Honeywell Y343B1002 User Manual

Page 1
Honeywell
THE Y343B IGNITION PACKAGE PROVIDES DIRECT SPARK IGNITION (DSI) FOR GAS HEATING SYSTEMS. THE PACKAGE IN CLUDES THE S87D ELECTRONIC MODULE, Q354A FLAME SENSOR, Q347A SPARK IG NITER-SENSOR AND 392286-1 IGNITION CABLE.
SOLID STATE DESIGN □ Compact, solid state components provide accurate, long-lasting performance. □ No mechanical friction or wear.
MAXIMUM OPERATING SAFETY □ Proves presence of flame on burner igni tion, then protects against burner flame-out and interruption of electric power or gas sup ply during run cycle. □ Open or short circuit in any electronic com ponent results in safety shutdown.
USES FLAME RECTIFICIATION PRINCIPLE □ Any false flame signal, including electrical short or ground, results in safety shutdown. □ Ignition is started, main burner is ignitied, burner flame is proved and continuously monitored during main burner-on period. Ig nition spark is discontinued when flame is proved.
CONVENIENT REMOTE RESTART PROCEDURE □ After safety shutdown, equipment must be manually reset from remote thermostat or temperature controller. □ System automatically locks out after trial-for-ignition. If malfunction exists, correc tion must be made before system is manually reset.
LOW VOLTAGE CONTROL CIRCUIT □ Permits use of 24 V thermostat for op timum temperature control. □ Reduced wiring costs — both on appliance and on job.
GAS VALVE CONTROL □ S87D internal relay switches the gas valve on and off. □ System can be used with a 2-stage gas valve, if desired.
ALARM CONTROL □ Optional alarm circuit provides 24 Vac for an automatic visual or audible signal if any part of system malfunctions and causes a lockout.
L.H. 1-83»
Form Number 68-0014
©Honeywell Inc. 1983
Y343B1002
Page 2
The Y343B1002 Direct Spark Gas Burner Ignition Package includes the S87D Electronic Module, Q347A Spark Igniter-Sensor, Q354A Flame Sensor and 392286-1 Ignition Cable Assembly.
Other controls needed to complete the heating sys tem include a 24 V, DSI gas valve; 24 V thermostat: 24 V transformer and high temperature limit controller.

S87D CONTROL MODULE

The S87D contains the electronic components of
the system and also serves as a central v\/iring panel for the external controls. Powered by a 24 V trans former and controlled by a thermostat, it performs the following functions.
1. Checks for a false flame condition (short to
ground). Module will lock out if false flame condition is present.
2. Generates a potential of 15,000 V (open circuit)
at the spark-igniter stud for direct ignition of the main burner.
3. Operates gas valve (internal relay controls inde
pendent gas valve circuit).
4. Senses the presence of main burner flame and
discontinues ignition spark. If the burner fails to ignite within the trial-for-ignition period, safety lockout oc curs.
5. If there is a loss of power, the system will shut
down safely. Start-up is initiated when power is restored.
6. If there is a loss of main burner flame, the timed
trial-for-ignition is repeated. Safety shutdown occurs if flame is not reestablished within the trial-for-ignition
period.
7. Normally closed contacts in internal relay may
be used for an alarm circuit to signal safety shutdown
of system.
ELECTRICAL RATINGS:
Voltage and Frequency—24 Vac, 60 Hz. Current Rating—0.2 A plus gas valve current draw.
SAFETY LOCKOUT TIMING: 11 seconds. FLAME FAILURE REIGNITION TIME: 0.8 seconds
maximum.
FLAME CURRENT SIGNAL REQUIRED: 1.5 pA dc
minimum.
SPARK GENERATOR VOLTAGE: 15,000 V open
circuit. MOUNTING: Mounts in any position. See Fig. 1. DIMENSIONS: See Fig. 1.
FIG. 1—DIMENSIONS FOR S87 IN in. [mm IN
BRACKETS].
(continued on page 3)
ORDERING INFORMATION
WHEN PURCHASING REPLACEMENT AND MODERNIZATION PRODUCTS FROM YOUR TRADELINE WHOLESALER OR YOUR DISTRIBUTOR, REFER TO THE TRADELINE CATALOG OR PRICE SHEETS FOR COMPLETE ORDERING NUMBER, OR SPECIFY—
Combination gas control (for DSI
1. Order number Y343B1002.
2. Safety lockout timing (11 seconds).
3. DSI system controls, as required. a. 24 V, 60 Hz transformer. b. Low voitage thermostat or temperature controller.
IF YOU HAVE ADDITIONAL QUESTIONS, NEED FURTHER INFORMATION, OR WOULD LIKE TO COMMENT ON OUR PRODUCTS OR SERVICES, PLEASE WRITE OR PHONE:
1. YOUR LOCAL HONEYWELL RESIDENTIAL SALES OFFICE (CHECK WHITE PAGES OF YOUR PHONE
DIRECTORY).
2. RESIDENTIAL DIVISION CUSTOMER SERVICE HONEYWELL INC., 1885 DOUGLAS DRIVE NORTH MINNEAPOLIS, MINNESOTA 55422 (612)542-7500
(IN CANADA—HONEYWELL LIMITED/HONEYWELL LIMITEE, 740 ELLESMERE ROAD, SCARBOROUGH, ONTARIO M1P 2V9). INTERNATIONAL SALES AND SERVICE OFFICES IN ALL PRINCIPAL CITIES OF THE
WORLD.
c.
application). High iimit temperature controiler and
d.
auxiiiary safety controis.
Aiarm signai (if required).
e.
Page 3
AMBIENT TEMPERATURE RATING: Minus 40 F to
plus 175 F [minus 40 C to plus 79 C].
WIRING CONNECTIONS: 1/4 in. [6.4 mm] male
quick-connect terminals, for all except ALARM ter minal. ALARM terminal, 1/4 in. [6.4 mm] female quick-connect. 1/4 in. [6.4 mm] diameter stud base for ignition cable.
REPLACEMENT PARTS: 3 A fuse.

