The XNX™ Universal Transmitter, now with HART EDDL/DTM, marks a new turn in gas detection from Honeywell Analytics. It
supports the widest range of Sensors on a common platform and offers a modular choice of inputs and outputs. XNX is
designed for flexible integration, simple installation, user-friendly operation and straight-forward maintenance. It is ideal for use
with a range of gas monitoring controllers or industry standard PLCs. The introduction of our HART Enhanced Device
Descriptor Language (EDDL) & Device Type Manager (DTM) software provides users with an at-a-glance indication of the
health of their gas detectors in the field.
High performanceEasy to Install
- Flammable gas detection 0 to 100% LFL/LEL - 3 or 4 wire operation, source, sink or isolated
- Point IR with heated optics provides immunity
to poisoning and no hidden faults
- Open-path IR flammable gas detection in LELm measurement
- Electrochemical cell offers toxic gas detection
- IR cell provides CO2 and combustible gas
monitoring
- Robust and reliable operation in explosive
areas and harsh environments
Cost Effective
- Minimal training required - Self-test and fault indication features
- Simple plug-in Sensors and replaceable cells
- NEMA 4X IP66 rated for rugged indoor/outdoor use
- Five conduit entries for ease of installation
Easy to Use
(visual icons, colored buttons, text, etc.) to display gas and Sensor
readings
- User interface supported by 8 selectable languages (English, Spanish,
German, Italian, Portuguese, French, Russian, Chinese)
Flexible OperationCertifications
- 3 Versions - supports (Catalytic Bead and IR
Cell), Electrochemical Cell and IR (point and
open-path) gas detection
- Multi-Purpose Detector (MPD) with field
serviceable mV, Catalytic bead and IR Cell
capability
- 4-20 mA with HART® as standard - Class I Zone 1 Group IIC, Class II, Zone 20 & 21
- HART Enhanced Device Description
Language (EDDL) & Device Type Manager
(DTM) software*
- Multiple communications optionsinclude up to
3 relays, Modbus® and FOUNDATION® H1
Fieldbus
- Optional local IS port for handheld HART
configurator
- UL, CSA, FM, DEMKO, DEKRA, InMetro, TUV, ABS, HART, IELDBus
Foundation, GOST and KTL approved for Hazardous Locations, Gas
Performance and SIL 2 ratings among others
- Class I, Div 1, Groups A, B, C & D; Class II, Div 1, Groups F and G;
Hazardous Locations
- Intrinsically safe barriers for HART
and EC connections
- For additional information on certifications and approvals contact
Honeywell Analytics
AFH
NNN
2
. XNX™ Universal Transmitter
> MPD Sensor
The MPD (Multi-Purpose Detector), a low-cost Infrared or Catalytic bead sensing cell for monitoring flammable industrial gases in hazardous areas. Through the XNX, the MPD can
5
2.1 XNX Order Number and Pricing Configurator
The XNX™ Universal Transmitter is designed for flexible integration, simple installation, user-friendly operation and straight-forward maintenance. The XNX supports a wide range
of Sensors on a common platform and offers a modular choice of inputs and outputs.
> Sensor Personality>
ElectrochemicalENNone
Infrared (Optima/Excel) or 4-20 mA input (Sensepoint, etc.)
milliVoltVMModbus
IRRelay
> Enclosure Material
AluminumA
Painted Stainless SteelSN
> Agency Approval & Thread Type
ATEX/IEC M25AMNNN
UL/CSA 3/4” NPTUT
INMETRO 3/4” NPTBTCB1
> XNX Base UnitIF1
XNX Base Unit XNXIV1
Order number:
XNX
UT
Interface Options
F
E
Foundation Fieldbus
> Local HART
H
and Range
IC1
None
Local HART® Port
None*
*for milliVolt versions only (must
select 'V' sensor personality)
Catalytic Bead %LEL
IR %LEL Flammable
IR CH4 0-5% Vol/100% LEL
IR CO2 0-5% Vol
*Always used for “I” and “E” Sensor personality.
For example, the order number for an XNX (XNX-) configured for UL/CSA Approval and 3/4" NPT thread type (UT), Aluminum enclosure (A), Electrochemical
personality (E-), Foundation Fieldbus interface (F), and Local HART (H) would be XNX-UTAE-FHNNN.
sensor
Multi-Purpose Detector (MPD)
support a variety of communications protocol used in industrial communications systems.
