JUMO 705040 User Manual

JUMO mTRON T
- Web browser
- Setup program
- PCA Communication Software PCC
- Plant Visualization Software SVS3000
- Programming system CODESYS
LAN
Com2
RS422/485 or RS232, Modbus master/slave or PROFIBUS-DP slave
System bus
Com1
RS422/485 or RS232, Modbus master/slave
Com1
Com2
USB
RS422/485 or RS232,
Modbus master/slave,
connection for bar code scanner
RS422/485 or RS232,
Modbus master/slave,
connection for bar code scanner
Host and device
max. 100 m
max. 100 m
Measuring, Control, and Automation System
System Description
B 705000.8
2014-05-06/00575652
Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.1 Structure of this system description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 The JUMO mTRON T measuring, control, and automation system . . . . . . . . . . . . . . . . . . . . . . . 8
1.2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2.2 Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2.3 Base units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.2.4 Input/output modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.2.5 Special modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.2.6 Operating, visualization, recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.2.7 Power supply units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.2.8 PC programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.3 Content of the technical documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.3.1 Device documentation in printed form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.3.2 Device documentation in the form of PDF files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.3.3 Documentation for optional software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.3.4 Device documentation on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.3.5 Training documents on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.4 Available technical documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.4.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.4.2 Base units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.4.3 Input/output modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.4.4 Special modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1.4.5 Operating, visualization, recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1.4.6 Power supply units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
2.1 Warning symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.2 Note signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.3 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.4 Qualification of personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3 Acceptance of goods, storage, and transport . . . . . . . . . . . . . . . . . . . . . . . . .25
3.1 Checking the delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2 Notes on storage and transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.3 Returning goods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.3.1 Accompanying letter for repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.3.2 Protection against electrostatic discharge (ESD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.4 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4 Identifying the device version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
4.1 Nameplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3
Contents
4.3.1 General accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.2 Central processing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.3 Controller module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
5.1 General information on installation/dismounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.2 Module sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2.1 System with centralized module assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2.2 System with decentralized module assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3 Installation/dismounting on DIN rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.3.1 Base units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.3.2 Input/output modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.3.3 Special modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.4 Mounting in a panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.4.1 Multifunction panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.5 Replacing module inserts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.5.1 Input/output modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.5.2 Special modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
6.1 Installation notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.2 Electrical isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.3 Voltage supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.4 Current load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.5 System bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7 Startup and configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
7.1 Setup program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
7.2 Multifunction panel 840 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
8 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
8.1 General technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.1.1 Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.1.2 Electrical safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.1.3 Protection type according to DIN EN 60529 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.1.4 Protection rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.1.5 EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.1.6 Voltage supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.1.7 Ambient requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.1.8 Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.1.9 Climatic tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.1.10 Mechanical tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
4
Contents
8.2 System expansion (system version 02) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
8.3 Training courses/seminars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5
Contents
6

1.1 Structure of this system description

This system description, which is also a component of the system manual (accessories), de­scribes features that relate to the overall measuring, control, and automation system or are equally applicable for all modules.
The complete scope of information for each module is contained in the downloadable operating manuals.
NOTE!
The user should follow the individual sections of this system description step for step to gain an overview of the measuring, control, and automation system and the available technical documentation.
Content of the individual sections
Section Explanation
1 Introduction Initial information on the measuring, control, and automation sys-
tem
Find out how the technical documentation is structured

1 Introduction

2 Safety information Symbols and types of figures used and their meanings 3 Receipt of goods, storage,
and transport
4 Identifying the device version
5 Installation Correctly fitting or installing the devices, taking into conside ratio n
6 Electrical connection Safely connecting the devices, taking into consideration the "in-
7 Startup and configuration
Checking the delivery for damage and completeness
Notes on storage and transport
Handling the packaging material
Notes on disposal
Detecting which device version is indicated by the specifications on the nameplate
the prevailing climatic conditions at the installation location
stallation notes"
Starting up and configuring the system using the setup program (overview).
Configuring and operating the system using the multi function p an­el (overview).
NOTE!
All additional information is module-specific and is contained in the respective index divider of the system manual and in the downloadable operating manuals.
7
1 Introduction
- Web browser
- Setup program
- PC Evaluation Software PCA3000
- PCA Communication Software PCC
- Plant Visualization Software SVS3000
- Programming system CODESYS
LAN
Com2
RS422/485 or RS232, Modbus master/slave or PROFIBUS-DP slave
System bus
Com1
RS422/485 or RS232, Modbus master/slave
Com1
Com2
USB
RS422/485 or RS232,
Modbus master/slave,
connection for bar code scanner
RS422/485 or RS232,
Modbus master/slave,
connection for bar code scanner
Host and device
max. 100 m
max. 100 m

1.2 The JUMO mTRON T measuring, control, and automation system

1.2.1 Overview

1.2.2 Brief description

The modular measuring, control, and automation system is suitable for the precise detection, regulation, control, and recording. Special features of the system are the easy operation and the corresponding software components, the high measuring accuracy and regulation quality
8
as well as the sturdy and service-friendly mechanical system. An application consists of a base unit (central processing unit), a maximum of 30 input/output
modules (multichannel controller module, analog input module 4-channel, analog input mod ule 8-channel, digital input/output module 12-channel), and if necessary the multifunction p anel, up to four operating panels, and router modules for distributed module arrangement. For user­friendly all-in-one solutions, various PC programs are available.
Automation solutions for small and medium size machine lines are possible due to the integra­tion of an optional PLC including programming system according to IEC 61131-3.
The base unit is equipped with a sturdy metal case; the router module and the input and output modules are equipped with a plastic case. All these devices can be fitted on a 35 mm DIN rail. The multifunction panel with TFT touch screen has a metal case with decor foil and is intended for mounting into a panel cut-out.
The system operates at a voltage of DC 24 V. The supply of operating voltage is only requ ired at the base unit (central processing unit), at the router module, and at the multifunction panel.

1.2.3 Base units

The base unit, up to 30 input/output modules, and up to 30 router modules can be used to
build a compact and economic central or decentral measuring, control, and automation sys­tem (visualization and operation either with the multifunction panel or the plant visualization software JUMO SVS3000).
The base unit s cont ain the process image of the application. Furthermore, all configuration
and parameter data of the system are stored in these modules (except for the multifunction panel). As a result, individual input/output modules can be replaced with Plug and Play.
All base units operate at a voltage supply of DC 24 V.
The setup program or the multifunction panel ca n be used to comfortab ly configure and pa-
rameterize the base units.
LEDs are used to indicate the voltage supply as well as the operating status of a module
and of the interfaces.
Central processing unit
The central processing unit is the basis for the maximum ex­tension of the system
Nine program generators (option)
64 limit values are monitored
An integrated PLC acc. to IEC 61131-3 (option)
Math and logic function (option) for all connected multichannel controller modules
Two interfaces for field bus applications; optional:
- RS232, Modbus RTU as master or slave
- RS422/485 Modbus RTU as master or slave
- PROFIBUS-DP as slave (as of system version 02)
One USB device interface (setup)
System bus connection at the front (Bus Out)
A LAN interface (Ethernet) for HTTP and Modbus/TCP as master and slave
Integrated web server
E-mail transmission
The central processing unit operates at a voltage supply of DC 24 V and supplies the connected input/output modules
Dimensions (W x H x D): 135 mm x 101 mm x 67.1 mm (without connection elements)
For further information: Refer to data sheet 705001
1 Introduction
Additional base units in preparation.
9
1 Introduction

