Installer: Leave installation instructions with the homeowner.
Homeowner: Keep installation instructions for future reference.
IMPORTANT :
Installateur : Remettre les instructions d'installation au propriétaire.
Propriétaire : Conserver les instructions d'installation pour référence ultérieure.
W10526078A
30" (76.2 CM) SLIDE-IN DUAL FUEL
DOWNDRAFT RANGES
INSTRUCTIONS POUR L’INSTALLATION DES CUISINIÈRES
À BI-COMBUSTIBLE ENCASTRABLES À ÉVACUATION
DESCENDANTE DE 30" (76,2 CM)
Table of ContentsTable des matières
RANGE SAFETY .............................................................................2
CONVERSIONS POUR CHANGEMENT DE GAZ.......................45
Conversion pour l'alimentation au propane ..............................45
Conversion pour l'alimentation au gaz naturel ..........................47
RANGE SAFETY
You can be killed or seriously injured if you don't immediately
You
can be killed or seriously injured if you don't
follow
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
follow instructions.
instructions.
DANGER
WARNING
WARNING: If the information in this manual is not followed exactly, a fire or explosion
may result causing property damage, personal injury or death.
– Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance.
– WHAT TO DO IF YOU SMELL GAS:
•
Do not try to light any appliance.
•
Do not touch any electrical switch.
•
Do not use any phone in your building.
•
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
•
If you cannot reach your gas supplier, call the fire department.
– Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
WARNING: Gas leaks cannot always be detected by smell.
Gas suppliers recommend that you use a gas detector approved by UL or CSA.
For more information, contact your gas supplier.
If a gas leak is detected, follow the “What to do if you smell gas” instructions.
IMPORTANT: Do not install a ventilation system that blows air downward toward this gas cooking appliance. This type of
ventilation system may cause ignition and combustion problems with this gas cooking appliance resulting in personal injury or
unintended operation.
2
In the State of Massachusetts, the following installation instructions apply:
■ Installations and repairs must be performed by a qualified or licensed contractor, plumber, or gasfitter qualified or licensed by
the State of Massachusetts.
■ If using a ball valve, it shall be a T-handle type.
■ A flexible gas connector, when used, must not exceed 3 feet.
Tip Over Hazard
A child or adult can tip the range and be killed.
Install anti-tip bracket to floor or wall per installation instructions.
Slide range back so rear range foot is engaged in the slot of the anti-tip bracket.
Re-engage anti-tip bracket if range is moved.
Do not operate range without anti-tip bracket installed and engaged.
Failure to follow these instructions can result in death or serious burns to children and adults.
To verify the anti-tip bracket is installed and engaged:
• Slide range forward.
• Look for the anti-tip bracket securely attached to floor or wall.
• Slide range back so rear range foot is under anti-tip bracket.
• See installation instructions for details.
WARNING
Anti-Tip
Bracket
Range Foot
3
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed here.
Tool s nee ded
■ Tape measure
■ Phillips screwdriver
■ Flat-blade screwdriver
■ ¹⁄₈" flat-blade screwdriver
■ Level
■ Hand or electric drill
■ Wrench or pliers
■ Pipe wrench
■ ¹⁵⁄₁₆" combination wrench
■ ¹⁄₈" (3.2 mm) drill bit (for
wood floors)
■ Marker or pencil
Parts supplied
Check that all parts are included.
■ LP/Natural Gas Conversion Kit (taped behind access panel)
■ 2 - Burner caps
■ 3 - Burner grates
■ 1 - Air grille
■ 3 - Oven racks
■ 1 - Metal ground strap (for 3-wire connection)
■ Blower motor
■ 2 - vent clamps
■ Flexible vent
■ Flow tester card
■ Blower location template
■ 4 - #8 x ¾" screws (for mounting blower motor bracket)
■ Anti-tip bracket (taped to package containing literature in
oven cavity)
Anti-tip bracket must be securely mounted to the back wall or
floor. Thickness of flooring may require longer screws to
anchor bracket to subfloor. Longer screws are available from
your local hardware store.
Parts needed
■ One of the following Jenn-Air wall caps:
®
Jenn-Air
Order Part Number A405
Jenn-Air
Order Part Number A406
Jenn-Air
Order Part Number A403
To order, see the “Assistance or Service” section of the Use
and Care Guide.
