Honeywell Y594 User Manual

Y594
(Multistage Thermostat Subbase)
TRADELINE
®
APPLICATION
These Y594G and Y594J combination packs are designed to meet the specific requirements of Carrier heat pump equipment. The Y594 packs are designed for 2 stage heat and 1 stage cool applications. The system switch is SUPL HT-HEAT-OFF-COOL or SUPL HT-ON-OFF. The fan switch is AUTO-ON. See Table 1 for model information and cross reference from Carrier part numbers.
Table 1. Heat Pump Thermostat/Subbase Combinations.
OS No.
Y594G1666 7 T874G2004
Y594G1674 6 T874G2004
Y594J1001 5 T874J1069
Y594J1019 4 T874J1069
Thermostat Ratings
SWITCHING: sealed mercury switch. SWITCH RATINGS:
First Stage Heating and Cooling: 6.5A inrush, 1.5A
maximum running at 25 Vac.
Second Stage Heating and Cooling: 1.5A maximum
running at 30 Vac.
Changeover Switch: 6.5A inrush, 1.5A running at 25
Vac.
HEAT ANTICIPATOR:
First Stage Heating and Cooling: fixed voltage type,
1.0A.
Second Stage Heating: adjustable, 0.10 to 1.2A; other
models, fixed voltage type, 1.0A.
TEMPERATURE SETTING RANGE: 42°F to 88°F (6°C to
31°C).
Fig.
No. Contains Replaces Honeywell Replaces Carrier
Q674L1892
Q674J1274
Q674L1900
Q674J1282
Y507J1011 T874G1055
Y507J1003 T874G1055
Q674L1041
Q674J1035
T874J1002
Q674L1074 or Q674L1637
T874J1002
Q674J1068 or Q674J1159
Package
INSTALLATION INSTRUCTIONS
Subbase Ratings
SWITCH RATING: 7.5A inrush, 2.5A running at 30 Vac. MOUNTING: Designed for mounting on wall or horizontal
outlet box.
Changeover
Mode
99TZ90041106 HH07AT171
99TZ90040106 HH07AT171
HH07AT175
HH07AT175
HH93AZ175
HH93AZ173
HH93AZ186 or HH93AZ195
HH93AZ183 or HH93AZ196
OPERATION
The two stages of heat are energized sequentially with changes in temperature. Stage one comes on first; then if the temperature at the thermostat continues to move away from the setpoint, the second stage comes on. The thermostat is set with about 2°F (1°C) between stages. As the heating equipment runs and the temperature begins to move back toward the set point, stage 2 goes off first, then stage one.
Subbases include an LED (light emitting diode) indicator. This indicator lights to show that the heat pump cannot operate and the supplemental heat stage is providing all heating. This condition can occur in two instances; when the subbase system switch is set at SUPL. HT. and when the heat pump compressor has malfunctioned.
The LEDs are not field replaceable.
Manual changeover in cooling
Auto changeover in cooling
Manual changeover in cooling
Auto changeover in heating
Copyright © 1995 Honeywell Inc. • • All Rights Reserved
X-XX UL
69-0920
Y594 (MULTISTAGE THERMOSTAT SUBBASE) PACKAGE
RECYCLING NOTICE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube.
INSTALLATION
When Installing this Product
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Disconnect power supply to prevent electrical
shock or equipment damage.
Run wires as close as possible to the sub-
base. To prevent interference with the thermostat linkage, keep wire length to a minimum. Push excess wire back into the hole, and plug hole to prevent drafts from affecting thermostat operation.
Do not overtighten thermostat captive
mounting screws because damage to subbase threads can result.
Do not short across coil terminals on relay.
This may burn out the heat anticipator.
Never install more than one wire per terminal
unless factory-supplied jumper with spade terminal is used.
IMPORTANT
Thermostats are calibrated at the factory by using subbases mounted at true level. Inaccurate sub­base leveling will cause thermostat control deviation.
Location
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average room temperatures.
Do not mount the thermostat where it may be affected by: drafts, or dead spots (no air movement) behind doors,
in corners, and above or below shelves.
hot or cold air from ducts.radiant heat from the sun, lights, or appliances.concealed pipes and chimneys.unheated or uncooled areas such as an outside wall
behind the thermostat.
Mounting and Wiring the Subbase
Disconnect power supply to prevent electrical shock or equipment damage. All wiring must comply with local electrical codes and ordinances. Follow equipment manufacturer wiring instructions when available.
Mount the subbase on a wall or horizontal outlet box. To mount it on a vertical outlet box, order Honeywell part no. 196393A Cover Plate Assembly, which includes an adapter ring with two screws for vertical outlet box mounting and a cover plate to cover marks on the wall.
To install subbase, proceed as follows:
Prepare a hole for the thermostat wires at the
chosen location. Run wires to location.
