Interlogix 60-804-01 Specsheet

Page 1
Note
   

Document Number: 466-1633 Rev. B September 2000

ITI Part No. 60-804 & 60-810
Installation Instructions

Product Summary

The ITI® SuperBus 2000 2 x 20 VFD (vacuum fluorescent display) Alphanumeric Touchpad gives you complete on­site system programming and operation control of a com­patible security system (see the section “Specifications”).
A two-line, 40-character display provides visual system status messages. The display identifies any programmed location, allowing the user to determine where an alarm, trouble, or open-sensor condition exists.
Other features include: Touchpad buttons that light up after the first button
press and remain lit until about 15 seconds after the last button press.
Adjustable display brightness. Built-in hardwire input (can be supervised with EOL
resistor in SuperBus 2000 panels).
Built-in door, which covers right-side buttons (60-810
only).
SuperBus 2000 Panels
SuperBus 2000 panels assign mo dule unit numbers automatically when the panel is powered up. This eliminates manually setting unit numbers and the chance of identical unit number conflicts.
SuperBus 2000 Panels
Advent Concord (software versions 2.0 and newer) Concord Express
SuperBus panels communicate w ith SuperBus 2000 modules but require the module unit number to be set manually. Touchpads automatically default to unit number
001.
SuperBus Panels
UltraGard Concord (software versions 1.0–1.6)
vs.
SuperBus Panels

Installation Guidelines

For the maximum number of bus devices and
touchpads per panel see Table 1.

Table 1: Maximum Bus Devices Per Panel

Panel Maximum Bus

Devices
UltraGard 8 Concord 16 Advent 62 Concord Express 4
Do not exceed the total panel output power when using
panel power for bus de vices , t ouc hp ads , an d h ardwi red sensors that require it (see specifi c panel Installation Instructions).
Maximum current draw from the touchpad is 120 mA. Minimum current draw from the touchpad when the
panel is operating only on backup battery is 15 mA.
Mount the touchpad in an environmentally controlled
area (32° to 140°F) (0° to 60°C).
When using the optional touchpad hardwire input, use
only shielded wire (22-gauge or larger), and do not exceed the maximum wire length limits in Table 2 between the touchpad and detection device.
Shield wire must be connected to earth ground.

Table 2: Hardwire Input Wire Length Limits

Gauge Max. Wire

Length
18 (shielded) 1000 Feet 22 (shielded) 350 Feet

SuperBus® 2000 2 x 20 VFD Alphanumeric Touchpad

When mounting the touchpad back-plate, allow a 1-
inch clearance on all sides since the touchpad is larger than the back-plate.
Use 4-conductor, 22-gauge or larger stranded wire from
the touchpad to the control panel.
Follow the wire length limits outlined in the specific
panel Installation Instructions between the touchp ad and control panel.
1
Page 2

Tools Needed

The following must be observed in UL installations

The touchpad hardwire input must not be used for fire
alarm initiating devices.
Only UL-listed devices may be connected to the touch-
pad hardwire input.
The touchpad hardwire input can be configured for
normally closed or normally open protection devices.
For UL installations with UltraGard and Concord (soft-
ware versions 1.0–1.6) panels, do not use the touchpad hardwire input.
Tools Needed
Drill with bits Screwdrivers #6 screws and anchors (included) Panhead screws for a gang box installation Saw or utility knife for cutting wallboard
Note
Do not use screws larger than #6 or the touchpad will not seat properly onto the back-plate.

Installation

To mount the touchpad in a gang box:

1. Separate the mounting bracket from the back-plate by loosening the two bottom screws and unlatching the tabs from the mounting slots (see Figure 1).
2. Line up the gang bo x mo unting holes with the holes on the gang box (see Figure 2).
3. Secure the back-plate to the gang box with panhead screws.
Note
Do not overtighten screws or the back-plate may bind and prevent the touchpad from mounting properly.
WALL MOUNTING HOLES (X4)
BACK PLATE MOUNTING TABS (X3)
WIRE
ACCESS
HOLE
The touchpad can be installed on a wall or in a gang box.

