6.9Approvals/marks of conformity ................................................................ 36
7Glossary 37
1.1Preface
E
B
1 Introduction
Please read these Operating Instructions before commissioning the
instrument. Keep the manual in a place that is accessible to all users at all
times.
Please assist us to improve this operating manual, where necessary.
Your comments will be appreciated.
If any difficulties should arise during commissioning, you are asked
not to carry out any manipulations that could endanger your rights
under the instrument warranty!
Please contact the nearest subsidiary or the head office in such a
case.
When returning modules, assemblies or components, the
regulations of EN 61340-5-1 and EN 61340-5-2 “Protection of
electronic devices from electrostatic phenomena” must be
observed. Use only the appropriate ESD packaging for transport.
Please note that we cannot accept any liability for damage caused
by ESD.
ESD=electrostatic discharge
5
1 Introduction
1.2Arrangement of the documentation
The documentation for this instrument is addressed to equipment
manufacturers (OEMs) and users with appropriate technical expertise. It
consists of the following parts:
Instrument documentation in printed form
B 706585.1Operating Instructions
The operating instructions are an extract from the operating manual and cover
the basic operation of the paperless recorder.
B 706585.4(.1)Installation Instructions
The installation instructions describe the installation of the recorder and the
connection of the supply and signal cables. The instructions also contain a list
of the technical data.
B 706585.4Installation instructions for recorders with die-cast zinc front
B 706585.4.1 Installation instructions for recorders with stainless steel front
Instrument documentation in the form of PDF files
The “Instrument documentation in the form of PDF files” is on the CD that is
included in the delivery.
B 706585.0Operating Manual
It contains information about commissioning, operation, parameterization and
configuration on the instrument.
B 706585.1Operating Instructions
The operating instructions are an extract from the operating manual and cover
the basic operation of the paperless recorder.
B 706585.2.0Interface Description (serial interfaces)
This provides information on the communication (RS232/RS485) with
supervisory systems.
Interface Description (Ethernet interface)
This provides information on the connection of a paperless recorder to a
company-internal network. This description is integrated into B 706585.2.0.
B 706585.2.3Interface Description (PROFIBUS-DP interface)
This provides information on the connection of a paperless recorder to a
PROFIBUS-DP system.
6
B 706585.4(.1)Installation Instructions
The installation instructions describe the installation of the recorder and the
connection of the supply and signal cables. The instructions also contain a list
of the technical data.
B 706585.4Installation instructions for recorders with die-cast zinc front
B 706585.4.1 Installation instructions for recorders with stainless steel front
B 706585.6Setup Program
The manual describes the function of the setup program. The setup program is
available as an option.
T 706585Data Sheet
The data sheet contains general information, the order details and the
technical data.
B 709701.0PC Evaluation software PCA3000
The operating manual describes the operation and the features of the PC
evaluation software.
1 Introduction
PCA3000 serves to visualize and evaluate process data (measurement data,
batch data, messages, instrument audit trails, ...). The process data can be
read in via the CompactFlash memory card, or made available through the
PCC software.
B 709702.0PCA Communications software PCC
The operating manual describes the operation and the features of the PCA
Communications software.
PCC is responsible for the data transfer from the recorder to a PC, or to a
network.
B 709703.0PC Security Manager Software PCS
The operating manual describes the operation and the features of the PC
Security Manager software.
The PCS ensures that only authorized persons can gain access to the system
components (instrument, PC software) and use electronic signatures on
electronic documents.
The configuration of the Security Manager can only be performed by the
system administrator.
7
1 Introduction
B 709704.0PC Audit Trail Manager Software PCAT
The operating manual describes the operation and the features of the PC audit
trail manager software.
PCAT documents actions performed in the PC software components, which
lead to modifications of files, user lists (rights files), device lists etc. The
different message types are: “Information”, “Warnings” and “Errors”.
Audit trail records cannot be modified.
Device audit trail data are not shown in PCAT, only in PCA3000.
Internet
All documents are available for downloading at www.jumo.net
8
1.3Typographical conventions
V
E
Warning signs
The signs for Danger and Caution are used in this manual under the following
conditions:
Danger
This symbol is used when there may be danger to personnel if the
instructions are ignored or not followed correctly!
Caution
This symbol is used when there may be damage to equipment or data if the
instructions are ignored or not followed correctly!
Caution
This symbol is used where special care is required when handling
components liable to damage through electrostatic discharge.
1 Introduction
Note signs
h
Note
This symbol is used when your special attention is drawn to a remark.
Reference
This symbol refers to further information in other manuals, chapters or
sections.
Action instruction
This symbol indicates that an action to be performed is described.
The individual steps are marked by this asterisk, e.g.
h Rotate control knob
h Press control knob
9
1 Introduction
10
2 Identifying the instrument version
2.1Nameplate
PositionThe nameplate is glued onto the paperless recorder.
