Data sheetT 705090-X
Operating instructions QS5.241XOperating instructions QS10.241X-
8
1.2Safety information
&
1.2.1Warning symbols
DANGER!
This symbol indicates that injury to persons caused by electrical shock may occur, if the
respective protective measures are not carried out.
WARNING!
This symbol in connection with the signal word indicates that injury of persons may occur,
if the respective protective measures are not carried out.
CAUTION!
This symbol in combination with the signal word indicates that damage to assets or data
loss will occur if suitable precautions are not taken.
CAUTION!
This sign indicates that components could be destroyed by electrostatic discharge
(ESD = Electro Static Discharge), if the respective cautionary measures are not taken.
Only use the ESD packages intended for this purpose to return device inserts, assembly
groups or assembly components.
1 Introduction
READ DOCUMENTATION!
This symbol – placed on the device – indicates that the associated device documentation
has to be observed. This is necessary to recognize the kind of the potential hazards as
well as to take the measures to avoid them.
1.2.2Note signs
TIP!
This symbol refers to important information about the product or its handling or additional
use.
REFERENCE!
This symbol refers to further information in other sections, chapters, or manuals.
FURTHER INFORMATION!
This sign is used in the tables and refers to further information in connection with the table.
DISPOSAL!
This device and, if installed, the batteries must not be disposed of in the garbage can after
use! Please ensure that they are disposed of properly and in an environmentally friendly manner.
9
1 Introduction
1.2.3Intended use
The modules described are intended for measuring, control, an d automation t asks in an ind ustrial environment, as described in the technical data. Oth er uses or uses beyond th ose defined
are not viewed as intended uses.
The modules are built according to the relevant standards and directives as well as the applicable safety regulations. Nevertheless, incorrect use may lead to bodily injury or property damage.
To avoid danger, the modules may only be used:
•For the intended use
•When in good order and condition
•When taking into account the technical documentation provided
Even if a module is used correctly and according to the intended use, it may still cause appli-
cation-related dangers (e.g. due to missing safety devices or incorrect settings).
1.2.4Qualification of personnel
This document contains the necessary information for the intended use of the modules to which
it relates.
It is intended for technically qualified personnel who have received special training and have
the appropriate knowledge in the field of automation technology (measuring, process, and control technology).
The appropriate level of knowledge and the technically fault-free implementation of the safety
information and warnings contained in the technical documentation provided are prerequisites
for risk-free mounting, installation, and startup as well as for ensuring safety when operating
the described modules. Only qualified personnel have the required specialist knowledge to correctly interpret and implement the safety information and warnings contained in this document
in specific situations.
10
1.3Acceptance of goods, storage, and transport
1.3.1Checking the delivery
•Ensure that the packaging and contents are not damaged
•Check that the delivery is complete using the delivery papers and the order details
•Inform the supplier immediately if there is any damage
•Store damaged parts until clarification is received from the supplier
1.3.2Notes on storage and transport
•Store the module in a dry and clean environment. Observe the admissible ambient conditions (see "Technical data")
•The transport of the module is to be shockproof
•The original packaging provides optimum protection for storage and transport
1.3.3Returning goods
In the event of repair, please return the module in a clean and complete state.
Use the original packaging to return goods.
1 Introduction
Accompanying letter for repair
Please include the completed accompanying letter for repair when returning goods.
Do not forget to state the following:
•Description of the application and
•Description of the error that has occurred
The accompanying letter for repair can be downloaded online from the manufacturer's website
(use the search function if necessary).
Protection against electrostatic discharge (ESD)
(ESD = electrostatic discharge)
To prevent damage from ESD, electronic modules or components must be handled, packaged,
and stored in an ESD-protected environment. Measures against electrostatic discharge and
electrical fields are described in DIN EN 61340-5-1 and DIN EN 6 1340-5-2 "Protection of electronic devices from electrostatic phenomena".
When returning electronic modules or components, please note the following:
•Sensitive components must only be packaged in an ESD-protected environment. Workspaces such as this divert electrostatic charges to ground in a controlled manner and prevent static charges due to friction capacities.
•Only use packaging for ESD-sensitive modules/components. These must consist of conductive plastics.
No liability can be assumed for damage caused by ESD.
11
1 Introduction
CAUTION!
Electrostatic charges occur in non-ESD protected environments.
Electrostatic discharges can damage modules or components.
For transport purposes, use only the ESD packaging provided.
1.3.4Disposal
Disposing of the device
DISPOSAL!
