Data Sheet 603051
Surface-mounting thermostats, type series AMTHF
with 2, 3 or 4 1-pole snap switches
Special features
Protection rating IP 54
tested as per DIN EN 14597 (replacement for DIN 3440)
Type AMTHFs-13
Brief description
Add-on thermostats are used to control and monitor thermal processes. The devices of type series AMTHF are available with 2, 3 or 4 switching stages as temperature controllers (TR) and temperature monitors (TW). The sequential gap in Kelvin for the individual circuit stages is fac­tory-set fixed as per customer request. Add-on thermostats operate according to the fluid ex­pansion principle, a microswitch is used as an electrical switching element.
Page 1/8
Switching function
Temperature controller (TR) and temperature monitor (TW)
If the temperature exceeds the setpoint value set on the temperature probe, the microswitch will be tripped by the transmission mechanics and the current circuit opened or closed. The mi­croswitch is reset to its original status once the setpoint value set is gone below (by the hyster­esis).
Types
Types
with rigid shaft with capillary
AMTHFs-13 AMTHFf-13 TR 2
AMTHFs-133 AMTHFf-133 TR 3
AMTHFs-1333 AMTHFf-1333 TR 4
AMTHFs-23 AMTHFf-23 TW 2
AMTHFs-233 AMTHFf-233 TW 3
AMTHFs-2333 AMTHFf-2333 TW 4
Switching function Circuit stages
Type AMTHFf-13
2013-03-07/00439872
Data Sheet 603051
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road East Syracuse, NY 13057, USA Phone: 315-437-5866
1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com
Technical data
Control range and probe table — fluid-filled
Control /
limit value
ranges
Hysteresis
%
°C
1
-20 to +040
2.5 5 7
1
0 to +050
+20 to +090
0 to +100
2.5 5 7
1
2.5 5 7
1
2.5 5 7
1
+30 to +110
0 to +150
2.5 5 7
1
2.5 5
0 to +200
+50 to +200
+50 to +250
+50 to +300
1
Values in brackets only on request taking the operating statuses and the desired capillary length into consideration
1
2.5 1
2.5 1
2.5 5
1
2.5
max.
probe
temperature
°C
+ 050 + 050 + 095 + 100
+ 060 + 060 + 105 + 110
+ 115 + 115 + 140 + 175
+ 125 + 125 + 165 + 200
+ 135 + 135 + 170 + 200
+ 173 + 173 + 200
max. switch head temperature
°C
+050 +050
+050 (80) +050 (80)
+060 +060
+060 (80) +060 (80)
+080 +080 +080 +080
+080 +080 +080 +080
+080 +080 +080 +0
80
+080 +080 +080
1
1
1
1
+ 230 +080 1
+ 230 +080 1
+ 228 + 228 + 300
+ 345 + 345
+080 +080 +080
+080 +080
possible capillary
lengths in
m
5
3 3 5 5
1 1 5 5
2 2 5 5
2 2 5 5
1
1 1 5
2
max.
sequential
gap
K
5 8 25 50
5 10 25 50
7 14 35 70
10 20 50 100
8 16 40 80
15 30 75
20 40
15 30
20 40 100
25 50
Page 2/8
Probe length dimension "L" in mm,
Probe Ø "d" in mm
Ø"6"=Standard
ø 6 ø 8
245 245 138 103
283 283 159 117
210 210 121 91
157 157 94 73
188 188 110 84
113 113 72
145 145 91 73
165 165 101 80
127 127 82 67
100 100 68 58
116 116 76 63
78 78 57
113 78
139 92
105 105 64
70 70 49
87 61
Control range and probe table — gas-filled
Control /
limit value
ranges
°C
+20 to +400
+20 to +500
Hysteresis
%
6 10
3/5 6 10
max.
probe
temperature
°C
+ 460 + 500
+ 530 + 575 + 575
max. switch head temperature
°C
+080 +080
+080 +080 +080
possible capillary
lengths in
m
5
1 5 5
max.