■ Metal ducting
■ Vent clamps
5" (12.7 cm) Round Surface Wall Cap Damper
®
6" (15.2 cm) Round Surface Wall Cap Damper
®
3¼" x 10" (8.3 x 25.4 cm) Surface Wall Cap Damper
■ Pipe-joint compound
resistant to LP gas
■ ³⁄₁₆" (4.8 mm) carbide-tipped
masonry drill bit (for
concrete/ceramic floors)
■ Noncorrosive leak-detection
solution
For LP/Natural Gas
Conversions
■ ½" combination wrench
■ ¼" (6 mm) nut driver
■ ⁹⁄₃₂" (7 mm) nut driver
■ Masking tape
■ 2 - 2" x 4" x 8¾" (5.0 x 10.2 x 22.2 cm) wood spacers (for left
or right side venting)
■ Concrete anchors (for concrete floor mounting)
Check local codes and consult gas supplier. Check existing gas
supply and electrical supply. See “Electrical Requirements” and
“Gas Supply Requirements” sections.
Location Requirements
IMPORTANT: Observe all governing codes and ordinances. Do
not obstruct flow of combustion and ventilation air.
■ It is the installer’s responsibility to comply with installation
clearances specified on the model/serial rating plate. The
model/serial rating plate is located behind the storage drawer
on the right-hand side of the oven frame or on the right-hand
side of the bottom oven frame, depending on your model.
■
The range should be located for convenient use in the kitchen.
■ Recessed installations must provide complete enclosure of
the sides and rear of the range.
■ To eliminate the risk of burns or fire by reaching over heated
surface units, cabinet storage space located above the
surface units should be avoided. If cabinet storage is to be
provided, the risk can be reduced by installing a range hood
or microwave hood combination that projects horizontally a
minimum of 5" (12.7 cm) beyond the bottom of the cabinets.
■ All openings in the wall or floor where range is to be installed
must be sealed.
■ Cabinet opening dimensions that are shown must be used.
Given dimensions are minimum clearances.
■ The floor anti-tip bracket must be installed. To install the anti-
tip bracket shipped with the range, see “Install Anti-Tip
Bracket” section.
■ Grounded electrical supply is required. See “Electrical
Requirements” section.
■ Proper gas supply connection must be available. See “Gas
Supply Requirements” section.
■ Contact a qualified floor covering installer to check that the
floor covering can withstand at least 200°F (93°C).
■ Use an insulated pad or ¼" (0.64 cm) plywood under range if
installing range over carpeting.
IMPORTANT: To avoid damage to your cabinets, check with your
builder or cabinet supplier to make sure that the materials used
will not discolor, delaminate or sustain other damage. This oven
has been designed in accordance with the requirements of UL
and CSA International and complies with the maximum allowable
wood cabinet temperatures of 194°F (90°C).
Mobile Home - Additional Installation Requirements
The installation of this range must conform to the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile Home Construction
and Safety, Title 24, HUD Part 280). When such standard is not
applicable, use the Standard for Manufactured Home
Installations, ANSI A225.1/NFPA 501A or with local codes.
In Canada, the installation of this range must conform with the
current standards CAN/CSA-A240-latest edition, or with local
codes.
Mobile home installations require:
■ When this range is installed in a mobile home, it must be
secured to the floor during transit. Any method of securing
the range is adequate as long as it conforms to the standards
listed above.
4
Product Dimensions
D
C
E
A
F
G
D
C
B
A
G
F
E
D
C
B
A
D
E
F
G
H
B
I
I
C
Model JDS9860
*Range can be raised approximately 1" (2.5 cm) by adjusting
the leveling legs.
**When installed in a 24" (61.0 cm) base cabinet with
25" (63.5 cm) countertop; front of oven door protrudes
5" (12.7 cm) beyond 24" (61.0 cm) base cabinet.
Cabinet Dimensions
Cabinet opening dimensions shown are for 25" (64.0 cm)
countertop depth, 24" (61.0 cm) base cabinet depth and
36" (91.4 cm) countertop height.
Range may be installed with zero clearance to combustible
construction at the rear and on the sides below the cooktop.
A. 30³⁄₄" (78.1 cm)
B. 23" (58.4 cm) countertop notch to rear of
cooktop
C. Gas information plate (located on the
right-hand side of the bottom oven frame)
D. Model/serial number plate (located on the
right-hand side of the bottom oven frame)
Model JDS9865
NOTE: Cooktop shown may differ from your model.