1.2.4 Input/output modules

The modules are equipped with removable terminal strips with Push-In technology for the electrical connection.
All input/output modules operate at a voltage supply of DC 24 V.
The setup program, the multifunction p anel or the optional PLC can be used to comfort ably configure and parameterize the modules.
LEDs are used to indicate the voltage supply as well as the operating status of a module and the input/output statuses.
For service work (replacemen t) or adding option al boards, the module insert can be easily pulled out of the case at the front.
Multichannel controller module
2-channel PID controller with relay output or logic output to control solid-state relays
Up to 4 PID controller channels can be activated (cascadable)
Two universal analog inputs, two digital inputs (DC 0/24 V) and two digital outputs (relay or logic DC 0/15 V)
Supported measuring probes: Thermocouples, RTD tempera­ture probes, resistance transmitters, resistance/potentiome­ters, or standard signals (current or voltage)
The analog inputs are electrically isolated from each other
Three option slots for the extension of up to four universal analog inputs, eight digital inputs, three analog outputs, or eight digital outputs
Su pported controller types: Two-state controller, three-state controller, modulating controller, continuous controller, or con­tinuous controller with integrated actuator controller
Customer-specific linearization possible by using a formula
Limit value monitoring
Four formulae for math and logic functions (option)
One counting input up to 10 kHz
The module operates independently (configurable) which means the control task is carried out even if the base unit or the higher-ranking system malfunctions
If the controller is replaced during service work the new con­troller (identical type) is automatically configured
Dimensions (W x H x D): 45 mm x 103.6 mm x 101.5 mm (without connection elements)
For further information: Refer to data sheet 705010
10
Relay module 4-channel
Four relay outputs controlled via the system bus by digital sig­nals
Each relay is equipped with a changeover contact AC 230 V / 3 A
Separate terminal strip per relay output
Automatic configuration after the module insert has been ex­changed during service work
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm (without connection elements)
For further information: Refer to data sheet 705015
Analog input module 4-channel
Four universal analog inputs
Supported measuring probes: Thermocouples, RTD tempera­ture probes, resistance transmitters, resistance/potentiome­ters or standard signals (current or voltage)
The analog inputs are electrically isolated from each other
Customer-specific linearization possible by using a formula or up to 45 pairs of values
Limit value monitoring
Automatic configuration after the module insert has been ex­changed during service work
A digital input (DC 0/24 V) is also provided
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm (without connection elements)
1 Introduction
For further information: Refer to data sheet 705020
Analog input module 8-channel
Eight analog inputs for RTD temperature probes Pt100, Pt500 or Pt1000 in 2-wire circuit
The analog inputs are not electrically isolated from each other
Limit value monitoring
Automatic configuration after the module insert has been ex­changed during service work
A digital input (DC 0/24 V) is also provided
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm (without connection elements)
For further information: Refer to data sheet 705021
11
1 Introduction
Digital input/output module 12-channel
12 channels which can be respectively configured as digital in­puts (DC 0/24 V) or as digital outputs (DC 0/24 V, 500 mA)
Supply of external voltage through terminal at the front
Automatic configuration after the module insert has been ex­changed during service work
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm (without connection elements)
For further information: Refer to data sheet 705030

1.2.5 Special modules

Router module
The router module distributes the input/output modules to several DIN rails/control cabinets (decentralized arrangement)
It uses the system bus to link modules to the base unit or the multifunction panel
Up to 100 m distance between two router modules or between a router module and the base unit or the multifunction panel
Up to 30 router modules are possible
The router module operates at a voltage supply of DC 24 V and supplies the connected input/output modules
No configuration of the router module required
For applications such as Hot Connect, for example, the ad­dress of the router module can be set by rotary coding switch­es
Three RJ45 system bus connections at the front (1 × Bus In, 2 × Bus Out), electrically isolated
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm (without connection elements)
For further information: Refer to data sheet 705040
12

1.2.6 Operating, visualization, recording

Multifunction panel 840
Touchscreen with front made of aluminum incl. design foil (IP67)
TFT color monitor 21.3 cm (8.4”), resolution 640 x 480 pixels, 256 colors, with LED backlight
As an interface between man and machine it allows an optimal and clearly-arranged view of the process statuses and param­eters of the system
Display (in real time) and operation of controller screen, pro­cess screen, program editor, and recording function (option)
Configuration of all connected modules
Setpoint values and batch texts are directly entered on the screen
Data archiving and evaluation with PC
The multifunction panel operates at a voltage supply of DC 24 V
A setup program can be used to comfortably configure the multifunction panel
Two interfaces for field bus applications; optional:
- RS232, Modbus RTU as master or slave
- RS422/485, Modbus RTU as master or slave
One USB device interface (setup)
Two USB host interfaces (memory stick)
Two system bus connections (Bus In and Bus Out)
A LAN interface (Ethernet) for HTTP and Modbus/TCP as master and slave
Integrated web server
E-mail transmission
Connection possibility for barcode scanner
Dimensions (W x H x D): 235mm x 195mm x 58mm
For further information: Refer to data sheet 705060
1 Introduction
13
1 Introduction
Operating panels 350, 570, 1040
TFT color display (64k colors) with resistiv-touch technology
Display sizes 8.9 cm (3.5''), 14.5 cm (5.7''), and 26.4 cm (10.4'')
Display resolutions 320 × 240 pixels and 640 × 480 pixels
Different case materials (plastics, metal)
Protection type IP65 (at the front)
Voltage supply DC 24 V
Ethernet interface (RJ45) for connection to the system
Up to four operating panels per central processing unit (PLC option required)
Specific process screens for operating the system
Direct access to PLC variables
System structure:
For further information: Refer to data sheet 705065
14

1.2.7 Power supply units

Power supply units 705090/...
Voltage supply AC 100 V... 240 V
150 % peak load capability (for typical 4 s)
M inimum current inrush
Floating DC-OK relay contact
Efficiency up to 93.5 %
Active power factor correction (PFC)
Active filter against mains transients
Quick connection due to spring-cage terminals
Dimensions (WxHxD): 705090/05-33: 40 mm x 130.5 mm x 121.5 mm 705090/10-33: 60 mm x 130.5 mm x 121.5 mm
For further information: Refer to data sheet 705090
1 Introduction
15
1 Introduction

1.2.8 PC programs

Setup program
Setup program for project planning and configuration of the entire measuring, control, and automation system
A complete PLC can be activated as an option. The setup program is distinguished by:
User-friendly configuration, parameterization, and startup of the base units, the input/output modules, and the multifunction panel
Automatic import of the hardware configuration into the PLC programming software CODESYS
Program editor
Process screen editor
The project file contains all data that is relevant for the configura­tion, parameterization, and visualization. The file also contains the controller programs and, if applicable, the customer-specific PLC code.
For further information: Refer to operating manual 705000.6
PC Evaluation Software PCA3000
Professional evaluation software to manage, archive, visualize and evaluate process data (measuring data, batch data, messages, ...)
The process data can be imported via USB memory stick or pro­vided by the software PCC.
Data memory: Clearly arranged and easy backup and ar­chiving of all process data in a data file
Data backup: Archive data can directly be imported from CD/ DVD and then displayed
Data export: Data export to HTML level or ASCII text file (for evaluation in Excel) or customer-specific forms
Communication: The communication software PCC optimally adapted to PCA3000 can be used to comfortably import data via an interface or a modem
For further information: Refer to operating manual 709701.0
PCA Communication Software PCC
The communication software PCC optimally adapted to PCA3000 can be used to comfortably import data via an interface or modem.
Data memory: Clearly-arranged, easy backup and archiving of all process data in a data file
Teleservice function (display of the process data)
For further information: Refer to operating manual 709702.0
16
Plant Visualization Software JUMO SVS3000
Plant Visualization Software for online visualization, batch report­ing and operation of the measuring, control and automation system with a networked PC
This software ensures quick familiarity and easy creation of appli­cations. The user is able to quickly configure an individual applica­tion according to his/her requirements due to the prepared masks (process, group, trend screens).
Easy and quick application creation
Extensive library with predefined graphical elements
System operation via group masks
Extensive do cumentation function with continuous and batch related evaluation
Search function for date/time, plant, and batch criteria to be defined
Automatic print and data export
Recipe function
Quick and easy commissioning/startup due to installation menu
Alarm and event list
Pa ssword protected
History and real time trend
Networ k compatible
Connection of bar code scanner
Remote alerting (optional)
For further information: Refer to data sheet 700755
1 Introduction
17
1 Introduction

1.3 Content of the technical documentation

The documentation for the measuring, control, and automation system is intended for plant manufacturers and users with specialist training. It has a modular structure and comprises dif­ferent sections.

1.3.1 Device documentation in printed form

B 7050XX.4
Installation instructions
A hard copy of the installation instructions is included in the scope of delivery of every modu le. The installation instructions describe the installation of the device and the connection of the
supply and signal cables. They also contain the order details and a list of technical data. The scope of delivery for a power supply unit includes a hard copy of the operating instructions.
These include information on installation and electrical connection.
B 705000.0
System manual
A hard copy of the system manual can be provided as an accessory subject to charge. The system manual describes the scope of services of the measuring, control, and automation
system and provides all information for project design and startup. Index divider 1 "System description" summarizes the information applicable to all modules.
Module-specific descriptions in the following sections complement the specifications stated here.
Index divider 2 "Setup program" describes the project design of the overall system.