ContentsIt contains important information, such as:
DescriptionDesignation on
the nameplate
Device typeTyp706585/18-321-33/020
Part no.TN00xxxxxx
Serial no.F-Nr0022969000013050006
Supply voltageAC 110 — 240 V
TypPlease check the type supplied against your order document. Refer to
Chapter 2.2 “Order details” for identification of the type.
TNThe part no. provides an unambiguous definition of an article from the catalog.
It is used in communication between the sales department and the customer.
F-NrThe serial number (F-Nr) indicates the production date (year/week). The figures
concerned are in positions 12, 13, 14, 15.
Example:
F-Nr 0022969000013050006
This shows that the paperless recorder was manufactured in 2013, week 5.
8Factory setting (German/English)
9Set to customer specification
(4)Module slot 1
0Not used
23 analog inputs and 8 binary inputs/outputs
36 analog inputs
(5)Module slot 2
0Not used
23 analog inputs and 8 binary inputs/outputs
36 analog inputs
(6)Module slot 3
0Not used
16 relay outputs
23 analog inputs and 8 binary inputs/outputs
36 analog inputs
(7)Voltage supply
25AC/DC 20 to 30 V, 48 to 63 Hz
33AC 100 to 240 V +10/-15 %, 48 to 63 Hz
(8)Extra codes memory
020Lithium battery for memory buffering (ex-factory)
021Storage capacitor
(9)Extra codes
.Not used
260Math and logic module
(10)Extra codes housing
.Not used
350Universal carrying case TG-35
444Stainless steel front with touchpad
(11)Extra codes
.Without extra codes
267PROFIBUS-DP interface
a
This extra code is available in combination with voltage supply AC 100 to 240 V, not with low supply voltage.
UL and ATEX approvals not applicable. The protection type in the carrying case corresponds to IP20, outside IP20D.
a
Order code(1)(2)(3)(4)(5)(6)(7)(8)(9)(10)(11)
Order example706585/--/,,,
List extra codes in sequence, separated by commas.
12
2 Identifying the instrument version
2.3Standard accessories
• 1 Installation Instructions B 706585.4
• 1 Operating Instructions B 706585.1
• 4 mounting brackets
•1 panel seal
• 1 CD with detailed operating instructions and supplementary
documentation (see Chapter 1.2 “Arrangement of the documentation”)
The installation site should be as free as possible from vibration.
Electromagnetic fields, such as those caused by motors, transformers,
frequency converter etc. should be avoided as far as possible.
The ambient temperature at the site can be 0 to 50 °C, at a relative humidity of
75 %, no condensation.
v Chapter 4.1 “Installation notes”
3.2Dimensions
Recorder with
zinc diecast
front
3 Installation
Panel cut-out
15
3 Installation
Panel seal
3.3Mounting in a panel
h Fit panel seal (IP65 seal).
h Insert the paperless recorder from the front into the panel cut-out.
h From behind the panel, hook the four mounting brackets into the grooves
on the sides of the housing and tighten them evenly up against the back of
the panel.
16
4.1Installation notes
•The device is designed for installation in electrical cabinets, machines, or
systems. External fuse protection and shut-off must be provided for the
device. The fuse must not exceed 20 A.
An instrument fuse is already built into the device itself (depending on the
device design).
AC/DC20—30V, 48—63Hz: fuse 2.5A slow-blow
AC 100 — 240 V +10/-15 %, 48 — 63 Hz: fuse 1.25 A slow-blow
•The choice of cable, the installation and the electrical connection must
conform to the requirements of VDE 0100 “Regulations on the Installation
of Power Circuits with Nominal Voltages below 1000 V” or the appropriate
local regulations.
•Work inside the instrument must only be carried out to the extent
described and, like the electrical connection, only by qualified personnel.
•For service and repair work the device must be disconnected from the
power supply (all poles).
•To generate the operating voltage of 20 ... 30 V for Extra Low Voltage
(ELV), the maximum nominal voltage of an external power supply must
not exceed 240 V (line-to-line and line-to-neutral). If the external nominal
voltage is greater than 240 V, an Safety Extra Low Voltage (SELV) power
supply must be used. For line-to-line supply of the external power supply,
the power supply must have all-pole fuse protection. The fuse must shut
off both connections.
4 Electrical connection
•Run input, output and supply cables separately and not parallel to one
another.
•In EMC disturbed environments, all input and output cables without
connection to the mains supply must be arranged as twisted and
screened cables. Earth the screen on the instrument side to the earth
potential.
•Ground the instrument at the PE terminal of the supply voltage connector
to the protective earth conductor. This cable must have the same crosssection as that used for the supply cables. Earthing cables must be wired
in a star configuration to a common earth point that is connected to the
protective earth conductor of the electrical supply.
•Do not connect any additional loads to the supply terminals of the
instrument.
•The device is not suitable for use in areas with an explosion hazard (Ex
areas).
