Honeywell Y460A2003 User Manual

69-1358
The Round® Creative Series
M6115
BULB SWITCH
ANTICIPATOR SCALE
ANTICIPATOR
Y460A2003 Thermostat
INSTALLATION MANUAL
The Y460A2003 Thermostat is for 15 to 30 Vac control of gas- or oil-fueled warm air, steam or hot water heating/electric cooling systems.

Your Y460A Thermostat

Follow these instructions step-by-step for proper
installation of your Honeywell t hermostat. It is recommended that as you read, understa nd and complete each step, you check √ it off with a pencil or pen.

1 PREPARE FOR INSTALLATION

Assemble the following required tools:
Flat-bladed screwdrive r; hand or power drill with 3/16 in. (4.8 mm) dril l bit; wi re cutte r/stripper or shar p knife; bubble level or plumb bob and line.
FLAT BLADE SCREWDRIVER
WIRE CUTTER/STRIPPER OR SHARP KNIFE, IF NEEDED TO STRIP WIRES
SPIRIT LEVEL OR PLUMB BOB AND LINE TO LEVEL THERMOSTAT FOR ACCURATE OPERATION
IMPORTANT:
For cooling systems, do not operate cooling if outdoor temperature is below 50°F (10°C).
Test your heating and/or cooling systems to be sure
they are working, especially if they have been inoperative for any length of time. If either system does not work, contact your local heating/air conditioning dealer for assistance.
HAND OR POWER DRILL WITH 1/16 INCH DRILL BIT, IF NEEDED TO DRILL HOLES IN WALL
MASKING TAPE, IF NEEDED TO LABEL WIRES AS THEY ARE DISCONNECTED FROM OLD THERMOSTAT
M 835
IMPORTANT:
Turn off power to the system at the main fuse or circuit breaker panel. Most buildings have a separate switch box or circuit br eaker for dis­connecting power to the furnace.

2 UNPACK YOUR THERMOSTAT

Carefully unpack your new thermostat.
Remove and discard the shipping wrap; be sure to
save the screws and the instructions. Remove the thermostat co ver and set it aside to use
later. Remove the red plastic insert that holds t he mercury
switch in place.

3 REMOVE YOUR OLD THERMOSTAT

Remove the cover of the old thermostat. If the cover
does not snap off when pulled firmly from the bottom, look for screw(s) to loosen to unlock the cover. Before removi n g
the old thermostat from the wall, look at it carefully to locate the heat anticipator adjustment mechanism. Look at the illustration to help you recognize the heat anticipator. Make a note here ______________ of that anticipator setting for use in St ep 7. Th e heat ant icipator po inter, if adjustable, will be set at one of a series of numbers representing the electrical current rating of the primary control in your furnace: .2, .4, .8, etc or 0.2,
0.4, 0.8, etc. If no heat anticipator/indication is showing, go on to the next step. Loosen screw(s) holding the thermost at base to the
subbase or wall and lift it away.
® U.S. Registered Trade m ark Copyright © 1999 Honeywell Inc. • •All Rights Reserved
THE ROUND® CREATIVE SERIES Y460A2003 THERMOSTAT
Disconnect wires from
the old thermostat subbase. Wrap the wires around a pencil or other object, as shown, to prevent them from falling back into the wall opening.
NOTE: As you disconnect each wire, use masking
tape to tape the end and label with the letter of the terminal designation to allow easier recon­nection to the new subbase.
Keep the old thermostat for reference until your new
thermostat is functioning correctly.
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of it properly.
Contact your local waste management authority for instructions regardi ng recy cl ing and th e prop er disp osal of the old thermostat. If you have questions, call the Honeywell Customer Response Center at 1-800-468-
1502.
or
WIRES THROUGH WALL OPENING
M5136
MOLDED POST (2)

4 MOUNT THE SUBBASE

IMPORTANT:
Install your thermostat about 5 ft (1.5m) a bove the floor in an area with good air circul ation at average temperature. Do not instal l i t wher e it may be affected by:
drafts, or dead spots behind doors and in
corners.
hot or cold air from ducts.radiant heat from sun or appliances.concealed pipes and chimneys.unheated (uncooled) are as s uch as a n outsi de
wall behind the thermostat.
Bring the thermostat cable through the subbase
entrance hole. Fasten the subbase to the wall or outl et box with the
mounting screws as shown in the illustrat ion.
OPENING FOR THERMOSTAT WIRING (PLUG) (WITH INSULATION)

