The documents specified below are available for the measuring, control, and automation system.
1.1.1General information
ProductType of documentationNo.PrintedPDF file
Measuring,
control, and
automation system
1
Accessory subject to charge
2
Includes an overview of the purpose and content of all documents
1.1.2Base units
Data sheetT 705000-X
System manual
Setup program manualB 705000.6-X
System description
1
2
1 Introduction
B 705000.0X-
B 705000.8-X
ProductType of documentationNo.PrintedPDF file
Central
processing unit
Data sheetT 705001-X
Operating manualB 705001.0-X
Modbus interface descriptionB 705001.2.0-X
Installation instructionsB 705001.4XX
1.1.3Input/output modules
ProductType of documentationNo.PrintedPDF file
Multichannel
controller module
Relay module
4-channel
Analog
input module
4-channel
Data sheetT 705010-X
Operating manualB 705010.0-X
Installation instructionsXX
Data sheetT 705015-X
Operating manualB 705015.0-X
Installation instructionsB 705015.4XX
Data sheetT 705020-X
Operating manualB 705020.0-X
Installation instructionsB 705020.4XX
Analog
input module
8-channel
Digital input/
output module
12-channel
Data sheetT 705021-X
Operating manualB 705021.0-X
Installation instructionsB 705021.4XX
Data sheetT 705030-X
Operating manualB 705030.0-X
Installation instructionsB 705030.4XX
5
1 Introduction
1.1.4Special modules
ProductType of documentationNo.PrintedPDF file
Router moduleData sheetT 705040-X
Installation instructionsB 705040.4XX
1.1.5Operating, visualization, recording
ProductType of documentationNo.PrintedPDF file
Multifunction
panel 840
Data sheetT 705060-X
Operating manualB 705060.0-X
Modbus interface descriptionB 705060.2.0-X
Installation instructionsB 705060.4XX
1.1.6Power supply units
ProductType of documentationNo.PrintedPDF file
24 V power supply
units
Data sheetT 705090-X
Operating instructions QS5.241X-
Operating instructions QS10.241X-
6
1.2Safety information
&
1.2.1Warning symbols
DANGER!
This symbol indicates that injury to persons caused by electrical shock may occur, if the
respective protective measures are not carried out.
WARNING!
This symbol in connection with the signal word indicates that injury of persons may occur,
if the respective protective measures are not carried out.
CAUTION!
This symbol in combination with the signal word indicates that damage to assets or data
loss will occur if suitable precautions are not taken.
CAUTION!
This sign indicates that components could be destroyed by electrostatic discharge
(ESD = Electro Static Discharge), if the respective cautionary measures are not taken.
Only use the ESD packages intended for this purpose to return device inserts, assembly
groups or assembly components.
1 Introduction
READ DOCUMENTATION!
This symbol – placed on the device – indicates that the associated device documentation
has to be observed. This is necessary to recognize the kind of the potential hazards as
well as to take the measures to avoid them.
1.2.2Note signs
TIP!
This symbol refers to important information about the product or its handling or additional
use.
REFERENCE!
This symbol refers to further information in other sections, chapters, or manuals.
FURTHER INFORMATION!
This sign is used in the tables and refers to further information in connection with the table.
DISPOSAL!
This device and, if installed, the batteries must not be disposed of in the garbage can after
use! Please ensure that they are disposed of properly and in an environmentally friendly manner.
7
1 Introduction
1.2.3Intended use
The modules described are intended for measuring, control, and automation tasks in an industrial environment, as described in the technical data. Other uses or uses beyond those defined
are not viewed as intended uses.
The modules are built according to the relevant standards and directives as well as the applicable safety regulations. Nevertheless, incorrect use may lead to bodily injury or property damage.
To avoid danger, the modules may only be used:
•For the intended use
•When in good order and condition
•When taking into account the technical documentation provided
Even if a module is used correctly and according to the intended use, it may still cause application-related dangers (e.g. due to missing safety devices or incorrect settings).
1.2.4Qualification of personnel
This document contains the necessary information for the intended use of the modules to which
it relates.
It is intended for technically qualified personnel who have received special training and have
the appropriate knowledge in the field of automation technology (measuring, process, and control technology).
The appropriate level of knowledge and the technically fault-free implementation of the safety
information and warnings contained in the technical documentation provided are prerequisites
for risk-free mounting, installation, and startup as well as for ensuring safety when operating
the described modules. Only qualified personnel have the required specialist knowledge to correctly interpret and implement the safety information and warnings contained in this document
in specific situations.
8
1.3Acceptance of goods, storage, and transport
1.3.1Checking the delivery
•Ensure that the packaging and contents are not damaged
•Check that the delivery is complete using the delivery papers and the order details
•Inform the supplier immediately if there is any damage
•Store damaged parts until clarification is received from the supplier
1.3.2Notes on storage and transport
•Store the module in a dry and clean environment. Observe the admissible ambient conditions (see "Technical data")
•The transport of the module is to be shockproof
•The original packaging provides optimum protection for storage and transport
1.3.3Returning goods
In the event of repair, please return the module in a clean and complete state.
Use the original packaging to return goods.
1 Introduction
Accompanying letter for repair
Please include the completed accompanying letter for repair when returning goods.
Do not forget to state the following:
•Description of the application and
•Description of the error that has occurred
The accompanying letter for repair can be downloaded online from the manufacturer's website
(use the search function if necessary).
Protection against electrostatic discharge (ESD)
(ESD = electrostatic discharge)
To prevent damage from ESD, electronic modules or components must be handled, packaged,
and stored in an ESD-protected environment. Measures against electrostatic discharge and
electrical fields are described in DIN EN 61340-5-1 and DIN EN 61340-5-2 "Protection of electronic devices from electrostatic phenomena".
