Jungheinrich ETV211 User Manual

õUNGHEINRICH Event Messages
1 3 05 1
XX
E
F
Event number
Event group
Function group
S
Sub-index
Event Messages
05.12 1
G
This display units shows a four-digit event message for every
Z
event. Trucks that only use one luminous display (e.g. LED) show the event through a flashing code (see "Display System”). Each event message is also stored in the master logbook. The master logbook describes the event in more detail through the sub index behind the event message (FEXX).

Event numbering display

F E XX S
F Function group; E Event group
XX Event number S Sub index
The first two characters “F, E” refer to the category. The middle
Z
two digits “XX” refer to the event. From these two digits the range:
• 1 to 50 describes standard events (uniform basic events) which can occur in any function group.
• 51 to 99 describes specific events.
The event is described in further detail through the last characters “S” (single digit / multi-digit). This process ensures that a unique number is assigned to each event. Example:

Sub-division of function group "F"

System: Overlapping functions that cannot be assigned to any other
0
function group) Example: seat switch / deadman switch or master controller
1 Travel
2 Hydraulics (load handling)
3 Steering and travel
4 Displays/controls, interface
5 Charger (either on-board or external charger)
6 Reserved
7 Reserved
8 Reserved
Special functions
9
Example: ISM
õUNGHEINRICH Event Messages

Sub-division of event group “E”

Display system

05.12 2
G
Fault reset or
0
no fault
General fault / additional functions
1
Example: Logic error, e.g. both directions selected simultaneously
Current
2
(input interface, device-internal, output interface)
Voltage
3
(input interface, device-internal, output interface)
4 Temperature
Hardware
5
Example: Output transformer short circuit, EEPROM not responding, …
Software (internal software, application software, data record /
6
parameters) Example: EEPROM data error
7 Additional modules
The system distinguishes between:
• event messages caused by operator errors.
• event messages caused by truck errors.
For operator errors there are three versions that can be displayed in the truck depending on the display unit options.
• Event number display (e.g. CANDIS)
• Pictogram display
• Text message display
For truck errors the event number and possibly a fault graphic icon (e.g. service key) will also be displayed.
Trucks that only use one luminous display (e.g. LED) use the following flashing code:
• Each character of the four-digit event number is shown with a 2 Hz / 0.5 sec frequency (flashing).
The figure “zero” is displayed by flashing ten times.
Z
• After each character of the four-digit event message there is a pause (LED off) of one second.
• After the complete four-digit event message a 3 second pause (LED off) is set.
8 CAN monitoring
External fault
9
Example:
ISM
õUNGHEINRICH Event Messages
05.12 3

Description / cause / action and effects

The following table lists the event message with a description / cause / action and effect.
Z
Each event group (E) with the corresponding event number (XX) can be combined with different function groups (F), hence in the following table the placeholder “F” is used for the first character “F” of the four-digit event number. It also shows the operating status when the event occurred:
Operating status Explanation
Occurs during / directly after truck power up
Bootloader
(basic initialisation of components, possible change to flash mode). Example: Checking the RAM / ROM (memory check)
G
System start
Self test
Operation Occurs during operation
System end Occurs during truck power-down (correct powering down of components, …)
Undefined Can occur at any time
Occurs during installation of operating software of individual components. Example: correct hardware installed, ...
Occurs during the self-test of each component, as coordinated by the master
The main contactor is then closed
õUNGHEINRICH Event Messages

“Event messages” table

05.12 4
G
F E XX S Operational
Status
_ 1 01 1 System start
_1
_ 1 2 Self test
02
_ 1 3 Self test
_1 4
_1 03
1 Self test
Self test
Operation
1 Self test
2 Self test
3 Self test
Description Cause / Triggering Event Action
Supply via unexpected key switch input
Contact closed instead of open
Contact open instead of closed
Main contactor permanently on
Main contactor feedback input implausible
Output transformer faulty (phase U)
Output transformer faulty (phase V)
Output transformer faulty (phase W)
Evaluation of three key switch inputs. Possible encodings are 1, 2 or 4, otherwise the event message is triggered.
On power-up the capacitor voltage should be one volt (1 V) below the battery voltage.
When the main contactor has switched on the capacitor voltage should be the same as the battery voltage (within 500 msec.), otherwise the event message is produced.
respectively for t = 100 msec.: U_capacitor >= U_key - 3 V, if a) Monitoring processor tries to open the main contactor and if a) Control processor tries to open the main contactor
Feedback signal from main contactor status implausible with main contactor control (error activated after limit time)
The semi-jumpers 1, 2 and 3 are controlled in turned for 50 msec at 25% PWM (pulse width modulation) when the output transformer is closed (“Output transformer deactivated” signal). The event message is issued if at the end of the 50 msec period of the respective phase the following applies: V
Phase_X
< (V
capacitor
/ 2) - 25%
- Check key switch input connection against the wiring diagram;
- Replace controller;
- Test the main contactor output of the controller;
- Check wire connection;
- Replace contactor;
- Test the main contactor output of the controller;
- Check wire connection;
- Replace contactor;
- Replace controller;
- Test the main contactor output of the controller;
- Check wire connection;
- Replace contactor;
- Replace controller;
õUNGHEINRICH Event Messages
05.12 5
G
F E XX S Operational
Description Cause / Triggering Event Action
Status
1 Self test
_1 04
2 Self test
3 Self test
_ 1 04 4 Operation
Output transformer faulty (phase U)
Output transformer faulty (phase V)
Output transformer faulty (phase W)
Error bit set for power stage ID
_ 1 05 1 Self test Motor cutout
Semi-jumpers 1, 2 and 3 are controlled in turn for 50 msec at 25% PWM (pulse width modulation). The event message is issued if at the end of the 50 msec period of the respective phase the following applies: V
Phase_X
V
Phase_X
> (V < (V
capacitor
capacitor
/ 4) 25% or / 4) - 25%
"Error, power stage ID : The power card of the power stage can only obtain faulty information (ID) about the identity and hence suitability of the card for the intended powering of the operating system when the error bit is set"
Semi-jumpers 1, 2 and 3 are controlled in turn for 50 msec at 25% PWM (pulse width modulation). The event message is issued if at the end of the 50 msec period of at least one of the two non-controlled phases the following applies: V
Phase
V
Phase
> (V < (V
capacitor
capacitor
/ 4) 25% or / 4) - 25%
- Replace controller;
- Replace controller;
- Check motor connection wire (wire breakage);
- Replace motor;
_ 1 05 2 Self test
"Combi controller behaviour for non-controlled power stages" logic implausible
Semi-jumpers 1, 2 and 3 of a combi controller power part are controlled in turn for 50 msec at 25% PWM (pulse width modulation). The event message is issued if at the end of the 50 msec period of at least one of the semi-jumpers of the other power part the following applies: V
Phase_X
V
Phase_X
> (V < (V
capacitor
capacitor
/ 2) + 15% or / 2) - 15%
- Switch the truck off and on again;
- Check the motor connections;
- Check for a short between two power stages or motors;
- Replace signal-evaluating controller;
õUNGHEINRICH Event Messages
05.12 6
G
F E XX S Operational
Status
_ 1 06 1 Operation
_ 1 06 2 Operation
_ 1 06 3 Operation
Description Cause / Triggering Event Action
Safety switch inputs implausible
Deadman switch inputs implausible
Slack chain safety device inputs implausible
The safety switch consists of a NC and a NO contact. When the button is pressed both contacts connect simultaneously. As a result, only the 0/1 and 1/0 combinations should occur. During operation combinations 0/0 and 1/1 (500 msec.) trigger the event message. For a valid combination (0/1 or 1/0, 500 msec) the event message and the truck response are reset. For an implausible condition the seat switch is considered to be open (-> the truck brakes with the coasting ramp).