5 WIRE THE SUBBASE

NOTE: All wiring must comply with local electrical
OUTLET BOX
1
Q539 SUBBASE
Y460
THERMOSTAT CABLE
CAPTIVE MOUNTING
USE Q539 SUBBASE FOR HEAT AND/OR COOL
1
APPLICATIONS WITH SWITCHING.
Tighten the screws aft er using a spirit level or plumb line to accurately level the subbase. It must be level to maintain accurate calibration.
PLUMB LINE MARKERS
Follow the instructions provided by the heating or heating/cooling equipment manufacturer. If not available, refer to the thermostat wiring diagram.
SCREWS (3)
ENTRANCE HOLE
MOUNTING HOLE (3)
M13417
SPIRIT LEVEL
MOUNTING SLOT (3)
M13415
codes and ordinances.
1
Q539 SUBBASE
Y460
CAPTIVE MOUNTING
USE Q539 SUBBASE FOR HEAT AND/OR COOL
1
APPLICATIONS WITH SWITCHING.
69-1358 2
SCREWS (3)
WALL
THERMOSTAT CABLE ENTRANCE HOLE
M13416

Wire the Subbase

Refer to the illustration to str ip the thermostat wire
insulation from the wire where it connects to the terminal, as necessary. Refer to the labels you placed on the wires when you
removed the old thermostat. Match the letter of your old thermostat wire with the corresponding terminal letter on your new thermostat. Connect the wires to the matching terminals on the
subbase. If your old thermostat had an R terminal, and your new one has RC and RH terminals, connect the old wire R to terminal RH, and add a small piece of wire to use as a jumper t o c onnect RC to RH. The drawing shows how to jumper RC to RH.
THE ROUND® CREATIVE SERIES Y460A2003 THERMOSTAT
G
R
H
R
C
W
Firmly tighten the screws.
Push the excess wire back into the wall.
Plug the hole with nonflammable insulation to
prevent drafts from affecti ng the thermostat operation.
Y460A for heating/cooling system using separate RC­RH terminals. If old thermostat has single R terminal, refer to jumper drawing in Subbase Wiring procedure.
HEAT
F
F
O
COOL
R
H
R
C
2
FAN RELAY
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
IN HEATING, THE FAN IS CONTROLLED BY ANOTHER CONTROLLER,
2
SUCH AS A HONEYWELL L4064 FAN AND LIMIT CONTROLLER OR FAN TIMER.
SHOWS VOLTAGE RATING
SHOWS ANTICIPATOR SETTING
8406
V8043E 1004 4 24V 50/60CY .32 AMP
ZONE VALVE
If the current rating is still unavailable:
Remove the W wire from the subbase.
G
Y
W
HEATING RELAY OR VALVE COIL
@ 60CY
Y
EXAMPLE: FOR RC TO RH JUMPER, STRIP WIRE END LONG ENOUGH TO JOIN BOTH TERMINALS.
M1277A
FAN
ON
AUTO
COOLING CONTACTOR COIL
1
SHOWS VOLTAGE RATING
FROM MAIN FUEL SUPPLY
M13418
TYPICAL GAS VALVE

6 MOUNT YOUR THERMOSTAT

Set the heat anticipator indicator to 1.2 before
mounting to prevent the anticipator from burning out during installation.
1.0 .8
.6
.5
.4
.3
SCALE
HOLE SUITABLE FOR PENCIL POINT TO MOVE INDICATOR
Align the thermostat over the subbase and tighten
the three captive mounting screws (see Step 4). These captive mounting screws complete th e electrical connections to the ther mostat.
.2
.12
.15
LONGER

7 SET HEAT ANTICIPATOR INDICATOR

Be sure the thermostat adjustable heat anticipator is
set correctly to accuratel y control the temperature. An incorrect setting (if too high) can result in wide room temperature swings or (if too low) burn out the anticipator, which voids the thermostat warranty. Make sure you have the current draw (anticipator
setting) for your system. This is the number you wrote in the box in Step 3. If you were unable to find the current draw for Step 3, this information can be found printed on the p rimary co ntrol at t he fur nac e or boiler. The primary control is usually a gas valve, a relay or burner control box, Aquastat® Controller or zone valve with the thermostat wires connected to it. These controls are usually located behind the furnace cover; see the illustration.
OIL BURNER CONTROL
SHOWS CURRENT DRAW
TO
24 Vac 50/60 Hz
0.4 AMP
Connect one probe of an ac ammeter (0 to 2.0A,
for example) to the W wire and connect the other probe to the W terminal.
BURNER
SHOWS ANTICIPATOR SETTING
HEAT ANTICIPATOR INDICATOR
M1368
SHOWS VOLTAGE
30 VAC
RATING
0
.2
A
M
P
T T F F
M6116B
3 69-1358
THE ROUND® CREATIVE SERIES Y460A2003 THERMOSTAT
Let the system operate through the ammet e r for
at least one minute before taking a reading. Record the reading here ______________ .
Reconnect the W wire to the W terminal. Move the heat anticipator indicator to match the
number you recorded in Step 3 or in Step 7.
NOTE: Hot water and steam systems require you to
multiply the current rating times 1.3. For elec­tric heat systems, add the fan relay current, usually 0.2A to 0.4A.
Snap the cover ring over the thermostat dial.