•Electromagnetic compatibility (EMC) conforms to the standards and
regulations cited in the technical data.
v Chapter 6 “Technical data (extract from data sheet)”
•Inductive loads close to the instrument, such as contactors or solenoid
valves, should have RC modules fitted for interference suppression.
17
4 Electrical connection
Module slot 3 (top)
Relay card
}
Module slot 2 (middle)
6 analog channels or
3 analog channels and
8 binary inputs/outputs
}
Module slot 1 (bottom)
6 analog channels or
3 analog channels and
8 binary inputs/outputs
}
21
22
23
31
32
33
41
42
43
51
52
53
61
62
63
71
72
73
123
4
1011
12
1
2
3
4
5
6
9
8
7
B12
B 9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
+
U
U
+
-
-
--
in
out
U
U
out
U
U
in
33
44
11
22
12341234123
4
12341234123
4
12341234123
4
8.
9.
11.
10.
14.
3.
2.
1.
12
13
11
5.
6.
7.
PE
N
L1
(L+)
(L-)
4.
15.
Connector number
13
14
15
16
17
18
4
3
2
1
B20
B17
B18
B19
B21
B22
B23
B24
B12
B 9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
U
U
U
+
+
U
U
+
+
U
-
-
-
-
-
-
in
out
in
out
in
out
123
4
123
4
123
4
9
8
7
123
4
1011
123
4
123
4
12
1
2
3
4
1
2
3
4
1
2
1
2
3
4
3
1
2
3
4
1
2
3
4
1
5
4
2
3
4
6
11
22
33
44
1
2
3
4
11
22
33
44
12.
13.
11.
9.
8.
10.
3.
2.
1.
12
13
11
5.
6.
7.
PE
N
L1
(L+)
(L-)
4.
15.
}
Module slot 2 (middle)
6 analog channels or
3 analog channels and
8 binary inputs/outputs
}
Module slot 1 (bottom)
6 analog channels or
3 analog channels and
8 binary inputs/outputs
}
Connector number
Module slot 3 (top)
6 analog channels or
3 analog channels and
8 binary inputs/outputs
4.2Procedure
h Make the electrical connection as per Chapter 4.4 “Connection diagram”.
h Apply strain relief for the connecting cables, if necessary.
Instrument
variant 1
Instrument
variant 2
18
Connector
Binary
inputs/outputs
Ethernet
interface
Relay
contacts
Test voltage
contacts to
relay coil
2.3kV AC
Test voltage
AC supply: 2.3kV/50Hz
AC/DC supply: 2.3kV/50Hz
RS232 for
barcode reader
Supply
AC or AC/DC
Serial interface
RS232 / RS485
CompactFlash
memory card
USB
interfaces
Analog input 1 — 18
summary
4 Electrical connection
Connector/slotFunction
1Relay output
2RS232 for barcode reader
3PROFIBUS-DP
4Supply voltage
5USB host interface
6Ethernet
7RS232 and RS485
8Analog input
9Analog input or binary inputs/outputs
10Analog input
11Analog input or binary inputs/outputs
12Analog input
13Analog input or binary inputs/outputs
14Relay card (for instrument variant 1)
15USB device interface
4.3Overview of the electrical isolation
19
4 Electrical connection
V
3.
2.
1.
12
13
11
PE
N
L1
(L+)
(L-)
4.
PE
N
L1
(L+)
(L-)
4.
L1 N
L1 N
PE
PE
21
22
23
31
32
33
414243
51
52
53
61
62
63
71
72
73
123
4
1011
12
1
2
3
4
5
6
9
8
7
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
+
U
U
+
-
-
--
in
out
U
U
out
U
U
in
33
44
11
22
12341234123412341234123
4
12341234123
4
8.
9.
11.
10.
14.
3.
2.
1.
12
13
11
5.
6.
7.
PE
N
L1
(L+)
(L-)
4.
15.
123
4
10 11
12
1
2
3
4
5
6
9
8
7
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
+
U
U
+
-
-
--
in
out
U
U
out
U
U
in
33
44
11
22
12341234123412341234123
4
12341234123
4
8.
9.
11.
10.
13
14
15
16
17
18
4
3
2
1
B20
B17
B18
B19
B21
B22
B23
B24
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
U
U
U
+
+
U
U
+
+
U
-
-
-
-
-
-
in
out
in
out
in
out
1
2
3
4
1
2
3
4
1
2
3
4
9
8
7
1
2
3
4
1011
1
2
3
4
1
2
3
4
12
1
2
3
4
1
2
3
4
1
2
1
2
3
4
3
1
2
3
4
1
2
3
4
1
5
4
2
3
4
6
11
22
33
44
1
2
3
4
11
22
33
44
12.
13.
11.
9.
8.
10.
3.
2.
1.
12
13
11
5.
6.
7.
PE
N
L1
(L+)
(L-)
4.