1.3.2 Device documentation in the form of PDF files

The device documentation files specified below are saved as PDF files on the DVD contained in the scope of delivery of a base unit.
T 705000
Data sheet
The data sheet provides general information on the measuring, control, an d automation system and forms the basis for plant planning and purchase decisions.
T 7050XX
Data sheet
The data sheets of the individual modules provide spe cific information, order det ails, and tech­nical data.
B 7050XX.0
Operating manual
The operating manuals of the individual modules contain all information on installation, electri­cal connection, startup, operation, and – if required – parameterization and configuration.
18
B 7050XX.2.0
Interface description (Modbus interface)
It provides information on communication with other devices or superordinate systems using the Modbus protocol (Modbus RTU, Modbus TCP).
B 7050XX.4
Installation instructions
The installation instructions describe the installation of the device and the connection of the supply and signal cables. The instructions also contain a list of the technical data.
B 7050XX.5.X
Operating manual (application)
The operating manual describes the use of a certain application (e. g. PLC application).

1.3.3 Documentation for optional software

The manuals specified below are available on the Internet as PDF files. They also form part of the scope of delivery of the respective software.
1 Introduction
B 705000.6
B 709701.0
B 709702.0
B 700755.0
Setup program
The manual describes the function of the setup program.
PC evaluation software PCA3000
The operating manual describes the operation and the features of the PC evaluation sof tware. The PC evaluation software helps to visualize and evaluate the recorded process data (mea­surement data, batch data, messages, etc.).
PCA communication software PCC
The operating manual describes the operation and the features of the PCA communication software. The PCA communication software is responsible for the data transfer from a device or system to a PC or to a network.
Plant visualization software SVS3000
The operating manual describes the operation and features of the plant visualization software. The plant visualization software is responsible for networking interface-ready process devices with a PC.
19
1 Introduction

1.3.4 Device documentation on the Internet

All documents are available for download on the Internet at www.jumo.net. Download procedure:
Step Action
1 On the JUMO website, enter the number of th e relevant pro duct group in the sea rch field at
the top right (e.g. 705001 for the central processing unit) and st art the search.
The search results are listed.
2 Select product (click the link). 3 In the "Documentation" dropdown list, select the desired documentation in the required
national language (click the link).
4 +++++Open the PDF document or save it as a file.

1.3.5 Training documents on the Internet

Training documents (eLearning courses) on various topics are available at www.jumo.net. Procedure:
Step Action
1 On the JUMO website, navigate to the "Support/Services" area. 2 In the "Information & Training" menu on the left-hand side, select "eLearning courses". 3 Click the link "Review of our eLearning courses". 4 Select the desired eLearning course from the overview (click the link).
The presentation starts.
20

1.4 Available technical documentation

The documents specified below are available for the measuring, control, and automation sys­tem.

1.4.1 General information

Product Type of documentation No. Printed PDF file
Measuring, control, and automation system
1
Accessory subject to charge
2
Includes an overview of the purpose and content of all documents

1.4.2 Base units

Data sheet T 705000 - X System manual Setup program manual B 705000.6 - X System description
1
2
1 Introduction
B 705000.0 X -
B 705000.8 - X
Product Type of documentation No. Printed PDF file
Central processing unit
Data sheet T 705001 - X Operating manual B 705001.0 - X Modbus interface description B 705001.2.0 - X Installation instructions B 705001.4 X X

1.4.3 Input/output modules

Product Type of documentation No. Printed PDF file
Multichannel controller module
Relay module 4-channel
Analog input module 4-channel
Data sheet T 705010 - X Operating manual B 705010.0 - X Installation instructions X X Data sheet T 705015 - X Operating manual B 705015.0 - X Installation instructions B 705015.4 X X Data sheet T 705020 - X Operating manual B 705020.0 - X Installation instructions B 705020.4 X X
Analog input module 8-channel
Digital input/ output module 12-channel
Data sheet T 705021 - X Operating manual B 705021.0 - X Installation instructions B 705021.4 X X Data sheet T 705030 - X Operating manual B 705030.0 - X Installation instructions B 705030.4 X X
21
1 Introduction

1.4.4 Special modules

Product Type of documentation No. Printed PDF file
Router module Data sheet T 705040 - X
Installation instructions B 705040.4 X X

1.4.5 Operating, visualization, recording

Product Type of documentation No. Printed PDF file
Multifunction panel 840
Operating panels Data sheet T 705065 - X
Data sheet T 705060 - X Operating manual B 705060.0 - X Modbus interface description B 705060.2.0 - X Installation instructions B 705060.4 X X

1.4.6 Power supply units

Product Type of documentation No. Printed PDF file
24 V power supply units
Data sheet T 705090 - X Operating instructions QS5.241 X ­Operating instructions QS10.241 X -
22

2.1 Warning symbols

&
DANGER!
This symbol indicates that personal injury caused by electrical shock may occur if the re­spective precautionary measures are not carried out.
WARNING!
This symbol in connection with the signal word indicates that personal injury may occur if the respective precautionary measures are not carried out.
CAUTION!
This symbol in connection with the signal word indicates that damage to assets or data loss will occur if the respective precautionary measures are not taken.
CAUTION!
This symbol indicates that components could be destroyed by electrostatic discharge (ESD = Electro Static Discharge) if the respective cautionary measures are not taken. Only use the ESD packages intended for this purpose to return device inserts, assembly groups, or assembly components.

2 Safety information

READ DOCUMENTATION! This symbol – placed on the device – indicates that the associated device documentation
has to be observed. This is necessary to recognize the kind of the potential hazards as
well as the measures to avoid them.

2.2 Note signs

NOTE!
This symbol refers to important information about the product, its handling, or additional use.
REFERENCE! This symbol refers to further information in other sections, chapters, or manuals.
FURTHER INFORMATION!
This symbol is used in the tables and refers to further information in connection with the table.
DISPOSAL!
This device and the batteries (if installed) must not be disposed in the garbage can after use! Please ensure that they are disposed properly and in an environmentally friendly manner.
23
2 Safety information

2.3 Intended use

The modules described are intended for measuring, control, an d automation t asks in an ind us­trial environment, as described in the technical data. Oth er uses or uses beyond th ose defined are not viewed as intended uses.
The modules are built according to the relevant standards and directives as well as the appli­cable safety regulations. Nevertheless, incorrect use may lead to bodily injury or property dam­age.
To avoid danger, the modules may only be used:
For the intended use
When in good order and condition
When taking into account the technical documentation provided Even if a module is used correctly and according to the intended use, it may still cause appli-
cation-related dangers (e.g. due to missing safety devices or incorrect settings).

2.4 Qualification of personnel

This document contains the necessary information for the intended use of the modules to which it relates.
It is intended for technically qualified personnel who have received special training and have the appropriate knowledge in the field of automation technology (measuring, process, and con­trol technology).
The appropriate level of knowledge and the technically fault-free implementation of the safety information and warnings contained in the technical documentation provided are prerequisites for risk-free mounting, installation, and startup as well as for ensuring safety when operating the described modules. Only qualified personnel have the required specialist knowledge to cor­rectly interpret and implement the safety information and warnings contained in this document in specific situations.
24

3 Acceptance of goods, storage, and transport

3.1 Checking the delivery

Ensure that the packaging and contents are not damaged
Check that the delivery is complete using the delivery papers and the order details
Inform the supplier immediately if there is any damage
Store damaged parts until clarification is received from the supplier

3.2 Notes on storage and transport

Store the module in a dry and clean environment. Observe the admissible ambient condi­tions (see "Technical data")
The transport of the module is to be shockproof
The original packaging provides optimum protection for storage and transport

3.3 Returning goods

In the event of repair, please return the module in a clean and complete state. Use the original packaging to return goods.

3.3.1 Accompanying letter for repair

Please include the completed accompanying letter for repair when returning goods. Do not forget to state the following:
Description of the application and
Description of the error that has occurred
The accompanying letter for repair can be downloaded online from the manufacturer's website (use the search function if necessary).

3.3.2 Protection against electrostatic discharge (ESD)

(ESD = electrostatic discharge) To prevent damage from ESD, electronic modules or components must be handled, packaged,
and stored in an ESD-protected environment. Measures against electrostatic discharge and electrical fields are described in DIN EN 61340-5-1 and DIN EN 6 1340-5-2 "Protection of elec­tronic devices from electrostatic phenomena".
When returning electronic modules or components, please note the following:
Sensitive components must only be packaged in an ESD-protected environment. Work­spaces such as this divert electrostatic charges to ground in a controlled manner and pre­vent static charges due to friction capacities.
Only use packaging for ESD-sensitive modules/components. These must consist of con­ductive plastics.
No liability can be assumed for damage caused by ESD.
25
3 Acceptance of goods, storage, and transport
CAUTION!
Electrostatic charges occur in non-ESD protected environments. Electrostatic discharges can damage modules or components. For transport purposes, use only the ESD packaging provided.