When returning electronic modules or components, please note the following:
•Sensitive components must only be packaged in an ESD-protected environment. Workspaces such as this divert electrostatic charges to ground in a controlled manner and prevent static charges due to friction capacities.
•Only use packaging for ESD-sensitive modules/components. These must consist of conductive plastics.
No liability can be assumed for damage caused by ESD.
9
1 Introduction
CAUTION!
Electrostatic charges occur in non-ESD protected environments.
Electrostatic discharges can damage modules or components.
For transport purposes, use only the ESD packaging provided.
1.3.4Disposal
Disposing of the device
DISPOSAL!
Devices and/or replaced parts should not be placed in the refuse bin at the end of their service life as they consist of materials that can be recycled by specialist recycling plants.
Dispose of the device and the packaging material in a proper and environmentally friendly
manner.
For this purpose, observe the country-specific laws and regulations for waste treatment and
disposal.
Disposing of the packaging material
The entire packaging material (cardboard packaging, inserts, plastic film, and plastic bags) is
fully recyclable.
10
1.4Identifying the Device Version
(B)
(A)
1.4.1Nameplates
Position
The nameplate (B) is affixed to the module case.
An additional nameplate with reduced information is located on the module insert (A). This du-
plicate identification is important when replacing a module insert or retrofitting optional modules.
1 Introduction
Contents
It contains important information. This includes:
Device type
Compare the specifications on the nameplate with the order.
Identify the supplied device version using the order details of the respective module.
Part no. (TN)
The part no. clearly identifies an article in the catalog. It is important for communication between the customer and the sales department.
DescriptionDesignation on the name-
plate
Device type (A + B)Type705021/36
Part no. (B)TN00XXXXXX
Fabrication number (A + B)F-Nr0070033801211010006
Voltage supply (B)-DC 24 V +25/-20 %
Example
11
1 Introduction
Fabrication no. (F-Nr)
Among other things, the fabrication number contains the date of production (year/week).
Example: F-Nr = 0070033801211010006
The figures concerned are in positions 12, 13, 14, and 15 (from the left).
The device was therefore produced in the 1st calendar week of 2011.
1.4.2Order details
(1)Basic type
705021Analog input module 8-channel
(2)Voltage supply
36DC 24 V +25/-20 %
(1)(2)
Order code/
Order example705021/36
1.4.3Scope of delivery
1 analog input module, 8-channel
1 Installation Instructions B 705021.4
1.4.4General accessories
ArticlePart no.
JUMO mTRON T system manual, English00575577
MiniDVD with setup program (full version), programming software CODESYS V3, and
detailed documentation; incl. USB cable
PC Evaluation Software PCA300000431882
Release automatic print for PC Evaluation Software PCA300000505548
PCA Communication Software PCC00431879
Plant Visualization Software JUMO SVS3000: See data sheet 700755-
USB cable A-plug mini-B-plug 3 m00506265
00569494
12
2.1Brief description
8 Analogeingänge
Pt100, Pt500, Pt1000 in
Zweileiterschaltung
1 Digitaleingang
(DC 0/24 V)
705021
Spannungsversorgung
Systembus
The analog input module 8-channel is equipped with eight analog inputs for RTD temperature
probes in 2-wire circuit as well as one digital input (DC 0/24 V). The analog inputs are not electrically isolated from each other. The digitized input values/states are available in the system
for further processing.
LEDs are used to indicate applied voltage supply, the module operating status, as well as the
digital input status.
A setup program can be used to comfortably configure the analog input module.
For service work, the module insert can be easily pulled out of the case at the front. The case
including the bus PCB remains mounted on the DIN rail.
2.2Block diagram
2 Description
13
2 Description
14
3 Installation
3.1General information on installation/dismounting
DANGER!
With multichannel controller module 705010 and relay module 705015, the load circuits from
relay or solid state relay outputs can be operated with a dangerous electrical voltage (e.g.
230 V).
There is a risk of electric shock.
Prior to the installation/dismounting of these modules or the removal of the module insert, the
load circuits are to be disconnected from the voltage and the terminal strips are to be removed from the module. This work must only be performed by qualified personnel.
WARNING!
The modules must never be installed in areas with an explosion hazard.
There is the risk of an explosion.
The entire system must only be used outside of areas with an explosion hazard.
Mounting site
All modules have protection type IP20 and are only intended for use in fireproof control cabinets
or switch boxes. The mounting site should be virtually vibration-free. Electromagnetic fields
caused by equipment such as motors or transformers should be avoided.
Multifunction panel 840 has protection type IP67 at the front and is intended for installation in
a panel cut-out. The rear has protection type IP20.
Climatic conditions
The ambient temperature and the relative humidity at the mounting site must correspond to the
technical data. Aggressive gases and vapors have a negative effect on the operating life of the
modules. The mounting site must be free from dust, powder, and other suspended matter so
that the cooling slots do not become blocked.
DIN rail
All modules are mounted on a DIN rail according to DIN EN 60715 (35 mm × 7.5 mm × 1 mm).
For reasons of stability, the spacing of the fastening screws for the DIN rail should not exceed
200 mm. The minimum distances for the modules that are specified in the module-specific installation or operating instructions must be observed.
Installation position
The DIN rail should be mounted horizontally so that all modules are arranged vertically. Otherwise the admissible ambient temperature range will be restricted.
Space requirement
The modules require the minimum distances shown in the following figure for the purpose of
installation/dismounting and for future maintenance or replacement. In the event of shorter distances the minimum bending radius of the cables, the performance of the electrical installation,
and the clear arrangement of the plant are no longer guaranteed.
15
3 Installation
130
203.6
51.8
30
70
51.8
Minimum distances
3.2Installation/dismounting on DIN rail
All modules in the system are intended for installation on a DIN rail according to DIN EN 60715
(35 mm × 7.5 mm × 1 mm).