> Agency Approval> Port Threads
ATEXAT
UL/CSA UM
INMETRO B
>MPD Base Unit
MPD Base Unit MPD
Order number:
For example, the order number for an MPD (MPD-) configured for UL/CSA Approval (U), 3/4” NPT thread type (T), and Catalytic Bead %LEL Sensor (CB1) would be MPD-
XNX MPD ATEX/IECEx IR cartridge 0-100% LEL propane (flammables)
MPD-AMIV1
XNX MPD ATEX/IECEx IR cartridge 0-100% LEL methane
MPD-AMIC1
XNX MPD ATEX/IECEx IR cartridge CO
2
0-5% VV
2
. XNX™ Universal Transmitter
6
2.2 Toxic and Oxygen Smart Sensors
A wide range of toxic and oxygen sensors, featuring patented Surecell™ and Reflex technology, are available for use with the XNX™ Universal Transmitter. Featuring
a field replaceable sensor, these sensors are shipped pre-calibrated to the range listed below.
XNX™ Sensors
t NumberDescription
Par
XNXXSO1FMOxygen (O2) 23% v/v fixed (FM approved)
2
MPD: Multi-Purpose Detector (mV) - UL/CSA (3/4 in. NPT)
Part NumberDescription
Note: When remote Mounting the MPD, Ferrite Bead (0060-1051) is required.
MPD: Multi-Purpose Detector (mV) - ATEX/IECEX (M25)
Part NumberDescription
Part Number
Description
S3KDMK
Duct mount Kit
Part Number
Description
Note: S3KDMK and 1226A0382 should be order together
1226A0411
Calibration gas flow adaptor (for use with MPD)
02000-A-1645
Calibration gas flow adaptor (for use with Sensepoint Sensors)
00780-A-0035
Calibration gas flow adaptor (for use with 705 Sensors)
02000-A-1640
Weatherproof cap (for use with MPD and Sensepoint Sensors)
02000-A-1635
Weatherproof cap (for use with 705 Sensors)
Part Number
Description
Note: must be used with SPXCDWP weather protection housing.
S3KWPWeatherproof housing (for use with corrosives)
S3KCALCalibration gas flow adaptor (for use with EC Sensors)
SPXCDCCCollecting cone for use with lighter than air gases
Replacement Toxic and Oxygen Sensor Cartridges
Sulfur dioxide (SO2) 0-15.0 ppm (5.0 to 20.0 ppm, 5 ppm); 0-50.0 ppm (20.0 to 50.0 ppm, 10 ppm)
Flow housing XNX S3K MPD, IR, cat beadSVIP3766-008
XNXCOMBKit
3. Sensepoint XRL
Sensepoint XRL is fully configurable via Bluetooth on your Android Smart Device.
Part Number
Description
SPLIC1BAXYNUZZ
SPXRL-BT-cULus-CO 300ppm-mA-YEL
Part Number
Description
SPLIC1BAXCNUZZ
SPXRL-BT-cULus-CO 300ppm-mA-CHR
10
Sensepoint XRL is a fixed point gas leak detector that is designed to meet the needs of
ndustrial applications. With over 50 years experience in gas leak detection, Honeywell
i
offers a flexible range of highly-reliable sensing devices to meet those needs.
• Quick installation
• Rapid configuration
• Simple to operate
• Straightforward to maintain
Honeywell innovation enables customers to pair the gas detector with their mobile phone,
and then use an app to perform many tasks related to installation, commissioning and
maintenance.
3.1 Instruments
Each Sensepoint XRL is supplied with registration sheet, 3/4 NPT or M20 metal stopping plug, Hex Allen key and quick start guide.
PXRL-Module Set-mA - H2S High Range
SPXRL-Module Set-mA - H
2
SPXRL-Module Set-mA - NO2 (Available Q4 2017)
SPXRL-Module Set-Modbus - O
2
SPXRL-Module Set-Modbus - H2S Low Range
SPXRL-Module Set-Modbus - H2S High Range
S
PXRL-Module Set-Modbus - H
2
SPXRL-Module Set-Modbus - NO2 (Available Q4 2017)
Sensepoint XCL/XRL Replacement Sensor - O
2
Sensepoint XCL/XRL Replacement Sensor - H2S (Low and High Range)
Sensepoint XCL/XRL Replacement Sensor - H
Sensepoint XCL/XRL Replacement Sensor - NO
2
2
• Removable plug/socket type terminal
4. Sensepoint XCD
B, C and D, Class I, Division 2, Groups B,
14
LEL, C3H8, CH4, H2S, CO, CO2, H2, NO2, O2
The Sensepoint XCD range provides comprehensive monitoring of flammable, toxic
and oxygen gas hazards in potentially explosive atmospheres, both indoors and
outdoors. Users can modify detector operation using the LCD and magnetic
switches without ever needing to open the unit. This enables one-man, nonintrusive operation and reduces routine maintenance time and costs.