To mount the touchpad on a wall:

1. Separate the mounting bracket from the back-plate by loosening the two bottom screws and u nlatching the tabs from the mounting slots (see Figure 1).
2. Place the back-plate on the wall and mark the four mounting holes and the wire access hole (see Figure 2). Be sure to leave a 1-inch clearance on all sides of the back-plate.
3. Drill holes and insert appropriate anchors.
4. Secure the back-plate to the wall with included screws.
5. Cut a hole in the wall where the wire access hole was marked to pull your cable through.
MOUNTING SLOTS
OPENING FOR CONNECTOR
CABLE OPENING
GANG BOX MOUNTING HOLES (X2)
Figure 2. Back-Plate and Mounting Holes
3101G02B.DS4

Wiring

Wiring consists of connecting the touchpad wiring harness to the panel terminals. You may also connect an optional hardwire sensor to the touchpad hardwire input wires.

Before You Begin

1. Disconnect the panel AC power transformer and backup battery (turn off power switch on UltraGard panels).
2. Run a 4-conductor, 22-gauge wire cable from the panel to the touchpad location.
3. Splice the 4-conductor cable wires to the matching col­ored wires located on the touchpad wiring harness.
Find your panel in the next section for specific wiring instructions.
LOOSEN BOTTOM SCREWS (X2)
Figure 1. Touchpad Mounting Slots
2
3101G03B.DSF
SuperBus® 2000 2 x 20 VFD Alphanumeric Touchpad
Page 3
Wiring
Note
Note
C
3
4 5 6
GND
+12V
BUS
BUS
B
BUS
A
PANEL TERMINALS
NOT USED
OPTIONAL
N/C SWITCH
YELLOW
BLACK
RED
WHITE GREEN
TOUCHPAD
WIRING HARNESS
49-430
TAB
SLOT (3)
8557155B.DSF
OPTIONAL
N/O SWITCH
WITH MAGNET
2K OHM
EOL RESISTOR
(Concord 2.0 or later
and Concord
Express panels)
SHIELDED
CABLE
Connect Shield to Earth Ground

Wiring Panels

UltraGard Panels

1. Connect the touchpad wiring to the panel terminals as shown in Figure 3. Wire multiple touchpads in parallel.
2. If desired, connect an optional hardwire switch to the yellow touchpad wires as shown in Figure 3 (unsuper­vised in UltraGard systems).
Note
The optional touchpad hardwire input must be added to panel memory. See the UltraGard pane l
Instructions
or
Reference Manual
for setting the con-
Installation
figuration.
3. Insert the touchpad wiring harness connector onto the pins located on the rear of the unit. Make sure the yel­low wires are to the left.
CONTROL PANEL
BUS
OPTIONAL
SWITCH
WITH MAGNET
(Not to be us e d in UL listed installati on s )
onnect Shield To Earth Ground
DC
OUT
12
BUS
A
13 14 15
GND
B
BLACK WHITE
GREEN RED
Concord Systems with software version 2.0 or newer­Wire a 2K ohm EOL resistor (49-467) in series with normally closed switches and in parallel with normally open switches (see Figure 4).
Concord Syst ems wit h softwar e vers i ons 1.0 1.6 - This switch must be unsup ervi s ed an d a resistor must not be used.
The optional touchpad hardwire input must be added to panel memory. See the Concord/Concord Express panel
Installation Instructions
for setting the
configuration.
3. Insert the touchpad wiring harness connector onto the pins located on the rear of the unit. Make sure the yel­low wires are to the left, as shown.
SHIELDED
CABLE

Concord/Concord Express Panels

1. Connect the touchpad wiring to the panel terminals as
YELLOW
NOT USED
WIRING HARNESS
49-430
Figure 3. Wiring the Touchpad to UltraGard Panels
TAB
SLOT (3)
8557148B.DS4
shown in Figure 4. Wire multiple touchpads in parallel.
2. If desired, connect an optional hardwire switch to the yellow touchpad wires as shown in Figure 4.
Concord Express Systems- Wire a 2K ohm EOL resis­tor (49-467) in series with normally closed switches and in parallel with normally open switches (see Figure 4).
Figure 4. Wiring the Touchpad to Concord and
Concord Express Panels

Advent Panels

1. Splice the touchpad wiring to the panel SuperBus wir­ing harness as shown in Figure 5. Wire multiple touch­pads in parallel.
2. If desired, connect an optional hardwire switch to the yellow wire s on the touchpad wiring harness. Wire a 2K ohm EOL resistor (49-467) in series with normally closed switches and in parallel with normally open switches (see Figure 5).
The optional touchpad hardwire input must be added to panel memory. See the Advent panel
Instructions
for setting the configuration.
Installation
SuperBus® 2000 2 x 20 VFD Alphanumeric Touchpad
3
Page 4