3.4 Disposal

Disposing of the device
DISPOSAL!
Devices and/or replaced parts should not be placed in the refuse bin at the end of their ser­vice life as they consist of materials that can be recycled by specialist recycling plants.
Dispose of the device and the packaging material in a proper and environmentally friendly manner.
For this purpose, observe the country-specific laws and regulations for waste treatment a nd disposal.
Disposing of the packaging material
The entire packaging material (cardboard packaging, inserts, plastic film, and plastic bags) is fully recyclable.
26

4.1 Nameplates

(A) (B)
The position and content of the nameplates is explained below using the example of the multi­channel controller module 705010.
Position
The nameplate (B) is affixed to the module case. Additional nameplates with reduced information are located on the module insert (A) and inside
the module case (C; not shown). This duplicate identification marking via nameplates (A) and (C) is important when replacing a module insert or retrofitting optional modules.

4 Identifying the device version

Content
The nameplates contain important information. This includes:
Device type
Compare the specifications on the nameplate with the order. Identify the supplied device version using the order details of the respective module.
Part no. (TN)
The part no. clearly identifies an article in the catalog. It is important for communication between the customer and the sales department.
Description Designation on the name-
plate
Device type (A + B + C) Typ 705010/18-113-36 Part no. (A + B + C) TN 00XXXXXX Fabrication number (A + B + C) F-Nr 0070033801211010006 Voltage supply (B) - DC 24 V +25/-20 %
Example
27
4 Identifying the device version
Fabrication no. (F-Nr)
Among other things, the fabrication number contains the date of production (year/week). Example: F-Nr = 0070033801211010006 The figures concerned are in positions 12, 13, 14, and 15 (from the left). The device was therefore produced in the 1st calendar week of 2011.
28

4.2 Scope of delivery

1x module in the ordered version 1x cover for system bus (for central processing unit and router module) 2x end brackets for DIN rail (for central processing unit and router module) 1x installation instructions B 7050xx.4 1x mini-DVD with setup program (demo version), programming software CODESYS V3, and
detailed documentation on the central processing unit
If you have any questions, please contact the supplier!

4.3 Accessories

The following articles are subject to charge and must be ordered separately:

4.3.1 General accessories

4 Identifying the device version
Article Part no.
JUMO mTRON T system manual, English 00575577 MiniDVD with setup program (full version), programming sof tware CODESYS V3, a nd
detailed documentation; incl. USB cable PC Evaluation Software PCA3000 00431882 Release automatic print for PC Evaluation Software PCA3000 00505548 PCA Communication Software PCC 00431879 Plant Visualization Software JUMO SVS3000: See data sheet 700755 ­USB cable A-plug mini-B-plug 3 m 00506265

4.3.2 Central processing unit

Accessories
Article Part no.
Interface modules (expansion boards): RS232 Modbus RTU 00569505 RS422/485 Modbus RTU 00569506 PROFIBUS-DP (slave; as of system version 02 and as of the central processing unit‘s
production date 27/2013 (calendar week)) Extra codes (activations):
00569494
00569507
Math/logic module (activation for all connected controller modules) 00569509 PLC according to IEC 61131-3 (CODESYS V3) 00569510 Program generator 1 to 9 00569511 Program generator 1 to 9 with process steps (as of system version 02) 00606498
29
4 Identifying the device version

4.3.3 Controller module

Accessories
Article Part no.
Modules for option slots (expansion boards): Analog input 00569497 Relay (changeover contact) 00569498 2 relays (N/O contacts with common pole) 00569499 Analog output 00569500 2 digital inputs 00569501 Solid-state relay 1 A 00569502 2 open-collector outputs 00569503
30

5 Installation

5.1 General information on installation/dismounting

DANGER!
With multichannel controller module 705010 and relay module 705015, the load circuits from relay or solid state relay outputs can be operated with a dangerous electrical voltage (e.g. 230 V). There is a risk of electric shock. Prior to the installation/dismounting of these modules or the removal of the module insert, the load circuits are to be disconnected from the voltage and the terminal strips are to be re­moved from the module. This work must only be performed by qualified personnel.
WARNING!
The modules must never be installed in areas with an explosion hazard. There is the risk of an explosion. The entire system must only be used outside of areas with an explosion hazard.
Mounting site
All modules have protection type IP20 and are only intended for use in fireproof con trol cabinets or switch boxes. The mounting site should be virtually vibration-free. Electromagnetic fields caused by equipment such as motors or transformers should be avoided.
Multifunction panel 840 has protection type IP67 at the front and is intended for installation in a panel cut-out. The rear has protection type IP20.
Climatic conditions
The ambient temperature and the relative humidity at the mounting site must correspond to the technical data. Aggressive gases and vapors have a negative ef fect on the operating life of the modules. The mounting site must be free from dust, powder, and other suspended matter so that the cooling slots do not become blocked.
DIN rail
All modules are mounted on a DIN rail according to DIN EN 60715 (35 mm × 7.5 mm × 1 mm). For reasons of stability, the spacing of the fastening screws for the DIN rail should not exceed 200 mm. The minimum distances for the modules that are specified in the module-specific in­stallation or operating instructions must be observed.
Installation position
The DIN rail should be mounted horizontally so that all modules are arranged vertically. Other­wise the admissible ambient temperature range will be restricted.
Space requirement
The modules require the minimum distances shown in the following figure for the purpose of installation/dismounting and for future maintenance or replacement. In the event of shorter dis­tances the minimum bending radius of the cables, the performance of the electrical inst allation, and the clear arrangement of the plant are no longer guaranteed.
Installation instructions of the individual modules
31
5 Installation

5.2 Module sequence

5.2.1 System with centralized module assignment

Example: Central processing unit with input/output modules
The central processing unit (A) is required for this purpose. It contains all configuration, param­eter, and pro cess data of the entire system and the customer-specific PLC a pplication (if appli­cable). All modules are mounted to the right; the sequence is at the user's discretion. They are snapped on to the DIN rail and moved to the left against the central processing unit or the pre­vious module until the plug connections for the voltage supply and the system bus are connect­ed. Any distance between two modules is not allowed.
A maximum of 30 input/output modules can be managed by one central processing unit.
Cover
Once all modules are installed the cover (B) must be positioned on the DIN rail from the right and moved to the left against the final module (B1). It protects the contacts of the final module against touching and contamination.
The cover is included in the scope of delivery of the central processing unit and therefore does not need to be ordered separately.
End brackets
The final mechanical element of the DIN rail is formed by an end bracket (C) on each side. The right end bracket is positioned on the DIN rail from the outside, moved to the left against the cover (C2), and fastened with a screwdriver (C3). The left end bracket is mounted according to the same principle following the installation of the central processing unit.
The end brackets are included in the scope of delive ry of the central processing unit and there­fore do not need to be ordered separately.
32

5.2.2 System with decentralized module assignment

Example: Modules on multiple DIN rails
5 Installation
A router module (A) is required for the construction of a decentralized measuring, control, and automation system. This is the case, for example, if not all modules fit on a DIN rail, or if mod­ules must be mounted at a distance of more than 100 m from the central processing unit or an upstream router module.
Cover
Once all modules are installed, the cover (B) must be positioned on the DIN rail from the right and moved to the left against the final module (B1). It protects the contacts of the final module against touching and contamination.
The strand with the router module is provided with a cover in the same manner. The cover is included in the scope of delivery of the central processing unit and the router mod-
ule. It therefore does not need to be ordered separately.
End brackets
The final mechanical element of the DIN rail is formed by an end bracket (C) on each side. The right end bracket is positioned on the DIN rail from the outside, moved to the left against the cover (C2), and fastened with a screwdriver (C3). The left end bracket is mounted according to the same principle following the installation of the central processing unit.
The strand with the router module is provided with end brackets in the same manner. The end brackets are included in the scope of delivery of the central processing unit and the
router module and therefore do not need to be ordered separately.
NOTE!
Therefore, the arrangement of modules on various DIN rails may also be required in order to differentiate between optional and mandatory modules (see setup program manual B 705000.6, Section "System bus": Alias device address).
33
5 Installation

