
CHECKING CONTINUITY WITH THE MULTIMETER
1. Rotate the thermostat shaft until an audible click is heard.
2. Rotate the thermostat shaft left and right ten times causing the switch to click on and off ten times, while using the Multimeter to verify continuity.
3. If the switch does not show continuity during all ten trials, replace the thermostat.
Disassembling the thermostat will void the thermostat warranty.
1. Set compression ring onto capillary end of bulb finger tight, 1/2” from end of capillary.
2. Insert new thermostat bulb through control panel back.
3. Apply oil resistant flexible sealant ontocompression fitting thread before installing fitting into fryer vessel.
4. Position bent portion of bulb against far right heat transfer tube and install compression fitting snugly into fryer vessel.
5. Adjust bulb so at least 2” of bent portion of it is next to heat transfer tube and tighten compression nut onto compression fitting for fryer 18 & up. The end of thermostat bulb should touch the burner tube for 14" fryers.
6. Refill fryer with oil to “fill level line”.
7. Start fryer, preheat and calibrate with thermometer.
SERVICE DIAGNOSIS
A properly adjusted Keating Incredible Frying Machine® (IFM), with no load, will cycle “On” approximately every 2 1/2 to 3 minutes. Each cycle will last 15 to 25 seconds, ensuring that the temperature setting is held within a narrow band.
• Every Keating Incredible Frying Machine® (IFM) has a number of safety controls to ensure safe operation and guard against component failure.
10
Remove the cover by loosening the screws to gain access to the burner viewing windows (14” Model Shown).
SELF-HELP GUIDE
11
Common Problems Probable Cause Solutions (Follow Sequentially)
1. No power to unit.
a. Power switch light ON only.
b. Power Switch light and Red
overmax temperature light on.
c. All lights are off.
a. Drain handle not locked into
place.
b. High limit light has tripped.
c. Breaker has tripped.
a. Locate the handle used to drain
oil from fryer. Pull handle up and push it in as far as possible, locking it into place and activating the safety switch.
b. Reset the high-limit (press the
red button located in the bottom of the control panel).
c. Reset the breaker located on the
bottom of the control panel, check the outlet or check the breaker at the wall.
2. Timers (or lights) ON but fryer does not try to light.
a. Thermostat off. a.Set the thermostat to desired
temperature.
3. Blower light on. Red burner light comes on and goes out after about 3 seconds.
a. Problem with the outlet at the
wall.
b. Gas not turned on or not hooked up.
a.Plug fryer in to a different
electrical outlet (must be properly grounded).
b.Ensure gas hose is securely
connected. Turn on main gas.
4. Not recovering. a. Gas pressure incorrect.
b. Thermostat not calibrated.
c. Overloading fryer.
a.Contact service agent to verify
proper gas pressure.
b.Calibrate the thermostat by
rotating the dial plate to match the actual temperature of the oil (See page 9).
c. Do not overfill baskets with food.
d.Do not overfill fryer with oil (check
the fill level stamped into the fry pot).
Loading...
+ 30 hidden pages