The following must always be installed on the left, at the start of the DIN rail:
•A central processing unit or
•A router module
These modules connect the input/output modules to the voltage supply and the system bus.
TIP!
To determine the required minimum width of the DIN rail, the widths of the individual modules
are to be added (see technical data of the modules in the respective data sheet or the
module-specific installation instructions).
The widths of the cover (17.5 mm) and both end brackets (each 9.5 mm) should also be
taken into consideration: 17.5 mm + 2 × 9.5 mm = 36.5 mm.
3.2.1Input/output modules
In a sequence at the user's discretion, input/output modules can be arranged to the right next
to a base unit or a router module.
16
Installation, using the example of a multichannel controller module 705010
(A)(A1)
(A2)
(D)
(C5)(D6)
(D7)
(C)(A)
(B4)(A3)
(B)
3 Installation
Example installation
Procedure:
StepActivity
1Mount the multichannel controller module (A) in the DIN rail from above (A1).
2Pivot the multichannel controller module (A) downward until it snaps into place (A2).
3Move the multichannel controller module (A) to the left against the previous module (A3)
until the plug connections for the voltage supply and the system bus are connected.
4Position additional modules (B) and move to the left against the previous module (B4).
5After the final module, position the cover (C) on the DIN rail and move to the left against the
module (C5).
6After attaching the cover, position the end bracket (D) on the DIN rail and move to the left
against the cover (D6).
7Fasten the end bracket (D) using a screwdriver (D7). For this purpose, ensure that the end
bracket and the cover are positioned flush against the final module.
17
3 Installation
(C2)
(D1)
(A4)(B3)
(C) (D)
(A)(B)
(A)
(F)
(E)
(E5)
(F7)
(A6)
(A8)
Dismounting, using the example of a multichannel controller module 705010
Removing the multichannel controller module from the DIN rail
18
Procedure:
StepActivity
1Fully release the end bracket (D) using a screwdriver (D1), press upward from below, pivot
2Move the cover (C) to the right (C2) until the side contacts of the neighboring module are
toward the front, and remove from the DIN rail.
Note: The end bracket does not need to be removed from the DIN rail if there is sufficient
space to the side to move it at least 20 mm to the right.
exposed. Then release the cover at the bottom using a screwdriver, press upward, and
remove from the DIN rail.
Note: The cover does not need to be removed from the DIN rail if there is sufficient space
to the side to move it at least 20 mm to the right.
3 Installation
StepActivity
3Move the modules (B) on the right next to the multichannel controller module that is to be
replaced (A) a minimum of 20 mm to the right (B3).
➥ These modules are isolated from the voltage supply and the system bus.
4Move the multichannel controller module (A) to the right (A4) until the side contacts of the
neighboring module (here: central processing unit) – on the left, next to the multichannel
controller module that is to be replaced – are exposed.
➥ The multichannel controller module is isolated from the voltage supply and the system
bus. This is a prerequisite for the dismounting of the multichannel controller module.
5If required, pull off the wired terminals (E) of the multichannel controller module (A) toward
the front (E5).
6Insert a suitable screwdriver (F) into the unlocking slot of the multichannel controller mod-
ule (A6) and press upward (F7).
7Pivot the multichannel controller module (A) upward off the DIN rail (A8) and remove it.
19
3 Installation
(A)
(E)
(B)(D)
(G)
(C)
(F)
(F)
(F)
3.3Replacing module inserts
3.3.1Input/output modules
DANGER!
With multichannel controller module 705010 and relay module 705015, the load circuits from
relay or solid state relay outputs can be operated with a dangerous electrical voltage (e.g.
230 V).
There is a risk of electric shock.
The load circuits are to be disconnected from the voltage supply prior to removing the wired
terminal strips. This work must only be performed by qualified personnel.
Replacement of a module insert, using the example of a multichannel controller module 705010
20
For service purposes (or when retrofitting options for the multichannel controller module), the
case (D) can remain in the system; only the module insert (B) is replaced. For this purpose, the
system does not need to be isolated from the voltage supply (hot swapping).
The system will detect a module insert of the same type that has been replaced and will automatically reconfigure it. Retrofitted functions for the multichannel controller module (expansion
slots) must be configured using the setup program or the multifunction panel.
The new module insert also has a new nameplate (G), which will differ from the old one at least
with regard to the fabrication number, and is no longer identical to nameplates (E) and (C) on
the case (D).
Therefore, in the event of replacement, the module insert will be supplied along with a new
nameplate that will be affixed to the case (D) in place of the old nameplate (C). This means that
the specifications of nameplates (G) and (C) once again correspond to one another.
CAUTION!
Only module inserts of the same type may be used for the replacement.
Otherwise, the function of the system may be affected.
The module inserts can be clearly identified using the nameplate.
CAUTION!
With the multichannel controller module 705010, a new module insert may contain retrofitted
inputs or outputs that have not yet been configured.
This can lead to unintended behavior, particularly at the outputs and the actuators connected
to them.
Prior to using the retrofitted inputs or outputs, ensure that these have been configured correctly.
Removing the module insert
StepActivity
1Disconnect load circuits from the relay or solid state relay outputs.
2Pull off the wired terminal strips (A) toward the front.
3 Installation
3Press the old module insert (B) together on the grooved surfaces at the top and bottom and
remove from the case (D).
4For the multichannel controller module, also remove the modules (F) of the expansion slots
from the case (D) toward the front, if required.
Mounting the module insert
StepActivity
1Affix the new nameplate in place of the old nameplate (C) in the case.
2For the multichannel controller module, also insert the modules (F) of the expansion slots
into the case (D), if required.
3Hold the new module insert (B) at the grooved surfaces on the top and bottom and insert
them into the case (D). For this purpose, ensure that the board of the module insert slides
into the guide rails of the case. For the multichannel controller module, also ensure that the
modules (F) of the expansion slots slide in the guide rails of the module insert.