During operation combinations 0/0 and 1/1 trigger the event message. The event message can only be reset by resetting the truck. The activation limit is 2000 msec.
During operation combinations 0/0 and 1/1 trigger the event message. For a valid combination (0/1 or 1/0), the event and the truck response are reset. The activation limit is 1000 msec.
- Check safety switch wire connection;
- Check safety switch;
- Replace safety switch;
Safety switches can include:
Z
- Deadman (foot switch),
- Seat switch,
- Tiller switch.
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
_ 1 06 4 Operation
_ 1 06 5 Operation
Cabin gate inputs implausible
Optional cabin gate inputs implausible
During operation combinations 0/0 and 1/1 trigger the event message. For a valid combination (0/1 or 1/0), the event and the truck response are reset. The activation limit is 2000 msec.
During operation combinations 0/0 and 1/1 trigger the event message. For a valid combination (0/1 or 1/0), the event and the truck response are reset. The activation limit is 2000 msec.
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
õUNGHEINRICH Event Messages
05.12 7
G
F E XX S Operational
Status
_ 1 06 6 Operation
_ 1 06 7 Operation
_ 1 06 8 Operation
_ 1 06 9 Operation
Description Cause / Triggering Event Action
Sideshift index inputs implausible
Aisle recognition right inputs implausible
Aisle recognition left inputs implausible
Load handling inputs: no signal
During operation combinations 0/0 and 1/1 trigger the event message after a traverse path of more than 30mm. For a valid combination (0/1 or 1/0), the event and the truck response are reset. The activation limit is 0 msec.
During operation combinations 0/1 and 1/0 trigger the event message after the truck has travelled more than 100mm. The event message can only be reset by resetting the truck. The activation limit is 100 msec.
During operation combinations 0/1 and 1/0 trigger the event message after the truck has travelled more than 100mm. The event message can only be reset by resetting the truck. The activation limit is 100 msec.
During operation combinations 0/0 and 1/1 trigger the event message. The event message can only be reset by resetting the truck. The activation limit is 2000 msec.
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Test sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
_ 1 06 10 Operation
_ 1 06 11 Operation
Load sensing inputs: no signal
Logic test: signal at working platform raised inputs improbable
If the weight display > 300 kg the load sensors must be applied. The event message can only be reset by resetting the truck. The activation limit is 2000 msec.
During operation combinations 0/0 and 1/1 trigger the event message. The event message can only be reset by resetting the truck. The activation limit is 2000 msec.
- Check wiring with multimeter;
- Test sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Test sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
õUNGHEINRICH Event Messages
05.12 8
G
F E XX S Operational
Status
_ 1 06 12 Operation
_ 1 06 13 Operation
_ 1 06 14 Operation
_ 1 06 15 Operation
Description Cause / Triggering Event Action
Logic test: signal at left/right gate lock inputs improbable
Logic test: No signal for gate lock despite gate lock being applied
Logic test: Signal for gate lock present despite gate lock not being applied
Logic test: No signal for gate lock despite the lift mechanism being above the set height
During operation combinations 0/1 and 1/0 trigger the event message. The activation limit is 2000 msec.
During operation no feedback triggers the message when applied. The activation limit is 2000 msec.
During operation a feedback triggers the message without being applied. The activation limit is 2000 msec.
During operation no feedback triggers the message when lift mechanism is above the set height. The activation limit is 2000 msec.
- Check wiring with multimeter;
- Test sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Test sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Test sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Test sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
_ 1 07 1 Operation
Operator protection switch inputs implausible
The body protection switch consists of a NC and a NO contact. When the button is pressed both contacts connect simultaneously. As a result, only the 0/1 and 1/0 combinations should occur. During operation combinations 0/0 and 1/1 (500 msec.) trigger the event message. For a valid combination (0/1 or 1/0, 500 msec) the event message and the truck response are reset.
- Check wire connections;
- Check operator protection switch;
- Replace operator protection switch;
õUNGHEINRICH Event Messages
05.12 9
G
F E XX S Operational
Status
_ 1 07 2 Operation
_ 1 08 1 Operation
_ 1 08 2 Operation
_ 1 08 3 Operation
Description Cause / Triggering Event Action
Acknowledge button inputs implausible
Touch mode switch inputs implausible
"Crawl speed redundant inputs" logic implausible
“Stop" button redundant inputs” logic improbable
During operation combinations 0/0 and 1/1 (500 msec.) trigger the event message. For a valid combination (0/1 or 1/0, 500msecs) the event and the truck response are reset.
The touch mode button consists of a NC and a NO contact. When the button is pressed both contacts connect simultaneously. As a result, only the 0/1 and 1/0 combinations should occur. During operation combinations 0/0 and 1/1 (500 msec.) trigger the event message. For a valid combination (0/1 or 1/0, 500 msec) the event message and the truck response are reset.