5.3 Installation/dismounting on DIN rail

All modules in the system are intended for installation on a DIN rail according to DIN EN 60715 (35mm×7.5mm×1mm).
The following must always be installed on the left, at the start of the DIN rail:
A central processing unit or
A router module
These modules connect the input/output modules to the voltage supply and the system bus.
NOTE!
To determine the required minimum width of the DIN rail, the widths of the individual modules are to be added (see technical data of the modules in the respective data sheet or the module-specific installation instructions). The widths of the cover (17.5 mm) and both end brackets (each 9.5 mm) should also be taken into consideration: 17.5 mm + 2 × 9.5 mm = 36.5 mm.
34
5 Installation
(A)
(A2)
(A1)
(B)
(B3)
(B4)

5.3.1 Base units

Installation of a base unit, using the example of a central processing unit 705001
Installing the end brackets
Procedure:
Step Activity
1 Mount the central processing unit (A) on the DIN rail from below and press upward (A1). 2 Pivot the central processing unit (A) toward the rear until it snaps into place (A2). 3 Position the end bracket (B) on the DIN rail and move to the right against the central pro-
cessing unit (B3). Fasten the end bracket using a screwdriver (B4).
35
5 Installation
(A) (C) (D)
(C3)
(D2)
(B)
(B4) (B4)
(B)
(A)
(E1)
(E)
(A6)
(A5)
Dismounting a base unit, using the example of a central processing unit 705001
Removing the central processing unit from the DIN rail
36
Procedure:
Step Activity
1 Remove the connection cables if required (Setup, LAN, Bus Out). 2 If required, use a screwdriver to release the wired terminal (E) of the central processing unit
(A) and pull off toward the front (E1).
3 Fully release the end bracket (D) using a screwdriver (D2), press upward from below, pivot
toward the front, and remove from the DIN rail. Note: The end bracket does not need to be removed from the DIN rail if there is sufficient
space to the side to move it at least 10 mm to the right.
5 Installation
Step Activity
4 Move the cover (C) to the right (C3) until the sid e co ntacts of the neighb or ing modu le are
exposed. Then release the cover at the bottom using a screwdriver, press upward, and remove from the DIN rail.
Note: The cover does not need to be removed from the DIN rail if there is sufficient space to the side to move it at least 10 mm to the right.
5 Move the modules (B) on the right next to the central processing unit (A) to the right (B4)
until the side contacts of the central processing unit are exposed. These modules are isolated from the voltage supply and the system bus.
6 Press the central processing unit (A) upward from underneath (A5), pivot off the DIN rail
toward the front (A6), and remove.
37
5 Installation
(A) (A1)
(A2)
(D)
(C5) (D6)
(D7)
(C)(A)
(B4)(A3)
(B)

5.3.2 Input/output modules

In a sequence at the user's discretion, input/output modules can be arranged to the right next to a base unit or a router module.
Installation, using the example of a multichannel controller module 705010
Example installation
Procedure:
Step Activity
1 Mount the multichannel controller module (A) in the DIN rail from above (A1). 2 Pivot the multichannel controller module (A) downward until it snaps into place (A2). 3 Move the multichannel controller module (A) to the left against the previous module (A3)
until the plug connections for the voltage supply and the system bus are connected.
38
4 Position additional modules (B) and move to the left against the previous module (B4). 5 After the final module, position the cover (C) on th e DIN rail and move to the lef t against the
module (C5).
5 Installation
Step Activity
6 After attaching the cover, position the end bracket (D) on the DIN rail and move to the left
against the cover (D6).
7 Fasten the end bracket (D) using a screwdriver (D7). For this purpose, ensure that the end
bracket and the cover are positioned flush against the final module.
39
5 Installation
(C2)
(D1)
(A4) (B3)
(C) (D)
(A) (B)
(A)
(F)
(E)
(E5)
(F7)
(A6)
(A8)
Dismounting, using the example of a multichannel controller module 705010
Removing the multichannel controller module from the DIN rail
40
Procedure:
Step Activity
1 Fully release the end bracket (D) using a screwdriver (D1), press upward from below, pivot
2 Move the cover (C) to the right (C2) until the sid e co ntacts of the neighb or ing modu le are
toward the front, and remove from the DIN rail. Note: The end bracket does not need to be removed from the DIN rail if there is sufficient
space to the side to move it at least 20 mm to the right.
exposed. Then release the cover at the bottom using a screwdriver, press upward, and remove from the DIN rail.
Note: The cover does not need to be removed from the DIN rail if there is sufficient space to the side to move it at least 20 mm to the right.
5 Installation
Step Activity
3 Move the modules (B) on the right next to the multichannel controller module that is to be
replaced (A) a minimum of 20 mm to the right (B3). These modules are isolated from the voltage supply and the system bus.
4 Move the multichannel controller module (A) to the right (A4) until the side contacts of the
neighboring module (here: central processing unit) – on the left, next to the multichannel controller module that is to be replaced – are exposed.
The multichannel controller module is isolated from the voltage supply and the system
bus. This is a prerequisite for the dismounting of the multichannel controller module.
5 If required, pull off the wired terminals (E) of the multichannel controller module (A) toward
the front (E5).
6 Insert a suitable screwdriver (F) into the unlocking slot of the multichannel controller mod-
ule (A6) and press upward (F7).
7 Pivot the multichannel controller module (A) upward off the DIN rail (A8) and remove it.
41
5 Installation
(A1)
(A2)
(B)
(A)
(B3)
(B4)
(A)

5.3.3 Special modules

Installation, using the example of a router module 705040
Procedure:
Step Activity
1 Mount the router module (A) in the DIN rail from above (A1). 2 Pivot the router module (A) downward until it snaps into place (A2). 3 Position the end bracket (B) on the DIN rail and move to th e right against the router module
(B3).
4 Fasten the end bracket (B) using a screwdriver (B4). For this purpose, ensure that the end
bracket is positioned flush against the router module.
42
Dismounting, using the example of a router module 705040
(A)(B)
(A3)
(B2)
(A)
(C)
(D)
(D1)
(C5)
(A4)
(A6)
Removing the router module from the DIN rail
5 Installation
Procedure:
Step Activity
1 Remove the connection cables if required (Bus In, Bus Out1, Bus Out2).
2 If required, use a screwdriver to release the wired terminal (D) of the router module (A) and
3 Fully release the end bracket (B) using a screwdriver (B2), press upward from below, pivot
The router module, all modules on the right next to the router module, and, where appli-
cable, additional devices connected via Bus Out1 or Bus Out2 (router modules, multi­function panel) are isolated from the system bus.
pull off toward the front (D1). The connection to the voltage supply is isolated.
toward the front, and remove from the DIN rail. Note: The end bracket does not need to be removed from the DIN rail if there is sufficient
space to the side to move it at least 10 mm to the left.
43
5 Installation
Step Activity
4 Move the router module (A) to the left (A3) until the side contacts on the right side of the
5 Insert a suitable screwdriver (C) into the unlocking slot of the router module (A4) and press
6 Pivot the router module (A) upward off the DIN rail (A6) and remove it.
router module are exposed.
upward (C5).
44

5.4 Mounting in a panel

(A)
(B)
(B2)
(A1)
(C)
(C)
(C3)
(C3)
(D)
(D4)
(C)
(C)
(C)
(C)
(C)
(C)
(C3)
(C3)
(C3)
(C3)
(C3)
(C3)
(B2)
(B)

5.4.1 Multifunction panel

Mounting a multifunction panel 840 (705060)
5 Installation
Procedure:
Step Activity
1 Insert the device (A) into the panel cut-out (A1) fr om the fron t until the two side spr ing balls
(B) click into place (B2). The spring balls facilitate the mounting, but do not replace the fas­tening elements (step 2).
2 Insert the fastening elements (C) into the recesses of the case (C3) and use a screwdriver
(D) to evenly clamp them against the rear side of the panel with a torque of 0.5 Nm (D4).
NOTE!
The provided template is to be used to create the panel cut-out. This is the only way to guar­antee optimum positioning of the multifunction panel.
45
5 Installation
(A)
(E)
(B) (D)
(G)
(C)
(F)
(F)
(F)