8 SET THE TEMPERATURE

Turn the transparent dial until the desired point on
the setting scale is aligned with the point er , as shown in the illustration.
IMPORTANT:
During a call for heat or cool, an electrical spark can be seen through the colored decorator cover ring. Do not be alarmed; this is normal operation for a mercury switch.

Set Subbase Switch

CAUTION
Equipment Damage Hazard. Can cause permanent damage to the compressor.
Do not rotate the thermostat dial back and forth just to observe the electrical spark; observe the compressor five-minute minimal-off period.
To operate the heating system, set the subbase
System switch to Heat. To operate the cooling system, set the subbase System switch to Cool. Set it to Off if you want neither heating or coo li ng. Set the Fan switch to On for continuous fan
operation or to Auto for fan opera ti on during heating or cooling cycles.
TEMPERATURE SETTING
7
0
0
6
8
0
0
5
5
0
0
8
6
0
0
7
THERMOMETER
M13419

9 CHECK OUT THE SYSTEM

Heating

Turn down the temperature setting to the lowest
point. Move the System switch to Heat. Raise the temperature setting above room temperature; the heating equipment should start. Lower the temperature setting below room temperature; the heating system should stop.

Cooling

CAUTION
Equipment Damage Hazard. Can cause permanent damage to the compressor or other equipment.
To avoid possible compressor damage, allow the compressor to re main off for fi ve minutes before restarting.
To avoid possible equipment damage, do not operate cooling when the outs ide temperat ure is below 50°F (10°C).
See equipment manufacturer instructi ons.
CAUTION
Equipment Damage Hazard. Can cause permanent damage to the compressor.
Do not rotate the thermostat dial back and forth just to observe the electrical spark; observe the compressor five-minute minimal-off period.
Turn up the temperature set ti ng to the highest point.
Move the subbase System switch to Cool. Lower the temperature setting below the r oom temperat ure; the cooling equipment should start. Raise the tempera­ture setting above the room t emperatur e; th e cooli ng system should stop.

WARRANTY

Honeywell warrants this product, excluding battery, to be free from defects in the workmanship or ma terials, under normal use and service, f or a period of one (1) year from the date of purchase by the c onsumer. If, at any time during the warranty period, the product is defective or malfunctions, Honeywe l l shall repair or replace it (at Honeywel l s option) within a rea­sonable period of time.
If the product is defective,
i. return it, with a bill of sale or other dated proof of pur-
chase, to the retail er from which you purchased it, or
ii. package it carefully, along with proof of purchase
(including date of purchase) and a short description of the malfunction, and mail it, postage prepaid, to the fol­lowing address:
Honeywell Inc . Return Goods Depa rtment 1050 Berkshire Lane Plymouth, MN 55441-4437
This warranty do es not cover removal o r rei nstallation cost s. This warranty shal l not apply if it is shown by Honeywell that the defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer.
69-1358 4
THE ROUND® CREATIVE SERIES Y460A2003 THERMOSTAT
Honeywells sole responsibility shall be to repair or replace the product within the terms stated above. HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CON SE Q UENT IAL DAMAGES RESUL TIN G, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. Some states do not al l ow the exclusion or lim itation of inciden­tal or consequential damages, so this li m i ta tion may not apply to you.
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WAR­RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE
ONE YEAR DURATION OF THIS WARRANTY. Some states do not allow limit ations on how long an implied warranty lasts , so the above lim i tation may not app l y t o yo u.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state.
If you have any questions concerning this warranty , pl e ase write our Customer Assistance Center, Honeywell Inc., P.O. Box 524, Minneap ol i s, MN 55440-0524 or c al l 1-800-468­1502, Monday-Friday, 7:00 a.m. to 5:30 p.m., Central time. In Canada, write Retail Product s ON15-02H, Hone ywell Limited/ Honeywell Limi t ée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.
5 69-1358
Home and Building Control Home and Building Control
Honeywell Inc. Honeywell Limited-Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P.O. Box 524 North York, Ontario Minneapolis, MN 55408-0524 M2H 3N7
69-1358 G.H. 12-99 Printed in Mexico www.honeywell.com
Loading...