During operation combinations 0/0 and 1/1 (500 msec.) trigger the event message. For a valid combination (0/1 or 1/0, for 500 msec.) the event and truck response are reset. The status is assessed as an actuated status (adjustable crawl speed active)
The "Stop" button consists of an NC and an NO contact. When the button is pressed both contacts switch simultaneously. As a result, only the 0/1 and 1/0 combinations should occur. During operation the combinations 0/0 and 1/1 (500 msec) trigger the event message. For a valid combination (0/1 or 1/0, 500 msec) the event message and the truck's response are reset.
- Check wire connections;
- Check button;
- Replace button;
- Check wire connection;
- Check touch mode button;
- Replace touch mode button;
- Check wire connections;
- Check crawl speed button;
- Replace crawl speed button;
- Check parameter reading (side pedestrian mode activated?);
- Check wire connections;
- Press "Stop" button;
- Replace "Stop" button;
õUNGHEINRICH Event Messages
05.12 10
G
F E XX S Operational
Status
_ 1 09 1 Operation
_ 1 10 1 Operation
_ 1 10 2 Operation
Description Cause / Triggering Event Action
Weigher button inputs implausible
Lift/lower digital setpoints are invalid
Lift/lower analog setpoints are invalid
The weigher button consists of a NC and a NO contact. When the button is pressed both contacts connect simultaneously. As a result, only the 0/1 and 1/0 combinations should occur. During operation combinations 0/0 and 1/1 (500 msec.) trigger the event message. For a valid combination (0/1 or 1/0, 500 msec) the event message and the truck response are reset.
During operation the combination 1/1 for both buttons pressed simultaneously for 500 msec triggers the following event message. For a valid combination (0/0, 0/1 or 1/0 [button not pressed / only one button pressed]; 500 msec) the event message and the truck response are reset.
During operation the limits for 1/1 [both buttons pressed simultaneously] for 500 msec have been exceeded. For a valid combination (0/0, 0/1 or 1/0 [button not pressed / only one button pressed]; 500 msec) the event message and the truck response are reset.
- Check wire connection;
- Check weigher button;
- Replace weigher button;
- Check wire connection;
- Check button;
- Replace button;
- Check wire connection;
- Check button;
- Replace button;
_1 11 1 Operation
_1 11 2 Operation
_1 11 3 Operation
Braking setpoint and release contact implausible
Braking setpoint and release contact implausible
Braking setpoint and full brake contact implausible
The event message is triggered if the following applies for T = 250msec: V
brake pedal
Logic signal release contact = 1
The event message is triggered if the following applies for T = 250msec: V
brake pedal
Logic signal release contact = 0
The event message is triggered if the following applies for T = 250msec: V
brake pedal
Logic signal full brake contact = 1
< 12.5% and
> 25% and
< 65% and
- Check wire connection;
- Check pedal power supply;
- Replace pedal;
- Replace signal-evaluating controller;
- Check wire connection;
- Check pedal power supply;
- Replace pedal;
- Replace signal-evaluating controller;
- Check wire connection;
- Check pedal power supply;
- Replace pedal;
- Replace signal-evaluating controller;
õUNGHEINRICH Event Messages
05.12 11
G
F E XX S Operational
Status
_1 11 4 Operation
_1 11 5 Operation
_1 11 6 Operation
_ 1 12 1 Operation
_ 1 12 2 Operation
Description Cause / Triggering Event Action
Braking setpoint and full brake contact implausible
Combination "brake setpoint" against brake pressure invalid (movement without brake pressure)
Combination "brake setpoint" against brake pressure invalid (brake pressure without movement)
Travel setpoint and release contact invalid
Travel setpoint and release contact invalid
The event message is triggered if the following applies for T = 250msec: V
brake pedal
Logic signal full brake contact = 0
for T = 250 msec.: (V
brake pedal
brake pressure < 40 bar
for T = 250 msec.: (V
brake pedal
brake pressure > 20 bar
The event message is triggered if the following applies for T = 250msec: V
accelerator pedal
Logic signal release contact = 1
The event message is triggered if the following applies for T = 250msec: V
accelerator pedal
Logic signal release contact = 0
> 80% and
> 80%) and
< 20%) (>TV)) and
< 12.5% and
> 25 % and
- Check wire connection;
- Check pedal power supply;
- Replace pedal;
- Replace signal-evaluating controller;
- Check brake fluid level;
- Check proximity sensor;
- Check pressure sensors;
- Check brake fluid level;
- Check proximity sensor;
- Check pressure sensors;
- Check wire connection;
- Check accelerator pedal/tiller arm power supply;
- Replace accelerator pedal / tiller arm;
- Replace signal-evaluating controller;
- Check wire connection;
- Check accelerator pedal/tiller arm power supply;
- Replace accelerator pedal / tiller arm;
- Replace signal-evaluating controller;
_ 1 12 3 Operation
Total voltage "Travel1 setpoint" to "Travel2 setpoint" invalid
for T = 250msec: (V_accelerator pedal1 +V_accelerator pedal2 > 5.5V or V_accelerator pedal1 +V_accelerator pedal2 < 4.5V)
- Check wire connection;
- Check accelerator pedal/tiller arm power supply;
- Replace accelerator pedal / tiller arm;
- Replace signal-evaluating controller;
õUNGHEINRICH Event Messages
05.12 12
G
F E XX S Operational
Status
_ 1 13 1 Operation
_ 1 14 1 Self test
_ 1 15 1 Operation
_ 1 15 2 Operation
_ 1 16 1 Operation Irregular speed signal
Travel direction 1 and travel direction 2 invalid
Motor speed signal implausible
Motor powers without setpoint
Motor powers without setpoint
Description Cause / Triggering Event Action
During operation the combination 1/1 [both travel direction switch / button / twin pedal pressed] for 500 msec triggers the following event message. For a valid combination (0/0, 0/1 or 1/0 [travel direction switch/button/twin pedal not pressed or only one travel direction switch/button/twin pedal pressed]; 500 msec) the event message and the truck response are reset.