4Reattach the wired terminal strips (A).
TIP!
When mounting the module insert, ensure that the snap holders (under the grooved surfaces)
audibly snap into place.
TIP!
The availability of the system can be increased through the storage of module inserts and
modules for expansion slots.
21
3 Installation
103.6
22.5
6.6
101
94.5
101.5
14.5
3.4Dimensions
22
4.1Installation notes
TIP!
These installation notes apply for the entire measuring, control, and automation system and,
on some occasions, are only applicable for a specific module.
The respective connection diagram shows the context.
Qualification of personnel
•Work on the modules must only be carried out to the extent described and, like the electrical
connection, only by qualified personnel.
Cables, shielding, and grounding
•When selecting the cable material, when installing, and when performing the electrical connection of the module, the regulations of DIN VDE 0100 "Erection of power installations with
rated voltages up to 1000 V" and the respective national regulations (e.g. on the basis of
IEC 60364) are to be observed.
•Certain cables must be heat resistant up to at least 80 °C at maximum load. The relevant
instructions in the connection diagram of the affected modules must be observed.
•Route input, output, and supply cables separately and not parallel to one another.
•Only use shielded and twisted probe and interface cables. Do not route the lines close to
current-carrying components or cables.
•For temperature probes, ground the shielding on one side in the control cabinet.
•Do not perform loopthroughs on the grounding cables, but route the cables individually to a
shared grounding point in the control cabinet; in doing so, ensure that the cables are as
short as possible.
Ensure that the equipotential bonding is correct.
4 Electrical connection
Electrical safety
•Isolate power supply units from the voltage supply on the primary side if there is a risk of
touching parts with dangerous electrical voltage (e.g. 230 V) in the course of work.
•The fuse rating of the power supply units on the primary side should not exceed a value of
10 A (inert).
•With modules with relay or solid state relay outputs, the load circuits can be operated with
a dangerous electrical voltage (e.g. 230 V). Disconnect load circuits from the voltage supply
during installation/dismounting and electrical connection.
•In order to prevent the destruction of the relay or solid state relay outputs in the event of an
external short circuit in the load circuit, the load circuit should be fused to the maximum admissible output current.
•The modules are not suitable for installation in areas with an explosion hazard.
•In addition to a faulty installation, incorrectly set values on the module could also impair the
correct function of the following process. Therefore, ensure that safety devices independent
of the module (e.g. overpressure valves or temperature limiters/monitors) are available and
that it is only possible for qualified personnel to define settings. Please observe the corresponding safety regulations in this context.
23
4 Electrical connection
Analog input 7
Digital input
AC 30 V
DC 50 V
Analog input 5
Analog input 3
Analog input 1
»
AC 30 V
DC 50 V
Analog input 8
Analog input 6
Analog input 4
Analog input 2
Voltage supply Out
Side system bus In
Side system bus Out
Voltage supply In
References to other information
•The electromagnetic compatibility meets the standards and regulations cited in the technical data.
•The USB device interface and voltage supply in the central processing unit 705001 are not
electrically isolated. In general, please observe the specifications regarding electrical isolation.
4.2Electrical isolation
24
4.3Connection diagram
(1)
(2)
(3)
(4)
(5)
(7)
(6)
CAUTION!
At maximum load, the temperature may exceed 60 °C at the terminals.
As a result the insulation of the cable may be damaged.
The cable must be heat resistant up to at least 80 °C.
4.3.1Display and connection elements
4 Electrical connection
(1) Status displays (LED)
P = Voltage supply
S = Status
1 = Digital input
(LED is lit: Active)
(2) Analog input 1 to 6
(3) Voltage supply Out, DC 24 V
(4) Side system bus Out
(5) Analog input 7, 8;
digital input
(6) Side system bus In
(7) Voltage supply In, DC 24 V
25
4 Electrical connection
U
+
-
x
4.3.2Analog inputs
ConnectionInputTerminalsSymbol and terminal designation
RTD temperature probe
2-wire circuit
1
2
3
4
5
6
7
8
1 and 2
3 and 4
5 and 6
7 and 8
9 and 10
11 and 12
13 and 14
15 and 16
4.3.3Digital input
ConnectionInputTerminalsSymbol and terminal designation
Digital input DC 0/24 V117 and 1817
1, 3, 5, 7, 9 , 11, 13, 15
2, 4, 6, 8, 10,12, 14, 16
18
4.4Functional test
The voltage supply must be tested on completion of the electrical connection:
SignalMeaning
LED "P" (Power, green) is litThe module is being supplied with voltage
LED "P" (Power, green) is not litThe module is not supplied with voltage or there
through the side contacts.
is a problem with the electrical function of the
LED.
Remedy:
•Check the voltage supply to the side contacts
of the preceding module (top contact +24 V,
bottom contact GND).
•Check voltage supply at the "+24 V" and
"GND" terminals of the base unit or router
module.
•Check power supply unit and connection between the power supply unit and the base unit
or router module.
If the "Power" LED does not light up despite a
voltage supply being present, the module insert
or – if the bus board inside the case is faulty – the
entire module must be replaced.
Startup
The check described above completes the process of installation and electrical connection. For
startup, use the additional documentation (operating manual or system manual).
The "Introduction" section of this document contains an overview of all documentation for the
measuring, control, and automation system.
26
5.1Display and connection elements
(1)
(2)
(3)
(4)
(5)
(7)
(6)
5 Operation
(1) Status displays (LED)
P = Voltage supply
S = Status
1 = Digital input
(LED is lit: Active)
(2) Analog input 1 to 6
(3) Voltage supply Out, DC 24 V
(4) Side system bus Out
(5) Analog input 7, 8;
digital input
(6) Side system bus In
(7) Voltage supply In, DC 24 V
27
5 Operation
5.2LED displays
"P" LED (Power)
The LED is permanently lit in green if the module is being supplied with voltage.