Q347A SPARK IGNITER-SENSOR

The Q347A, powered by the S87D Electronic Mod
ule, produces a spark for direct ignition of the main burner. The Q347A consists of an inner electrode (insulated rod) and an outer electrode (rigid, formed strap bent at end to extend over tip of inner rod). Tip of electrodes extend into path of main burner gas; arcing across spark gap ignites gas.
SPARK GAP: 5/32 in. [4 mm]. LENGTH OF ELECTRODE ASSEMBLY (mounting sur
face to tip): 2-3/8 in. [60.3 mm].
ELECTRODE MATERIAL: Kanthal. MAXIMUM TEMPERATURE RATINGS: 1800 F [982 C]
at tip of electrode assembly, 1250 F [677 C] at ceramic insulator.
WIRING CONNECTION: 1/4 in. [6.4 mm] diameter base
stud for ignition cable. MOUNTING: Bracket, see Fig. 2. DIMENSIONS: See Fig. 2.

Q354A FLAME SENSOR

The Q354A consists of a flame rod supported in a ceramic insulator with mounting bracket. Positioned so that the end of the flame rod is immersed in the main burner flame, and with the burner head serving as the ground area, it operates on the flame rectification principle. In the presence of main burner flame, a direct current is established to prove burner ignition and to continuously monitor the flame during the burner-on period.
MAXIMUM TEMPERATURE RATING: 2200 F [1204 C]
at tip of rod, 1250 F [677 C] at ceramic insulator. WIRING CONNECTION: 1/4 in. [6.4 mm] male
quick-connect terminal.
FLAME ROD MATERIAL: Kanthal. MOUNTING: Bracket, see Fig. 3. DIMENSIONS: See Fig.3.
BRACKETS] OF Q347A.
FIG. 3—DIMENSIONS IN in. [mm IN BRACKETS] OF
Q354A.

392286-1 IGNITION CABLE

This cable is used to connect the Q347A Spark Igniter-Sensor to the S87 Electronic Module. CABLE: No. 16 gauge high tension, 485 F [251 C]
heated, oil resistant. LENGTH: 30 in. [762 mm]. CONNECTORS (2): 1/4 in. [6.4 mm] diameter spring
clip type with insulating boot. Two straight boots.