Logic test: after a short period of motor control, the speed sensor does not supply any signals
Motor powered for 500 msec without setpoint. Logic: implausible status in controller
Convergence problem in monitor for the motor speed Logic: implausible status in monitor
Jump from n_motor > 10% to n_motor < 1% and for T = 80 msec. the following applies: n_motor < 1%
- Check wire connection;
- Check travel direction switch/button/twin pedal;
- Check travel direction switch/button/twin pedal;
- Replace signal-evaluating controller;
- Rectify mechanical blockage of drive system;
- Check speed sensor power supply;
- Check wire connection;
- Replace speed sensor;
- Replace signal-evaluating controller;
- Check motor connections;
- Check motor model, replace if necessary;
- Check motor connections;
- Check motor model, replace if necessary;
- Check speed sensor power supply;
- Check wire connection;
- Replace speed sensor;
- Replace signal-evaluating controller;
õUNGHEINRICH Event Messages
05.12 13
G
F E XX S Operational
Status
_ 1 16 2 Operation
Description Cause / Triggering Event Action
Irregular speed signal (large jump in evaluated speed signal)
Incrementer damaged The AC-3 Power Control (U8) has identified the sensor bearing as being damaged. The AC-3 Power Control (U8) monitors sensor to ensure the impulse wires are single-channel, and to check for sudden changes in the pulse rate and for constant power supply. Sensor is damaged (broken wire, short circuit, incorrect pulses); Operating system wrongly flags a fault; AC-3 Power Control component (sensor bearing control) is faulty Jump from n_Motor> 10 % to n_Motor< 1 % and For T = 80 msec.: n_motor< 1%
No signals from incremental transmitter 1B5.
- Check incrementer signals with multimeter;
- Check speed sensor power supply;
- Check wire connection;
- Replace speed sensor;
- Replace signal-evaluating controller;
- Manually move the shuttle to the channel start, remove any blockage (use recovery vehicle);
- Reduce load on shuttle;
- Drive: check setpoint specification, motor controller 9U19 and drive motor including carbon brushes and incremental transmitter 1B5;
- Check wire connection;
- If the shuttle is overloaded, increase the travel speed;
_ 1 17 1 Operation
A speed sensor channel does not pulse
Both speed sensor tracks are counted. When the first deviation limit is reached the system waits for a feasible signal from the suspected broken track. When the second limit is reached the event message is generated.
- Check speed sensor incrementer channels;
- Replace speed sensor;
- Replace signal-evaluating controller;
õUNGHEINRICH Event Messages
05.12 14
G
F E XX S Operational
Status
_ 1 17 2 Operation
_ 1 17 3 Operation
Description Cause / Triggering Event Action
A speed sensor channel does not pulse
No speed signal from the travel impulse sensor although travel sensor indicates greater than
0.5 km/h.
Incrementer damaged The AC-3 Power Control (U8) has identified the sensor bearing as being damaged. The AC-3 Power Control (U8) monitors sensor to ensure the impulse wires are single-channel, and to check for sudden changes in the pulse rate and for constant power supply. Sensor is damaged (broken wire, short circuit, incorrect pulses); Operating system wrongly flags a fault; AC-3 Power Control component (sensor bearing control) is faulty Both sensor tracks are counted. When the first deviation limit is reached the system waits for a feasible signal from the suspected broken track. When the second limit is reached the event is generated.
The counts for both incrementers are compared. If the travel incrementer supplies a speed signal of > 0.05 km/ h and the travel pulse contact controller incrementer a speed signal of 0 km/h, the event is triggered. The activation limit is 100 msec.
- Check incrementer signals with multimeter;
- Check speed sensor power supply;
- Check wire connection;
- Replace speed sensor;
- Replace signal-evaluating controller;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
_ 1 17 4 Operation
_ 1 17 5 Operation
No speed signal from travel sensor although travel impulse sensor indicates greater than 0.5 km/h.
Deviation of more than
0.25 km/h between travel impulse sensor and travel sensor
The counts for both incrementers are compared. If the travel incrementer supplies a speed signal of 0 km/h and the travel pulse contact controller incrementer a speed signal of > 0.05 km/h, the event is triggered. The activation limit is 100 msec.
The counts for both incrementers are compared. If the speed signals of both incrementers differ by more than
0.025 km/h, the event is triggered. The activation limit is 100 msec.
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
õUNGHEINRICH Event Messages
05.12 15
G
F E XX S Operational
Status
_ 1 17 6 Operation
_ 1 17 7 Operation
_ 1 17 8 Operation
_ 1 17 9 Operation
_ 1 17 10 Operation
Description Cause / Triggering Event Action
Directions obtained from travel sensor and travel impulse sensor are contradictory
One incremental track height measurement of the proportional lift pulses, the other does not
One incremental track height measurement of the free lift pulses, the other does not
One incremental track height measurement of the auxiliary lift pulses, the other does not
Main lift does not lower despite the hydraulic motor turning
The counts for both incrementers are compared. If the speed of both incrementers > 0.01 km/h and the directions of the speed signals for both incrementers are contradictory, the event is triggered. The activation limit is 100 msec.
Both sensor tracks are counted. When the first deviation limit is reached the system waits for a feasible signal from the suspected broken track. When the second limit is reached the event is generated.
Both sensor tracks are counted. When the first deviation limit is reached the system waits for a feasible signal from the suspected broken track. When the second limit is reached the event is generated.
Both sensor tracks are counted. When the first deviation limit is reached the system waits for a feasible signal from the suspected broken track. When the second limit is reached the event is generated.
The counts for both incrementers are compared. If the lift controller incrementer supplies a speed signal, but the lift height measurement incrementer does not supply a signal after one second, the event is triggered. The activation limit is 20 msec.
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
_ 1 17 11 Operation
Main lift lowers despite the hydraulic motor not turning
The counts for both incrementers are compared. If the lift height measurement incrementer supplies a speed signal, but the lift controller incrementer does not supply a signal after one second, the event is triggered. The activation limit is 20 msec.
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
õUNGHEINRICH Event Messages
05.12 16
G
F E XX S Operational
Status
_ 1 17 12 Operation
_ 1 17 13 Operation
_ 1 17 14 Operation
_ 1 17 15 Operation
_ 1 17 16 Operation
_ 1 17 17 Operation
Description Cause / Triggering Event Action
Excessive deviation between lift speed and pump speed
Proportional lift incrementer 1: One channel defective
Proportional lift incrementer 2: One channel defective
Free lift incrementer 1: One channel defective
Free lift incrementer 2: One channel defective
Aux. lift incrementer 1: One channel defective
The counts for both incrementers are compared. If the incrementers for the lift control and lift height measurement are not synchronised within three seconds, the event is triggered. The activation limit is 100 msec.