Mounting the Touchpad

3. Insert the touchpad wiring harness connector onto the pins located on the rear of the unit. Make sure the yel­low wires are to the left (see Figure 5).
TO ADDITIONAL
SUPERBUS
TOUCHPADS
AND/OR
MODULES
PANEL SUPERBUS
WIRING
HARNESS 49-462
BLACK (GND)
WHITE (BUS B)
GREEN (BUS A)
RED (+12 VDC)
OPTIONAL
N/O SWITCH
WITH MAGNET
2K OHM
EOL RESISTOR
OPTIONAL
N/C SWITCH
WITH MAGNET
SHIELDED
Figure 5. Wiring the Touchpad to Advent Panels
CABLE
SPLICE
Connect Shield to Earth Ground
YELLOW
NOT USED
TOUCHPAD
WIRING HARNESS
49-430
TAB
SLOT (3)
8543109C.DSF
Mounting the Touchpad
1. Align the slots on the touchpad with the slots on the back-plate. Insert the mounting tabs into the mounting slots and press the keypad toward the wall/gang box .

2. Tighten the two bottom screws.

Setting Touchpad Unit Numbers

Note
In multiple partition systems all new touchpads default to partition 1. To change partition assignment please see specific panel partitions must be disarmed before entering program mode.
Installation Instructions
. All
these panels, alphanumeric touchpads default to 001. If desired or necessary, the unit number must be manually changed.
Guidelines for Assigning Alphanumeric Touchpad Unit Numbers (Concord panels with software versions 1.0–1.6 and UltraGard panels)
Use the following guidelines to avoid communication con­flicts between bus devices and the panel:
Always start with one touchpad connected to the panel
and make sure it i s worki ng pr operly b efor e connecti ng additional touchpads .
Whenever possible, such as in new installations, assign
alphanumeric touchpad unit numbers before beginning all other panel programming.
Other bus devices with device unit number DIP
switches (ESM, HIM, etc.) must be set to the desired unit number before app lying power and entering program mode.

Power Up and Bus Communication

Powering Up UltraGard Panels

First Touchpad

1. Disconnect all bus device wiring f rom the pan el ex cept for the touchpad location closest to the panel.
2. Verify that all wiring at the panel and touchpad wiring harness is correct.
3. With the panel power switch off, connect the panel bat­tery and plug in the panel AC power transformer.
4. Set the panel RUN/PROGRAM switch to RUN.
5. Turn on the panel power switch.
6. Put the touchpad into the manual configuration mode by pressing and ho ldi ng t he to uchpad D and 6 buttons until the display shows
7. Set the panel RUN/PROGRAM switch to PROGRAM and the display should read
8. Verify correct operation by pressing STATUS or BYPASS. The display should show a different menu item for each button pressed.
If your installation only calls for one alphanumeric touch­pad, you may proceed with other system programming. If you have more alphanumeric touchpads to connect and assign device addresses, use the following pro cedure before proceeding with any other system programming.
DA 001 (unit number 001).
PROGRAM MODE.
Panels automatically assign or learn the unit numbers of each bus device upon power up or entering programming mode. SuperBus 2000 panels (Advent panels and Concord panels with software version 2.0 or newer) automatically assign different unit numbers to each SuperBus 2000 mod­ule. SuperBus panels (Ul traGard panels and Co ncord panels with software versions 1.0–1.6) do not automatically assign different unit numbers to each SuperBus 2000 module. For
4
SuperBus® 2000 2 x 20 VFD Alphanumeric Touchpad
Page 5
Power Up and Bus Communication
Note
Note
Note
Additional Touchpad
1. Disconnect the panel AC power transformer, backup battery, and turn off the power switch.
2. Connect all bus device wiring to the panel (including the wiring that was disconnected in step on e o f the first touchpad installation), but make sure no new touchpads are connected to their wiring harnesses yet.
3. Verify that all wiring at the panel and at the added touchpad wiring harnesses are correct (but do not connect any touchpads to their wiring harness).
4. Apply power to the panel (tur n on the power switch).
5. Set the RUN/PROGRAM switch to PROGRAM. Existing (previously installed) tou c hpad(s) display
PROGRAM MODE.
Or—The displa y shows ENTER CODE or 1-OFF (1 blink-
ing), indicating you need to enter the install code. After entering the install code, existing touchpads disp lay
PROGRAM MODE.
Note
After entering the install code to get into program mode, the panel allows you to switch between RUN and PROGRAM mode for 1 hour without re-entering the code.
6. At an existing touchpad, pres s BYPASS or STATUS until the display sh ows TOUCHPAD OPTIONS.
7. Press COMMAND and the display shows
NUMBER.
UNIT
8. Press COMMAND; existing touchpads will display
DA 00N (where N is the unit number 0–7). Make a note
of this touchpad unit number.
9. Check the unit numbers of all other existing tou chpad s and write them down.
10. Check the unit number DIP switches on other bus devices (ESM, HIM, etc.) and make a note of their respective unit numbers.
11. Connect the wiring harness to one new touchpad.
12. Put the new touchpad into the manual configuration mode by pressing and holding the touchpad D and 6 buttons until the display shows
DA 001 (unit number
001).
13. Press BYPASS and the display shows
ENTER _.
14. Enter a unit number different from that of the existing touchpads and any other bus devices in the system by pressing any of the touchpad buttons numbered 0 through 7.
15. Press BYPASS then STATUS to lock in and display the new unit number for the touchpad.
16. Disconnect this touchpad and repeat steps 11 through 16 for any other new alphanumeric touchpads. Be sure to disconnect each touchpad after assigning its unit number.
17. After assigning unit numbers to all the new touchpads, connect each touchpad to its respective wiring harness.
18. Set the RUN/PROGRAM switch to RUN. All touch­pads should display
1 - OFF.
19. Set the RUN/PROGRAM switch to PROGRAM so the panel can learn all bus device unit numbers. All touch­pads should displ ay
PROGRAM MODE.
20. Set the RUN/PROGRAM switch to RUN.
21. At each touchpad, verify correct operation by pressing STATUS. The display should show the current system status.