5.5 Replacing module inserts

5.5.1 Input/output modules

DANGER!
With multichannel controller module 705010 and relay module 705015, the load circuits from relay or solid state relay outputs can be operated with a dangerous electrical voltage (e.g. 230 V). There is a risk of electric shock. The load circuits are to be disconnected from the voltage supply prior to removing the wired terminal strips. This work must only be performed by qualified personnel.
Replacement of a module insert, using the example of a multichannel controller module 705010
46
For service purposes (or when retrofitting options for the multichannel controller module), the case (D) can remain in the system; only the module insert (B) is replaced. For this purpose, the system does not need to be isolated from the voltage supply (hot swapping).
The system will detect a module insert of the same type that has been replaced and will auto­matically reconfigure it. Retrofitted functions for the multichannel controller module (exp ansion slots) must be configured using the setup program or the multifunction panel.
The new module insert also has a new nameplate (G), which will dif fer from the old one at le ast with regard to the fabrication number, and is no longer identical to nameplates (E) and (C) on the case (D).
Therefore, in the event of replacement, the module insert will be supplied along with a new nameplate that will be affixed to the case (D) in place of the old nameplate (C). This means that the specifications of nameplates (G) and (C) once again correspond to one another.
CAUTION!
Only module inserts of the same type may be used for the replacement. Otherwise, the function of the system may be affected. The module inserts can be clearly identified using the nameplate.
CAUTION!
With the multichannel controller module 705010, a new modu le insert may contain retrofitted inputs or outputs that have not yet been configured. This can lead to unintended behavior, particularly at the outputs and the actuators connected to them. Prior to using the retrofitted inputs or outputs, ensure that these have been configured cor­rectly.
Removing the module insert
Step Activity
1 Disconnect load circuits from the relay or solid state relay outputs. 2 Pull off the wired terminal strips (A) toward the front.
5 Installation
3 Press the old module insert (B) toge ther on the gro oved surfaces at the to p and bottom and
remove from the case (D).
4 For the multichannel controller module, also remove the modules (F) of th e expansion slot s
from the case (D) toward the front, if required.
Mounting the module insert
Step Activity
1 Affix the new nameplate in place of the old nameplate (C) in the case. 2 For the multichannel controller module, also insert the modules (F) of the expansion slots
into the case (D), if required.
3 Hold the new module insert (B) at the grooved surfaces on the top and bottom and insert
them into the case (D). For this purpose, ensure that the board of the module insert slides into the guide rails of the case. For the multichannel controller module, also ensure that the modules (F) of the expansion slots slide in the guide rails of the module insert.
4 Reattach the wired terminal strips (A).
NOTE!
When mounting the module insert, ensure that the snap holders (under the grooved surfaces) audibly snap into place.
NOTE!
The availability of the system can be increased through the storage of module inserts and modules for expansion slots.
47
5 Installation
(A)
(E)
(B) (D)
(F)
(C)

5.5.2 Special modules

Replacing the module insert of a router module 705040
For service purposes, the case (D) can remain in the system; only the module insert (B) is re­placed. Thanks to the hot connect functionality of the router module, this can even be per­formed during operation with the corresponding configuration (alias device address).
The new module insert also has a new nameplate (F), which differs from the old one at least with regard to the fabrication number and is no longer identical to nameplates (E) and (C) on the case (D).
Therefore, in the event of replacement, the module insert will be supplied along with a new nameplate that will be affixed to the case (D) in place of the old nameplate (C). This means that the specifications of nameplates (F) and (C) once again correspond to one another.
Removing the module insert
Step Activity
1 Pull off the connection cables if required (Bus In, Bus Out1, Bus Out2). 2 Pull off the wired terminal strip (A) toward the front. 3 Press the old module insert (B) toge ther on the gro oved surfaces at the to p and bottom and
remove from the case (D).
48
Mounting the module insert
Step Activity
1 Affix the new nameplate in place of the old nameplate (C) in the case. 2 Hold the new module insert (B) at the grooved surfaces on the top and bottom and insert
them into the case (D). For this purpose, ensure that the board of the module insert slides
into the guide rails of the case. 3 Reattach the wired terminal strip (A). 4 Reconnect the connection cables if required (Bus In, Bus Out1, Bus Out2).
NOTE!
When mounting the module insert, ensure that the snap holders (under the grooved surfaces) audibly snap into place.
NOTE!
The availability of the system can be increased through the storage of module inserts.
5 Installation
49
5 Installation
50

6.1 Installation notes

NOTE!
These installation notes apply for the entire measuring, control, and automation system and, on some occasions, are only applicable for a specific module. The respective connection diagram shows the context.
Requirements for the personnel
Work o n the modules must only be carried out to the extent described and, like the electrical connection, only by qualified personnel.
Before plugging and unplugging connection cables ensure that the person performing the work is electrostatically discharged (e.g. by touching grounded metallic parts).
Cables, shielding, and grounding
When selecting the cable material, when insta lling, and when performing the electrical con­nection of the module, the regulations of DIN VDE 0100 "Erection of power installations with rated voltages up to 1000 V" and the respective national regulations (e.g. on the basis of IEC 60364) are to be observed.
Certain cables must be heat resistant up to at least 80 °C at maximum load. The relevant instructions in the connection diagram of the affected modules must be observed.
Route input, output, and supply cables separately and not parallel to one another.
Only use shielded and twisted probe and interface cables. Do not route the lines close to current-carrying components or cables.
For temperature probes, ground the shielding on one side in the control cabinet.
Do not perform loopthroug hs on the grounding cables, but route the cables individua lly to a shared grounding point in the control cabinet; in doing so, ensure that the cables are as short as possible. Ensure that the equipotential bonding is correct.

6 Electrical connection

Electrical safety
Isolate power supply units from the voltage supply on the primary side if there is a risk of touching parts with dangerous electrical voltage (e.g. 230 V) in the course of work.
The fuse rating of the power supply units on the primary sid e should not exceed a value of 10 A (inert).
With modules with relay or solid state relay outputs, the load circuits can be operated with a dangerous electrical voltage (e.g. 230 V). Disconnect load circuits from the voltage supply during installation/dismounting and electrical connection.
In order to prevent the destruction of the relay or solid st ate relay output s in the event of an external short circuit in the load circuit, the load circuit should be fused to the maximum ad­missible output current.
The modules are not suitable for installation in areas with an explosion hazard.
In addition to a faulty inst allation, incorrectly set values on the module could also imp air the correct function of the following process. Therefore, ensure that safety devices independent of the module (e.g. overpressure valves or temperature limiters/monitors) are available and that it is only possible for qualified personnel to define settings. Please observe the corre­sponding safety regulations in this context.
51
6 Electrical connection
References to other information
The electromagnetic compatibility meets the standards and regulations cited in the techni­cal data.
The USB device interface and volt age supply in the central processing unit 705001 a re not electrically isolated. In general, please observe the specifications regarding electrical isola­tion.
52

6.2 Electrical isolation

Central processing unit 705001
USB device System bus Out 1
Ethernet Com 1 Com 2
System bus
24 V
AC 1500 V
~
~
AC 1500 V
~
~
AC 30, DC 50 V
~
~
AC 30, DC 50 V
~
~
Multichannel controller module 705010
Analog input 1
AC 3800 V
Option 1
Option 2
Option 3
Analog input 2 Relay output 3 Relay output 4
Digital input 1 to 2
AC 30 V, DC 50 V
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
Options for the multichannel controller module 705010
Analog input 3
Digital output 3
Input/output modules
Base units
AC 30 V, DC 50 V
AC 3800 V AC 30 V, DC 50 V
~
~
AC 30 V, DC 50 V
~
~
AC 30 V, DC 50 V
~
~
AC 30 V, DC 50 V
~
~
AC 30 V, DC 50 V
~
~
AC 30 V, DC 50 V
Digital output 4
~
~
AC 30 V, DC 50 V
Analog input 4
Digital input 7 to 8
Digital input 5 to 6
Analog output 3
Analog output 1
...
Relay output 10
Relay output 5
...
Open-collector output 9 to 10
Open-collector output 5 to 6
Solid state relay output 10
Solid state relay output 5
~
~
AC 3800 V
~
~
AC 800 V (peak)
~
~
AC 30 V, DC 50 V
Relay module 4-channel 705015
Relay output 1
AC 3800 V
~
~
~
~
Relay output 4
Digital input 9 to 10
Analog output 2
~
~
AC 30 V, DC 50 V
~
~
AC 30 V, DC 50 V
~
~
AC 30 V, DC 50 V
~
~
AC 30 V, DC 50 V
~
~
AC 3800 V
~
~
~
~
AC 30 V, DC 50 V
~
~
AC 30 V, DC 50 V
AC 800 V (peak)
AC 3800 V
...
Open-collector output 7 to 8
6 Electrical connection
53
6 Electrical connection
Analog input module 4-channel 705020
~
~
Digital input
AC 30 V, DC 50 V
Analog input module 8-channel 705021
~
~
~
~
Router module 705040
System bus In AC 500 V
~
~
System bus Out 1
AC 500 V
~
~
System bus
24 V
Voltage supply
Power supply units 24 V 705090
DC 24 V
3800 V
AC 230 V
~
~
SELV DIN EN 50178
...
Analog input 1
Analog input 4
Special modules
Multifunction panel 840 705060
Operating, visualization, recording
Com 1 Com 2
USB host USB device Ethernet System bus In
AC 30, DC 50 V
~
~
AC 1500 V
~
~
AC 1500 V
~
~
AC 30 V, DC 50 V
Digital input/output module 12-channel 705030
~
~
Digital input/output 1 to 12
AC 30 V, DC 50 V
System bus Out 2
AC 500 V
~
~
System bus Out
AC 1500 V
~
~
AC 30, DC 50 V
~
~
AC 30, DC 50 V
~
~
AC 30, DC 50 V
~
~
~
~
AC 30 V, DC 50 V AC 30 V, DC 50 V
Digital input
Analog input 1 to 8
~
~
AC 30 V, DC 50 V
54
6 Electrical connection
Setup
LAN Bus Out
Run Stop Reset
Power
Status
Bus Error
Com1
Com2
Com2
2
1
3
4
ON
2
1
3
4
ON
Com1
1 2
NOTE!
The external voltage supply for the digital input/output module 12-channel and the voltage sup­ply for controlling the digital inputs of this module must be switched on/off with a common dis­connecting device (common electrical circuit).