15.
13
14
15
16
17
18
4
3
2
1
B20
B17
B18
B19
B21
B22
B23
B24
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
U
U
U
+
+
U
U
+
+
U
-
-
-
-
-
-
in
out
in
out
in
out
1
2
3
4
1
2
3
4
1
2
3
4
9
8
7
1
2
3
4
10 11
1
2
3
4
1
2
3
4
12
1
2
3
4
1
2
3
4
1
2
1
2
3
4
3
1
2
3
4
1
2
3
4
1
5
4
2
3
4
6
11
22
33
44
1
2
3
4
11
22
33
44
12.
13.
11.
9.
8.
10.
2134
+
–
2134
2134
2134
2134
ESA
2134
2134
2134
4.4Connection diagram
The electrical connection must only
be carried out by specialist personnel.
Back panelv Chapter 4.2 “Procedure”
Connections
Terminal assignmentConnectorDiagram
Supply
voltage
Supply voltage
as on nameplate
Analog inputsThermocouple
RTD temperature probe
2-wire circuit
RTD temperature probe
3-wire circuit
RTD temperature probe
4-wire circuit
Connector 4
L1 (L+)
N (L-)
PE
Connectors
8 to 11
(input 1—12)
for instrument
variant 1
20
Resistance transmitter
E = end
S = slider
A = start
Potentiometer in
2-wire circuit
or
connectors
8 to 13
(input 1—18)
for instrument
variant 2
Potentiometer in
3-wire circuit
Potentiometer in
4-wire circuit
4 Electrical connection
21
22
23
31
32
33
414243
51
52
53
61
62
63
71
72
73
123
4
1011
12
1
2
3
4
5
6
9
8
7
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
+
U
U
+
-
-
--
in
out
U
U
out
U
U
in
33
44
11
22
12341234123412341234123
4
12341234123
4
8.
9.
11.
10.
14.
3.
2.
1.
12
13
11
5.
6.
7.
PE
N
L1
(L+)
(L-)
4.
15.
123
4
10 11
12
1
2
3
4
5
6
9
8
7
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
+
U
U
+
-
-
--
in
out
U
U
out
U
U
in
33
44
11
22
12341234123412341234123
4
12341234123
4
8.
9.
11.
10.
13
14
15
16
17
18
4
3
2
1
B20
B17
B18
B19
B21
B22
B23
B24
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
U
U
U
+
+
U
U
+
+
U
-
-
-
-
-
-
in
out
in
out
in
out
1
2
3
4
1
2
3
4
1
2
3
4
9
8
7
1
2
3
4
1011
1
2
3
4
1
2
3
4
12
1
2
3
4
1
2
3
4
1
2
1
2
3
4
3
1
2
3
4
1
2
3
4
1
5
4
2
3
4
6
11
22
33
44
1
2
3
4
11
22
33
44
12.
13.
11.
9.
8.
10.
3.
2.
1.
12
13
11
5.
6.
7.
PE
N
L1
(L+)
(L-)
4.
15.
13
14
15
16
17
18
4
3
2
1
B20
B17
B18
B19
B21
B22
B23
B24
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
U
U
U
+
+
U
U
+
+
U
-
-
-
-
-
-
in
out
in
out
in
out
1
2
3
4
1
2
3
4
1
2
3
4
9
8
7
1
2
3
4
10 11
1
2
3
4
1
2
3
4
12
1
2
3
4
1
2
3
4
1
2
1
2
3
4
3
1
2
3
4
1
2
3
4
1
5
4
2
3
4
6
11
22
33
44
1
2
3
4
11
22
33
44
12.
13.
11.
9.
8.
10.
Terminal assignmentConnectorDiagram
Analog inputsVoltage input 0 — 1 VConnectors
8 to 11
(input 1—12)
Voltage input 0 — 10 V
Current input
for instrument
variant 1
or
connectors
8 to 13
(input 1—18)
for instrument
variant 2
21
4 Electrical connection
13
14
15
16
17
18
4
3
2
1
B20
B17
B18
B19
B21
B22
B23
B24
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
U
U
U
+
+
U
U
+
+
U
-
-
-
-
-
-
in
out
in
out
in
out
1
2
3
4
1
2
3
4
1
2
3
4
9
8
7
1
2
3
4
1011
1
2
3
4
1
2
3
4
12
1
2
3
4
1
2
3
4
1
2
1
2
3
4
3
1
2
3
4
1
2
3
4
1
5
4
2
3
4
6
11
22
33
44
1
2
3
4
11
22
33
44
12.
13.
11.
9.
8.
10.
3.
2.
1.
12
13
11
5.
6.
7.
PE
N
L1
(L+)
(L-)
4.
15.
B4
B1
B2
B3
B5
B6
B7
B8
+
+
U
U
-
-
in
out
1
2
3
4
1
2
3
4
1
5
4
2
3
4
6
9.
