Honeywell XLS80e User Manual

XLS80e
Panel Configuration
Manual
March 2007, Issue 9
i
XLS80e Fire Alarm Control Panels
March 2007
Quick Contents Reference by
Section
XLS80e
0 1
2 3
4 5
6 7
8 9
User Menu:
3:Log/display/print menu 4:Set Clock 5:View Alarm Count 6:
Service Mon 01-May-2000 11:20:07
Configuration
User Menu:
1: 2:Disable/enable 3:Log/display/print menu 4:Set Clock
Service Mon 01-May-2000 11:20:07
Test
DISPLAY: SUMMARY - SEE SECTION DETAILED DESCRIPTION OF MENUS, SEE SECTION:
4
CONFIGURATION MENU: OVERVIEW - SEE SECTION DETAILED DESCRIPTIONS, SEE SECTION:
3
12
12 10
ALSO: TIME-OF-DAY - SEE SECTION SENSITIVITY & DELAYS RECOMMENDATIONS - SEE SECTION UPGRADING THE SOFTWARE - SEE APPENDIX AVAILABLE LOOP DEVICES - SEE APPENDIX XLSNET - SEE APPENDIX
9
13
1
2
3
POWER ON ­SEE SECTION 2
CONFIGURATION:
1: 2:Zone Text Editor 3:Panel Text Editor 4:Control Matrix Configuration
Service Mon 01-May-2000 11:20:07
Loop Device Configuration
5
6 7
CONFIGURATION:
4:Control Matrix Configuration 5:Network Configuration 6:Panel Settings 7:
Service Mon 05-DEC-2005 11:20:07
Virtual Point Configuration
14 8, 11 15
ii
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9 March 2007
Contents
1 Introduction 1
1.1 Associated Documents 1
1.2 System Design and Planning 1
1.3 Glossary of Icons 2
1.4 Software Version Number 4
1.5 EN54 Functions 4
1.6 Ancillary Functions 5
2 Power On/Start Up 7
3 Panel Configuration Overview 9
3.1 Where to Access the Configuration Actions 9
3.2 Configuration Actions 10
3.3 Using the Panel Controls and Indicators 11
3.3.1 Pushbuttons 11
3.3.2 Liquid Crystal Display 12
3.4 Using the Off-line Support Tool 13
3.5 Passcodes 13
3.6 Learn Devices on Loops 14
3.7 Configure Group of Devices 15
3.8 Configure Individual Device 15
3.9 Text Editing 16
3.10 Control Matrix 16
3.11 Time-of-Day 17
3.12 Setting the Clock 17
3.13 Panel Settings 17
3.14 System Networking 18
3.15 Delays 19
3.16 Virtual Point Configuration 19
4 The Display - Tabs, Events and
Menus 20
4.1 Introduction 20
4.1.1 Status: NORMAL 20
4.1.2 Tabs 20
4.1.3 Events 20
4.1.4 Menus 20
4.2 Tabs 21
4.3 Event Displays 22
iii
XLS80e Fire Alarm Control Panels
March 2007
4.4 Menu Displays 25
4.4.1 To Display the User Menu 25
4.4.2 To Navigate Through the Menus 26
4.4.3 Menu Structure 27
5 Loop Device Configuration 29
5.1 Configure Individual Device 29
5.1.1 Select a Device 29
5.1.2 Change Device Configuration
- Sensors 31
5.1.3 MULTI, MCS & GAS Sensitivities 37
5.1.4 Change Device Configuration
- Modules 39
5.2 Configure Group of Devices 43
5.3 Learn Devices on Loops 45
5.3.1 Starting the Procedure 45
5.3.2 Run in Auto-Learn Mode 47
5.3.3 Run in Manual Learn Mode 49
5.3.4 Error Messages 49
5.3.5 End of Learn Process 50
5.4 Change Zone Number 50
6 T ext Editing 51
6.1 Text Editing Pushbuttons 51
6.2 The Character Set 52
6.3 Zone Text Editing 52
6.4 Panel Text Editing 53
7 Control Matrix 54
7.1 Introduction 54
7.1.1 EN54 Requirements 55
7.2 Input Categories 56
7.3 Output Categories 58
7.4 Output Modes 59
7.5 Review/Edit Control Matrix 61
7.5.1 Review Entries 61
7.5.2 Edit Entries 62
7.6 Defining a Control Matrix Entry 63
7.6.1 Input Definitions 63
7.6.2 Output Definitions 69
7.6.3 Completion of New Entry 75
7.7 Disablement/Enablement Function 76
iv
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9 March 2007
7.8 Extinguishing System Function 77
7.8.1 T ypes of Control Matrix Entry 77
7.8.2 Minimum Configuration 77
7.8.3 Device Selection 78
7.8.4 HOLD Options 78
7.9 Logic Operation with Transfer Flags 79
7.9.1 Example Logic Operations 79
7.10 Print Control Matrix 81
8 Change Passcode 82
8.1 Introduction 82
8.2 How to Change a Passcode 83
9 Time-of-day Programming 85
9.1 Time-of-day Program Editing 85
9.2 Manual Override 87