One-Stop Shop
• Flammable (catalytic or infrared), toxic and
oxygen Versions available
• New and retrofit applications
• Suitable for indoor or outdoor use
• Stainless steel or aluminium explosion-proof
housing options
• IP66 as standard
Proven and Reliable Sensor Technology
• Surecell™ electrochemical Sensors
• Poison immune infrared Sensors
• Poison resistant catalytic bead Sensors
• Long life Sensors
Global Approvals
• Global approvals for US, Canada, Latin America,
Europe, China, Korea, and more
• Compliant with UL, INMETRO, ATEX, IECEx, CSA,
KTL, PA, GB and CCCF standards
Easy to Use
‑
• User friendly and intuitive tri
display with digits, bar graph and icons
• Fully configurable via magnetic switches
• Selectable sink or source 4-20 mA output
• Auto-inhibit during maintenance
• Modbus RTU communications for remote
diagnostics/configuration
colour backlit
Cost Effective
• Common transmitter platform
• Minimal training required
• Reduced spares
• Non-intrusive, one-man operation
• Plug-in Sensor replacement
• Modbus multi drop option offers
cabling savings
Simple Installation
• Plug-in display module removes to
give access to terminal area
• Integral Mounting bracket
• 2 x M20 or 3/4 in. NPT
Cable/conduit entries (certification
dependent)
blocks for ease of wiring
• Sink/source switch to suit preferred
wiring topology
Range of Optional Accessories
• Remote Sensor gassing Kit
• Duct Mounting Kit
• Calibration gas flow housing
• Collecting cone
Certifications
• UL/c-UL - Class I, Division 1, Groups
C & D, Class II, Division 1, Groups E, F &
G,
Class II, Division 2, Groups F & G. -40°C
to +65°C
• ATEX Ex II 2 GD Ex d IIC Gb T6 (Ta 40ºC to +65ºC) Ex tb IIIC T85°C Db IP66
• IEC Ex d IIC Gb T6 (Ta -40ºC to +65ºC)
Extb IIIC T85°C Db IP66
4. Sensepoint XCD
Part Number
Description
Part Number
Description
SPXCDULNFXM
UL/c-UL/INMETRO Approvals (LM25) with Modbus
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes catalytic
UL/c-UL/INMETRO Approvals (LM25)
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared carbon dioxide
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes oxygen EC
15
4.1 INSTRUMENT
SPXCDULNFX
SPXCDULNRX
SPXCDULNPX
SPXCDULNO1
SPXCDULNHX
SPXCDULNCX
SPXCDULNNX
SPXCDULNG1
SPXCDULNB1
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes catalytic sensor
cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather
protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared methane
sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather
protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared propane
sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather
protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes oxygen EC sensor
cartridge 0 to 25% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes hydrogen sulfide EC
sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather
protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes carbon monoxide EC
sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather
protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes nitrogen dioxide EC
sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather
protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes hydrogen EC sensor
cartridge 0 to 1000ppm, includes nylon weather protection
sensor cartridge 0 to 2.0% v/v, includes nylon weather protection
SPXCDULNRXM
SPXCDULNPXM
SPXCDULNO1M
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared
methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon
weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared
propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon
weather protection
sensor cartridge 0 to 25% v/v, includes nylon weather protection
4. Sensepoint XCD
Part Number
Description
SPXCDUSNFX
SPXCDUSNRX
protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared methane
protection
protection
protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes catalytic sensor
UL/c-UL/INMETRO Approvals (316SS)
weather protection
nylon weather protection
weather protection
16
SPXCDULNHXM
SPXCDULNCXM
SPXCDULNNXM
SPXCDULNG1M
SPXCDULNB1M
SPXCDUSNPX
SPXCDUSNO1
SPXCDUSNHX
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes hydrogen
sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes carbon
monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes nitrogen
dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes hydrogen
EC sensor cartridge 0 to 1000ppm, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted LM25, includes infrared
carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared propane
sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes oxygen EC sensor
cartridge 0 to 25% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes hydrogen sulfide EC
sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather
SPXCDUSNCX
SPXCDUSNNX
SPXCDUSNG1
SPXCDUSNB1
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes carbon monoxide EC
sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon weather
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes nitrogen dioxide EC
sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes hydrogen EC sensor
cartridge 0 to 1000ppm, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared carbon
dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection
4. Sensepoint XCD
Part Number
Description
SPXCDUSNFXM
Part Number
Description
SPXCDALMFX
SPXCDALMRX
carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes catalytic sensor
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared methane
weather protection
EC sensor cartridge 0 to 1000ppm, includes nylon weather protection
UL/c-UL/INMETRO Approvals (316SS) with Modbus
ATEX/IECEx/Asian Approvals (LM25)
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes catalytic
weather protection
weather protection
weather protection
nylon weather protection
17
SPXCDUSNRXM
SPXCDUSNPXM
SPXCDUSNO1M
SPXCDUSNHXM
SPXCDUSNCXM
SPXCDUSNNXM
SPXCDUSNG1M
SPXCDUSNB1M
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared
methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared
propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes oxygen
EC sensor cartridge 0 to 25% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes hydrogen
sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes carbon
monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes nitrogen
dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes hydrogen
XCD Gas Detector, 4 to 20 mA and Modbus output, UL/c-UL/INMETRO, 2 x 3/4" NPT entries, painted 316SS, includes infrared
SPXCDALMPX
SPXCDALMO1
SPXCDALMHX
SPXCDALMCX
SPXCDALMNX
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared propane
sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes nylon weather
protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes oxygen EC sensor
cartridge 0 to 25% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes hydrogen sulfide
EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes nylon weather
protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes carbon monoxide
EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution), includes nylon
weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes nitrogen dioxide
EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm (5 ppm resolution), includes nylon weather
protection
4. Sensepoint XCD
Part Number
Description
SPXCDALMFXM
Part Number
Description
SPXCDASMFX
SPXCDASMRX
hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes
nylon weather protection
nylon weather protection
nylon weather protection
includes nylon weather protection
ATEX/IECEx/Asian Approvals (LM25) WITH Modbus
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS,
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS,
includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm
ATEX/IECEx/China Approvals (316SS)
18
SPXCDALMG1
SPXCDALMB1
SPXCDALMRXM
SPXCDALMPXM
SPXCDALMO1M
SPXCDALMHXM
SPXCDALMCXM
SPXCDALMG1M
SPXCDALMB1M
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes hydrogen EC
sensor cartridge 0 to 1000ppm, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes infrared carbon
dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes
infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes
infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and 100%LEL (10%LEL resolution), includes
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes
oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes
hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between 10 and 100ppm (1 ppm resolution), includes
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes
carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and 1000ppm (100 ppm resolution),
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted LM25, includes
infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection
SPXCDASMPX
SPXCDASMO1
SPXCDASMHX
SPXCDASMCX
SPXCDASMNX
SPXCDASMG1
SPXCDASMB1
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS,
includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and
100%LEL (10%LEL resolution), includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS,
includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS,
(1 ppm resolution), includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS,
includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD between 100 and
1000ppm (100 ppm resolution), includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS,