6.3 Voltage supply

The DC 24 V voltage supply is provided by an external power supply unit and fed in via the base unit (central processing unit) or a router module. For this purpose, these modules have a 2-pole terminal strip with Push-In technology that can be accessed from the front (1). The ter­minal strip can be removed after releasing a screw connection.
The input/output modules are supplied with voltage via the side contact s (2) of the base unit or router module.
The voltage supply for the multifunction panel – also DC 24 V – is to be fed in via a terminal strip (1 1) on the multifunction panel. This also involves a 2-pole terminal strip with Push-In tech­nology that can be removed after releasing the screw connection.
Voltage supply of a base unit, using the example of a central processing unit
1 Voltage supply In, DC 24 V 2 Voltage supply Out, DC 24 V
The router module has identical connections to the voltage supply (note the reversed arrange­ment of the +24 V and GND terminals).
NOTE!
Only use the installation instructions or the operating manual of the affected module for the electrical connection. Follow the safety information stated there.
55
6 Electrical connection
(11)
CAUTION!
Long connecting cables can cause a significant voltage drop at high current load (max. 8 A). This may lead to an underflow of the minimum allowable input voltage of DC 19.2 V. To prevent this, the output voltage of the power supply has to be increased if possible. Hereby it is important to ensure that the maximum allowable input voltage of DC 30 V is not exceeded at any module.
Voltage supply of a multifunction panel 840
56
11 Voltage supply In, DC 24 V
NOTE!
Only use the installation instructions or the operating manual of the multifunction panel 840 for the electrical connection. Follow the safety information stated there.

6.4 Current load

CAUTION!
The maximum current load of the plug-in connections is 8 A. The system may be damaged if this current limit is exceeded. Distribute modules between multiple DIN rails and also power supply units, if required.
Determining the maximum current without the setup program
The current consumption for each module is stated in the technical data. The currents can be added until the maximum value of 8 A is reached (base unit and input/output modules connect­ed to it).
Additional input/output modules must then be mounted on the right, next to a router module on an additional DIN rail. In this case, the maximum admissible current consumption is also 8 A (router module input/output modules connected to it).
Where applicable, a second power supply unit is required for the voltage supply to the router module.
Base units
Designation Current consumption
6 Electrical connection
Central processing unit Max. 350 mA
Input/output modules
Designation Current consumption
Multichannel controller module Max. 300 mA Relay module 4-channel 120 mA Analog input module 4-channel 130 mA Analog input module 8-channel 80 mA Digital input/output module 90 mA
Special modules
Designation Current consumption
Router module 100 mA
Operating, visualization, recording
Designation Current consumption
Multifunction panel 840 Max. 750 mA
Determining the maximum current with the setup program
The setup program determines how many modules can be installed alongside one another. If the maximum current is exceeded, the user will be required to install additiona l modules on the right next to a router module on an additional DIN rail.
Where applicable, a second power supply unit is required for the voltage supply to the router module.
57
6 Electrical connection
CAUTION!
The current consumption of the system can exceed the current load capacity of the used power supply units. The power supply units may be damaged. The dimensioning of the power supply units must be sufficiently large.
58

6.5 System bus

Setup
LAN Bus Out
Run Stop Reset
Power
Status
Bus Error
Com1
Com2
Com2
2
1
3
4
ON
2
1
3
4
ON
Com1
3
7
Side system bus
The side system bus connects the base unit or router module to the input/output modules ar­ranged on the same DIN rail.
Either
a base unit or
a router module
must always be installed on the left, at the st art of the DIN rail. The distinguishing feature is that their plug-in connections are only to the right; all other modules have plug-in connections on both sides.
The system bus on the side is physically implemented as a point-to-point connection. The con­nection is only ever made between two neighboring modules. If a module or a module insert does not function or is removed, the modules to the right can no longer be reached.
NOTE!
The further to the left a module is installed, the greater the probability that the mod ule can still be reached in the event that a different module fails.
6 Electrical connection
System bus connections of a base unit, using the example of a central processing unit
3 Side system bus Out 7 System bus Out
The router module has an identical connection for the side system bus, but a total of three RJ45 sockets for connecting to the base unit (Bus In), the multifunction panel, or additional router modules (Bus In, Bus Out1, Bus Out2).
59
6 Electrical connection
(4)
(5)
System bus connections of a multifunction panel 840
4 System bus In 5 System bus Out
System bus between base unit, router module, and multifunction panel
T o connect the base unit to a multifunction p anel or a router module, a connection is established via the RJ45 sockets (Bus Out – Bus In). For this purpose, use a commercially available net­work cable (patch or crossover cable) that corresponds to at least category 5 and has S/FTP shielding.
The connection can be established directly at a distance of up to 100 m. At greater distances, an additional router module will be required at a maximum of 100 m away. The distance can also be extended using a multifunction panel.
NOTE!
Commercially available Ethernet switches must not be used for the system bus. A connection between the system bus and a company network (LAN) is also not admissible.
The following figure shows an example for the connection between a central processing unit, multiple router modules, and a multifunction panel.
60
6 Electrical connection
(5)
(4)
(3)
(2)
(1)
(1) Router module with downstream modules (2) Network cable (patch or crossover cable), at
least CA T5 (S/FTP); dist ance per connection up to 100 m
(3) Multifunction panel; instead of a router mod-
ule
(5) Router module with downstream modules
(4) Router module without downstream modules
to increase the range
61
6 Electrical connection
62

7 Startup and configuration

A setup program is available for the measuring, control, and automation system. The setup pro­gram must be used for system startup; the first step is to perform project configuration. For ex­ample, this also includes:
Creating a project and selecting the first module (e.g. central processing unit)
Creating the hardware assignment. In other words, selecting the remaining modules includ­ing the optional extensions (inputs/outputs, interfaces)
Selecting special software and hardware versions, if required
Activating optional functions (e.g. math/logic, PLC)
Settings and texts for collective alarms (system and modules)
Project-specific settings (e.g. project descriptio n, language selection, collective alarm, PLC application, time zone)
User administration
Following the project configuration, the individual modules and the multifunction panel must be configured. This task is also performed using the setup p rogram. For example, this includes the configuration (and/or parameterization) of the following functions:
Inputs and outputs, interfaces, internal signals
Limit value monitoring
Controller
Math/logic (option)
Program generator (option)
PLC (option)
Recording function (option)
With a few exceptions, the configuration of the modules can also be performed on the multi­function panel. A prerequisite for this is that the hardware assignment was created using the setup program and transferred to the system.
The following manual contains information on the configuration and startup of the overall mea­suring, control, and automation system:
Manual, setup program B 705000.6 In this manual, the user can find a simple example that describes the basic procedure during
the initial startup of the measuring, control, and automation system. In addition, a separate operating manual is available for each module; it describes the config-
uration of the module. Chapter 1.4 "Available technical documentation", page 21
Both of the following sections are only intended to provide a brief insight into the setu p program and the multifunction panel. For more information, see the respective manual.
63
7 Startup and configuration

7.1 Setup program

The setup program (accessories) is installed on a PC and connected to the base unit (e.g. cen­tral processing unit) via a USB or LAN interface. In this way, the entire system can be conve­niently configured, parameterized, and operated. The setup data is transferred from the base unit via the system bus to the connected input/output modules, of which there may be a maxi­mum of 30, even if these are connected via a router module. The base unit continuously com­pares the saved system configuration with the input/output modules that are present. For this reason, a module insert of an identical type can simply be replaced when service work is being performed. The new module insert is automatically detected by the base unit and configured (Plug and Play).
Manual, setup program B 705000.6
NOTE!
The setup program is an essential requirement for the initial startup and also for making changes to the hardware assignment. Certain parameters of the modules and the multifunc­tion panel can also only be configured using the setup program.
64