sequential
gap
K
75 200
48 95 250
Probe length dimension "L" in mm,
Probe Ø "d" in mm
Ø"6"=Standard
ø 6 ø 8
237 127
278 176 95
Capillary and temperature probe
Type Scale limit value Capillary Temperature probe Remarks
AMTHF
up to 200 °C
up to 350 °C
up to 500 °C
up to 350 °C
Copper (Cu), ø 1.5mm
Material No. Cu-DHP
Copper (Cu), ø 1.5mm
Material No. Cu-DHP
Stainless steel (CrNi), ø 1.5mm
Stainless steel (CrNi), ø 1.5mm
Copper (Cu), Material No. Cu-DHP
Stainless steel (CrNi), Material No. 1.4571
Stainless steel (CrNi), Material No. 1.4571
Stainless steel (CrNi), Material No. 1.4571
hard soldered
hard soldered
welded
welded
against surcharge
Capillary length 1000 mm, max. 5000 mm as standard min. bending radius of the
capillary
Note: If the max. admissible temperature is not reached on the probe, capillary and switching head,
2013-03-07/00439872
it is possible to increase the capillary length, where it is limited to 1, 2 or 3 m as per the control range and probe table, on request. Please specify the temperature values occurring on the thermostats.
5mm
137 81
158 106 65
Data Sheet 603051
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road East Syracuse, NY 13057, USA Phone: 315-437-5866
1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com
Electrical data
Switching element 2, 3 or 4 1-pole snap switch
Microswitch with change-over contact
max. contact rating Hysteresis
switching function
2.5%, 5%, 6%, 7%, 10%
TR, TW
TR, TW
1%, 3%
N/C contact,
terminal 2
AC 230 V +10%,
16 (3) A, cos ϕ = 1(0.6)
DC 230 V +10%, 0.25A
AC 230 V +10%, 6 (2) A, cos ϕ = 1(0.6)
DC 230 V +10%, 0.25A
N/O contact,
AC 230 V +10%, 8 (1.5) A, cos ϕ = 1(0.6) DC 230 V +10%, 0.25A
Contact reliability To ensure high switching reliability, we recommend a minimum load of:
AC / DC = 24 V, 20 mA
Rating surge voltage
1500 V (via the switching contacts 400 V)
Overvoltage category II
Required fuse rating see max. contact rating
Electrical connection
Screw connection up to 2.5 mm
2
cable cross section
Operating data
Hysteresis in % of the control / limit value range
Switching function with fluid-filled measuring system
Rated value Possible process value
TR, TW 2.5 2.5 max. 3.5 serial
55 max. 6on request 77 max. 8on request 11 max. 2Surcharge
with gas-filled measuring system 55 max.11serial 6 6 max. 14 on request
10 10 max. 16 on request
3 2.5 max. 4 Surcharge
Sequential gap for multi-pin version
with hysteresis Sequential gap from the scale range Switching point accuracy
of the sequential gaps from
1%
2.5%
3%, 5%
6%, 7%, 10%
minimum maximum
1% 1% 2%
as per
control range table
3%
The sequential gap is specified in K in relation to the set point value of contact deck I.
Prefix - = switching prior to reaching the set point value,
Prefix + = switching after reaching the set point value.
Enter "0" for the sequential gap for a simultaneously switching version.
Switching point accuracy in % of the control/limit value range
medium ambient temperature influence
Switching function
TR 1%, 2.5%
TW 1%, 2.5%
When the ambient temperature on the switch head and/or the capillary deviates
from the calibration temperature +22 °C, a switch point offset occurs.
fluid-filled gas-filled
5% 7%
5% 7%
Higher ambient temperatures = lower switching point
Hysteresis
- -
3%, 5%,
6%, 10%
- -
3%, 5%,
6%, 10%
in the upper third of the
Lower ambient temperature = higher switching point
For temperatures with scale limit value / limit value
< 200 °C ÷ 200 °C +350 °C ÷ 400 °C +500 °C
TR, TW TR, TW TR, TW
Hysteresis in %
1/2.5 5 7 1/2.5 5 3/5 6 10
Ambient temperature influence on the switch head in %/K
0.15 0.26 0.34 0.12 0.21 0.12 0.17 0.24 Ambient temperature influence on the capillary in %/m
0.05 ·K·m 0.09 · K·m 0.04·K ·m 0.05 · K·m
2013-03-07/00439872
If the operating temperature on the switch head deviates essentially from the ambient calibration temperature +22 °C,
this can be taken into account on request during adjustment against surcharge.
Page 3/8
terminal 4
the scale range
1%1%
<2% <3%
scale or limit value
± 1.5% ± 3.0% ± 4.0%
+0 / -3% +0 / -6% +0 / -8%