Devices and/or replaced parts should not be placed in the refuse bin at the end of their service life as they consist of materials that can be recycled by specialist recycling plants.
Dispose of the device and the packaging material in a proper and environmentally friendly
manner.
For this purpose, observe the country-specific laws and regulations for waste treatment a nd
disposal.
Disposing of the packaging material
The entire packaging material (cardboard packaging, inserts, plastic film, and plastic bags) is
fully recyclable.
12
1.4Identifying the device version
(A)(B)
1.4.1Nameplates
Position
The nameplate (B) is affixed to the module case.
Additional nameplates with reduced information are located on the module insert (A) and inside
the module case (C; not shown). This duplicate identification marking via nameplates (A) and
(C) is important when replacing a module insert or retrofitting optional modules.
1 Introduction
Content
The nameplates contain important information. This includes:
Device type
Compare the specifications on the nameplate with the order.
Identify the supplied device version using the order details of the respective module.
Part no. (TN)
The part no. clearly identifies an article in the catalog. It is important for communication between the customer and the sales department.
DescriptionDesignation on the name-
plate
Device type (A + B + C)Typ705010/18-113-36
Part no. (A + B + C)TN00XXXXXX
Fabrication number (A + B + C)F-Nr0070033801211010006
Voltage supply (B)-DC 24 V +25/-20 %
Example
13
1 Introduction
Fabrication no. (F-Nr)
Among other things, the fabrication number contains the date of production (year/week).
Example: F-Nr = 0070033801211010006
The figures concerned are in positions 12, 13, 14, and 15 (from the left).
The device was therefore produced in the 1st calendar week of 2011.
Identifying the optional modules
The device type (Typ) also contains information about factory-fitted optional modules (in the
example above – 705010/18-113-36 – this is string 113). The optional modules can be identified by the order details.
This chapter contains additional information to identify optional modules:
Chapter 10 "Retrofitting inputs/outputs", page 137
TIP!
The information on the nameplates must also be considered when replacing the module insert
(Chapter 3.3 "Replacing module inserts", page 24).
0Not used
1Analog input 2
2Relay (changeover contact)
32 relays (N/O contacts with common pole)
4Analog output
52 digital inputs
6Solid-state relay 1 A
72 open-collector outputs
(5)Option slot 2
0Not used
1Analog input 2
2Relay (changeover contact)
32 relays (N/O contacts with common pole)
4Analog output
52 digital inputs
6Solid-state relay 1 A
72 open-collector outputs
(6)Option slot 3
0Not used
2Relay (changeover contact)
32 relays (N/O contacts with common pole)
4Analog output
52 digital inputs
6Solid-state relay 1 A
72 open-collector outputs
(7)Voltage supply
36DC 24 V +25/-20 %
1 Introduction
(1)(2)(3)(4)(5)(6)(7)
Order code/--
Order example705010/18-000-36
15
1 Introduction
1.4.3Scope of delivery
1 multichannel controller module in the ordered version
1 Installation instructions B 705010.4
1.4.4Accessories
ArticlePart no.
Modules for option slots (expansion boards):
Analog input00569497
Relay (changeover contact)00569498
2 relays (N/O contacts with common pole)00569499
Analog output00569500
2 digital inputs00569501
Solid-state relay 1 A00569502
2 open-collector outputs00569503
1.4.5General accessories
ArticlePart no.
JUMO mTRON T system manual, English00575577
MiniDVD with setup program (full version), programming sof tware CODESYS V3, a nd
detailed documentation; incl. USB cable
PC Evaluation Software PCA300000431882
Release automatic print for PC Evaluation Software PCA300000505548
PCA Communication Software PCC00431879
Plant Visualization Software JUMO SVS3000: See data sheet 700755USB cable A-plug mini-B-plug 3 m00506265
00569494
16
2.1Brief description
2 universal analog inputs
Option 1
2 digital inputs
(DC 0/24 V)
2 digital outputs:
Relay
Logic
(N/O)
or
(DC 0/15 V,
to control an external
solid-state relay)
705010
Option 2
Option 3
Voltage supply
System bus
The multichannel controller module supports up to four PID controller channels (cascadable).
In the standard version, two high-quality universal analog inputs for thermocouples, RTD temperature probes, resistance transmitters, resistance/potentiometers, and standard signals are
available. Two digital inputs (DC 0/24 V) and two digital outputs as a relay with N/O contact
(AC 230 V / 3 A) or as a logic output (DC 0/15 V) are also available as part of the standard version. Due to the three option slots (option 1, 2, and 3), the module can be extended up to four
universal analog inputs, eight digital inputs, three analog outputs, or eight digital outputs.