Channel A or channel B are defective on the incrementer
Channel A or channel B are defective on the incrementer
Channel A or channel B are defective on the incrementer
Channel A or channel B are defective on the incrementer
Channel A or channel B are defective on the incrementer
- Check the hydraulic system for leaks;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
_ 1 17 18 Operation
_ 1 17 19 Operation
_ 1 17 20 Operation
Logic test: Main lift does not lower despite pump rotating
LH load wheel sensor incrementer deviation
RH load wheel sensor incrementer deviation
The counts for both incrementers are compared. If the lift controller incrementer supplies a speed signal, but the lift height measurement incrementer does not supply a signal after one second, the event is triggered. The activation limit is 20 msec.
Incorrect counting detected between ChA and ChB.
Incorrect counting detected between ChA and ChB.
- Check incrementer signals with multimeter;
- Check wiring with multimeter;
- Replace speed sensor;
- Check sensor / magnet assembly;
- Replace sensor;
- Check sensor / magnet assembly;
- Replace sensor;
õUNGHEINRICH Event Messages
05.12 17
G
F E XX S Operational
Status
LH load wheel sensor
_ 1 17 21 Operation
_ 1 17 22 Operation
_ 1 17 23 Operation
_ 1 18 1 Undefined
_ 1 19 1 Operation Cabin position implausible
excessive deviation from reading to drive wheel
RH load wheel sensor excessive deviation from reading to drive wheel
Three channel incrementer comparison with sensor bearing incrementer
Speed sensor in load wheel sensor damaged
Description Cause / Triggering Event Action
Incorrect counting detected between LH load wheel sensor and drive wheel incrementer.
Incorrect counting detected between RH load wheel sensor and drive wheel incrementer.
The sensor bearing and three channel incrementer are synchronised with respect to each other every 120 mm. The error is generated if the sensor bearing deviates from the three channel sensor by >= 5 mm.
This event message is not currently used.
For T >= limit time: detection of a status change of the lower limit platform sensor from the zero position to the "platform raised" position during travel
- Check sensor / magnet assembly;
- Check tyre quality;
- Replace sensor;
- Check sensor / magnet assembly;
- Check tyre quality;
- Replace sensor;
- Test the electrical function of the sensor bearing
- Test the mechanical function of the sensor bearing
- Check speed sensor power supply;
- Check wire connection;
- Replace speed sensor;
- Replace signal-evaluating controller;
- Check wiring from controller to platform lower limit sensor;
- Check / replace lower limit sensor;
- Check lift motor power cables;
- Replace the signal-generating controller;
õUNGHEINRICH Event Messages
05.12 18
G
F E XX S Operational
Status
_ 1 20 1 Operation Drive wheel slip excessive
_ 1 21 1 Self test Output stage faulty
_1 22 1
“Digital signal” logic/signal shape implausible
Description Cause / Triggering Event Action
Excessive slip / drive has probably been tipped The AC-3 Power Control (U8) has detected excessive deviation (slip) between the phase current frequency and the speed. The activation limit is 20 msec. More torque is required from / placed on the motor than it can provide / accept; Field current is reduced excessively; Error accompanying sensor bearing control or output stage protection; Operating system does not allow enough slip for the driven motor; AC-3 Power Control component is damaged
The lift actuator jumper is controlled for max. 40 msec at 100 % PWM (pulse width modulation). The event message is triggered if the pump voltage drops within this time below 10% of the capacitor voltage: V
This event message is triggered if the signal shape or modulation of a digital signal is implausible.
pump
> V
capacitor
/ 10.
- Check motor connection wire (wire breakage);
- Check motor model, replace if necessary;
- Check motor and replace if necessary;
- Check motor connection wire (wire breakage);
- Check motor model, replace if necessary;
- Replace controller;
- Replace tiller head;
_ 1 23 1 Operation
_ 1 23 2 Operation
Brake response switch signal implausible (in idle)
Brake response switch signal implausible (in idle)
The event message is triggered if after the brake applies the feedback switch does not report this status (after 1sec.).
The event message is triggered if after the brake is released the feedback switch does not report this status (after 300 msec.).
- Remove physical blockage from the brake;
- Check wire connection;
- Check switch and replace if necessary;
- Replace signal-evaluating controller;
- Remove physical blockage from the brake;
- Check wire connection;
- Check switch and replace if necessary;
- Replace signal-evaluating controller;
õUNGHEINRICH Event Messages
05.12 19
G
F E XX S Operational
Status
_ 1 23 3 Operation
_ 1 23 4 Operation
_ 1 23 5 System start
_ 1 23 6 Operation
Description Cause / Triggering Event Action
Brake response switch signal implausible (speed > 1km/h)
Failsafe brake does not hold (on a ramp)
Failsafe brake does not hold (during system start)
Left load wheel brake not controlled but feedback signal present
This event message is triggered if the response switch signals applied status during travel.
This event message is triggered if for T > 250 msec the transmission reports an actual speed of > 20 rpm when the brake is applied.
Left load wheel brake not controlled but feedback signal is still present The activation limit is 1000 msec.
- Remove physical blockage from the brake;
- Check wire connection;
- Check switch and replace if necessary;
- Replace signal-evaluating controller;
- Check brake wear, replace wear parts / brake if necessary.
- Measure current through the magnetic coil (you should not be able to measure any current when the brake is applied).
- Replace signal-issuing controller;
- Check brake wear, replace wear parts / brake if necessary.
- Measure current through the magnetic coil (you should not be able to measure any current when the brake is applied).
Replace signal-issuing controller;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if
necessary;
_ 1 23 7 Operation
Left load wheel brake controlled although feedback signal missing
Left load wheel brake controlled but feedback signal is not present The activation limit is 1000 msec.
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if
necessary;
õUNGHEINRICH Event Messages
05.12 20
G
F E XX S Operational
Status
_ 1 23 8 Operation
_ 1 23 9 Operation
_ 1 23 10 System start
_ 1 23 11 Operation
Description Cause / Triggering Event Action
Right load wheel brake not controlled but feedback signal present
Right load wheel brake controlled although feedback signal missing
Hydraulic failsafe brake cannot be released (pressure > 3 bar for energised brake)
Manual parking brake feedback contacts implausible
Right load wheel brake not controlled but feedback signal is still present The activation limit is 1000 msec.