GAS CONTROLS

Combination gas controls are directly controlled by the internal relay in the S87D. Maximum electrical rating for DSI gas valve control is 2.0 A. See individual publication for complete specifications and installation instructions on the following recommended gas controls.
68-0014
Page 4
TABLE 1—GAS CONTROLS.
CAPACITY RANGE OF
TYPE OF PRESSURE
MODEL NO.
V845A VR8450A V845C Step-open VR8450C Step-open noto 290 3.1 to 7.8 VR8540A VR8590A VR8600A
REGULATOR
Standard noto 335 3.1 to 9.5 60-2315 Standard noto 290 3.1 to 7.8 68-0016
Two-stage noto 290 3.1 to 7.8 68-0021
Negative Negative 37 to 400 I.Oto 11.3 68-0017
STANDARD MODEL
cfh mVhr
noto 335 3.1 to 9.5 60-2315
37 to 400
I.Oto 11.3
PUBLICATION FORM
NUMBER
68-0016
68-0017

AUXILIARY CONTROLS

REQUIRED FOR BASIC DSI SYSTEM
1. TRANSFORMER. Select transformer with ade
quate VA. S87D requires a 24 Vac transformer. For common system transformers, capacity must be ade quate for S87D, temperature controller, gas control and any other device powered by the transformer (see Table 2).
2. LOW VOLTAGE TEMPERATURE CONTROLLER.
Select a 24 Vac thermostat for single-stage or
two-stage burner control (depending on heating sys tem).
DETERMINED BY PARTICULAR APPLICATION
Refer to separate publications for information on the
controls utilized by the appiiance manufacturer. These
INSTALLATION
WHEN INSTALLING THIS IGNITION PACKAGE. ..
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure it is suitable for your application.
3. The installer must be a trained, experienced
service technician.
4. After installation is complete, check out system
operation.
controis are:
1. High iimit temperature controlier and other safety
controis as required.
2. Gas vaive. Refer to Tabie 1 above.
3. Alarm signal as desired for the circuit under
control of the S87D.
CAUTION
1. When using a common transformer to power both S87D and gas control circuit, use a good quality transformer of adequate VA. If trans
former VA is inadequate, the S87D internal relay may chatter.
2. When two or more transformers are used, they
must be properly phased and grounded.

S87D CONTROL MODULE

Select a location within 30 in. [762 mm] maximum of the burner that will permit a direct cable route to the Q347A spark igniter. Ready access to the terminals is necessary for wiring and servicing. Do not exceed the ambient temperature rating given in the SPECIF ICATION section.
The S87 may be mounted in any position. See Fig. 1 for mounting dimensions. Use No. 6-32 machine screws or No. 8 sheetmetal screws 1 in. long for fastening. Fasten securely.
CAUTION
1. Disconnect power supply before wiring to pre vent electrical shock or equipment damage.
2. If a new gas control is to be installed, turn off gas supply before starting installation. Be sure to conduct a Gas Leak Test after the gas control is installed (follow manufacturer’s instructions).
IMPORTANT-
If this is a replacement application, follow the
appliance manufacturer’s instructions. The manu facturer usually provides wiring diagrams, start-up and checkout instructions and service
procedures for their system. If manufacturer’s instructions are not available, the information below may be used as a general guide.

Q347A SPARK IGNITER-SENSOR

The Q347A should be rigidly mounted in an ac
cessible location. It must remain in a fixed position relative to the main burner. The Q347 may be mounted on a separate bracket or on the same bracket with the Q354A Flame Sensor. On multiple burners, the 0347
may be mounted at one end of the row and the 0354 at
the other end to delay spark cutoff until all burners are ignited.
IMPORTANT-
The ignition cable limits the distance between the
0347 and S87 to 30 in. [762 mm] or less. This may affect the location selected for the 0347 and/or S87. Ignition cable must not touch grounded
object or current-carrying wires.
Page 5
Position the Q347 so that only the tips of the elec
trodes are immersed in the burner flame. The burner must ignite smoothly — usually this will be ac complished with tip of electrodes (spark gap) spaced approximately 1/4 in. [6.4 mm] from the surface of the burner. Gas must flow into one of the three open sides of the spark gap (where outer electrode does not block gas). The center electrode must not be near any ground.
The spark gap is factory-adjusted to 5/32 in. [4 mm]. If this setting is disturbed in shipment or installation, readjust by carefully bending the bent tip of the ground (outer) electrode only.