The digitized input values/states are available in the system for further processing. The digital
and the analog outputs can be actuated by t he system (via the connection list or directly by the
PLC) or directly by the module.
The module operates independently , even if the central processing unit fails or the higher-ranking system malfunctions. This behavior can be configured.
LEDs are used to indicate applied voltage supply, the module operating status, as well as the
status of the digital inputs/outputs.
For expansion of the inputs/outputs or for service work, the module insert can be easily pulled
out of the case at the front. The case including the bus PCB remains mounted on the DIN rail.
A setup program allows the user to comfortably configure and parameterize the multichannel
controller module.
2 Description
2.2Block diagram
17
2 Description
18
3 Installation
3.1General information on installation/dismounting
DANGER!
With multichannel controller module 705010 and relay module 705015, the load circuits from
relay or solid state relay outputs can be operated with a dangerous electrical voltage (e.g.
230 V).
There is a risk of electric shock.
Prior to the installation/dismounting of these modules or the removal of the module insert, the
load circuits are to be disconnected from the voltage and the terminal strips are to be removed from the module. This work must only be performed by qualified personnel.
WARNING!
The modules must never be installed in areas with an explosion hazard.
There is the risk of an explosion.
The entire system must only be used outside of areas with an explosion hazard.
Mounting site
All modules have protection type IP20 and are only intended for use in fireproof con trol cabinets
or switch boxes. The mounting site should be virtually vibration-free. Electromagnetic fields
caused by equipment such as motors or transformers should be avoided.
Multifunction panel 840 has protection type IP67 at the front and is intended for installation in
a panel cut-out. The rear has protection type IP20.
Climatic conditions
The ambient temperature and the relative humidity at the mounting site must correspond to the
technical data. Aggressive gases and vapors have a negative ef fect on the operating life of the
modules. The mounting site must be free from dust, powder, and other suspended matter so
that the cooling slots do not become blocked.
DIN rail
All modules are mounted on a DIN rail according to DIN EN 60715 (35 mm × 7.5 mm × 1 mm).
For reasons of stability, the spacing of the fastening screws for the DIN rail should not exceed
200 mm. The minimum distances for the modules that are specified in the module-specific installation or operating instructions must be observed.
Installation position
The DIN rail should be mounted horizontally so that all modules are arranged vertically. Otherwise the admissible ambient temperature range will be restricted.
Space requirement
The modules require the minimum distances shown in the following figure for the purpose of
installation/dismounting and for future maintenance or replacement. In the event of shorter distances the minimum bending radius of the cables, the performance of the electrical inst allation,
and the clear arrangement of the plant are no longer guaranteed.
19
3 Installation
130
203.6
51.8
30
70
51.8
Minimum distances
3.2Installation/dismounting on DIN rail
All modules in the system are intended for installation on a DIN rail according to DIN EN 60715
(35mm×7.5mm×1mm).
The following must always be installed on the left, at the start of the DIN rail:
•A central processing unit or
•A router module
These modules connect the input/output modules to the voltage supply and the system bus.
TIP!
To determine the required minimum width of the DIN rail, the widths of the individual modules
are to be added (see technical data of the modules in the respective data sheet or the module-specific installation instructions).
The widths of the cover (17.5 mm) and both end brackets (each 9.5 mm) should also be taken into consideration: 17.5 mm + 2 × 9.5 mm = 36.5 mm.
3.2.1Input/output modules
In a sequence at the user's discretion, input/output modules can be arranged to the right next
to a base unit or a router module.
20
Installation, using the example of a multichannel controller module 705010
(A)(A1)
(A2)
(D)
(C5)(D6)
(D7)
(C)(A)
(B4)(A3)
(B)
3 Installation
Example installation
Procedure:
StepActivity
1Mount the multichannel controller module (A) in the DIN rail from above (A1).
2Pivot the multichannel controller module (A) downward until it snaps into place (A2).
3Move the multichannel controller module (A) to the left against the previous module (A3)
until the plug connections for the voltage supply and the system bus are connected.
4Position additional modules (B) and move to the left against the previous module (B4).
5Aft er the final module, position the cover (C) on the DIN rail and move to the left a gainst the
module (C5).
6After attaching the cover, positio n th e en d br ac ke t (D) on the DIN rail and mov e to th e left
against the cover (D6).
