
TruPortal™ IP-based Single
Door Controller (IPSDC)
Quick Reference
en-US
Introduction
The TruPortal IP-based Single Door Controller (IPSDC) provides
distributed processing for the interface of access control readers,
digital inputs, and outputs to the TruPortall System Controller.
The IPSDC is pre-configured to use Power-over-Ethernet (PoE),
using electrical power from Ethernet cabling, but can also be
configured to use an auxiliary power supply.
Model Numbers
The IPSDC is available in the following configurations:
• TP-ADD-1DIP: TruPortal single-door base kit. Consists of a
TruPortal IPSDC, installed in a UL-listed enclosure.
• TP-ADD-1DIP-BRD: TruPortal IPSDC board only . Capable of
controlling one door. No enclosure or readers included.
Installation Procedure
To install the IPSDC, perform the procedures described in the
following sections, in the order in which they are presented.
1. Mount the enclosure.
2. Set the dual in-line package (DIP) switches.
3. Connect the reader(s) and inputs.
4. Connect the door strikes.
5. Connect the power.
6. Verify proper operation on power up.
7. Configure the IP address of the IPSDC and the IP address of
the System Controller (TP-SYS).
WARNING: Circuit board components are vulnerable to damage
by electrostatic discharge (ESD). ESD can cause
immediate or subtle damage to sensitive electronic
parts. An electrostatic charge can build up on the
human body and then discharge when touching a
board. A discharge can be produced when walking
across a carpet and touching a board, for example.
Packing List
• IPSDC printed circuit board (PCB) assembly and overlay
• Hardware kit
- Ground terminal lug
- SEMS screws
- Protection diodes for door strike wiring
- Metal Oxide Varistor (MOV) surge absorbers for door
strike wiring
- Ferrite for use with network cables
- 1K end-of-line resistors
• Lock (quantity = 1)
• Enclosure
• Enclosure mounting template
• Installation screwdriver
• TruPortal IP-based Single Door Controller (IPSDC) Quick
Reference (this document)
P/N 460939301B • REV 01.00 • 30OCT13 1
WARNING: Do not apply power to any component during
Mounting the Enclosure
1. Using the template provided, mark and then drill the four
mounting holes.
2. Bolt the enclosure securely to the wall, using four #8 thread
lag bolts or equivalent.
Before handling any board, make sure to dissipate
any charge by touching the ground. This discharges
any static electricity build-up.
installation. Damage to components may occur if
power is incorrectly applied.

Setting the DIP Switches
Set DIP switches before installing and wiring readers. See Figure
10 on page 7 for switch locations.
Switch Purpose
SW1 – Select Custom
Wiegand Card Format
SW2 Set all four DIP switches to OFF
1. Use the System Administration > Card Formats page
in the TruPortal User Interface to configure Wiegand
card formats.
Set SW1-1 to OFF and set SW1-2 thru
[1]
SW1-4 to ON.
The inputs can be configured as supervised or nonsupervised. Inputs configured as supervised digital inputs
require End-of-Line (EOL) resistors.
• The reader interface has built-in pull-up resistors to
accommodate cable lengths over 500 feet (152.4 meters). No
external pull-up resistors are required for the reader interface.
Table 1: Maximum Peripheral Loads
Reader/Strike PoE Auxiliary Power Supply
Voltage (DC) 12 24 12 24
T otal watts available 8 10 12 20
The following table provides switch settings for input types:
SW1-5 and SW1-6 SW1-7 SW1-8
Supervised DI/REX 1,
4-State
Supervised DI/REX 1,
2-State (default)
N/A ON N/A
N/A OFF N/A
Note: After changing DIP switch settings to modify input types,
be sure to reboot the IPSDC.
Switches SW4—SW7 are right-angle, momentary-contact push
buttons described in the following table and shown in Figure 11 on
page 8.
Switch Purpose
SW4 – Boot Mode Manually enables the ICT . See the TruPortal
Software User Guide for details.