Q354A FLAME SENSOR

The Q354 should be rigidly mounted in an accessible
location. It must remain in a fixed position relative to the main burner. Mount the Q354 on a separate bracket or on the same bracket with the Q347 Spark Igniter.
Tip of rod must be immersed in main burner flame.
Depth of immersion (usually about 1 In. [25.4 mm]) and distance from rod to burner surface (usually 1/4 in. [6.4 mm]) depends on type of burner and flame configura
tion. Position selected must produce sensor current of
1.5 microamperes (minimum). See Fig. 9, Page 10, to measure current.
The main burner serves as the grounding area for the flame signal. Install ground wire from the main
burner to the ground terminal of the S87D.

WIRING

■GENERAL PRECAUTIONS-
1. Check the wiring diagram furnished by the appliance manufacturer, if available, for circuits differing from the ones shown in this publication. Carefully follow all instructions af fecting the general procedures outlined below.
2. All wiring must comply with applicable elec trical codes and ordinances.
3. Disconnect the power supply before wiring to prevent electrical shock and equipment damage.
4. The flame sensor leadwire should be kept as short as possible and should not be allowed to rest against grounded metal surfaces.
5. A common ground is required for the S87D Electroic Module, Q347A Spark Ig niter-Sensor, Q354A Flame Sensor and main burner. The S87 ground (GND) terminal in ternally grounds one side of the transformer. Any auxiliary controls or limits used must not be in the grounded leg.
6. Ignition cable should not touch any metal sur
face or current-carrying wires. It must not be more than 30 in. [762 mm] long.
7. Do not short valve terminals as this may burn out the temperature controller or the transformer.

AUXILIARY CONTROLS

CAUTION
1. If a common transformer is used to power both the S87D and the burner valve circuit, its capacity (VA) must be adequate for all of the system components (see Table 2).
2. Turn off gas supply before beginning installa
tion. After Installing gas control, be sure to conduct Gas Leak Test, page 8.
Install the auxiliary controls required in the complete
control system, following the instructions of the ap pliance or control manufacturer.
TABLE 2—TRANSFORMER RATINGS FOR
S87D AND DUAL VALVE COMBINATION
MINIMUM
VA
RATING CURRENT
(24 V transformer)
20 30 40 1.1 to 1.4 55 1.5 to 2.0
GAS CONTROL.
TOTAL
VALVE S87D
(in amperes)
Up to 0.6 0.2
0.7 to 1.0
CURRENT
(in amperes)
0.2
0.2
0.2

S87D CONTROL MODULE

1. Connect the system components to the S87D
quick-connect terminals as shown in the wiring dia grams. Refer to the appliance manufacturer's instruc tions for wiring any other auxiliary controls.
2. Adjust thermostat heat anticipator to match system current draw. The current draw equals the total current required for the S87D (0.2 A) plus the gas valve. Gas valve must be designed for DSI application.

Q347A SPARK IGNITER AND IGNITION CABLE

1. Connect the GND burner, quick-connect terminal
on the S87D to one of the mounting screws on the Q347A as shown in Fig. 4. The S87 and 0347 must have a common ground. Use thermoplastic insulated wire
with a minimum rating of 105 C [221 F] for the ground wire; asbestos insulation is not acceptable. If neces
sary, use a shield to protect the wire from radiant heat generated by the burner.
2. Connect one end of the ignition cable (supplied
with the Y343B package) to the ignition terminal on the
S87 and the other end to the Q347. NOTE: Ignition cable must not run in contact with a
metal surface or current-carrying wires. Use ceramic
or plastic standoff insulators to protect voltage to
spark electrode from being reduced. If cable passes through a metal panel, use an insulated bushing in the panel to prevent voltage reduction to spark electrode.
68-0014
Page 6