includes nitrogen dioxide EC sensor cartridge 0 to 10ppm, user selectable FSD between 10 and 50ppm
(5 ppm resolution), includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS,
includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA output, ATEX/IECEx/Asian approvals, 2 x M20 entries, painted 316SS,
includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather protection
4. Sensepoint XCD
Part Number
Description
20% and 100%LEL (10%LEL resolution), includes nylon weather protection
20% and 100%LEL (10%LEL resolution), includes nylon weather protection
ATEX/IECEx/Asian Approvals (316SS) with Modbus
100%LEL (10%LEL resolution), includes nylon weather protection
19
SPXCDASMFXM
SPXCDASMRXM
SPXCDASMPXM
SPXCDASMO1M
SPXCDASMHXM
SPXCDASMCXM
SPXCDASMG1M
SPXCDASMB1M
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries,
painted 316SS, includes catalytic sensor cartridge 0 to 100%LEL, user selectable FSD between 20% and
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries,
painted 316SS, includes infrared methane sensor cartridge 0 to 100%LEL, user selectable FSD between
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries,
painted 316SS, includes infrared propane sensor cartridge 0 to 100%LEL, user selectable FSD between
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries,
painted 316SS, includes oxygen EC sensor cartridge 0 to 25% v/v, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries,
painted 316SS, includes hydrogen sulfide EC sensor cartridge 0 to 50ppm, user selectable FSD between
10 and 100ppm (1 ppm resolution), includes nylon weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries,
painted 316SS, includes carbon monoxide EC sensor cartridge 0 to 300ppm, user selectable FSD
between 100 and 1000ppm (100 ppm resolution), includes nylon weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries,
painted 316SS, includes hydrogen EC sensor cartridge 0 to 1000ppm, includes nylon weather protection
XCD Gas Detector, 4 to 20 mA and Modbus output, ATEX/IECEx/Asian approvals, 2 x M20 entries,
painted 316SS, includes infrared carbon dioxide sensor cartridge 0 to 2.0% v/v, includes nylon weather
protection
4. Sensepoint XCD
Part Number
Description
S3KCAL
SPXCDCC
SPXCDDMK
SPXCDMTBR
SPXCDSDP
Part Number
Description
SPXCDXSFXSS
SPXCDXSRXSS
SPXCDXSO1SS
SPXCDXSHXSS
SPXCDXSCXSS
SPXCDXSNXSS
SPXCDXSG1SS
SPXCDXSPXSS
SPXCDXSB1SS
Part Number
Description
SPXCDWP
SPXCDSRLS
SPXCDAKS
SPXCDHWES
SPXCDEBS
SPXCDMAG
Part Number
Description
SPXCDDMT
SPXCDDMF
SPXCDDMTM
SPXCDDMFM
Part Number
Description
SPXCDTMO
SPXCDTMT
SPXCDTMF
Calibration cap
Collecting cone for use with lighter than air gases, must be used with SPXCDWP
Duct mounting kit
Mounting bracket (inc. bolts, nuts, brackets)
Sunshade / deluge protection
Each replacement terminal module includes pre-configured PCB (for Sensor and range), terminals, screws, ‘U’ clamp, plastic cover and fixing
Replacement display module for oxygen (O2) & toxic
Replacement display module for FL & IR
Replacement display module (O2 & Toxic) with MODBUS
Replacement display module (FL & IR) with MODBUS
Carbon Monoxide 0-300ppm (100 to 1000ppm, 100ppm)
Nitrogen Dioxide 0-10ppm (10.0 to 50.0ppm, 5ppm)
Hydrogen 0-1000ppm only
Propane IR 0-100%LEL (20 to 100%LEL, 10%LEL)
Carbon Dioxide IR 0-2.00% v/v only
XCD TRANSMITTER (WITHOUT SENSOR)
Replacement terminal module for oxygen (O2)
Replacement terminal module for toxic
Replacement terminal module for FL and IR
Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm)
Sensepoint XCD Accessoies
Sensepoint XCD Replacement Toxic, Flammable and Oxygen Cartridges
Flammable CAT 0-100%LEL (20 to 100%LEL, 10%LEL)
Methane IR 0-100%LEL (20 to 100%LEL, 10%LEL)
Oxygen 25.0% v/v only
20
4.2 Accessories
4.3 Sensepoint Replacement Toxic, Flammable and Oxygen Cartridges
4.4 Spares (Miscellaneous)
4.5 Spares (Replacement Display Module)
Each replacement Display Module includes pre-configured PCB (for Sensor and range), backlit LCD and plastic housing. The unit is a plug in
replacement and simply requires configuration after fitting via the menu.
4.6 Spares (Replacement Terminal Module)
screws.
4. Sensepoint XCD
Part Number
Product
Components
* XCDTOXKit should be used with XCD-Flammable IR
Contains Part Numbers
21
4.7 Calibration Kits and Components
XCDTOXKitXCD Toxic Kit*
XCDCOMBKitXCD Combustibles
Kit
XCDRTDKitXCD RTD
XCDRFDKitXCD RFD
Tubing, flow adaptor, regulator,
carrying case
Tubing, flow adaptor, regulator,
carrying case
Calibration cover, potentiometer,
adjustment tool, flow housing,
regulator, tubing
Tubing, flow adaptor, regulator,
carrying case
The Sensepoint RFD is a remote flammable detection system for LEL
control panel during maintenance.