Powering up Concord Panels with Software Version 2.0 or Newer and Concord Express Panels

1. V er ify that all wiring between the panel and touchpad is correct.
2. Connect the panel battery and plug in the panel trans­former. Alphanumeric touchpads show “SCANNING BUS DEVICES,” then a date and time display.
3. Verify correct operation by pressing . The display should show the current system status.
If after pressing the touchpad does not display the current system status, see “Troubleshooting.”

Powering up Concord Panels with Software Versions 1.0–1.6

First Touchpad

1. V er ify that all wiring between the panel and touchpad is correct.
2. Check the unit number DIP switches on all other bus devices (ESM, HIM, etc.) and make note of their respective unit numbers.
Touchpads default to unit number 001 when first installed. If possible, leave this unit number open. If unit number 001 is not available, or there are multiple touchpads installed see the section “Additional Touchpads” below.
3. Connect the panel battery and plug in the panel trans­former. Alphanumeric touchpads show “SCANNING BUS DEVICES,” then a date and time display.
4. Verify correct operation by pressing . The display should show the current system status.
If after pressing the touchpad does not display the current system status, see “Troubleshooting.”

Additional Touchpads

1. V er ify that all wiring between the panel and touchpad is correct.
2. Check the unit number DIP switches on other bus devices (ESM, HIM, etc.) and make a note of their respective unit numbers.
3. Connect the panel battery and plug in the panel trans­former. Alphanumeric touchpads show “SCANNING BUS DEVICES,” then a date and time display.
SuperBus® 2000 2 x 20 VFD Alphanumeric Touchpad
5
Page 6