Q354A FLAME SENSOR

1. Mate quick-connect terminals (1/4 in. [6.4 mm})' are provided on both the Q354 and S87D. Connect the SENSOR terminal on the S87 to the terminal on the Q354 as shown in Fig. 4. Use thermopiastic insulated
wire with a minimum rating of 105 C [221 F] for the fiame sensor ieadwire; asbestos insulation is not acceptabie.
The auxiliary controls (transformer, thermostat, limit) must be connected to the 24 V terminal, gas valve must be connected to the VALVE terminals and the alarm control to the ALARM terminal on the S87D. Only one side of the transformer secondary can be connected to the 24 V (GND) terminal. A short to ground could cause the system to malfunction.
Connect the system transformer, thermostat, high
temperature iimit controller, combination gas valve and alarm (if used) as shown in Fig. 4.
FIG. 4—WIRING HOOKUP FOR Y343B PACKAGE IN A
TYPICAL DSI HEATING SYSTEM.
FIG. 5—WIRING HOOKUP FOR Y343B PACKAGE IN A TYPICAL HEATING- COOLING SYSTEM.
Page 7
FIG. 6—WIRING HOOKUP FOR Y343B PACKAGE IN A TYPICAL TWO-STAGE DSI HEATING SYSTEM.
A \ POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
/ 2\ ALTERNATE LIMIT CONTROLLER LOCATION.
A 3 A REPLACEABLE FUSE.
FIG. 7—S87D SIMPLIFIED SCHEMATIC DIAGRAM.
- INTERNAL WIRING
-EXTERNAL WIRING
ANY DUAL VALVE
• - O AS COWTROL—-
68-0014
Page 8
The following start-up and checkout procedures are
basic to the S87. If possible, refer to the specific
instructions provided by the appliance manufacturer
since the appiication and controls used may differ.
NOTE: If one of the system components fails, the S87
will either not operate or it will go into safety iockout (depending on the type of failure). If the system does not perform as outlined in START SYSTEM and CHECK SAFETY LOCKOUT steps below, refer to the SERVICE section to determine the cause.

START SYSTEM

1. Turn on power and gas suppiy.
2. Perform the following Test for Gas Leaks.
VZ;m777777777777777777777777777r7777rT7^

CHECK SAFETY LOCKOUT

1. With the system power off and the temperature
controller set to call for heat, manually shut off the gas supply.
2. Turn power on to energize the S87 and begin
spark ignition. Immediately start timing.
3. Determine the number of seconds to safety
lockout (spark cutoff). It should not exceed the time shown in Table 3.
TABLE 3—S87 LOCKOUT TIMES.
SPECIFIED S87 LOCKOUT
TIME (stamped on
S87 Control Module)
11.0 sec.
SAFETY LOCKOUT TIME
SHOULD NOT EXCEED—
15.0 sec.
W/W////////////////////////////////A
DO NOT OMIT THIS TEST.
With main burner in operation, paint pipe joints, gas tubing connections, and valve gasket lines with rich soap and water solution. Bubbles in dicate gas leaks. To stop leak, tighten joints and/or screws, or replace gasket. Never use a flame to check for gas leaks.
3. Set temperature controller to call for heat and watch for spark at the igniter. Time the length of the spark operation; it must be within the lockout timing period (see Table 3).
4. Check that the system starts as follows: Spark turns on, gas valve opens at once, and burner ignites after gas reaches the main burner. Once burner flame is established, spark igniter shuts off.
NOTE: If the gas control has been replaced or serviced,
lightoff may not be satisfactory until air has been purged from the gas line or the gas input and combustion air have been adjusted (see manufac turer’s instructions).

OPERATION

4. After spark cutoff, manually reopen gas supply
cock. No gas should flow to the main burner.
5. Reset system as described below.

RESET S87 AFTER SAFETY LOCKOUT

If the control goes into safety lockout, it will remain
locked out until the system is reset.
To reset the system, adjust the thermostat setting
below room temperature, wait 30 seconds, and move
the thermostat setting up to call for heat. Normal
ignition should occur as described in START SYSTEM,
above.