B2
B3
B4
B5
B6
B7
B8
+
-+
B1
-
UinU
out
+-
24V external
supply voltage
Load
B1
B2
B3
B4
B5
B6
B7
B8
Uin+
Uin-
Uout+
Uout-
13
14
15
16
17
18
4
3
2
1
B20
B17
B18
B19
B21
B22
B23
B24
B12
B9
B10
B11
B13
B14
B15
B16
B4
B1
B2
B3
B5
B6
B7
B8
+
+
U
U
U
+
+
U
U
+
+
U
-
-
-
-
-
-
in
out
in
out
in
out
1
2
3
4
1
2
3
4
1
2
3
4
9
8
7
1
2
3
4
1011
1
2
3
4
1
2
3
4
12
1
2
3
4
1
2
3
4
1
2
1
2
3
4
3
1
2
3
4
1
2
3
4
1
5
4
2
3
4
6
11
22
33
44
1
2
3
4
11
22
33
44
12.
13.
11.
9.
8.
10.
3.
2.
1.
12
13
11
5.
6.
7.
PE
N
L1
(L+)
(L-)
4.
15.
B12
B9
B10
B11
B13
B14
B15
B16
U
+
+
U
-
-
in
out
1
2
3
4
10 11
1
2
3
4
1
2
3
4
12
11.
B10
B11
B12
B13
B14
B15
B16
+
-+
B9
-
UinU
out
B9
B10
B11
B12
B13
B14
B15
B16
Uin+
Uin-
Uout+
Uout-
Terminal assignmentConnectorDiagram
Binary inputs/
outputs
H The configuration in the instrument or in the setup program
defines whether it is a binary input or binary output.
B1 ... B8
voltage-controlled
LOW = -3 to +5 V DC
HIGH = 12 to 30 V DC
Example:
Binary input 20 (B20)
is operated from the
internal supply
voltage.
Diagram of the
connector:
Relay 2
changeover (SPDT)
Relay 3
changeover (SPDT)
Relay 4
changeover (SPDT)
Relay 5
changeover (SPDT)
Relay 6
changeover (SPDT)
Relay 7
changeover (SPDT)
Connector 14
only for
instrument
variant 1
23
4 Electrical connection
3.
2.
1.
12
13
11
PE
N
L1
(L+)
(L-)
4.
2.
2
1
3
4
5
6
7
8
9
3.
2.
1.
12
13
11
PE
N
L1
(L+)
(L-)
4.
3.
2
1
3
4
5
6
7
8
9
5.
6.
7.
15.
5.
5.
6.
7.
15.
6.
8
1
5.
6.
7.
15.
7.
2
1
3
4
5
6
7
8
9
Terminal assignmentConnectorDiagram
InterfacesRS232C for barcode reader
9-pin SUB-D socket connector
2 RxDreceive data
3 TxDtransmit data
5 GND ground
PROFIBUS-DP
9-pin SUB-D socket connector
(extra code)
3 RxD/TxD-P B conductor
Receive/transmit data
positive
5 DGND
Data transmission ground
6 VP supply voltage positive
8 RxD/TxD-N A conductor
Receive/transmit data
negative
USB host interface
for memory sticks
The recorder without stainless
steel front also has a USB host
interface on the front panel,
connected in parallel. The two
interfaces cannot both be
operated at the same time.
Connector 2
Connector 3
Connector 5
Ethernet
RJ45 socket connector
1 TX+ transmit data +
2 TX- transmit data 3RX+ receive data +
6RX+ receive data -
RS232C
9-pin SUB-D socket connector
(switchable to RS485)
2 RxD receive data
3 TxDtransmit data
5 GND ground
Connector 6
Connector 7
24
4 Electrical connection
5.
6.
7.
15.
7.
2
1
3
4
5
6
7
8
9
5.
6.
7.
15.
15.
Terminal assignmentConnectorDiagram
RS485
9-pin SUB-D socket connector
(switchable to RS232)
3TxD+/RxD+
Transmit/receive data +
5 GND ground
8TxD-/RxD-
Transmit/receive data -
USB device interface
for connecting a PC
The recorder without stainless
steel front also has a USB
device interface on the front
panel, connected in parallel.
The two interfaces cannot both
be operated at the same time.
Binary inputsTriggering via external relays and external supply voltage:
Triggering via external relays and internal supply voltage:
26
4 Electrical connection
paperless
recorder
paperless
recorder
Triggering via external opto-coupler and internal supply voltage:
Triggering via external switches (potential-free) and internal supply voltage:
27
4 Electrical connection
paperless
recorder
paperless
recorder
Binary outputsTriggering of external relays via external supply voltage:
Triggering of external relays via internal supply voltage:
By triggering the external relays via the internal supply voltage the total
current must not exceed 60 mA.