Right load wheel brake controlled but feedback signal is not present. The activation limit is 1000 msec.
for 500 msec.: brake energised and pressure on emergency stop mechanism > 3 bar
If the combinations 0/0 and 1/1 appear for longer than the limit time, a message is activated.
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if
necessary;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if
necessary;
- Listen to check if emergency stop mechanism switches:
- If so, check the pressure sensor and replace if necessary;
- If not, check the relay and replace if necessary;
- Check brake wear, replace wear parts / brake if necessary;
- Check wire connection;
- Check switch and replace if necessary;
- Replace signal-evaluating controller;
_ 1 24 1 Operation Lift height signal implausible
_ 1 24 2 Operation
“Stacking height redundant inputs” logic implausible
The lift height sensor sequence is implausible. This
event message is triggered if the following applies for T => 500 msec: Sequence of 2 lift height signals is implausible, e.g.
Top lift height signal without Bottom lift height signal
For t = 100 msec. the NC and NO contacts have the same condition
- Check wire connection;
- Check sensor and replace if necessary;
- Replace signal-evaluating controller;
- Check wire connection;
- Check sensor and replace if necessary;
- Replace signal-evaluating controller;
õUNGHEINRICH Event Messages
05.12 21
G
F E XX S Operational
Status
_ 1 24 3 Operation
_ 1 24 4 Operation
_ 1 24 5 Operation
_ 1 24 6 Operation
_ 1 24 7 Operation
Description Cause / Triggering Event Action
“Free lift sensor redundant inputs” logic implausible
Lifting stroke greater than 2x free lift, however mast lift has not been detected
“Lift limit switch redundant inputs” logic implausible
“Initial lowering limit redundant inputs” logic implausible
Logic: lift system limit switch faulty.
For t = 250 msec. the NC and NO contacts have the same condition When the event occurs, the master assumes that the truck is in the mast lift stage.
Integrated lift stroke is greater than 2x the set free lift height, however sensor indicates free lift. When the event occurs, the master assumes that the truck is in the mast lift stage.
For t = 100 msec. the NC and NO contacts have the same condition
For t = 100 msec. the NC and NO contacts have the same condition
No positive signal at 7B38.1 - 7B38.4 during lifting or lowering.
- Check wire connection;
- Check sensor and replace if necessary;
- Check wire connection;
- Check sensor and replace if necessary;
- Check wire connection;
- Check sensor and replace if necessary;
- Replace signal-evaluating controller;
- Check wire connection;
- Check sensor and replace if necessary;
- Replace signal-evaluating controller;
- Try not to use the lift system as the lift limit is deactivated. The lift mechanism could move too far and get damaged;
- If absolutely necessary, lower the lift mechanism manually. Note that lowering must end as soon as the shuttle can move freely underneath the pallets.
- Check lift limit switch 7B38.1-7B38.4, check signal return to inputs R3-R6 of main controller 8U37;
- Check wire connection;
_ 1 24 8 Operation
Lift stroke greater than 1.5x free lift, however mast lift has not been detected
Integrated lift stroke is greater than 1.5x the set free lift height, however sensor indicates free lift. When the event occurs, the master assumes that the truck is in the mast lift stage. Event is reset when mast lift is detected.
- Free lift sensor check (position, contamination)
- Set free lift height check
- Pump drive check (pump worn?)
õUNGHEINRICH Event Messages
05.12 22
G
F E XX S Operational
Status
_ 1 25 1 Operation
_ 1 25 2 Operation
_ 1 26 1 Operation
_ 1 26 2 Operation
Description Cause / Triggering Event Action
Signal on load sensing inputs is implausible
No load sensing signal when weight > 300 kg
Feedback from a main contactor contact or the emergency stop relay although the Emergency Disconnect switch is not activated.
Feedback from the Emergency Disconnect switch at channel 1 of the Safe computer although the Emergency Disconnect switch has not been activated
During operation combinations 0/0 and 1/1 trigger the event message. The event message can only be reset by resetting the truck. The activation limit is 2000 msec.
Plausibility test: If the weight display > 300 kg the load sensors must be applied. The event message can only be reset by resetting the truck. The activation limit is 2000 msec.
Feedback from a main contactor contact or the emergency stop relay although the Emergency Disconnect switch is not activated. The event message can only be reset by resetting the truck. The activation limit is 100 msec.
Feedback from the Emergency Disconnect switch at channel 1 of the Safe computer although the Emergency Disconnect switch has not been activated. The event message can only be reset by resetting the truck. The activation limit is 100 msec.
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
_ 1 26 3 Operation
Feedback from the main contactor level 1 control at channel 1 of the Safe computer although contactor level 1 has not been activated.
Feedback from the main contactor level 1 control at channel 1 of the Safe computer although contactor level 1 has not been activated. The event message can only be reset by resetting the truck. The activation limit is 100 msec.
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
õUNGHEINRICH Event Messages
05.12 23
G
F E XX S Operational
Status
_ 1 26 4 Operation
_ 1 26 5 Operation
_ 1 26 6 Operation
Description Cause / Triggering Event Action
Feedback from the main contactor level 2 control at channel 1 of the Safe computer although contactor level 1 has not been activated.
Feedback from the Emergency Disconnect switch at channel 2 of the Safe computer although the Emergency Disconnect switch has not been activated
Feedback from the main contactor level 1 control at channel 2 of the Safe computer although contactor level 1 has not been activated.
Feedback from the main contactor level 2 control at channel 1 of the Safe computer although contactor level 1 has not been activated. The event message can only be reset by resetting the truck. The activation limit is 100 msec.
Feedback from the Emergency Disconnect switch at channel 2 of the Safe computer although the Emergency Disconnect switch has not been activated. The event message can only be reset by resetting the truck. The activation limit is 100 msec.
Feedback from the main contactor level 1 control at channel 2 of the Safe computer although contactor level 1 has not been activated. The event message can only be reset by resetting the truck. The activation limit is 200 msec.