7.2 Multifunction panel 840

7 Startup and configuration
The multifunction panel 840 with TFT -touchscreen allows easy and clearly-arran ged measured data visualization, operation, configuration, and parameterization of the system.
The TFT color screen has a screen size of 21.3 cm (8.4“), a resolution of 640 × 480 pixels, 256 colors, and LED backlight.
As the interface between man and machine, the panel allows an optimum and clearly-arranged view of the process status and the system parameters. In addition, it is perfe ctly suitable for the display and operation of controller screens, process screens, the program editor, and the op­tional recording function. Setpoint values, batch text, parameters, and configuration data can be directly entered and changed by the user on the screen.
The process data that is transmitted by the system bus is shown in real time. Data archiving and evaluation is made possible by established PC-programs.
In addition to the standard interfaces (LAN, USB), two optional serial interfaces can be con­nected to a barcode scanner, modem, or other Modbus devices (master, slave).
The user can comfortably configure the multifunctional panel 840 with the setup program. Operating manual, multifunction panel 840 B 705060.0
NOTE!
Some of the parameters of the multifunction panel and the modules can only be configured using the setup program. The setup program is an essential requirement for the initial startup of the system and for making changes to the hardware assignment.
65
7 Startup and configuration
66

8.1 General technical data

8.1.1 Directives

2006/95/EC Low Voltage Directive
2004/108/EC Electromagnetic Compatibility Directive

8.1.2 Electrical safety

According to DIN EN 61010-1
Overvoltage category III, pollution degree 2

8.1.3 Protection type according to DIN EN 60529

IP20 modules
Multifunction panel on front IP67, on rear IP20

8.1.4 Protection rating

8 Appendix

Overvoltage category III, pollution degree 2
Protection rating I
(with internal isolation to SELV current circuits)
Multichannel controller module
Relay module 4-channel
Protection rating III
Multifunction panel 840
Central processing unit
Router module
Analog input module 4-channel
Analog input module 8-channel
Digital input/output module 12-channel

8.1.5 EMC

Interference emission: Class A – only for industrial use –
Interference immunity: Industry requirement

8.1.6 Voltage supply

DC 24 V (19.2 V to 30 V) SELV
Residual ripple: 5 %
Supply voltage range according to IEC 61131-1 standard: DC 20.4 to 28.8 V
67
8 Appendix

8.1.7 Ambient requirements

Multifunction panel 840
Indoor use
Ambient temperature: -20 to +55 °C
Storage temperature: -30 to +70 °C
•Humidity ≤ 90 % rel. humidity without condensation
Site altitude: Up to 2000 m above sea level
Modules
Indoor use
Ambient temperature: -20 to +55 °C
Storage temperature: -40 to +70 °C
•Humidity: ≤ 90 % rel. humidity without condensation
Site altitude: Up to 2000 m above sea level

8.1.8 Conformity

CE (symbol of conformity according to DIN EN 61010-1 (LVD) + DIN EN 61326 (EMC))

8.1.9 Climatic tests

Classification acc. to DIN EN 60721-3-3, class 3K3, but with extended temperature and humidity range
Tests acc. to DIN EN 50178 requirements
- Dry heat (table 11): DIN EN 60068-2-2, test Bd
- Damp heat (table 12): DIN EN 60068-2-78, test Ca
Tests acc. to DIN EN 61131-3 requirements
- Dry heat: DIN EN 60068-2-2, test Bb
- Cold: DIN EN 60068-2-1, test Ab
68

8.1.10 Mechanical tests

Modules for DIN rail mounting
Classification acc. to DIN EN 60721-3-3, table 6, class 3M2
Sinusoidal vibration, stationary
Test method Acc. to DIN EN 60068-2-6,
Deflection amplitude 1,5 mm Accelaration amplitude 5 m/s Deflection frequency range 2 Hz ≤ f ≤ 9Hz Crossover frequency 9 Hz Accelaration frequency range 9 Hz ≤ f ≤ 200 Hz Vibration type Continuously at a rate of 1 octave/minute Vibration duration 20 cycles for each of three axes which are perpendicular to
Shocks, non-stationary
Test method Acc. to DIN EN 60068-2-27,
Total shock-response spectrum Type L Peak accelaration 40 m/s Shock duration 22 ms Number of shocks in each direction 100 ± 5 (a total of 600 shocks)
test Fc
2
(~ 0,5 g)
each other
test Ea and guidance: Shock
2
8 Appendix
69
8 Appendix
Multifunction panel
Vibration test acc. to DIN EN 50178, table 14
Sinusoidal vibration, stationary
Test method Acc. to DIN EN 60068-2-6,
Deflection amplitude 0,075 mm Accelaration amplitude 10 m/s Deflection frequency range 10 Hz ≤ f ≤ 57 Hz Crossover frequency 57 Hz Accelaration frequency range 57 Hz ≤ f ≤ 150 Hz Vibration type Continuously at a rate of 1 octave/minute Vibration duration 10 cycles for each of three axes which are perpendicular to
Shock test
Shock
Test method Acc. to DIN EN 60068-2-27,
Basic form of shock Half sine wave Peak accelaration 250 m/s Shock duration 10 ms Number of shocks in each direction Single shock: 3 ± 0; continuous shock: 5000 ± 10
test Fc
2
(~ 1 g)
each other
test Ea and guidance: Shock
2
Drop test (with packaging) acc. to DIN EN 60068-2-32, method 1
70

8.2 System expansion (system version 02)

The expansion of the setup program and the system software allows the measuring, control, and automation system to offer new features which are intended to be used in such areas as process engineering:
Program generator with process steps
Expanded user administration
Expanded process screen editor
Program generator with process steps
The nine program generators support the use of up to 100 process steps.
In every process step, the permissible setpoint values and control contacts are selected and the time limits of a program section are defined. This specification is normally done by the plant manufacturer because specific knowledge of the plant is necessary for this job.
While entering a program in the program editor , a specific process step is assigned to each program section. This means that the conditions which are defined in the pr ocess step are valid for the particular program section. As a result, only the permissible setpoint values and control contacts are used in the program section. Furthermore, the section time lies with in the predefined limits.
8 Appendix
Expanded user administration
Up to 16 user groups are supported by the system. Specific user rights that deal with the displaying and editing of certain system values or the controlling of cert ain system functions are assigned to each user group.
Up to 50 users can be managed in the system. Each user get s the right s of the user group.
The user group rights are exclusively defined with the setup program. The users them­selves can be administrated with the setup program or the multifunction panel. The option to restrict the user administration to the multifunction panel is available.
Expanded process screen editor
In each of a maximum of 18 process screens up to 16 levels can now be defined. The single objects of a process screen are assigned to a level.
Visibility and editability of a level can be influenced by the user group or by the PLC.
Additional object types allo w the selection of programs and process step s, are used to dis­play batch texts, or provide the user logon/logoff in the process screen.
By hiding the JUMO toolbar, the whole screen area is available for the customer-specific process screen.
71
8 Appendix

8.3 Training courses/seminars

Further training has become indispensable in the area of modern automation technology. As one of the leading manufacturers of systems for measurement and con trol technology , we want to pass on our specialist knowledge on products and general fundament al topics to customers and employees.
For this purpose, we have established a training center in Fulda, Germany, which is equipped with the latest technology. In addition to communicating theoretical contexts, the focus is on practical training in the individual courses, with tasks performed on models and simulators. Im­portant knowledge for day-to-day work is communicated in the course of the practical aspect s.
You can find an overview of the courses on offer in our training calendars. A detailed brief de­scription is available for each course, including the target group, learning objectives, and a de­scription of the content.
You can obtain more detailed information on training, the individual seminars, and the registra­tion formalities from:
JUMO GmbH & Co. KG Seminar Department Manfred Schleicher Moritz-Juchheim-Straße 1 36039 Fulda, Germany Phone: +49 (0)661 6003-396 Fax: +49 (0)661 6003-604 E-mail: manfred.schleicher@jumo.net
72
JUMO GmbH & Co. KG
Street address: Moritz-Juchheim-Straße 1 36039 Fulda, Germany Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow - Essex CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 63 52 62 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road East Syracuse, NY 13057, USA Phone: 315-437-5866
1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com
Loading...