E. 29" (73.4 cm) from
handle to back of range**
F. 2 9 ⁷⁄₈" (75.9 cm)*
G. 35
³⁄₄
" (90.8 cm) height to
underside of cooktop
edge with leveling legs
screwed all the way in*
A. 13" (33.0 cm) upper cabinet depth
B. 30" (76.2 cm) min. opening width
C. For minimum clearance to the top of the cooktop, see NOTE.
D. 23¹⁄₄" (59.1 cm) opening depth
E. 30" (76.2 cm) min. opening width
F. Electrical and gas supply - 5½" (14.0 cm) min. from either cabinet,
10" (25.4 cm) max. from floor. Nothing located in shaded area can
extend more than 2¼" (5.7 cm) from back wall or range will not slide
all the way back. Grounded outlet must be flush mounted.
G. Cabinet door or hinge should not extend into cutout.
H. 18" (45.7 cm)
I. 3" (7.6 cm) min. clearance from both sides of the range to the side
wall or other combustible material.
NOTE: 24" (61.0 cm) minimum when bottom of wood or metal
cabinet is shielded by not less than ¹⁄₄" (0.64 cm) flame retardant
millboard covered with not less than No. 28 MSG sheet steel,
0.015" (0.4 mm) stainless steel, 0.024" (0.6 mm) aluminum or
0.020" (0.5 mm) copper.
30" (76.2 cm) minimum clearance between the top of the cooking
platform and the bottom of an uncovered wood or metal cabinet.
A.
30⁷⁄₈
" (78.4 cm)
B. 35³⁄₄" (90.8 cm) height to
underside of cooktop edge
with leveling legs screwed all
the way in*
C. Model/serial number plate
(located behind the storage
drawer on the right-hand side
of the oven frame)
D. 29⁷⁄₈" (75.9 cm)
E. Gas information plate (located
behind the storage drawer on the
left-hand side of the oven frame)
F. 29" (73.7 cm) from handle to
back of range**
G. 27" (68.6 cm) from handle to rear
of cooktop
5
Venting Requirements
A
B
A
B
A
B
IMPORTANT: This range must be exhausted outdoors. See
“Venting Methods” section.
■ Do not terminate the vent system in an attic or other enclosed
area.
■ Use a Jenn-Air wall cap.
■ Vent system must terminate to the outside.
■ Use only a 6" (15.2 cm) round metal vent or a 3¼ x 10"
(8.3 cm x 25.4 cm) rectangular vent, except as follows:
5" (12.7 cm) round metal vent must be used for venting
lengths of 10 ft (3.0 m) or less.
■ Rigid metal vent is recommended. For best performance, do
not use plastic or metal foil vent.
■ Before making cutouts, make sure there is proper clearance
within the wall or floor for the exhaust vent.
■ Do not cut a joist or stud unless absolutely necessary. If a
joist or stud must be cut, then a supporting frame must be
constructed.
■ The size of the vent should be uniform.
■ The vent system must have a damper. If roof or wall cap has a
damper, do not use damper supplied with the range hood.
■ Use vent clamps to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening around the
cap.
■ Determine which venting method is best for your application.
For Best Performance:
■ Use 26-gauge minimum galvanized or 25-gauge minimum
aluminum metal vent. Poor quality pipe fittings can reduce
airflow. Flexible metal vent is not recommended.
NOTE: Local codes may require a heavier gauge material.
■ Metal duct may be reduced to 30-gauge galvanized steel or
26-gauge aluminized steel if allowed by local codes. This
reduction is based on information in the International
Residential Codes Section M1601.1 (2006 edition).
■ Do not install 2 elbows together.
■ Use no more than three 90° elbows.
■ If an elbow is used, install it as far away as possible from the
hood’s vent motor exhaust opening.
■ Make sure there is a minimum of 18" (45.7 cm) of straight
vent between the elbows if more than one elbow is used.
■ Elbows too close together can cause excess turbulence that
reduces airflow.
■ Do not use a 5" (12.7 cm) elbow in a 6" (15.2 cm) or 3¹⁄₄" x 10"
(8.3 x 25.4 cm) system.
■ Do not reduce to a 5" (12.7 cm) system after using a
6" (15.2 cm) or 3¹⁄₄" x 10" (8.3 x 25.4 cm) fittings.
■ Avoid forming handmade crimps. Handmade crimps may
restrict airflow.