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
_ 1 26 7 Operation
_ 1 26 8 Operation
No feedback from the Emergency Disconnect switch at channel 1/2 of the Safe computer although the Emergency Disconnect switch has been activated
No feedback from relay K1 despite Safe computer activation
No feedback from the Emergency Disconnect switch at channel 1/2 of the Safe computer, although activated The event message can only be reset by resetting the truck. The activation limit is 200 msec.
No feedback from relay K1 although the Safe computer has been activated. The event message can only be reset by resetting the truck. The activation limit is 200 msec.
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
õUNGHEINRICH Event Messages
05.12 24
G
F E XX S Operational
Status
_ 1 26 9 Operation
_ 1 26 10 Operation
_ 1 26 11 Operation
_ 1 26 12 Operation
_ 1 26 13 Operation
Description Cause / Triggering Event Action
No feedback from relay K2 despite Safe computer activation
No feedback from relay K3 despite Safe computer activation
No feedback from relay K4 despite Safe computer activation
No feedback from main contactor 1 despite "main contactor 1" signal activation
No feedback from main contactor 2 despite "main contactor 2" signal activation
No feedback from relay K2 although the Safe computer has been activated. The event message can only be reset by resetting the truck. The activation limit is 200 msec.
No feedback from relay K3 although the Safe computer has been activated. The event message can only be reset by resetting the truck. The activation limit is 200 msec.
No feedback from relay K4 although the Safe computer has been activated. The event message can only be reset by resetting the truck. The activation limit is 200 msec.
No feedback from main contactor 1 although the Safe computer has been activated. The event message can only be reset by resetting the truck. The activation limit is 200 msec.
No feedback from main contactor 2 although the Safe computer has been activated. The event message can only be reset by resetting the truck. The activation limit is 200 msec.
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
_ 1 26 14 System start
_ 1 26 15 Operation
Test routine for emergency stop circuit by the Safe computer has failed
Different input statuses between the two Safe computers
Power up test for emergency stop circuit by the Safe computer has failed The event message can only be reset by resetting the truck. The activation limit is 20 msec.
Redundant controllers of the Safe computer have detected different input statuses. The event message can only be reset by resetting the truck. The activation limit is 100 msec.
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
õUNGHEINRICH Event Messages
05.12 25
G
F E XX S Operational
Status
_ 1 26 16 Operation
_ 1 26 17 Operation
_ 1 26 18 Operation
_ 1 27 1 Operation
_ 1 28 1 Operation
_ 1 28 2 Operation
Description Cause / Triggering Event Action
Comparison of channel A / channel B of external Emergency Disconnect of APM + PLC for diversity
Monitoring of APM+ Emergency Stop cancel request and the power supply.
Monitoring of APM+ Emergency Stop cancel request and the power supply.
Main Lift lowers without activation signal
Main lift: free lift has lowered before proportional lift
Main lift: proportional lift has lowered before free lift
The error is triggered for the combination 1/0 or 0/1. Activation limit 100 ms.
The Emergency Stop request is withdrawn via the CanBus, however there is no corresponding Emergency Disconnect feedback.
The Emergency Stop request is set via the CanBus, however there is no corresponding Emergency Disconnect feedback.
Main Lift stage has lost height without request. The event message appears as soon as the lift height lowers by more than 50 mm without request.
The free lift stage has moved hydraulically although the proportional lift stage was not fully retracted.
The proportional lift stage has moved hydraulically although the free lift stage was not fully retracted.
- Check information in the truck display
- Assess wiring
- Check information in the truck display
- Assess wiring
- Check information in the truck display
- Assess wiring
- Check mast mechanics;
- Check mast hydraulics;
- Check mast mechanics;
- Check mast hydraulics;
- Check mast mechanics;
- Check mast hydraulics;
_ 1 29 1 Operation
_ 1 29 2 Operation
_ 1 29 3 Operation
_ 1 29 4 Operation
Main lift: Permissible lowering speed exceeded
Aux. lift: Permissible lowering speed exceeded
Sideshift: Permissible speed exceeded
Rotate: Permissible speed exceeded
The permissible lowering speed has been exceeded.
The permissible lowering speed has been exceeded.
The permissible speed has been exceeded.
The permissible speed has been exceeded.
- Check mast mechanics;
- Check mast hydraulics;
- Compare actual speed with data sheet values;
- if it is too high, adjust to data sheet value;
- Compare actual speed with data sheet values;
- if it is too high, adjust to data sheet value;
- Compare actual speed with data sheet values;
- if it is too high, adjust to data sheet value;
õUNGHEINRICH Event Messages
05.12 26
G
F E XX S Operational
Status
_ 1 30 1 Operation
_ 1 30 2 Operation
_ 1 30 3 Operation
_ 1 30 4 Operation
_ 1 31 1 System start
Description Cause / Triggering Event Action
Main lift does not reach pre­tension moment in prescribed time
Aux. lift does not reach pre­tension moment in prescribed time
Pallet clamp does not reach the closed limit position in prescribed time
Pallet clamp does not reach the open limit position in prescribed time
Emergency stop circuit power-up test: Emergency Stop switch activated, but CAN-BUS not OK
The pre-tension moment could not be established in the set time.
The pre-tension moment could not be established in the set time.
The pallet clamp closed limit position could not be reached in the set time.
The pallet clamp open limit position could not be reached in the set time.
CAN-BUS status damaged during booting. The event message can only be reset by an Emergency Stop reset. The activation limit is 1000 msec.
- Check the pre-tension moment and adjust if necessary;
- Check mast mechanics;
- Check mast hydraulics;
- Check the pre-tension moment and adjust if necessary;
- Check mast mechanics;
- Check mast hydraulics;
- Check the hydraulic setpoint and adjust if necessary;
- Check the pallet clamp mechanisms for sluggishness;
- Check the hydraulic setpoint and adjust if necessary;
- Check the pallet clamp mechanisms for sluggishness;
- Check wiring with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
_ 1 31 2 System start
_ 1 31 3 System start
Emergency stop circuit power-up test: no activation of any pulse contact controllers
Emergency stop circuit power-up test: no lift controller activation
No pulse contact controller has reported charge circuit activation. The charging of the pulse contact controllers must be finished within 10 seconds. The activation limit is 1000 msec.
The hydraulic controller has not reported charge circuit activation. The charging of the pulse contact controllers must be finished within 10 seconds. The activation limit is 1000 msec.