SW5 – Hardware Reset Reboots the IPSDC. Use this switch only if
performing a controlled manual shutdown, as
instructed by T echnical Support.
SW6 – Shutdown Request See Safe Shutdown Procedure on page 5.
SW7 – Restore Defaults Press SW7 for a minimum of five (5) seconds,
then release to return the configuration to factory
default settings:
Primary Connection Type: Ethernet
IP Address: 192.168.6.6
Subnet Mask: 255.255.255.0
Gateway: 192.168.6.1
Note: A TruPortal IPSDC Power Requirement Wattage
Calculator is included on the product disc in the
\Documentation\en-US folder for use in determining
peripheral loads.
Table 2: Device Current
Average
Operating
Device
T-100 reader 12 55 .66
T-200 reader 12 55 .66
T-500 reader 12 95 1.14
T-520 reader 12 105 1.26
T-525 reader 12 140 1.68
Securitron M62 Magnalock
[1]
strike
Securitron M62 Magnalock
[1]
strike
HES, Inc 5000-12/24D strike 12 230 2.76
HES, Inc 5000-12/24D strike 24 115 2.76
Rutherford 4114x05x32D strike 12 190 2.28
Von Duprin 5100 3FP695
12 VDC
Von Duprin 5100 3FP695
24 VDC
Voltage
12 240 2.88
24 140 3.36
12 290 4.68
24 195 4.68
Measured
Current (mA) Watts
Note: The reader board address is internally set to Address 1.
Connecting the Readers and Inputs
Use Figure 10 on page 7 to wire the readers and inputs. Refer to
the reader documentation for wiring instructions.
RCR-REX 12 28 0.34
RCR-REX 24 17 0.41
1. When using magnetic strikes with auto-voltage select, additional power allowances must be considered due to autovoltage circuitry operation.
Note the following details:
• IPSDCs do not support the following TruPortal features:
Buzzer actions initiated by action triggers, auxiliary inputs/
outputs, and reader tamper inputs.
• The reader DI port (J2) has two digital inputs which are used
for door status devices (door contacts and exit request input).
2 TruPortal IP-based Single Door Controller Quick Reference

Connecting the Door Strikes
One door DO relay is dedicated to the J2 reader port. The door
DO is used for strike control, and may implement an external relay
if necessary.
Figure 1: Door Strike Configuration Using Internal Power (PoE or 24 VDC)
Figure 2: Door Strike Configuration Using External Power
Callout Description
1 Strike Relay Normally Closed (NC)
2 Strike Relay Common
3 Strike Relay Normally Open (NO)
4
5
Protection diode required
12 or 24 VDC Strike
[1]
[2]
6 Strike voltage selection. Jumper pins 1 and 2 for 24 VDC strikes;
jumper pins 2 and 3 for 12 VDC strikes.
7 See strike manufacturer’s installation guide for conductor size
(AWG).
1. Use 1N4002, 1N4003, or 1N4004 diodes.
2. Refer to the TruPortal IPSDC Power Requirements Wattage
Calculator worksheet included on the product disc for strike
type and size.
The following table describes connector J2 in Figure 2.
Callout Description
1 Strike Relay NC
2 Strike Relay Common
3 Strike Relay NO
4
5
Protection diode required
12 or 24 VDC Strike
6 Strike voltage selection. Set jumper to Neutral (no connection)
position.
7 See strike manufacturer’s installation guide for conductor size
(AWG)
8 Strike power supply
9 Provide current restriction device, less than 2 amps through relay.
1. Use 1N4002, 1N4003, or 1N4004 diodes and Metal Oxide
Varistors (MOVs) for AC strikes.
2. Refer to the TruPortal IPSDC Power Requirements Wattage
Calculator worksheet included on the product disc for strike
type and size.
[1]
[2]
TruPortal IP-based Single Door Controller Quick Reference 3