■ Use a Jenn-Air vent cap for proper performance. If an
alternate wall or roof cap is used, be certain the cap size is
not reduced and that it has a backdraft damper.
■ Use vent clamps to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening around the
cap.
The length of vent system and number of elbows should be kept
to a minimum to provide efficient performance.
The maximum equivalent length of the vent system is
60 ft (18.3 m). For altitudes above 4,500 ft (1272 m), reduce
recommended vent run by 20% for best performance.
Cold Weather Installations
An additional backdraft damper should be installed to minimize
backward cold air flow and a thermal break installed to minimize
conduction of outside temperatures as part of the vent system.
The damper should be on the cold air side of the thermal break.
Makeup Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale. Consult
your HVAC professional for specific requirements in your area.
Venting Methods
Common venting methods are shown for a downdraft range. The
downdraft range may be vented through the wall or floor.
Wall Venting
A. Wall cap
B. 6" (15.2 cm) round roof venting
Floor Venting
Venting Between Floor Joists
A. Wall cap
B. 6" (15.2 cm) round roof venting
Left or Right Side Venting
Venting Behind Cabinet Kickplate
A. Wall cap
B. 6" (15.2 cm) round roof venting
6
Concrete Slab Installations - Exhaust Through Wall
A
B
C
D
E
F
G
H
J
K
I
L
A
B
C
D
E
F
G
I
J
H
K
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent Piece6" (15.2 cm) Round
A. Wall cap
B. 6" (15.2 cm) round metal vent
C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. Concrete slab
F. 6" (15.2 cm) round PVC sewer pipe
G. 6" (15.2 cm) round 90° PVC sewer pipe elbow
H. Tightly pack gravel or sand completely around pipe.
I. 30 ft (9.1 m) max.
J. 6" (15.2 cm) round 90° PVC sewer pipe elbow
K. 6" (15.2 cm) round PVC coupling
L. 12" (30.5 cm) minimum
Concrete Slab Installations - Exhaust Through Window Well
IMPORTANT: Window well installation for electric models only.
45° elbow2.5 ft
(0.8 m)
90° elbow5.0 ft
(1.5 m)
6" (15.2 cm)
wall cap
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) transition
6" (15.2 cm) to 3¹⁄₄" x 10"
(8.3 cm x 25.4 cm) transition
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) 90° elbow
0.0 ft
(0.0 m)
4.5 ft
(1.4 m)
1 ft
(0.3 m)
5.0 ft
(1.5 m)
transition
A. Wall cap
B. 12" (30.5 cm) minimum
C. Concrete slab
D. 6" (15.2 cm) round PVC sewer pipe
E. 6" (15.2 cm) round PVC sewer pipe
F. 6" (15.2 cm) round 90° PVC sewer pipe elbow
G. Tightly pack gravel or sand completely around pipe.
H. 42 ft (12.8 m) max.
I. 6" (15.2 cm) round PVC coupling
J. 6" (15.2 cm) minimum
K. Window well
Calculating Vent System Length
IMPORTANT: This range is rated at 60 ft (18.3 m) of straight duct.
Low range is up to 30 ft (9.1 m); high range is 31 ft (9.4 m) to
60 ft (18.3 m).
If equivalent duct length exceeds 30 ft (9.1 m), the blower must
be converted to high range.
■ Do not convert to high range for shorter lengths. This will
cause excessive noise, conditioned air loss and affect the
flame pattern on gas ranges.
■ To convert blower for high range installations, see the
“Install Downdraft System” section.
6" (15.2 cm) to 3¹⁄₄" x 10"
(8.3 cm x 25.4 cm) 90° elbow
transition
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
90° elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
flat elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
wall cap
5.0 ft
(1.5 m)
5.0 ft
(1.5 m)
12.0 ft
(3.7 m)
0.0 ft
(0.0 m)
7
90˚ elbow
2 ft
(0.6 m)
6 ft (1.8 m)
wall cap
Example vent system
Maximum length= 60 ft (18.3 m)
1- 90° elbow= 5 ft (1.5 m)
8 ft (2.4 m) straight= 8 ft (2.4 m)
1 - wall cap= 0 ft (0 m)
System length= 13 ft (3.9 m)
NOTE: For external venting, flexible vent is not recommended.
Flexible vent creates back pressure and air turbulence that
greatly reduce performance.