"S" LED (Status)
This LED indicates the status of the module. Diagnostics requires the setup program or a Web
browser as appropriate.
LED "1"
The LED indicates the status of the digital input.
LED lights up yellow = digital input is active
5.2.1Display modes
The following table lists all possible states of the "S" LED (Status).
Display modeDescriptionGreen sym-
bol
---LED state not relevant------
OffLED off
OnLED on (permanently lit)
FlickeringLED flickers (50 ms on, 50 ms off)
Single flickeringLED flashes briefly (50 ms on, 200 ms off)
BlinkingLED flashes (200 ms on, 200 ms off)
Single flashLED flashes once (200 ms on, 1000 ms off)
Double flashLED flashes twice (on/off/on for 200 ms each
time, 1000 ms off)
Triple flashLED flashes three times (on/off/on/off/on for
200 ms each time, 1000 ms off)
Quadruple flashLED flashes four times (on/off/on/off/on/off/on for
200 ms each time, 1000 ms off)
Blinking red/greenLED flashes red and green (200 ms red, 200 ms
green)
On green/
Single flickering red
LED lights up green, flashes red (50 ms red)
Red symbol
28
5.2.2System states and errors
The following table lists all the system states and errors that are indicated by the "S" LED (Status). In most cases, further diagnostics must be performed with the setup program.
5 Operation
Category"S" LED
(Status)
Start errorModule error (hardware does not
Start errorInternal error (bootloader)
Start errorNo firmwareLEDReplace module
Bus statusNo connection to central processing
Bus statusSystem in "Stop" (INIT) state – no
Bus statusSystem in "Stop" (PREOP) state – no
Operation
(Priority 1)
Operation
(Priority 2)
Operation
(Priority 3)
Operation
(Priority 3)
MeaningDiagnos-
tics with
LEDReplace module
start up)
LEDReplace module
Various errors during startup (e.g. no
memory, initialization error)
LEDCheck whether the central pro-
unit
LED
error, only in start phase
LED
error, only in start phase
Calibration modeLED/setup
program
Collective alarm (incl. out of range)LED/setup
program
System in "Stop" (SAFEOP) state –
no error
System in "Run" (OP) state – no
error
LED
LED
Recommended action
cessing unit is running; check
cabling and topology
29
5 Operation
30
TIP!
?
The parameters described in this section can be configured either with the setup program or
on the multifunction panel.
6.1Digital selector
The digital selector contains all digital signals that are available in the analog input module 8channel to configure the following functions.
•Alarm suppression (see Chapter 6.2.1 "Alarms", page 34)
•Signal suppression (see Chapter 6.3 "Digital input", page 38)
The following table lists all digital signals. The entry in the "Type" column indicates the source
of the signal:
•Internal: Internal signal of the analog input module 8-channel (including the signal of the digital input)The signal is also transmitted to the base unit via the system bus, to allow it to be
used by other modules.
•External: External input (NV_...) that must be linked in the NV connecting list to a signal
from another module (see Chapter 6.4 "NV connecting list", page 40).
The signal name "NV_..." indicates the intended use; in principle, the signal can also be
used for other purposes.
6 Configuration
Alarm
CategorySignalTypeDescription
InactiveNo signal selected
Analog inputsAI01Alarm1 to AI08Alarm1InternalAlarm signal 1 of analog input 1 to
8
AI01Alarm2 to AI08Alarm2 InternalAlarm signal 2 of analog input 1 to
8
Digital inputsDI01InternalSignal of digital input
Signal rejectionsNV_SR01 to NV_SR09ExternalSignal for activating signal sup-
The collective alarm of the analog input module 8-channel is made up of all functions for which
the "Collective alarm" alarm type has been activated.
31
6 Configuration
6.2Analog inputs
The eight analog inputs are measuring inputs for RTD temperature probes in 2-wire circuit.
Setup dialog
Parameter
ParameterSelection/settingsDescription
SensorSelection of measuring probe for the relevant analog input
No choiceNo sensor selected
RTD temp. probe 2-wRTD temperature probe in 2-wire circuit
LinearizationAvailable options and factory settings depend on the measuring probe selected.
Linear
Pt100DIN EN 60751
Pt500DIN EN 60751
Pt1000DIN EN 60751
Pt100JJIS 1604
Pt100GGOST 6651-94
Scale
start
Scale
end
TAG number7 charactersIdentification marking (documentation in
Unit5 characters (%)Unit for numerical representation of
Factory setting depends on the linearization.
-99999 to +99999Start value of display range
Factory setting depends on the linearization.
-99999 to +99999End value of display range
PLC)
measured value
32
6 Configuration
?
?
?
ParameterSelection/settingsDescription
Offset typeType of measured value offset
StandardizedOffset of standardized measured value
(after linearization)
PhysicalOffset of physical measured value
(before linearization)
Offset-100 to 0 to +100Correction value
Filter time constant
Offset type
To offset plant-specific deviations, the measured value can be offset for each analog input.
When doing this, the offset type is used to specify the type of measured value offset.
"Standardized" offset type: The measured value is offset after linearization (temperature value
in °C or °F).
"Physical" offset type: The physical measured value is offset before linearization (resistance
in ohms).
A typical application scenario for the "physical" offset type is compensation of the lead wire resistance when using an RTD temperature probe.
Offset
A positive or negative form of the correction value is added to the measured value (entering a
negative correction value reduces the measured value).
Filter time constant
The filter time constant is used to adjust the digital input filter (2nd order filter). If the input signal
changes suddenly, approx. 26 % of the change is recorded following a period that corresponds
to the filter time constant (2 × filter time constants: approx. 59 %; 5 × filter time constants:
approx. 96 %). A large filter time constant means a high level of attenuation of interference signals, a slow reaction time of the actual value display, and low limit frequency (low-pass filter).