Pull about 6 in. (152 mm) of wire through the hole.
IMPORTANT
Use 18 gauge, color-coded thermostat cable for proper wiring.
If mounting the subbase on a vertical outlet box,
install adapter ring with the two screws provided in the assembly. See Fig. 1.
Pull wire through cover plate, if used, and subbase
wire opening. Secure the cover plate and subbase with the two screws provided, but do not tighten down.
Level the subbase using a spirit level. See Fig. 2.
Tighten subbase mounting screws. The subbase mounting slots provide for minor out-of-level adjustments.
IMPORTANT
An incorrectly leveled subbase will cause the temperature control to deviate from setpoint
Connect the system wires to the subbase. See
Fig. 4-7. A letter is stamped near each terminal for identification. The terminal barrier permits straight or conventional wraparound wiring connections. See Fig. 3. Either method is acceptable. Run wires as close as possible to the subbase, keeping wire length to a minimum. Push excess wire back into hole. Plug hole to prevent drafts.
Mounting the Thermostat
Remove the thermostat cover by pulling the bottom
edge of the cover away from the base until it snaps free of the retaining posts.
NOTE: The cover is hinged at the top and must be
removed by pulling out at the bottom.
Carefully remove and discard the polystyrene
packing insert that protects the mercury switches during shipment.
Turn the thermostat over and locate the spring
fingers that engage the subbase contacts. Make sure the spring fingers are NOT bent flat, preventing proper electrical contact with the subbase.
Set adjustable heat anticipator indicators, if
provided, as described in Setting the Heat Anticipator(s) section.
69-0920
2
Y594 (MULTISTAGE THERMOSTAT SUBBASE) PACKAGE
VERTICAL OUTLET BOX
1 HORIZONTAL OUTLET BOX
SUBBASE
SUBBASE MOUNTING SCREWS (2)
CAPTIVE MOUNTING SCREWS (2)
1 NOT INCLUDED WITH UNIT.
2 ACCESSORY PARTS AVAILABLE (193121A).
Fig. 1. Installation of subbases and thermostat on
SPIRIT LEVEL
TOP MOUNTING HOLES (2)
outlet box.
1
6
0
5
T
A
E
H
WIRING TERMINAL
MOUNTING SCREWS (2)
ADAPTER RING
0
8
0
7
0
2
THERMOSTAT
L
O
THERMOSTAT
O
C
0
8
0
COVER
7
0
0 6
5
50 60 70 80
THERMOSTAT CABLE OPENING
COVER PLATE
Note the tabs along the top inside edge of the
thermostat base. The tabs fit into the subbase
2
notches. Mount the thermostat on the subbase and tighten the captive mounting screws. See Fig. 1. Do not overtighten captive mounting screws. This can damage the threads in the subbase.
Place the upper edge of the thermostat cover on the
base and swing cover downward until it engages retaining posts on base. Tighten the locking cover screws if assembly is provided.
SETTING
Setting the 2nd Stage (Y594G1666 and Y594G1674 Only) Heat Anticipator
Set the adjustable heat anticipator to match its primary control current draw. If the primary control nameplate has no rating or if further adjustment is necessary, use the following procedure to measure the current draw of each stage:
Remove thermostat from the subbase. Make sure
the power is on.
Connect an ac ammeter of appropriate range
between the heating terminals of the subbase: Stage 2: between W2 and R.
Move the system switch to HEAT or ON.After one minute, read the ammeter and record the
reading.
Remount the thermostat and use a ballpoint pen to
M6009
set the adjustable heat anticipator(s) to match the reading(s) measured in step 4. See Fig. 8.
Temperature Setting
Move the heating and cooling levers to the desired positions. The minimum differential between heating and cooling setpoints is 3°F (2°C). Some thermostat models have nonadjustable lever stops, which set the maximum heating control point at 68°F or 72°F (20°C or 22°C) and the minimum cooling control point at 78°F (26°C). Do not attempt to exceed these limits. Some models have only one lever for heating and cooling.
MOUNTING HOLES (2)
FOR STRAIGHT INSERTION– STRIP 5/16 in. (8 mm)
SUBBASE TERMINAL SCREW
POST (2) FOR MOUNTING THERMOSTAT
Fig. 2. Leveling the subbase.
FOR WRAPAROUND– STRIP 7/16 in. (11 mm)
BARRIER
Fig. 3. Wiring connections.
TO SPRING FINGER CONTACTS ON THE THERMOSTAT (UP TO 12)
M927
M928
Subbase Setting
Available subbase system switch positions vary by thermostat model. Positions control thermostat operation as follows:
OFF: Heating and cooling systems are off. If the fan
switch is at the AUTO position, the fan is also off.
HEAT: Heating system is controlled by the thermostat.
Cooling system is off.
COOL: Cooling system is controlled by the thermostat.