CHECKOUT

Start system and observe operation through at least
one complete cycle to make certain all controls are operating safely.
OPERATION
The S87D is powered by a 24 Vac transformer and
activated when the temperature controller calls for heat. Operation is as follows (refer to Fig. 8).
When the S87 is activated, an internal transformer
provides power to the electronic generator circuit for
spark ignition and the safety lockout timing begins. At the same time, the S87 opens the gas control’s main valves which allows gas to flow to the main burner.
Power is supplied to the generator until:
• the main burner lights and flame sensor current
reaches 1.5 uA, or...
• the safety lockout timing period ends.
If the main burner lights, a circuit is completed through the flame to the burner head to ground. This current flow returns the safety lockout timer to the reset (normal) condition and interrupts the spark ignition
circuit. Should the current flow be interrupted; i.e., flame-out condition, the trial-for-ignition begins again.
The S87 will keep the gas control main valve open as
long as there is a call for heat and current through the flame sensing circuit. If, however, the safety lockout timing period ends before the main burner lights or the flame sensor establishes enough current, the system will go into safety lockout.
When the system goes into safety lockout, power to
the generator is interrupted, the gas control circuit is
interrupted and the alarm relay circuit is completed. The system will stay locked out until it is reset by
moving the thermostat set point below room tem
perature, no call for heat, for 30 seconds.Then, re-energize the system by moving the thermostat set point 5 F [2.8 C] above room temperature.
Page 9
1J TEMPERATURE CONTROLLER
CALLS FOR HEAT
POWER INTERRUPTION >
-1
SVSTLM SHUTS OFF, RESTARTS WHEN
i
/ SVS'
POw
POWER IS RESTORED.
SPARK GENERATOR POWERED
0
MAIN VALVE OPERATORS OPEN
I IF FLAME CURRENT SENSED
MAIN BURNER OPERATION
TEMPERATURE CONTROLLER
SATISFIED
FIG. 8—NORMAL SYSTEM SEQUENCE OF OPERATION.
• IMPORTANT -
1. Only persons trained and experienced in DSI
systems should service this equipment.
2. If a condition exists that causes the S87D electronic module to go into safety lockout, meter readings must be taken quickly after restart — within trial-for-ignition period.
3. Always de-energize the system for at least 30 seconds before recycling for further tests.
4. The S87D electronic module cannot be re paired. If the troubleshooting procedure in dicates a malfunction in the S87, it must be replaced.
5. The following service procedures are for the S87 and basic DSI systems. On all installa tions, refer to the appliance manufacturer’s service instructions.

PRELIMINARY CHECK

The following checks should be made before trou
bleshooting the system.
1. Check for power to the heating appliance and the
S87D.
2. Check fuse on S87D electronic module and re
place if blown.
3. Make certain that the manual shutoff gas cock in
the supply line and on the combination gas control valve are open.
4. Make certain that all wiring connections are clean
and tight.
5. Make certain the S87 is not in safety lockout. De-energize the system by moving the thermostat set point below room temperature. Wait at least 30 seconds
and re-energize the system by moving the thermostat set point 5 F [2.8 C] above room temperature.
6. Check ceramic insulator on flame sensor and
spark igniter. A cracked insulator will allow current to leak to ground. Replace device If insulator is cracked.
7. Check the flame sensor and its mounting bracket.
Correct the position if bent out of shape.
8. Review the S87 normal sequence of operation.
See START SYSTEM section.
IF NO SPARK. S87 GOES
INTO LOCKOUT AFTER \ TIMING PERIOD. SVSTEM I MUST BE RESET 7
IF FLAME CURRENT NOT SENSED
K

S87D COMPONENT CHECKS

SPARK IGNITION CIRCUIT
The step-up transformer in the S87 provides spark
ignition at 15,000 volts (open circuit). To check the
spark ignition circuit, proceed as follows:
1. Shut off gas supply to the gas control.
2. Disconnect the ignition cable at the S87 stud
terminal to isolate the circuit from the spark-igniter.
Prepare a short jumper wire, using heavily insulated
wire such as ignition cable.
CAUTION
Do not allow fingers to touch either the stripped end of the jumper or the stud terminal. This is a very high voltage circuit and electricai shock can result.
3. Perform this test immediately upon energizing
the system — before the S87D goes into safety lockout and interrupts the spark circuit. Touch one end of the jumper firmly to the S87 GND terminal. (DO NOT remove the existing ground lead.) Slowly move the other end of the jumper wire toward the stud terminal on the S87 to establish a spark. Pull the wire away from the stud and note the length of gap at which spark discontinues.
4. A spark length of 1/8 in. [3.2 mm] or more
indicates satisfactory voltage output. If no arc can be established or the maximum spark is less than 1/8 in. [3.2 mm], and power to the S87 input terminals was proved, replace the S87.