0 s to 0.6 s to 100 sTime constant for adjusting the digital
input filter (0 s = filter off)
Status after change of configuration
The input values before the change of configuration are not saved; the new input values are
available approx. 2 seconds after the change of configuration.
Behavior after power on
All analog inputs are initialized and start their measurements over (no statuses are saved with
power off).
33
6 Configuration
?
?
?
6.2.1Alarms
Limit value monitoring with one or two alarms and various alarm types can be activated for each
analog input. In addition, this function is required in order to trigger the collective alarm of the
module if the event of deviation above or below the measuring range (out of range).
Setup dialog
Parameter
ParameterSelection/settingsDescription
Alarm type 1, 2OffMonitoring is not active.
Min. alarmAlarm is issued if the limit value is not
met.
Max. alarmAlarm is issued if the limit value is
exceeded.
Limit value 1, 2-99999 to 0 to +99999Limit value at which an alarm is issued.
Kind of alarm 1, 2 The alarm type is not set by default.
Collective alarmAlarm results in collective alarm of the
module.
EventAlarm results in an entry (event text) in
the event list.
Event text 1, 2Use default text or select other text from
the list.
Switching differential
0 to 99999Used to suppress constant switching
Text that is entered in the event list for
an alarm (if Alarm type = "Event").
operations in the event of minor fluctuations of the input signal around the limit
value.
34
Alarm suppression
Alarm delay0 s to 65535 sDelay time for alarm activation
Digital selector (Inactive)
Chapter 6.1 "Digital selector", page
31
Signal to activate the alarm suppression
Alarm type and switching differential
(1)
(2)
(3)
(3)
1
0
(1) Min. alarm/limit value1 Alarm on
(2) Max. alarm/limit value0 Alarm off
(3) Switching differential
Event text
Setup program: Selection of text from a list
Click the "..." button to open a list with the text numbers and the associated texts. The texts can
be edited.
Multifunction panel: Selection of text using the text number
The setup program is required to view and edit the texts.
6 Configuration
Collective alarm for out of range
In the event of deviation above or below the measuring range (out of range, O-o-R) or in the
event of a probe/conductor break or probe/conductor short-circuit, the collective alarm of the
module can also be triggered. To do this, you must activate at least one alarm type and select
the "Collective alarm" alarm type.
If the alarm type is only being activated for this purpose, the measuring range start (for Min.
alarm) or measuring range end (for Max. alarm) must be entered as a limit value. Otherwise,
in the event of deviation above or below the value – for example if the default value 0 is retained
– this also results in a module collective alarm.
The collective alarm of the module is entered in the event list of the central processing unit,
which enables you to identify the affected module. If there is also a need to identify the affected
analog input, you must also activate the "Event" alarm type and select an appropriate event
text.
35
6 Configuration
20°C / 80°C
20°C / 80°C
15°C / 70°C
(4)
(3)
(1)
(2)
6.2.2Fine adjustment
You can use customer-specific fine adjustment to correct the measured values of the analog
input. In contrast to offsetting, which is used to specify a constant correction value for the entire
characteristic line, fine adjustment can also be used to change the gradient of the characteristic
line.
Setup dialog
Parameter
ParameterSelection/settingsDescription
Actual start value -99999 to 0 to +99999Lower display value
Target start value -99999 to 0 to +99999Lower reference value
Actual end value-99999 to 1 to +99999Upper display value
Example
Target end value-99999 to 1 to +99999Upper reference value
The temperature inside a furnace is measured with an RTD temperature probe and displayed.
Due to the temperature drift of the sensor, the true temperature (reference measurement) deviates from the displayed value. The amount of deviation is different at the upper and lower
measuring points, meaning that measured value offset is not suitable.
Actual start value: 15 °C (displayed value)
Target start value: 20 °C (reference measurement)
Actual end value: 70°C (displayed value)
Target end value: 80 °C (reference measurement)
(1)Display value(2)Reference value
(3)Furnace(4)Sensor in RTD temperature probe
36
Performing fine adjustment
2080
20
80
70
15
(2)
y
(1)
x
1) Determine the lower value (as low and constant as possible) with the reference measuring
device.
Example: Set furnace temperature to 20 °C.
2) Enter the display value as the actual start value and the reference value as the target start
value.
Example: Enter 15 and 20.
3) Determine the upper value (as high and constant as possible) with the reference measuring
device.
Example: Increase furnace temperature to 80 °C.
4) Enter the display value as the actual end value and the reference value as the target end
value.
Example: Enter 70 and 80.
Characteristic line
The following diagram shows the changes in the characteristic line caused by the fine adjustment (point of intersection with the x axis as well as the gradient).
6 Configuration
yDisplay value(1)Characteristic line before fine adjustment
xReference value(2)Characteristic line after fine adjustment
Resetting the fine adjustment
The following settings must be made to reverse the fine adjustment:
Actual start value = target start value
Actual end value = target end value
37
6 Configuration
?
6.3Digital input
In addition to the analog inputs the module provides a digital input.
The status of the digital input is indicated by a LED. The display corresponds to the output sig-
nal to the system bus.
Setup dialog
Parameter
ParameterSelection/settingsDescription
Mode: Delay0 s to 65535 sDelay time during change of input signal
from Low to High (or from High to Low in
the case of active inverting)
InvertingInversion of the input signal
NormalNot inverted
InverseInverted
TAG number7 charactersIdentification marking (documentation in
PLC)
Signal suppression
Level at suppression
Alarm typeThe alarm type is not set by default.
Digital selector (Inactive)
Chapter 6.1 "Digital selector", page
31
Output level during active signal suppression
No choiceLow level (0)
ActiveHigh level (1)
Collective alarmAlarm results in collective alarm of the
EventAlarm results in an entry (event text) in
Signal (high-active) for suppression of
the input signal
module.
the event list.