Heating system is off.
ON: Thermostat automatically switches between heat
and cool modes, depending on the indoor tempera­ture.
SUPL. HT.: Supplemental heat is energized. Cooling
system is off. Compressor cannot operate.
Fan switching positions control fan operation as follows:
ON: Fan operates continuously. AUTO: Fan operates with heat pump and supplemental
heat as controlled by the thermostat.
3
69-0920
Y594 (MULTISTAGE THERMOSTAT SUBBASE) PACKAGE
R
9
OFF ON SUPL.
HEAT
32
6
ON
SUPL. HEAT
FIELD WIRING CONNECTION
DENOTES CONNECTION POINT BETWEEN SUBBASE AND THERMOSTAT
THERMOSTAT SUBBASE
FALL
H1
H1 ANTICIPATOR
H2 ANTICIPATOR
H2
RISE
CO
C1
FALL
RISE
CO
2
4
5
6
8
9
C1 ANTICIPATOR
10
11
12
3
CO STAGE
H1
H2
FAN SWITCH
AUTO
ON
SYSTEM SWITCH
SUPL. HT.
ON
OFF
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
CO
C1
5
ON FAN
AUTO
10 8
12
SUPL. HEAT
ON
G
Y
11
4
R
Y
G
W2
SUPL. HT. LED (RED)
L
C
E
X
P
O
O
P
E
L
C
W2
X
SYSTEM COMPONENTS
L1
L2
(HOT)
1
COMPRESSOR CONTACTOR
FAN RELAY
HEAT RELAY 1
OUTDOOR THERMOSTAT
HEAT RELAY CONTACT 1
HEAT RELAY CONTACT 2
"P" RELAY
HEAT RELAY 2
HEAT RELAY 3
COOL CHANGEOVER VALVE
"X" RELAY
M4563
69-0920
Fig. 4. Y594J1019 Thermostat/Subbase switching and internal connections.
4
Y594 (MULTISTAGE THERMOSTAT SUBBASE) PACKAGE
R
C0
C1
9
COOL OFF HEAT
SUPL. HEAT
HEAT
3
6
HEAT
SUPL. HEAT
FIELD WIRING CONNECTION
DENOTES CONNECTION POINT BETWEEN SUBBASE AND THERMOSTAT
THERMOSTAT SUBBASE
FALL
H1
2
3 H1 ANTICIPATOR
4
H2
C1 ANTICIPATOR
RISE
CO
ANTICIPATOR
5
6
8
9
10
11
12
FALL
H2
RISE
CO
C1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
C0 STAGE
H1
H2
FAN SWITCH
AUTO
SYSTEM SWITCH
SUPL. HT.
HEAT
OFF
COOL
2
5
ON
10
COOL
SUPL. HEAT
FAN
8
12
11
HEAT
ON
AUTO
4
SUPL. HT. LED (RED)
G
Y
O
P
E
L
C
W2
X
SYSTEM COMPONENTS
L1
L2
(HOT)
1
R
Y
G
2
W2
L
C
E
X
P
O
COMPRESSOR CONTACTOR
FAN RELAY
OUTDOOR THERMOSTAT
HEAT RELAY CONTACT 1
HEAT RELAY CONTACT 2 HEAT RELAY 3
"P" RELAY
HEAT RELAY 1
HEAT RELAY 2
"X" RELAY
COOL CHANGEOVER VALVE
M4564
Fig. 5. Y594J1001 Thermostat/Subbase switching and internal connections.
5
69-0920
Y594 (MULTISTAGE THERMOSTAT SUBBASE) PACKAGE
RISE
FALL
R
OFF ON
SUPL. HEAT
4
ON
SUPL. HEAT
FIELD WIRING CONNECTION
DENOTES CONNECTION POINT BETWEEN SUBBASE AND THERMOSTAT
H1 ANTICIPATOR
H1
FALL
H2
H2 ANTICIPATOR
CO
RISE
C1 ANTICIPATOR
C1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ON FAN
2
AUTO
ON
SUPL. HEAT
6
8
L
SUPL. HT. LED (RED)
9
1
COOL CHANGEOVER VALVE
O
G
R
W
E
L
C
Y
C1
CO
10
H1
H2
SUPL. HEAT
1
FAN SWITCH
AUTO
SYSTEM SWITCH
SUPL. HT.
ON
OFF
ON
2
N.O. SWITCH – INSTALLER ADDED, TO LIGHT EM. HT. LED WHEN COMPRESSOR OPERATION IS NOT NORMAL.