IGNITION CABLE

Check the electrical continuity of the ignition cable
and make certain the cable is not in contact with metal surfaces. The total cable length should not exceed 3 ft [0.9 m]. A loose connection to the spark igniter-sensor may not conduct a signal even though spark ignition is satisfactory. Check connections to the stud terminal on the S87D and the boot connection to the spark ig niter-sensor and make certain they are clean and tight.
68-0014
Page 10

GROUNDING CONNECTIONS

A common ground is required for the burner, spark igniter-sensor mounting bracket and the GND terminal of the S87. If ground is poor or erratic, safety shutdown may occur occasionally even though operation is nor­mai at time of checkout. Therefore, if nuisance shut downs have been reported, be sure to check ground connections.
Electrical ground connections at the spark ig
niter-sensor and the S87D must be clean and tight. If leadwire is damaged or deteriorated, use only No. 14 or No. 18 gauge, moisture-resistant, thermoplastic in sulated wire with 105 C [221 F] minimum rating as replacement.

FLAME SENSOR CIRCUIT

The S87D provides ac power to the flame sensor which the burner flame rectifies to direct current. If the flame signal back to the S87 is not at least 1.5 pA dc, the system will lock out.
The output of the flame sensing circuit can be checked directly on the S87D. Check the flame sensing circuit as follows.
1. Connect a meter (dc microammeter scale) in series with the sensor wire as shown in Fig. 9. Use the Honeywell W136A Test Meter or equivalent. Disconnect the sensor wire at the S87D. Connect the red (positive) lead of the meter to the free end of the sensor wire. Connect the black (negative) meter lead to the sensor terminal on the S87.
2. Restart the system and read the meter. The flame sensor current must be at least 1.5pA and steady. If the reading is less than 1.5 pA or unsteady, see LOW OR UNSTEADY FLAME CURRENT section, below.
Burner Flame
The flame sensor must be constantly immersed in flame. Check burner flame conditions as shown in Fig. 10. If necessary, improve the flame condition or relocate the flame sensor to a place on the main burner where flame conditions are better.
Flame Sensor
The flame signal is best when about 1 in. [25.4 mm] of flame rod is immersed in the burner flame. A bent flame rod or mounting bracket can affect flame signal. Bend flame rod bracket to correct position if necessary.
Excess temperature at the ceramic flame rod insulator may cause leakage to ground, decreasing the flame signal. Replace the flame sensor if the ceramic insulator is cracked, and relocate the sensor to an area of lower ambient temperature if necesary.
Electrical Connections and Shorts
Connections at the flame sensor must be clean and tight. If wiring needs replacement, use moisture­resistant No. 18 wire rated for continuous duty up to 105 C [221 Fj.
FLAME SENSOR CURRENT CHECK—USE iiA SCALE
FIG. 9—S87 FLAME CURRENT MEASUREMENT.

LOW OR UNSTEADY FLAME CURRENT

If the current to the S87D flame circuit is less than 1.5
uA or is unsteady, check the burner flame and flame sensor location and electrical connections as follows.

CHECKOUT AFTER SERVICE

Perform the following steps before leaving the job
(described in CHECKOUT section)—
• START SYSTEM
• SAFETY LOCKOUT CHECK
• SAFETY LOCKOUT RESET Also perform any other checks recommended by the
heating appiiance manufacturer if system components other the the Y343B were serviced.
10
Page 11
start the system by setting the thermostat (tem
perature controller) to call tor heat. Observe the system response and establish the type of malfunction or deviation from normal operation by using Table 4.
Use Table 4 by following the instructions in the
boxes. If the condition is true or okay (answer is yes), go
TABLE 4—S87 DIRECT SPARK IGNITION SYSTEM TROUBLESHOOTING
DIRECT SPARK IGNITION SYSTEM TROUBLESHOOTING TABLE
down to the next box. If the condition is not true or not okay (answer is no), go to the box at right. Continue checking and answering conditions in each box until a problem and/or repair is explained. After any main tenance or repair, the troubleshooting sequence should be repeated until normal system operation is obtained.
HONEYWELL MINNEAPOLIS, MN 55408 INTERNATIONAL Sales Offices in all principal cities of the world. Manufacturing in
Australia, Canada, Finland, France, Germany, Japan,.Mexico, Spain, Taiwan, United Kingdom, U.S.A.
PRINTED IN U.S.A
Loading...