Electrical Requirements - U.S.A. Only
The electrical connection to this range is designed only for use
with a flexible power cord. All ranges are shipped with a specially
designed 4-wire power supply cord. This cord should be used on
all new branch circuits, mobile homes and when local codes
prohibit grounding though the neutral. For a 3-wire power supply
cord replacement, service kit Part Number 74011285 must be
used.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path and wire gauge are in accordance with local
codes.
Do not use an extension cord.
Be sure that the electrical connection and wire size are adequate
and in conformance with the National Electrical Code, ANSI/
NFPA 70-latest edition and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
WARNING: Improper connection of the equipment-grounding
conductor can result in a risk of electric shock. Check with a
qualified electrician or service technician if you are in doubt as to
whether the appliance is properly grounded. Do not modify the
power supply cord plug. If it will not fit the outlet, have a proper
outlet installed by a qualified electrician.
Electrical Connection
To properly install your range, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
■ Range must be connected to the proper electrical voltage
and frequency as specified on the model/serial number rating
plate. The model/serial rating plate is located behind the
storage or warming drawer on the right-hand side of the oven
frame or on the right-hand side of the bottom oven frame,
depending on your model. Refer to the figures in the “Product
Dimensions” section of the “Location Requirements” section.
■ This range is manufactured with a 4-wire 40-amp power cord.
For a 3-wire connection order UL listed power cord Part
Number 74011285.
8
Range Rating*Specified Rating of
Power Supply Cord Kit
and Circuit Protection
120/240 Volts120/208 VoltsAmps
8.8 - 16.5 KW
16.6 - 22.5 KW
7.8 - 12.5 KW
12.6 - 18.5 KW
40 or 50**
50
*The NEC calculated load is less than the total connected load
listed on the model/serial rating plate.
**If connecting to a 50-amp circuit, use a 50-amp rated cord with
kit. For 50-amp rated cord kits, use kits that specify use with a
nominal 1³⁄₈" (34.9 mm) diameter connection opening.
■ A circuit breaker is recommended.
■ Wire sizes and connections must conform with the rating of
the range.
■ The wiring diagram is located at the back of the warming
drawer.
If connecting to a 4-wire system:
The green ground wire of the 4-wire power supply cord must be
connected to the cabinet. See “Electrical Connection” section.
Grounding through the neutral conductor is prohibited for new
branch-circuit installations (1996 NEC); mobile homes; and
recreational vehicles, or an area where local codes prohibit
grounding through the neutral conductor.
When a 4-wire receptacle of NEMA Type 14-50R is used, a
matching UL listed, 4-wire, 250-volt, 40- or 50-amp, range power
supply cord (pigtail) must be used. This cord contains 4 copper
conductors with ring terminals or open-end spade terminals with
upturned ends, terminating in a NEMA Type 14-50P plug on the
supply end.
The fourth (grounding) conductor must be identified by a green or
green/yellow cover and the neutral conductor by a white cover.
Cord should be Type SRD or SRDT with a UL listed strain relief
and be at least 4 ft (1.22 m) long.
4-wire receptacle (14-50R)
The minimum conductor sized for the copper 4-wire power
cord are:
40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding
If connecting to a 3-wire system:
Local codes may permit the use of a UL listed, 3-wire, 250-volt,
40- or 50-amp range power supply cord (pigtail). Order UL listed
3-wire power cord Part Number 74011285. This cord contains 3
copper conductors with ring terminals or open-end spade
terminals with upturned ends, terminating in a NEMA Type 10-50P
plug on the supply end. Connectors on the appliance end must be
provided at the point the power supply cord enters the appliance.
This uses a 3-wire receptacle of NEMA Type 10-50R. For a 3-wire
power supply cord replacement, service kit Part Number
74011285 must be used.
3-wire receptacle (10-50R)
Electrical Requirements - Canada Only
WARNING
Electrical Shock Hazard
Electrically ground range.
Failure to do so can result in death, fire, or
electrical shock.
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a qualified person make sure
gas pressure does not exceed 14" (36 cm) water
column.
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
†®TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path is adequate and wire gauge are in accordance
with local codes.
Be sure that the electrical connection and wire size are adequate
and in conformance with CSA Standard C22.1, Canadian
Electrical Code, Part 1 - latest edition, and all local codes and
ordinances.
A copy of the above code standards can be obtained from:
Canadian Standards Association
178 Rexdale Blvd.
Toronto, ON M9W 1R3 CANADA
■ Check with a qualified electrical installer if you are not sure
the range is properly grounded.