2
4
6
8
9
10
G
Y
O
E
W2
C
SYSTEM COMPONENTSSUBBASETHERMOSTAT
1
L1 (HOT)
L2
FAN RELAY
OUTDOOR
2
2
THERMOSTAT
EM. HT. RELAY CONTACT 1
EM. HT. RELAY CONTACT 2
EM. HT. RELAY 1
EM. HT. RELAY 2
EM.HT. RELAY 3
COMPRESSOR CONTACTOR 1
M4565
69-0920
Fig. 6. Y594G1674 Thermostat/Subbase switching and internal connections.
6
Y594 (MULTISTAGE THERMOSTAT SUBBASE) PACKAGE
FALL
RISE
R
COOL OFF HEAT
SUPL. HEAT
4
HEAT
SUPL. HEAT
FIELD WIRING CONNECTION
DENOTES CONNECTION POINT BETWEEN SUBBASE AND THERMOSTAT
H1 ANTICIPATOR
H1
FALL
H2
H2 ANTICIPATOR
CO
C1 ANTICIPATOR
RISE
C1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
10
1
2
4
6
8
9
10
CO
H1
H2
SUPL. HEAT
C1
SUPL. HT.
ON FAN
AUTO
8
9
HEAT
2
SUPL. HEAT
FAN SWITCH
AUTO
ON
SYSTEM SWITCH
HEAT
OFF
COOL
2
N.O. SWITCH – INSTALLER ADDED, TO LIGHT EM. HT. LED WHEN COMPRESSOR OPERATION IS NOT NORMAL.
L
SUPL. HT. LED (RED)
1
6
G
Y
O
E
W2
C
SYSTEM COMPONENTSSUBBASETHERMOSTAT
COOL CHANGEOVER VALVE
O
G
R
OUTDOOR
W
2
E
2
L
C
Y
THERMOSTAT
HEAT RELAY CONTACT 1
HEAT RELAY CONTACT 2
COMPRESSOR FAULT
L1 (HOT)
L2
FAN RELAY
HEAT RELAY 1
HEAT RELAY 2
HEAT RELAY 3
COMPRESSOR CONTACTOR 1
1
M4566
Fig. 7. Y594G1666 Thermostat/Subbase switching and internal connections.
7
69-0920
Y594 (MULTISTAGE THERMOSTAT SUBBASE) PACKAGE
LED Indication
Set system switch on subbase at SUPL. HT. The SUPL. HT. LED should light. Simulate compressor failure and energize the system. The FAULT LED should light.
0
.1
.12
.15
.2
.3
.4
1.2
.8
STAGE TWO ANTICIPATOR HEATING CONTROL
.6
MOVE INDICATOR TO MATCH CURRENT RATING OF PRIMARY CONTROL
M4550
Fig. 8. Adjustable heat anticipator shown.
To switch positions, use thumb and index finger to slide lever to desired position. Switch lever must stop in detent directly over the desired function indicator mark for proper system operation.
CHECKOUT
Heating
Set the system switch on the subbase at HEAT or ON and the fan switch at AUTO. Move the heating lever on the thermostat about 10°F (6°C) above room temperature. Heating (both stages if two-stage thermostat) should start if there is no time delay or outdoor temperature limiting system, and the fan should come on. Move the heating lever about 10°F (6°C) below room temperature. Heating and fan should shut off.
Cooling
CAUTION
Do not operate cooling if outdoor temperature is below 50°F (10°C). Refer to manufacturer recom­mendations.
Set the system switch on the subbase to COOL or ON and the fan switch to AUTO. Move the cooling lever on the thermostat about 10°F (6°C) below room temperature. Cooling and fan should start. Move the cooling lever about 10°F (6°C) above room temperature. Cooling and fan should stop.
CALIBRATION
Thermostat
These thermostats are accurately calibrated at the factory.
They do not
Thermometer
The thermometer in your thermostat has been accurately calibrated at the factory. The thermometer should only adjustment if it has been dropped or shifted due to mishandling.
If the setpoint lever and the thermometer reading do not agree, use the following procedure:
have provision for field calibration
Remove the thermostat cover by pulling up from the
bottom edge of the cover away from the base until it snaps free of the cover clip.
Set the thermostat cover on a table near an
accurate thermometer.
Allow ten minutes for cover thermometer to sense
area temperature; compare the readings. Be careful not the touch the thermometer or breathe on it.
If the readings are the same, replace cover and put
the system into operation.
If the readings are different, insert a small screw-
driver in the thermometer slot and turn it until the thermometers have the same reading. See Fig. 9.
Replace thermostat cover and put the system into
operation.
.
Fan
Set the fan switch to ON. Move the system switch to different positions; the fan should run continuously. Move the fan switch to AUTO. Move the system switch to different positions. Fan operation is controlled with the heating or cooling system.
Home and Building Control
Honeywell International, Inc. 1985 Douglas Drive North Golden Valley, MN 55422
69-0920
J.H. 5-95 www.honeywell.com/yourhome
Home and Building Control
Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9
M5070
Fig. 9. Thermometer calibration.
8
Loading...