28
Start-up screen
5 Functional test
After the paperless recorder has been installed and wired up, it can be
commissioned. After applying or switching on the supply voltage, the start-up
screen will appear for a short time.
The visualization will start automatically after the initialization phase.
Visualization
Further steps
The paperless recorder is now in the recording phase.
The recorder can be configured by an authorized person, either by
using the control knob (rotating and pressing) or with the help of
the PC setup program.
Further information about configuration can be found in the
Operating Manual B 706585.0.
Finally, make another check that the connection, configuration and
function of the recorder are all correct.
29
5 Functional test
30
6 Technical data (extract from data sheet)
6.1Analog inputs
Thermocouple
DesignationMeasuring rangeAccuracy
Fe-CuNi L DIN 43710
Fe-CuNi J EN 60584
Cu-CuNi U DIN 43710
Cu-CuNi T EN 60584
NiCr-Ni K EN 60584
NiCr-CuNi E EN 60584
NiCrSi-NiSi N EN 60584
Pt10Rh-Pt S EN 60584
Pt13Rh-Pt R EN 60584
Pt30Rh-Pt6Rh B EN 60584
W3Re/W25Re D
W5Re/W26Re C
W3Re/W26Re
Chromel-copel GOST R 8.585-2001
Chromel-alumel GOST R 8.585-2001
PLII (Platinel II)
Shortest spanType L, J, U, T, K, E, N, chromel-alumel, PLII: 100 °C
Range start/endfreely programmable within the limits, in 0.1 °C steps
Cold junctionPt100 internal or thermostat external constant
Cold junction accuracy (internal)±1 °C
Cold junction temperature (external)-50 to +150 °C adjustable
Sampling cycleChannel 1 to 18: 125 ms in total
Input filter2nd order digital filter; filter constant adjustable from 0 to 10.0 sec
Electrical isolationsee “Electrical data” on page 35 and
Resolution> 14 bit
Featuresalso programmable in °F
a
The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced
with short spans.
-200 to +900 °C
-200 to +1200 °C
-200 to +600 °C
-270 to +400 °C
-200 to +1372 °C
-200 to +1000 °C
-100 to +1300 °C
0 to 1768 °C
0 to 1768 °C
0 to 1820 °C
0 to 2495 °C
0 to 2320 °C
0 to 2400 °C
-200 to +800 °C
-200 to +1372 °C
0 to 1395 °C
Type S, R, B, D, C, W3Re/W26Re, chromel-copel: 500 °C
“Overview of the electrical isolation” on page 19
±0.1 %
±0.1 % from -100 °C
±0.1 % from -150 °C
±0.1 % from -150 °C
±0.1 % from -80 °C
±0.1 % from -80 °C
±0.1 % from -80 °C
±0.15 %
±0.15 %
±0.15 % from 400 °C
±0.15 % from 500 °C
±0.15 % from 500 °C
±0.15 % from 500 °C
±0.15 % from -80 °C
±0.1 % from -80 °C
±0.15 %
a
RTD temperature probe
DesignationConnection
circuit
Pt100 EN 60751
(TC = 3.85*10
Pt100 JIS 1604
(TC = 3.917*10
Pt100 GOST 6651-94 A.1
(TC = 3.91*10
Pt500 EN 60751
(TC = 3.85*10
Pt1000 EN 60751
(TC = 3.85*10
-3
1/°C)
-3
-3
1/°C)
-3
1/°C)
-3
1/°C)
1/°C)
2-/3-wire
2-/3-wire
4-wire
2-/3-wire
2-/3-wire
4-wire
2-/3-wire, 4-wire
2-/3-wire, 4-wire
2-/3-wire, 4-wire
2-/3-wire, 4-wire
2-/3-wire
2-/3-wire
4-wire
Measuring rangeAccuracyaMeasurement
current
-200 to +100 °C
-200 to +850 °C
-200 to +850 °C
-200 to +100 °C
-200 to +650 °C
-200 to +650 °C
-200 to +100 °C
-200 to +850 °C
-200 to +100 °C
-200 to +850 °C
-200 to +100 °C
-200 to +850 °C
-200 to +850 °C
±0.5 °C
±0.8 °C
±0.5 °C
±0.5 °C
±0.8 °C
±0.5 °C
±0.5 °C
±0.8 °C
±0.5 °C
±0.9 °C
±0.5 °C
±0.8 °C
±0.5 °C
250 µA
250 µA
250 µA
250 µA
250 µA
250 µA
250 µA
250 µA
100 µA
100 µA
100 µA
100 µA
100 µA
31
6 Technical data (extract from data sheet)
DesignationConnection
circuit
Ni100 DIN 43760
(TC = 6.18*10
Pt50 ST RGW 1057 1985
(TC = 3.91*10
Cu50
(TC = 4.26*10
Cu100 GOST 6651-94 A.4
(TC = 4.26*10
Connection circuit2-, 3-, or 4-wire circuit
Shortest span15 °C
Sensor lead resistancemax. 30 per conductor for 3-wire/4-wire circuit
Range start/endfreely programmable within the limits, in 0.1 °C steps
Sampling cycleChannel 1 to 18: 125 ms in total
Input filter2nd order digital filter; filter constant adjustable from 0 to 10 sec
Electrical isolationsee “Electrical data” on page 35 and
Resolution> 14 bit
Featuresalso programmable in °F
a
The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced
with short spans.