Range Rating*Rating of
Power
Supply Cord
Circuit
Protection
Gas Supply Requirements
Observe all governing codes and ordinances.
IMPORTANT: This installation must conform with all local codes
and ordinances. In the absence of local codes, installation must
conform with American National Standard, National Fuel Gas
Code ANSI Z223.1 - latest edition or CAN/CGA B149 - latest
edition.
IMPORTANT: Leak testing of the range must be conducted
according to the manufacturer’s instructions.
120/240 Volts120/208 VoltsAmpsAmps
8.8 - 16.5 KW
16.6 - 22.5 KW
*The NEC calculated load is less than the total connected load
listed on the model/serial rating plate.
■ A time-delay fuse or circuit breaker is recommended.
■ This range is equipped with a CSA International Certified
Power Cord intended to be plugged into a standard 14-50R
wall receptacle. Be sure the wall receptacle is within reach of
range’s final location.
7.8 - 12.5 KW
12.6 - 18.5 KW4050
40 or 50
50
■ Do not use an extension cord.
Type of G as
Natural gas:
This range is design-certified by CSA International for use with
Natural gas or, after proper conversion, for use with LP gas.
■ This range is factory set for use with Natural gas. See “Gas
Conversions” section. The gas information plate (located
behind the warming or storage drawer on the side of the oven
frame or on the side of the bottom oven frame, depending on
your model) has information on the types of gas that can be
used. If the types of gas listed do not include the type of gas
available, check with the local gas supplier.
LP gas conversion:
Conversion must be done by a qualified service technician.
No attempt shall be made to convert the appliance from the gas
specified on the model/serial rating plate for use with a different
gas without consulting the serving gas supplier. See “Gas
Conversions” section.
Gas Supply Line
■ Provide a gas supply line of ¾" (1.9 cm) rigid pipe to the
range location. A smaller size pipe on longer runs may result
in insufficient gas supply. With LP gas, piping or tubing size
can be ½" (1.3 cm) minimum. Usually, LP gas suppliers
determine the size and materials used in the system.
NOTE: Pipe-joint compounds that resist the action of LP gas
must be used. Do not use TEFLON
®†
tape.
9
Flexible metal appliance connector:
A
B
C
30"
(76.2 cm)
30 ¾"
(78.1 cm)
³⁄₈"
(1.0 cm)
■ If local codes permit, a new CSA design-certified,
4 to 5 ft (122 to 152.4 cm) long, ½" (1.3 cm) or
¾" (1.9 cm) I.D., flexible metal appliance connector may
be used for connecting range to the gas supply line.
Burner Input Requirements
Input ratings shown on the model/serial rating plate are for
elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at a
rate of 4% for each 1,000 ft (304.8 m) above sea level (not
applicable for Canada).
■ A ½" (1.3 cm) male pipe thread is needed for connection
to the female pipe threads of the inlet to the appliance
pressure regulator.
■ Do not kink or damage the flexible metal tubing when
moving the range.
Rigid pipe connection:
The rigid pipe connection requires a combination of pipe
fittings to obtain an in-line connection to the range. The rigid
pipe must be level with the range connection. All strains must
be removed from the supply and fuel lines so range will be
level and in line.
■ Must include a shutoff valve:
The supply line must be equipped with a manual shutoff
valve. This valve should be located in the same room but
external to the range opening, such as an adjacent cabinet. It
should be in a location that allows ease of opening and
closing. Do not block access to shutoff valve. The valve is for
turning on or shutting off gas to the range.
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least
1" water column pressure above the manifold pressure shown on
the model/serial rating plate.
Line pressure testing above ½ psi gauge (14" WCP)
The range and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of ½ psi (3.5 kPa).
Line pressure testing at ½ psi gauge (14" WCP) or lower
The range must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than ½ psi (3.5 kPa).
Countertop Preparation
(for Slide-in Ranges Only)
The cooktop sides of the slide-in range fit over the cutout edge of
your countertop.
If you have a square finish (flat) countertop and the opening width
is 30" (76.2 cm), no countertop preparation is required.
Formed front-edged countertops must have molded edge
shaved flat ³⁄₈" (1.0 cm) from each front corner of opening.
Tile countertops may need trim cut back ³⁄₈" (1.0 cm) from each
front corner and/or rounded edge flattened.