Deleting Touchpads/Unit Numbers from Panel Memory

4. At a touchpad, press and hold the D and 6 buttons (together) for at least 2 seconds. The display should show DA n, where n is the current unit number (000 –
015) for the touchpad.
Note
At this time, the tou chpad is in confi guration mode and no longer communicating with the panel. The system may immediately indicate a bus fail ure. Ignore the fail­ure and continue with the procedure. The failure will clear after the unit number has been successfully changed.
5. Press ƒ. The display shows ENTER _.
6. Enter an unused three digit unit number (000 – 015), then press ƒ. The display shows DA n, where n is the new unit number for the touchpad.
7. Press to exit from the configuration mode.
8. Repeat steps 4–8 for all connected alphanumeric touchpads.
Note
If the new unit number for the touchpad was previ­ously added (learned) by the panel, communication between the touchpad and the panel begins immedi­ately. However, if the new unit number for the touch­pad has never been added (learned) by the panel, continue with step nine.
9. Force the panel to scan bus devices.
For systems where this is the only installed touch-
pad, remove the panel AC power and backup bat­tery power, then re-apply power.
For systems with more than one touchpad, go to
another system touchpad and enter 8 + installer CODE (default = 4321) + 0 + 1. The display shows SCANNING BUS DEVICES, then a date and time display.
10. Exit the program mode. The touch pad and all other bus devices should operate correctly and any bus failures should be cleared.
Note
If the panel still indicates a bus failure the panel may have previously learned a unit number that is no longer used by any bus device. Delete the unused unit number.
Note
If the touchpad does not display anything or displays, “Touchpad Not Enrolled,” see “Troubleshooting.”

Existing Installations

1. V erify that all wiring between the panel and touchpad is correct.
2. Connect the panel battery and plug in the panel trans­former.
3. At an existing touchpad, press 8 to select SYSTEM MENU.
4. Press 0 to select ENTER PROGRAM MODE.
5. Enter your install access CODE (0123 is default ).
6. Enter item number 48001 to add bus devices. All installed devices are automatically added (learned) into panel memory when DEVICES ADDED is displayed.
7. Press once to exit program mode.
8. New alphanumeric touchpads shou ld d ispla y “Securi t y is Off,” while existing touchpads will display custom or programmed text.
Note
If the touchpad does not display anything or displays, “Touchpad Not Enrolled,” see “Troubleshooting.”
Deleting Touchpads/Unit Numbers from Pa nel Memory
Please see the specific Installation Instructions for informa­tion on deleting touchpads/unit numbers.

Adjusting Touchpad Brightness

Please see the specific panel Installation Instructions or User’s Manual for more information.

Testing

11. Verify correct operation by pressing . The display should show the current system status.
Note
If after pressing ‚ the touchpad does not display the current system status, see “Troubleshooting.”

Powering Up Advent Panels

New Installations

1. V erify that all wiring between the panel and touchpad is correct.
2. Connect the panel battery and plug in the panel trans­former. The alphanumeric touchpad should display “Security is Off,” or any other programmed text.
6
CAUTION
Contact the centra l monitoring s tation alarms to avoid dispatching local police and fire departments.
before
activating
T est the touchpad by arming and disarming the system, acti­vating the touchpad panics, bypassing sensors, and by turn­ing lights on and of f t o verify the correct op eration . Refer to the panel Owner’s Manual
for system operating instruc-
tions.

Panel Programming

An alphanumeric touchpad must be used to program some panels. For a complete description of programming com­mands, refer to the specific panel Installation Instructions.
SuperBus® 2000 2 x 20 VFD Alphanumeric Touchpad
Page 7

Troubleshooting

Tables 3, 4, and 5 describe actions you can take to correct problems you may experience when co nnecting bus dev ices to each of the different panels.
Table 3: UltraGard Troubleshooting

Problem Action/Solution

All touchpads display
1 - OFF
work or won ’t enter program mode.
The touchpad displ a ys the message
N
failed bus device).
The panel report s a trou ble condition on the touchpad loop.
but they don’t
BUS FAIL UNIT
(N = unit number of
1. Disconnect all touchpads except the original. Set the panel mode switch to PROGRAM, enter the install code, and switch back to RUN.
2. Assign a different unit num­ber to each touchpad using the procedure outlined in this document.

1. Turn off the panel power switch. Check the wiring at all bus devices and correct where necessary.

2. Assign a different unit num­ber to each touchpad using the procedure in this docu­ment.

3. Set the panel mode switch to PROGRAM then back to RUN.

1. Change the unit number on the new bus device to an unused unit number. Turn power OFF then ON. Set the mode switch to PRO­GRAM then back to RUN.

2. Turn off the panel power switch. Check and correct the touchpad wiring.

3. The panel must learn the hardwire loops again when a touchpad unit number is changed.

Table 4: Concord and Concord Express
Troubleshooting

Problem Action/Solution

The touchpad doesn’t power up (no display and no beeps when buttons are pressed).
The touchpad displ ay appears blank, but beeps sound when buttons are pressed.
The touchpad displays a flashing star [*], indicating a trouble condition, and the system doesn’t respond to commands from the touchpad.
1. Check for c orrect wiring connec­tions at the touchpad and panel terminals.