7Fasten the end br acket ( D) using a screwdrive r (D7). For this purpose, ensure that the end
bracket and the cover are positioned flush against the final module.
21
3 Installation
(C2)
(D1)
(A4)(B3)
(C) (D)
(A)(B)
(A)
(F)
(E)
(E5)
(F7)
(A6)
(A8)
Dismounting, using the example of a multichannel controller module 705010
Removing the multichannel controller module from the DIN rail
22
Procedure:
StepActivity
1Fully release the end bracket (D) using a screwdriver (D1) , press upward from below, pivot
2Move the cover (C) to the right (C2) until the side contacts of the neighboring module are
toward the front, and remove from the DIN rail.
Note: The end bracket does not need to be removed from the DIN rail if there is sufficient
space to the side to move it at least 20 mm to the right.
exposed. Then release the cover at the bottom using a screwdriver, press upward, and
remove from the DIN rail.
Note: The cover does not need to be removed from the DIN rail if there is sufficient space
to the side to move it at least 20 mm to the right.
3 Installation
StepActivity
3Move the modules (B) on the right next to the multichannel controller module that is to be
replaced (A) a minimum of 20 mm to the right (B3).
➥ These modules are isolated from the voltage supply and the system bus.
4Move the multichannel controller module (A) to the right (A4) until the side contacts of the
neighboring module (here: central processing unit) – on the left, next to the multichannel
controller module that is to be replaced – are exposed.
➥ The multichannel controller module is isolated from the voltage supply and the system
bus. This is a prerequisite for the dismounting of the multichannel controller module.
5If required, pull off the wired terminals (E) of the multichannel controller module (A) toward
the front (E5).
6Insert a suitable screwdriver (F) into the unlocking slot of the multichannel controller mod-
ule (A6) and press upward (F7).
7Pivot the multichannel controller module (A) upward off the DIN rail (A8) and remove it.
23
3 Installation
(A)
(E)
(B)(D)
(G)
(C)
(F)
(F)
(F)
3.3Replacing module inserts
3.3.1Input/output modules
DANGER!
With multichannel controller module 705010 and relay module 705015, the load circuits from
relay or solid state relay outputs can be operated with a dangerous electrical voltage (e.g.
230 V).
There is a risk of electric shock.
The load circuits are to be disconnected from the voltage supply prior to removing the wired
terminal strips. This work must only be performed by qualified personnel.
Replacement of a module insert, using the example of a multichannel controller module 705010
24
For service purposes (or when retrofitting options for the multichannel controller module), the
case (D) can remain in the system; only the module insert (B) is replaced. For this purpose, the
system does not need to be isolated from the voltage supply (hot swapping).
The system will detect a module insert of the same type that has been replaced and will automatically reconfigure it. Retrofitted functions for the multichannel controller module (exp ansion
slots) must be configured using the setup program or the multifunction panel.
The new module insert also has a new nameplate (G), which will dif fer from the old one at le ast
with regard to the fabrication number, and is no longer identical to nameplates (E) and (C) on
the case (D).
Therefore, in the event of replacement, the module insert will be supplied along with a new
nameplate that will be affixed to the case (D) in place of the old nameplate (C). This means that
the specifications of nameplates (G) and (C) once again correspond to one another.
CAUTION!
Only module inserts of the same type may be used for the replacement.
Otherwise, the function of the system may be affected.
The module inserts can be clearly identified using the nameplate.
CAUTION!
With the multichannel controller module 705010, a new modu le insert may contain retrofitted
inputs or outputs that have not yet been configured.
This can lead to unintended behavior, particularly at the outputs and the actuators connected
to them.
Prior to using the retrofitted inputs or outputs, ensure that these have been configured correctly.
Removing the module insert
StepActivity
1Disconnect load circuits from the relay or solid state relay outputs.
2Pull off the wir ed terminal strips (A) toward the front.
3 Installation
3Press the old module inse rt (B) together o n the grooved surface s at the top and bottom and
remove from the case (D).
4For the multichannel co ntroller module, also remove the modules (F) of the exp ansion slots
from the case (D) toward the front, if required.
Mounting the module insert
StepActivity
1Affix the new nameplate in place of the old nameplate (C) in the case.
2For the multichannel controller module, also insert the modules (F) of the expansion slots
into the case (D), if required.
3Hold the new module insert (B) at the grooved surfaces on the top and bottom and insert
them into the case (D). For this purpose, ensure that the board of the module insert slides
into the guide rails of the case. For the multichannel controller module, also ensure that the
modules (F) of the expansion slots slide in the guide rails of the module insert.