-3
1/°C)
-3
1/°C)
-3
1/°C)
-3
1/°C)
2-/3-wire, 4-wire -60 to +180 °C±0.4 °C
2-/3-wire
2-/3-wire
4-wire
4-wire
2-/3-wire
2-/3-wire
4-wire
4-wire
2-/3-wire
2-/3-wire
4-wire
4-wire
max. 10 per conductor for 2-wire circuit
“Overview of the electrical isolation” on page 19
Measuring rangeAccuracyaMeasurement
current
250 µA
-200 to +100 °C
-200 to +1100 °C
-200 to +100 °C
-200 to +1100 °C
-50to+100°C
-50to+200°C
-50to+100°C
-50to+200°C
-50to+100°C
-50to+200°C
-50to+100°C
-50to+200°C
±0.5 °C
±0.9 °C
±0.5 °C
±0.6 °C
±0.5 °C
±0.9 °C
±0.5 °C
±0.7 °C
±0.5 °C
±0.9 °C
±0.5 °C
±0.6 °C
250 µA
250 µA
250 µA
250 µA
250 µA
250 µA
250 µA
250µA
250 µA
250 µA
250 µA
250 µA
Resistance transmitter and potentiometer
DesignationMeasuring rangeAccuracy
Resistance transmitterup to 4000 ±4 100 µA
Potentiometer
potentiometer: 2-/3-/4-wire circuit
Shortest span60
Sensor lead resistancemax. 30 per conductor for 4-wire circuit
max. 10 per conductor for 2-/3-wire circuit
Resistance valuesfreely programmable within the limits, in 0.1 steps
Sampling cycleChannel 1 to 18: 125 ms in total
Input filter2nd order digital filter; filter constant adjustable from 0 to 10.0 sec
Electrical isolationsee “Electrical data” on page 35 and
“Overview of the electrical isolation” on page 19
Resolution> 14 bit
a
The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced
with short spans.
±400 m
±4
a
Measurement
current
250 µA
100 µA
32
6 Technical data (extract from data sheet)
Input for DC voltage, DC current
Basic rangeAccuracy
-12 to +112 mV
-10 to +210 mV
-1.5 to +11.5 V
-0.12 to +1.12 V
-1.2 to +1.2 V
-11.2 to +11.2 V
±100 V
±240 V
±6 mV
±1 mV
±2 mV
±12 mV
Shortest span5 mV
Range start/endfreely programmable within the limits in 0.01 mV steps
-1.3 to +22 mA
-22 to +22 mA
±20 A
±44 A
Shortest span0.5mA
Range start/endfreely programmable within the limits in 0.01 mA steps
Overrange/underrangeaccording to NAMUR NE 43
Sampling cycleChannel 1 to 18: 125 ms in total
Input filter2nd order digital filter; filter constant adjustable from 0 to 10.0 sec
Electrical isolationsee “Electrical data” on page 35 and
“Overview of the electrical isolation” on page 19
Resolution>14 bit
a
The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced
with short spans.
a
Input resistance
R
1M
E
R
470 k
E
R
470 k
E
R
470 k
E
R
470 k
E
R
470 k
E
burden voltage 3V
burden voltage 3V
Transducer short circuit/break
Short-circuit
a
Thermocouplenot detecteddetected
RTD temperature probedetecteddetected
Resistance transmitternot detecteddetected
Potentiometernot detecteddetected
Voltage ±210 mVnot detecteddetected
Voltage > ±210 mVnot detectednot detected
Currentnot detectednot detected
a
Programmable reaction of device, e.g. triggering alarm
Break
a
33
6 Technical data (extract from data sheet)
6.2Binary inputs/outputs (option)
Input or outputconfigurable as input or output
Number8, 16 or 24, depending on the device version,
to DIN VDE 0411, Part 500; max. 25 Hz, max. 32 V
Input
• levellogic "0": -3 to +5 V (input current max. ±1 mA),
logic "1": 12 to 30 V (2.5 mA input current 5mA)
• counting frequency8Hz
High-speed inputthe first two binary inputs of each module (B1, B2, B9, B10, B17, B18),
if the module is not fitted with relays or 6 analog inputs
• task count function, e.g. for flow measurement
• counting frequency10 kHz
Output
• typeopen-collector output, switches relative to positive voltage
• levellogic "0": transistor is inhibited
(max. permissible voltage across switching transistor 30 V,
max. leakage current 0.1 mA)
logic "1": transistor is switched on
(max. voltage across switching transistor 1.6 V, max. current 50 mA)
• sampling cycleat least 1 sec (1 Hz)
6.3Outputs
1 relay (ex-factory)changeover (SPDT), 3 A, 230 V AC
6 relays (option)changeover (SPDT), 3 A, 230 V AC
a
With resistive load.