A. Gas supply line
B. Shutoff valve “open” position
C. To range
Gas Pressure Regulator
The gas pressure regulator supplied with this range must be
used. The inlet pressure to the regulator should be as follows for
proper operation:
Natural gas:
Minimum pressure: 5" WCP
Maximum pressure: 14" WCP
LP gas:
Minimum pressure: 11" WCP
Maximum pressure: 14" WCP
Contact local gas supplier if you are not sure about the inlet
pressure.
If countertop opening width is greater than 30" (76.2 cm), adjust
the ³⁄₈" (1.0 cm) dimension.
Countertop must be level. Place level on countertop, first side to
side, then front to back. If countertop is not level, range will not
be level. Range must be level for satisfactory baking conditions.
10
INSTALLATION INSTRUCTIONS
WARNING
Excessive Weight Hazard
Use two or more people to move and install range.
Failure to do so can result in back or other injury.
WARNING
Tip Over Hazard
A child or adult can tip the range and be killed.
Install anti-tip bracket to floor or wall per installation
instructions.
Slide range back so rear range foot is engaged in the
slot of the anti-tip bracket.
Re-engage anti-tip bracket if range is moved.
Do not operate range without anti-tip bracket installed
and engaged.
Failure to follow these instructions can result in death
or serious burns to children and adults.
A
B
Unpack Range
1. Remove shipping materials, tape and film from the range.
Keep cardboard bottom under range.
2. Remove oven racks and parts package from inside oven.
3. To remove cardboard bottom, place range on its back, take
4 cardboard corners from the carton. Stack one cardboard
corner on top of another. Repeat with the other 2 corners.
Place them lengthwise on the floor behind the range to
support the range when it is laid on its back.
4. Using 2 or more people, firmly grasp the range and gently lay
it on its back on the cardboard corners.
5. Pull cardboard bottom firmly to remove.
6. Use an adjustable wrench to loosen the leveling legs.
7. Place cardboard or hardboard in front of range. Using 2 or
more people, stand range back up onto cardboard or
hardboard.
Adjust Leveling Legs
1. If range height adjustment is necessary, use a wrench or
pliers to loosen the 4 leveling legs.
This may be done with the range on its back or with the range
supported on 2 legs after the range has been placed back to
a standing position.
NOTE: To place range back up into a standing position, put a
sheet of cardboard or hardboard in front of range. Using 2 or
more people, stand range back up onto the cardboard or
hardboard.
2. Adjust the leveling legs to the correct height. Leveling legs
can be loosened to add up to a maximum of 1" (2.5 cm). A
minimum of ³⁄₁₆" (5 mm) is needed to engage the anti-tip
bracket.
NOTE: If height adjustment is made when range is standing,
tilt the range back to adjust the front legs, then tilt forward to
adjust the rear legs.
3. When the range is at the correct height, check that there is
adequate clearance under the range for the anti-tip bracket.
Before sliding range into its final location, check that the antitip bracket will slide under the range and onto the rear
leveling leg prior to anti-tip bracket installation.
Install Anti-Tip Bracket
1. Remove the anti-tip bracket that is taped to the package
containing literature.
2. Determine which mounting method to use: floor or wall.
If you have a stone or masonry floor, you can use the wall
mounting method.
3. Determine and mark centerline of the cutout space. The
mounting bracket can be installed on either the left side or
right side of the cutout. Position mounting bracket in cutout
so that right (or left) edge of the bracket is 14¹⁄₄" (36.2 cm)
from centerline, as shown.
A. Centerline
B. 14¹⁄₄" (36.2 cm)
11
4. Drill two ¹⁄₈" (3 mm) holes that correspond to the bracket
A
B
A
B
A
B
A
B
A
A
B
C
D
E
holes of the determined mounting method. See the following
illustrations.
Floor MountingWall Mounting
Rear Wall Venting
1. Mark the wall at the center of the cabinet opening.
2. Check for obstructions before marking the vent hole location.
Mark a horizontal line 8³⁄₁₆" (20.8 cm) from the floor. Mark a
vertical line up to a maximum of 2¼" (7.9 cm) from the right
side of the cabinet centerline.
A. #12 x 1⁵⁄₈" screws
B. Anti-tip bracket
A. #12 x 1⁵⁄₈" screws
B. Anti-tip bracket
5. Using the Phillips screwdriver, mount anti-tip bracket to the
wall or floor with the two #12 x 1⁵⁄₈" screws provided.