4Reattach the wired terminal strips (A).
TIP!
When mounting the module insert, ensure that the snap holders (under the grooved surfaces)
audibly snap into place.
TIP!
The availability of the system can be increased through the storage of module inserts and
modules for expansion slots.
25
3 Installation
3.4Dimensions
26
4.1Installation notes
TIP!
These installation notes apply for the entire measuring, control, and automation system and,
on some occasions, are only applicable for a specific module.
The respective connection diagram shows the context.
Qualification of personnel
•Work on the modules must only be carried out to the extent described and, like the electrical
connection, only by qualified personnel.
Cables, shielding, and grounding
•When selecting the cable material, when installing, and when performing the electrical connection of the module, the regulations of DIN VDE 0100 "Erection of power installations with
rated voltages up to 1000 V" and the respective national regulations (e.g. on the basis of
IEC 60364) are to be observed.
•Certain cables must be heat resistant up to at least 80 °C at maximum load. The relevant
instructions in the connection diagram of the affected modules must be observed.
•Route input, output, and supply cables separately and not parallel to one another.
•Only use shielded and twisted probe and interface cables. Do not route the lines close to
current-carrying components or cables.
•For temperature probes, ground the shielding on one side in the control cabinet.
•Do not perform loopthroughs on the grounding cables, but route the cables individually to a
shared grounding point in the control cabinet; in doing so, ensure that the cables are as
short as possible.
Ensure that the equipotential bonding is correct.
4 Electrical connection
Electrical safety
•Isolate power supply units from the voltage supply on the primary side if there is a risk of
touching parts with dangerous electrical voltage (e.g. 230 V) in the course of work.
•The fuse rating of the power supply units on the primary side should not exceed a value of
10 A (inert).
•With modules with relay or solid state relay outputs, the load circuits can be operated with
a dangerous electrical voltage (e.g. 230 V). Disconnect load circuits from the voltage supply
during installation/dismounting and electrical connection.
•In order to prevent the destruction of the relay or solid state relay outputs in the event of an
external short circuit in the load circuit, the load circuit should be fused to the maximum admissible output current.
•The modules are not suitable for installation in areas with an explosion hazard.
•In addition to a faulty installation, incorrectly set values on the module could also impair the
correct function of the following process. Therefore, ensure that safety devices independent
of the module (e.g. overpressure valves or temperature limiters/monitors) are available and
that it is only possible for qualified personnel to define settings. Please observe the corresponding safety regulations in this context.
27
4 Electrical connection
References to other information
•The electromagnetic compatibility meets the standards and regulations cited in the technical data.
•The USB device interface and voltage supply in the central processing unit 705001 are not
electrically isolated. In general, please observe the specifications regarding electrical isolation.
28
4.2Galvanic isolation
Open-collector outputs
»
Analog inputs
Digital inputs
DC 0/24 V
Solid-state relay outputs
»
800 V (peak)
System bus
Logic outputs
DC 0/15 V
»
»
AC 30 V
DC 50 V
Voltage supply
DC 24 V
Relay outputs
»
AC 3800 V
Analog outputs
»
AC 30 V
DC 50 V
AC 30 V
DC 50 V
AC 30 V
DC 50 V
AC 30 V
DC 50 V
Voltage supply Out
Side system bus In
Side system bus Out
Voltage supply In
4 Electrical connection
Inputs/outputsGalvanically isolated from each other
Relay outputsYes
Logic outputs DC 0/15 VYes
Solid state relay outputsYes
Open-collector outputsOutputs of different expansion slots
Analog outputsYes
Digital inputs DC 0/24 VInputs of different modules (motherboard, expansion slots)
Analog inputsYes
TIP!
Signals to digital inputs belonging to one module (motherboard or expansion slot) must have
the same ground reference to avoid undefined signal levels.
29
4 Electrical connection
4.3Connection diagram
CAUTION!
At maximum load, the temperature may exceed 60 °C at the terminals.
As a result the insulation of the cable may be damaged.
The cable must be heat resistant up to at least 80 °C.
CAUTION!
The controller module configuration does not necessarily correspond to the intended application during initial startup (e.g. "Independent controller" operating mode active).
This may result in undefined plant behavior.
Therefore, where possible during startup, no actuators should be connected and load current
circuits should be isolated. The plant installer is essentially responsible for the startup process.
30
Loading...
+ 118 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.