- Check the charging voltage on the controllers;
- Check wiring;
- Check the charging voltage on the controllers;
- Check wiring;
õUNGHEINRICH Event Messages
05.12 27
G
F E XX S Operational
Status
_ 1 31 4 System start
_ 1 31 5 System start
_ 1 31 6 System start
_ 1 31 7 System start
_ 1 32 1 System start
Description Cause / Triggering Event Action
Emergency stop circuit power-up test: no traction controller activation
Emergency stop circuit power-up test: no steering controller activation
Emergency stop circuit power-up test: no release of main contactor level 2
Emergency stop circuit power-up test: non-defined EMERGENCY STOP error
power circuit activated during charging
The traction controller has not reported load circuit activation. The charging of the pulse contact controllers must be finished within 10 seconds. The activation limit is 1000 msec.
The steering controller has not reported load circuit activation. The charging of the pulse contact controllers must be finished within 10 seconds. The activation limit is 1000 msec.
Feedback contact of second main contactor level not closed within 10 seconds. The activation limit is 1000 msec.
Other non-separated event message in main contactor circuit. This event message does not occur in normal operation. The activation limit is 1000 msec.
Charge
The AC-3 Power Control (U8) has been activated while its internal capacitors were charging. The main contactor was opened during active control. Power circuit activated during charging. The activation limit is 20 msec. The main contactor was disconnected during active control; The control system was activated before the main contactor was closed and the internal capacitors were charged; Installation of the AC-3 Power Control component is damaged; AC-3 Power Control component (voltage measurement) is damaged;
- Check the charging voltage on the controllers;
- Check wiring;
- Check the charging voltage on the controllers;
- Check wiring;
- Check the charging voltage on the controllers;
- Check wiring;
The event message should not occur.
Z
Otherwise contact troubleshooting specialists;
- Check power cables (main current connections, integrated charging circuit wiring,...);
- Check main current fuses and replace if necessary;
- Replace AC-3 Power Control interface card;
õUNGHEINRICH Event Messages
05.12 28
G
F E XX S Operational
Status
_ 1 32 2 Self test
_ 1 32 3 Self test
_ 1 33 1 Operation
_ 1 33 2 Operation
_ 1 33 3 Operation
Description Cause / Triggering Event Action
Capacitor pre-charge cannot be switched off
Capacitor pre-charge (output stage pre-charge) not complete
Ground system track 1 left actual value sensor system: invalid channel A / channel B value relationship
Ground system track 2 left actual value sensor system: invalid channel A / channel B value relationship
Ground system track 3 left actual value sensor system: invalid channel A / channel B value relationship
The capacitor voltage should reduce by at least 1 V within 750 msec. of the pre-charge circuit being switched off.
The condition (V-key - V-cap.) < limit voltage is not met within a fixed time after activating the pre-charge circuit.
Switch status of ground sensors unequal. The activation limit is 20 msec.
Switch status of ground sensors unequal. The activation limit is 20 msec.
Switch status of ground sensors unequal. The activation limit is 20 msec.
- Replace controller;
- Check battery voltage / key switch voltage;
- Check controller power connections for shorts;
- Replace component;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
_ 1 33 4 Operation
Ground system track 1 right actual value sensor system: invalid channel A / channel B value relationship
Switch status of ground sensors unequal. The activation limit is 20 msec.
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
õUNGHEINRICH Event Messages
05.12 29
G
F E XX S Operational
Status
_ 1 33 5 Operation
_ 1 33 6 Operation
_ 1 34 1 Operation
_ 1 34 3 Operation
_ 1 34 5 Operation
Description Cause / Triggering Event Action
Ground system track 2 right actual value sensor system: invalid channel A / channel B value relationship
Ground system track 3 right actual value sensor system: invalid channel A / channel B value relationship
Brake force governor: invalid channel A / channel B value relationship
Traverse sensor system: invalid channel A / channel B value relationship
Rotate sensor system: invalid channel A / channel B value relationship
Switch status of ground sensors unequal. The activation limit is 20 msec.
Switch status of ground sensors unequal. The activation limit is 20 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Check wiring with multimeter;
- Check sensor system with multimeter;
- Check computer component inputs;
- Repair faulty components and replace if necessary;
- Measure sensor signals with multimeter;
- Replace sensor;
- Measure sensor signals with multimeter;
- Replace sensor;
- Measure sensor signals with multimeter;
- Replace sensor;
_ 1 34 7 Operation
_ 1 34 9 Operation
Left hand support mushroom: invalid channel A / channel B value relationship
Right hand support mushroom: invalid channel A / channel B value relationship
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
- Measure sensor signals with multimeter;
- Replace sensor;
- Measure sensor signals with multimeter;
- Replace sensor;
õUNGHEINRICH Event Messages
05.12 30
G
F E XX S Operational
Status
_ 1 34 11 Operation
_ 1 34 13 Operation
_ 1 34 15 Operation
_ 1 34 21 Operation
_ 1 34 23 Operation
_ 1 34 25 Operation
Description Cause / Triggering Event Action
Steering actual value sensor systems: invalid channel A / channel B value relationship
Steering setpoint device: invalid channel A / channel B value relationship
Steering setpoint device optional: invalid channel A / channel B value relationship
Hydraulic setpoint device: invalid channel A / channel B value relationship
Travel setpoint device: invalid channel A / channel B value relationship
Hydraulic setpoint device optional: invalid channel A / channel B value relationship
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
- Measure sensor signals with multimeter;
- Replace actual value sensor;
- Measure sensor signals with multimeter;
- Replace setpoint sensor;
- Measure sensor signals with multimeter;
- Replace setpoint sensor;
- Measure sensor signals with multimeter;
- Replace setpoint sensor;
- Measure sensor signals with multimeter;
- Replace setpoint sensor;
- Measure sensor signals with multimeter;
- Replace setpoint sensor;
_ 1 34 27 Operation
_ 1 34 29 Operation
Travel setpoint device optional: invalid channel A / channel B value relationship
Accelerator pedal setpoint device: invalid channel A / channel B value relationship
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
Analog sensor value relationship deviates by more than
2.5°. The activation limit is 100 msec.
- Measure sensor signals with multimeter;
- Replace setpoint sensor;
- Check sensor wiring;
- Check sensor;
- Switch the truck off and on again;
- Inquire about software update;
- Replace signal-issuing controller;
Loading...
+ 154 hidden pages