2. Make sure the panel battery is connected correctly and that the panel transformer is plugged in.

3. Make sure the panel tr ansformer is not plugged into an electrical outlet controlled by a switch. Relocate the transformer to an unswitched outlet if necessary.
1. Check the touchpad display con­trast setting. It may be set to 0 (no display).
1. Check for c orrect bus wiring con­nections (green and white wires) at the touchpad and panel terminals.
2. Make sure the touchpad unit number is set to a number different from all other bus device unit numbers. If necessary, change the touchpad unit number. (Concord panels with software versions 1.0–1. 6 only).

Table 5: Advent Troubleshooting

Problem Action/Solution

The touchpad displ ay seems “stuck” in the program mode.
The touchpad displays
“**********
error message, or appears “dead” and does not respond to button presses.
The touchpad displays “Touchpad Not Enrolled.”
”, an

1. Check that the panel is not in the program mode of opera t ion.

1. Check that the wir ing connector is plugged into the back of the touchpad.

2. Check for incorrect wiring, opens, or shorts.

3. Check panel power.

4. From another touchpad enter program mode and veri f y t ouch ­pad is enrolled.
1. Perform the procedure for “Exist­ing Installations” under the sec­tion “Powering up A dvent Panels,” in this document.
Troubleshooting
SuperBus® 2000 2 x 20 VFD Alphanumeric Touchpad
7
Page 8

Specifications

0
Specifications
Touchpad/Panel Compatibility:

Touchpad Part No. Compatible Panel(s)

60-804-01 Advent 60-804-04 Concord, Concord Expr e ss 60-810-03-ED Concord 60-804-03 UltraGard
Power Requirements: 12 VDC nominal
120 mA maximum (from pa nel)
Display: 2-line, 40-character (2 x 20),
backlit, alphanumeric vacuum fluorescent
Zone Input: One supervisable hardwire zone
input
Data I/O: 4-wire ITI SuperBus 2000 auto
addressing digital data bus Storage Temperature: -30° to 140° F (-34° to 60° C) Operating Temperature: 32° to 140° F (0° to 60° C) Maximum Humidity: 90% (±5%) relative humidity, non-
condensing Listings (see note): UL 985 Household Fire Warning
System Units
UL 1023 Household Burgl ar-Alarm
System Units

Notices

FCC Part 15 Information to the User
Changes or modifications not expressly approved by Inte rac ti ve Tech­nologies, Inc. can vo id the user’s authority to operate the equipment.
FCC Part 15 Class A
This equipment has been tested and found to comply with the limits for a class A digital device , pur suant to part 15 of the FCC rules. Thes e limits are designe d to provide reasonable protection against ha rm ful interference when the equipment is operated in a commercial environ­ment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interfer­ence in which case users will be required to correct the interference at their own expens e.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not instal le d and used in accordance with the instructions, ma y cause harmful in te rference to radio comm unications. However, there is no guarantee that i nterference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, whi ch can be determined by turning the eq ui pment off and on, the user is encourag ed to tr y to correct the interf erence by one or more of the following measures:
Reorient or relocate the receiving ante nna.
Increase the separation between the equipment and receiver.
Connect the affected equipment and the panel receiver to separate
outlets, on different branc h circuits. Consult the dealer or an experienced radio/TV technician for help.
UL 1610 Central Station Burglar-
Alarm Units (Commercial
Burglary)
CSFM California State Fire
Marshall
Note
See specific panel
Installation Instructions
for complete UL installation requirements for the system you are installing.
Dimensions: 4.60” x 7.75” x 1.2” (H x W x D) Chassis Material: High-Impact ABS plastic Case Color: Belgian gray with gray imprints
8
I
nteractive Technologies, Inc.
2266 Second Street North North Saint Paul, MN 55109-290 T: 651/777-2690 F: 651/779-4890 1-800-777-1415 www.itii.com
© 2000 Interlogix™, Inc. ITI, SuperBus, Advent, and UltraGard are registered trademarks of Interlogix, Inc. Interlogix and Concord are trademarks of Interlogix, Inc.
SuperBus® 2000 2 x 20 VFD Alphanumeric Touchpad
Loading...