- cCSAus approved for Class I, Division 1, Groups B, C & D
- Performance approved to the following standards; C22.2-152,
SPXCDULNRFD
SPXCDULNRFDM
SPXCDUSNRFD
SPXCDUSNRFDM
SPXCDASMRFD
SPXCDALMRFD
SPXCDASMRFDM
SPXCDALMRFDM
5. Sensepoint XCD RFD
22
monitoring applications. The XCD RFD combines the XCD transmitter
with the 705 combustible Sensor, and is certified for use in Class I
Div. 1 rated areas. The XCD RFD offers one man, non-intrusive,
operation and reduces routine maintenance time and costs. The XCD
transmitter includes two programmable alarm/fault relays as well as an
industry standard 4-20 mA output, with optional Modbus RTU.
Calibration and relay operation of the transmitter may be adjusted via
the transmitters’ backlit LCD. Outputs are automatically inhibited
during adjustment thereby reducing the risk of false alarm at the
Sensepoint RFD is supplied with all necessary accessories for easy
installation. It can be mounted on a wall or 2" round support pole using
the universal bracket provided. The detector is ideal for use with either
conduit or steel wire armored cable and glands and includes both
3/4 in. NPT and M20 entries to the junction box.
Sensepoint RFD offers easy installation and fast routine operation.
Compatible with both standard and high temperature variants of the
Sensepoint and 705 flammable Sensors from Honeywell Analytics the
overall flexibility of the product range is increased. Meets Class I Div. 1
UL performance standards.
Note: Conduit and fittings not included
Certifications
Hazardous Locations.
LEL (*1–*8)
ANSI/ISA 121301
5.1 Sensepoint XCD RFD Transmitter
Transmitter - cCSAus Certified for North America (Class I, Div. 1, Groups B, C & D) - Transmitter only
Part NumberDescription
Transmitter with LM25, 3/4 in. NPT entry, aluminum
Transmitter with LM25, 3/4 in. NPT entry, Modbus, aluminum
Transmitter with 3/4 in. NPT entry, 316SS
Transmitter with 3/4 in. NPT entry, Modbus, 316SS
Transmitter - cCSAus Certified for North America (Class I, Div. 1, Groups B, C & D) - Transmitter only
Part NumberDescription
ATEX/IECEX & AP approved SP XCD RFD Transmitter with 316SS
ATEX/IECEX & AP approved SP XCD RFD Transmitter with LM25
ATEX/IECEX & AP approved SP XCD RFD Transmitter, 316SS, 2x M20 and 1x M25 entries, with ModBus
ATEX/IECEX & AP approved SP XCD RFD Transmitter, LM25, 2x M20 and 1x M25 entries, with ModBus
assembly, fitted with poison-resistant combustible gas detection elements.
Fully encapsulated, it is designed for use in hazardous locations. The Sensor is
electro-catalytic and consists of 2 beads of refractory oxide, formed on a fine
platinum wire coil. The active bead is coated with a catalyst material, while
the reference bead is glass coated. In the presence of gas, the catalyst coated
bead promotes the oxidation of the gas, causing it to heat up and increase in
electrical resistance. This change of resistance, relative to the reference bead,
can be measured and is in direct proportion to the concentration of
combustible gas.
6.1 INSTRUMENT
6.2 ACCESSORIES
02000-A-1640
00780-A-0076
02000-A-1635
02000-A-1642
Weatherproof cap for use with combustible detector including remote gassing
nozzle (for Sensepoint, Signalpoint, Satellite (with adapter), XNX MPD and Series
Stainless steel weather housing for Sensepoint HT or 705 HT (for use with in high
temperature applications or with duct mounting kits)
Weatherproof cap for use with toxic detector including remote gassing nozzle (for
Sensepoint, Signalpoint, Satellite (with adapter), XNX MPD and Series 2000)
Collecting cone for use with flammable detector (for Sensepoint, Signalpoint,
Features
• Fast response
• High resistance to catalytic
poisoning
• Low cost, high performance design
• Low Powerconsumption
• Accurate, trouble free gas
detection
• Corrosion resistant aluminum
construction
• Five year warranty
Approvals
• CSA & UL approved (705 HT UL only)
• Class I, Div 1, Groups B, C & D
705CALKIT
Calibration Kit:
Tubing, flow adaptor, regulator,
carrying case
6.3 SPARES
Contains:
‑
100‑004
998
00780‑A‑0035
998‑100‑012 (1.5LPM)
Sensor Fitted to
Remote Junction Box
Note: Conduit and fittings not included
7. Sensepoint XCD RTD
Cl2, CO, H2, H2S, NH3, NO, NO2, O2, SO2
- Reduce maintenance time and expense with non-intrusive,
25
Sensepoint XCD RTD from Honeywell Analytics makes it easy on your maintenance team, time and budget when
faced with the challenge of monitoring toxic gases in Class I, Div. 2 areas.