Alarm active atHigh (1)Alarm at high level (1)
Low (0)Alarm at low level (0)
38
ParameterSelection/settingsDescription
?
6 Configuration
Event textUse default text or select other text from
the list.
Signal suppression
When signal suppression is active, the input signal and the inverting and delay parameters are
irrelevant. In this case, a fixed signal with a configurable level is issued (to the system bus).
Event text
Setup program: Selection of text from a list
Click the "..." button to open a list with the text numbers and the associated texts. The texts can
be edited.
Multifunction panel: Selection of text using the text number
The setup program is required to view and edit the texts.
Status after change of configuration
The output signal to the system bus always adopts the status that corresponds to the current
configuration.
Behavior after power on
After initialization, the input signals are available immediately, according to their configuration.
Text that is entered in the event list for
an alarm (if Alarm type = "Event").
39
6 Configuration
6.4NV connecting list
The NV connecting list is used to link external inputs (NV_...) of the analog input module 8channel to signals from other modules via the system bus.
A comprehensive list with the module signals is included in the following chapter.
Chapter 6.4.1 "Digital signals (overview)", page 42
Further information about the signals can be found in the operating manual for the relevant
module.
Replacement values are available in the event that these signals are not available (connection
to base unit interrupted in "Stop" state).
Chapter 6.4.2 "Replacement values (overview)", page 47
TIP!
There is no NV connecting list in the input/output module configuration menu on the multifunction panel. Instead, a central NV connecting list is available in the configuration menu of
the base unit (CPU).
Setup dialog
Parameter
40
ParameterSelection/settingsDescription
Digital signal /
Valu e
Select input to be connected.List of external inputs of the module
If a connection has already been configured, the module and its signal are displayed in the "Value" column.
ParameterSelection/settingsDescription
?
6 Configuration
...\NV_SR01
(Example)
Replacement
value
This is the previously selected external input.
Select the module and – in the selector
next to it on the right – the signal to connect to the external input.
Replacement value for the relevant signal (The selection On/Off is active if a signal
is assigned to the external input.)
OffLow level (0)
OnHigh level (1)
Replacement value
The replacement value is used if the relevant signal is not available (connection to base unit
interrupted or system in "Stop" state).
Status after change of configuration
The connections are available immediately.
Behavior after power on
The connections are available immediately after system initialization.
List of modules in the system and the
relevant signals
41
6 Configuration
6.4.1Digital signals (overview)
The following table contains all signals that are available in the NV connecting list for connection to the external inputs (NV_...) of the analog input module 8-channel.
CategorySignalDescription
InactiveNo signal selected
Central processing unit
Digital variablesDigital variable 1 to 64Digital variable 1 to 64 (via interface)
Program
generator 1 to
Program
generator 9
Operating contact 1 to 16Operating contact 1 to 16 of program channels
(in the three program channels, operating contacts with the same name are linked with OR)
Mode: Basic statusStatus: Program is not running (basic status)
Mode: AutomaticStatus: Program is running (automatic mode,
no delay time or program end time)
Mode: Automatic 1Status: Program is running (automatic mode,
incl. delay time and program end time)
Mode: StandstillStatus: Program stopped during automatic
mode (time base stopped)
Mode: DelayStatus: Program start delayed (delay time
runs)
Mode: Program endStatus: Program ends (program end time runs,
corresponds to length of end signal)
Mode: ManualStatus: Manual mode
Tolerance band channel 1 to 3Tolerance band signal of program channel 1 to
3
42
PLC Binary output 27 to 32Signal of PLC digital output 27 to 32
Limit monitoringLimit monitoring 1 to 64Output signal of limit value monitoring 1 to 64
Binary linkingBinary linking 1 to 8Result of binary linking 1 to 8
PLC Binary output 9 to 32Signal of PLC digital output 9 to 32
Binary PLC output block 13 to
block 18
PLC Binary output 1 to 32Signal of PLC digital output 1 to 32
CategorySignalDescription
6 Configuration
Alarm analog
variables
Alarm integer
variables
Alarm1 ExAI1 to Alarm1 ExAI64Alarm signal 1 of analog variable 1 to 64
Alarm2 ExAI1 to Alarm2ExAI64Alarm signal 2 of analog variable 1 to 64
Alarm1 ExInt1 to Alarm1 ExInt64Alarm signal 1 of integer variable 1 to 64
Alarm2 ExInt1 to Alarm2ExInt64Alarm signal 2 of integer variable 1 to 64
43
6 Configuration
CategorySignalDescription
Alarms/
Faults
CAlarm/FaultSystem collective alarm or system fault (cen-
tral processing unit and modules)
CAlarm/Fault ackn.System collective alarm or system fault with
HWCounterSignalSignal of hardware counter in "fill" operating
mode (as shut-down signal when threshold
value reached)
45
6 Configuration
CategorySignalDescription
Analog input module 4-channel
Analog inputsAI01Alarm1 to AI04Alarm1Alarm signal 1 of analog input 1 to 4
Digital inputsDI01Signal of digital input
AlarmCollectiveAlarmModule collective alarm
Analog input module 8-channel
Analog inputsAI01Alarm1 to AI08Alarm1Alarm signal 1 of analog input 1 to 8
Digital inputsDI01Signal of digital input
AI01Alarm2 to AI04Alarm2Alarm signal 2 of analog input 1 to 4
AI01Alarm2 to AI08Alarm2Alarm signal 2 of analog input 1 to 8
AlarmCollectiveAlarmModule collective alarm
Digital input/output module 12-channel
Digital inputsDI01 to DI12Signal of digital input 1 to 12
AlarmCollectiveAlarmModule collective alarm
Multifunction panel 840
System bus
digital inputs
Alarm batch 1 to
Alarm batch 9
CollectiveAlarmCollective alarm of multifunction panel (pro-
FaultFault in multifunction panel (independent of
Batch 1 active to Batch 9 activeSignal for active batch 1 to 9
Push button 1 to
Push button 18
Collective alarm of batch 1 to 9 (process values)
cess values)
process values)
Status of push button 1 to 18 in process screen
46
6.4.2Replacement values (overview)
The following table contains the replacement values with their factory settings. Replacement
values can only be configured in the setup program.