Install Downdraft System
Determine Equivalent Length of Vent System
This range is equipped with a dual range blower. It is shipped
from the factory for Low Range installations. If vent system
equivalent length exceeds 30 ft (9.1 m), the downdraft blower
motor must be converted to High Range for best performance.
See “Calculating Vent System Length” section.
To Con v ert :
Gently remove the spring loaded Restricter Ring from the blower
inlet by pressing one of the 3 springs.
A. Maximum 2¼" (7.9 cm) from
the right of center
B. 8³⁄₁₆" (20.8 cm) from floor
3. Draw and cut a 6¼" (15.8 cm) diameter hole.
A. 6¼" (15.8 cm)
4. Position blower motor in cabinet opening. Connect vent
system to blower motor outlet using a vent clamp.
Top View
A. Restricter ring
B. Spring
Determine which venting method to use: floor, rear wall, or left or
right side venting. Go to the section for your type of venting.
12
A. 18¾" (47.6 cm) maximum from back
wall forward into cabinet opening
B. Inlet
C. Vent system
D. Vent clamp
E. Wall vent
5. Mount blower motor to the floor with 4 - #8 x ¾" hex head
A
B
A
B
C
D
E
F
A
B
screws provided.
Top View
NOTE: If the template is misplaced, the following
measurements can be used to determine the vent hole
location.
Top View
6. Go to the “Electrical Connection” section.
Floor Venting
1. Mark the floor at the center of the cabinet opening.
2. Position template on floor by matching the centerline of the
template to the centerline drawn on the floor and place
template 2¼" (5.7 cm) from the back wall.
3. Determine the correct position for the vent hole, depending
on obstructions (joists) in the floor.
The hole can be cut anywhere within the boundaries of the
larger hatched area.
The blower inlet must face the left side as shown on the
template.
Top View
A. 9" (22.8 cm)
B. 3¹⁄₈" (7.9 cm)
C. 6³⁄₈" (16.2 cm)
D. 2¼" (5.7 cm)
E. 12½" (31.7 cm)
F. 3½" (8.9 c m )
4. Draw and cut a 6¼" (15.8 cm) diameter hole.
5. Position blower motor in cabinet opening and mount blower
motor to the floor.
Top View
A. Inlet from range
B. Exhaust outlet
A. Inlet from range
B. Exhaust outlet
13
6. Connect vent system to blower motor outlet (option 1 shown)
A
B
C
D
A
B
A
A
B
A
A
with 4 - #8 x ¾" hex head screws provided.
3. Mark and cut a 14" x 11" (35.6 x 27.9 cm) opening in the floor
of the same cabinet as the vent hole opening.
Top View
A. Inlet
B. Vent clamp
C. Floor
D. Vent system
7. Go to the “Electrical Connection” section.
Left or Right Side Venting
1. Mark cabinet side for either a left or right side vent hole
location.
A. 31³⁄₁₆" (79.2 cm) to top of cabinet
B. 18" (45.7 cm) from back wall
2. Mark and cut a 5½" (13.9 cm) diameter hole in the desired
cabinet side.
A. 11" (27.9 cm) from front of cabinet
B. 14" (35.6 cm) from left side of cabinet
4. Remove 4 locknuts on the motor side of the blower and
remove the bracket.
View from Motor Side of Blower
A. Electrical connector
5. Lift and rotate the motor 180° to reposition the electrical
connection.
A. 5½" (13.9 cm) diameter hole
A. Electrical connector
6. Rotate bracket 180° and secure with 4 locknuts.
14
7. Remove the bracket from the other side of the blower motor,
A
B
C
D
D
A
B
C
rotate 180° and secure with 4 locknuts.
8. Position 2 wood spacers and mount them to the floor.
Top View
9. Mount blower motor to wood spacers using 4 - #8 x ¾" hex
head screws provided.
NOTE: Vent system will be connected after range has been
moved into it’s final location. “See Connect Range to
Downdraft System” section.
Top View
A. Wood spacers
B. Mounting bracket
C. Blower
10. Go to the “Electrical Connection” section.
A. 2" x 4" (5.0 x 10.2 cm) wood spacers
B. 2⁷⁄₈" (7.3 cm) from back wall to edge of wood spacer
C. 8¾" (22.2 cm)
D. 2⁵⁄₁₆" (5.8 cm) centerline of opening to wood spacer
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.