b
It is not permissible to mix SELV circuits and supply circuits.
a
a, b
6.4Interfaces
RS232/RS485 (connector 7)Qty. 1, switchable between RS232 and RS485
• protocolModbus master, Modbus slave and barcode reader
• baud rate9600, 19200, 38400
• modemcan be connected
•connectorSUB-D
• external inputsvia the Modbus master/slave function, 24 analog and 24 binary
RS232 for barcode reader
(connector 2)
• protocolModbus master, Modbus slave and barcode reader
• baud rate9600, 19200, 38400
•connectorSUB-D
• external inputsvia the Modbus master/slave function, 24 analog and 24 binary
Ethernet (connector 6)
• quantitymax. 1
• protocolsTCP, IP, HTTP, DHCP, SMTP, ModbusTCP
• baud rate10 Mbits/sec, 100 Mbits/sec
•connectorRJ45
• data formatHTML
Qty. 1
34
6 Technical data (extract from data sheet)
USB host (connector 5)
• quantity2 (or 1 with stainless steel front),
connector 5 and front connector (not with stainless steel front); no
parallel operation
• usefor connecting a memory stick
• max. current100 mA
USB device (connector 15)
• quantity2 (or 1 with stainless steel front), connector 15 and front connector
(not with stainless steel front); no parallel operation)
• usefor connecting to the (master) computer
6.5Screen
Resolution/size320 × 240 pixels/5.5"
Type/number of colorsTFT color screen/256 colors
Screen refresh rate> 150 Hz
Brightness settingadjustable on instrument
Screen saver (switch-off)through waiting time or control signal
6.6Electrical data
Supply voltage (switch-mode PSU)AC 100 to 240V +10/-15%, 48 - 63Hz or
AC/DC 20 to 30V, 48 - 63Hz (ELV)
Electrical safetyto EN 61010, Part 1, August 2002
overvoltage category II, pollution degree 2
Protection class Iterminal for PE conductor
Test voltages (type test)
• mains supply circuit to meas.
circuit
• mains supply circuit to housing
(protective conductor)
• measuring current circuits to
measuring current circuit and
housing500 V/50 Hz, 1 min
• electrical isolation between
analog inputsup to 30 V AC and 50 V DC
Supply voltage error< 0.1 % of range span
Power consumptionapprox. 40 VA
Data backupCompactFlash memory card
Electrical connection
• mains supply and relaysat rear through pluggable screw terminals, 5.08 mm raster,
• analog and binary inputsat rear through pluggable screw terminals, 3.81 mm raster,
with AC supply: 2.3 kV/50 Hz, 1 min,
with AC/DC supply: 2.3 kV/50 Hz, 1 min
with AC supply: 2.3 kV/50 Hz, 1 min,
with AC/DC supply: 2.3 kV/50 Hz, 1 min
max. conductor cross-section 2.5 mm
max. conductor cross-section 1.5 mm
2
or 2× 1.5 mm2 with ferrules
2
35
6 Technical data (extract from data sheet)
6.7Environmental influences
Ambient temperature range0 to +50 °C
Ambient temperature effect0.03 %/°C
Storage temperature range-20 to +60 °C
Climatic conditions 75 % relative humidity, no condensation
EMCEN 61326-1
• interference emissionClass A - only for industrial use -
• immunity to interferenceto industrial requirements
6.8Housing
Housing frontzinc die-casting, optionally in stainless steel (extra code)
Housing typehousing for flush-panel mounting to IEC 61554, in stainless steel
Bezel size144 mm × 144 mm to IEC 61554
Depth behind panel193 mm (incl. terminals)
Panel cut-out138
Panel thickness2 to 40 mm
Housing mountingin panel to DIN 43834
Operating positionunrestricted, but taking into account the viewing angle of the screen,
Enclosure protectionto EN 60529 Category 2, front IP65, rear IP20
Weightapprox. 3.5 kg
Installation 15
Installation notes 17
Installation site 15
Instrument documentation in printed form 6
Instrument documentation in the form of PDF files 6
Instrument version, identification of 11
Introduction 5
M
Mounting 16
N
Note signs 9
37
7 Glossary
O
Order details 12
P
Panel mounting 16
R
Returning 5
S
Standard accessories 13
Start-up screen 29
T
Technical data 31
Typographical conventions 9
V
Views 15
Visualization level 29
W
Warning signs 9
Warranty 5
38
JUMO GmbH & Co. KGJUMO Instrument Co. Ltd.JUMO Process Control, Inc.