Digital signals
6 Configuration
CategorySignalFactory
setting
Signal suppression
NV_SR01 to NV_SR09OffSignal for activating signal sup-
Description
pression
47
6 Configuration
48
TIP!
?
An active connection between the setup program and the central processing unit is required
to configure the parameters described in this section.
7.1Calibrate / test
7.1.1Analog input
CAUTION!
Incorrect settings may result in inadmissible changes to values.
This can have negative effects on the system function.
Individual functions must be changed only by (or under the instruction of) a service technician
of the device manufacturer.
Setup dialog
7 Online parameters
Parameter
ParameterSelection/settingsDescription
Measuring inputSelect input (drop-down list).Input on which the calibration or test is
to be performed.
SensorSelect sensor (drop-down list).Sensor type that is connected at the rel-
evant input.
Actual valueNoneDisplay of the actual value read out
TestClick the "Test" button.An additional window opens with
instructions for testing (see below).
49
7 Online parameters
Test
The results of the test measurement are shown in the display field.
7.1.2Digital input
Setup dialog
Parameter
50
ParameterSelection/settingsDescription
Read outClick the "Read out" button.The input is read out and the result is
displayed (LOW, HIGH).
7.1.3LED test
Setup dialog
7 Online parameters
Parameter
ParameterSelection/settingsDescription
S LEDTo test the LED, click the required status
to select it (OFF, red, or green).
After selection, the LED enters the chosen status immediately.
1 LEDTo test the LED, click the required status
(OFF or yellow) to select it.
After selection, the LED enters the chosen status immediately.
This function is used to test the electrical
function of the "S" LED (Status).
This function is used to test the electrical
function of LED "1".
TIP!
An LED maintains the set status until a new status is set or until the "LED test" dialog window
is closed.
51
7 Online parameters
7.1.4Calibration constants
Setup dialog
This dialog displays the calibration constants of the analog inputs.
7.1.5Versions
Setup dialog
52
This dialog displays the module versions.
8.1Technical data
8.1.1Analog inputs
General information
Number8
A/D converterResolution 16 bit
RTD temperature probe
8 Appendix
DesignationStandardMeasuring rangeMeasuring accu-
Pt100DIN EN 60751-200 to +850 °C50 ppm/K
2-wire circuit≤ 0.08 %
Pt500DIN EN 60751-200 to +850 °C50 ppm/K
2-wire circuit≤ 0.08 %
Pt1000DIN EN 60751-200 to +850 °C50 ppm/K
2-wire circuit≤ 0.08 %
Pt100JIS 1604-200 to +650 °C50 ppm/K
2-wire circuit≤ 0.08 %
Pt100GOST 6651-94-200 to +850 °C50 ppm/K
2-wire circuit≤ 0.08 %
Measuring currentPt100 approx. 380 μA, Pt 500, and Pt1000 approx. 150 μA; not con-
stant
Lead compensationA lead resistance can be compensated in the software by correcting
the process value.
1
The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced linearization accuracy.
racy
1
Ambient
temperature influence
Measuring circuit monitoring
In the event of an error the digitized output values move to a defined status.
Measuring elementOut of rangeProbe/cable short
circuit
RTD temperature probeIs detectedIs detectedIs detected
Probe/cable break
8.1.2Digital input
Number 1
Input signalDC 0/24 V
(PLC level; logical “0” = -3 to +5 V; logical “1” = +15 to +30 V)
53
8 Appendix
8.1.3Electrical data
Voltage supply
ConnectionLateral (feed via base unit or router module)
VoltageDC 24 V +25/-20 %
Residual ripple5 %
Current consumption80 mA (at DC 19.2 V)
Power consumption2 W
Inputs (terminals 1 to 18)
ConnectionAt the front (removable terminal strips with Push-In technology)
Conductor cross section on terminals 1 to 18
Wire or strand without ferruleMin. 0.14 mm
Strand with ferruleWithout plastic collar: Min. 0.25 mm2, max. 1.5 mm
With plastic collar: Min. 0.25 mm2, max. 0.5 mm
Stripping length on terminals 1 to 189 mm
Electrical safetyAcc. to DIN EN 61010-1
Overvoltage category III, pollution degree 2
Electromagnetic compatibilityAcc. to DIN EN 61326-1
Interference emissionClass A – only for industrial use –
Interference immunityIndustrial requirements
2
, max. 1.5 mm
2
2
2
8.1.4Case and ambient conditions
Case typePlastic case for DIN rail mounting in the control cabinet (indoor use);
DIN rail acc. to DIN EN 60715, 35 mm x 7.5 mm x 1 mm
Dimensions (W x H x D)22.5 mm x 103.6 mm x 101.5 mm (without connection elements)
WeightApprox. 125 g
Protection typeIP20, acc. to DIN EN 60529
Ambient temperature range-20 to +55 °C
Storage temperature range-40 to +70 °C
Resistance to climatic conditionsRelative humidity ≤ 90 % annual average without condensation (cli-
matic class 3K3 acc. to DIN EN 60721-3-3 with extended tempera-
ture and humidity range)
Site altitudeUp to 2000 m above sea level
Mechanical ambient conditions
1
Test conditions are listed in the System Descripton B 705000.8.
1
Classification acc. to DIN EN 60721-3-3, table 6, class 3M2