You can mount the unit away from the transmitter to obtain maximum gas detection coverage in areas not easily
accessible or where the Sensor would not be visible, as in high-or low-level concealed areas, or detection outside
the room being monitored. XCD RTD offers unrivaled flexibility and performance via its easily recognizable display
(traffic light pattern) to convey safety status, communication and Mounting options, and onboard diagnostics.
Reduce Cost of Ownership Over Life of the ProductGain Added Flexibility, Reliability and
Performance
- Cut stocking and procurement costs with a common
transmitter platform
one-man operation
- Simplify maintenance with plug‑in, removable Sensor
- Mount in the most difficult to access areas
- Reduce likelihood of human error via on-board
diagnostics and easy-to-read display
- Protect against dust/water ingress with IP66/67
rated stainless steel or aluminum enclosure
- Reduce inspection and training time with tri-color ‘traffic
light’ display conveying safety status at a glance
- Simplify set-up and configuration with non-intrusive
magnetic switches
Certifications
- cCSAus Ex d IIB+H2; Class I, Zone 1, AEx d
IIB+H2; Class I, Div 2, Groups B, C & D
- Class I, Zone 1, AEx d ia IIC Gb; Class I,
Div. 2, Groups B, C and D
- InMetro Ex d IIC T6 Gb, Ex tb IIIC T85ºC Db,
IP66, -40ºC < ta < +65ºC
- Prevent false alarms with auto‑inhibit during
maintenance
- Select sink or source 4-20 mA output; integral
or remote configuration
- Full range of accessories and purchase options
let you choose the remote monitoring system
that’s right for your application
- Optional Modbus RTU communications for
remote configuration
7. Sensepoint XCD RTD
7.1 Instrument
26
Sensepoint XCD RTD: Class I, Div. 2 Explosion Proof Transmitter 4-20 mA, 3 Relays) and Sensepoint Toxic Sensor
SPXCDMTBRPipe mounting bracket (inc. fixings and hex wrench set)
SPXCDSDPSunshade / deluge protection
02000-A-1635Series 2000 weather housing use with toxic Sensor
02000-A-1645Series 2000 flow housing assembly
2106B2114
For all XCD calibration kits and components, please consult the XCD product page or Calibration Kits and Calibration gas pages.
Toxic calibration kit with calibration cover, removal tool, potentiometer adjustment tool
Note: Flow housing (02000-A-1645) is required and must be ordered separately.
Part Number
Description
2106B1200
2106B1201
2106B1204
Part Number
Description
2106B2310
2106B2311
2106B2312
Note: For a complete sensor order correct number of FEEL Exe J.Box 2052D0001 and Weather Housing 00780-A-0076
Part Number
Description
2106B1700
2106B1701
2106B1702
2106B1801
2106B1400
2106B1401
8. Sensepoint Flammable and Toxic Hazardous Area
Approved Gas Detectors
Cl2, CO, H2, H2S, NH3, NO, NO2, O2, SO2
29
Sensepoint is a range of hazardous area certified combustible and toxic gas detectors
suitable for indoor and outdoor environments. The combustible version is disposable
whereas the toxic version allows users to replace the sensing element.
Certifications include
North America: cCSAus Class I Div. 2 (Toxic only)
European: ATEX
Australian: SAA
Performance approvals include
European combustible EN50054/57
European toxic pr EN45544
Casing manufactured from PPS plastic
Wiring
Combustible 3 wire mV
Toxic 2 wire 4-20 mA
Mounting thread
M20, M25, 3/4 in. NPT
Ordering information
Select gas range and thread from the following tables.
* please refer to the manual for gas specific unit and range
Note: For a complete sensor order correct number of BARTEC J.Box 00780-A-0100 and Weather Housing 02000-A-1640
Combustible Sensor - High Temperature (150°C with 3rd Party Performance Approval)