9.3 DISABLEMENT and ENABLEMENT Override 88
9.4 MULTI Thermal-Only Mode 89
9.5 Link to Day/Night Switch 89
10 Setting the Clock 90
11 Panel Settings 91
11.1 Internal Buzzer Options 91
11.2 LED ‘Blinking’ Mode 92
11.3 Number of LOOPS on Panel 93
11.4 Pulsing Sounder Modes 94
11.5 Walk Test Options (MCP/Sounder) 94
11.6 Automatic Test Options 95
11.7 Disablement Options 95
11.8 Loop Options 97
11.9 Panel Functions 97
11.10 Access Level for MUTE BUZZER etc. 98
11.11 Unlatched Non-alarm Input Logging 98
11.12 Relay Circuits SILENCE Option 99
11.13 Mains/PSU Fault Delays 99
11.14 LCD Backlight ‘On’ Duration 100
11.15 Blank Lines Between Printed Events 100
11.16 Isolated RS232 Port Set-up 101
11.17 Diagnostic RS232 Port Set-up 102
11.18 Remote Fire Output Options 103
v
XLS80e Fire Alarm Control Panels
March 2007
11.19 Day/Night Modes Configuration 104
11.20 Extinguishing System 105
11.21 Alarm Coincidence 106
11.22 Network Settings 107
11.23 Thermal Alarm Verification Time 107
12 User Menu at Level 3 Access 108
12.1 Control Output Tests 108
12.1.1 CMX Modules 109
12.1.2 Local Sounder Circuits 1 10
12.1.3 Relay Circuits 110
12.1.4 Virtual Output Points 111
12.1.5 Loop Sounders and Boosters 111
12.2 Bad Poll Log 112
12.3 Display Active Control Matrix Rules 112
12.4 Unconfigured Devices Scan Menu 112
12.4 Commissioning Mode for MCS Sensors 113
13 Sensitivity and Alarm Delay
Recommendations 114
13.1 Analogue Sensors Sensitivity 114
13.2 Analogue Device Verification 114
13.3 Module Delays 115
14 Master/Slave Network 116
14.1 Introduction 116
14.1.1 Number of Stations on Network 1 1 6
14.1.2 Number of Zones on Network 1 1 7
14.1.3 Information Distribution via Network 1 18
14.2 Network Configuration Procedures 119
14.2.1 Station Type 120
14.2.2 THIS Panel 121
14.2.3 Associate Repeaters with Panel 122
14.2.4 Completion of Network Configuration 122
14.3 Print Network Configuration 122
15 Virtual Point Configuration 123
15.1 Virtual Output Points 123
15.2 Virtual Input Points 124
15.3 Virtual Output Backup Sounder 124
vi
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9 March 2007
Appendix 1 Upgrading the Panel Software A1-1
Appendix 2 Available Loop Device Types A2-1
Appendix 3 XLSNET Network Configuration A3-1
1 Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
1 Introduction
This manual provides recommended procedures for the successful configuration of a complete Honeywell XLS80e Series integrated Fire Control System (including repeater panels). The procedures also apply for XLS80e Series stand-alone Fire Control units.
The XLS80e Series intelligent fire alarm controllers are designed for use with Honeywell’s range of addressable analogue sensors, control and monitoring modules and addressable call points. A unique signalling protocol is used, with digital address and control signals and analogue pulse width monitoring for the reply data from devices.
The serial communications interface operates under RS485 protocol. It enables the connection between control panels and repeaters.
1.1 Associated Documents
This manual should be read in conjunction with the following documents:
a. XLS80e Series Installation &
Commissioning Manual
b. XLS80e Series Operating Manual
(ref. 997-474-000-x).
1.2 System Design and Planning
It is assumed that the system, of which the XLS80e Series fire control equipment is a part, has been designed by a competent fire alarm system designer in accordance with the requirements of EN54 Part 14, BS 5839 Part 1: 1988 and any other local codes of practice that are applicable.
Be aware that....
This manual is not intended to be a fire detection system design guide and should only be used by (or under the supervision of) a qualified system design engineer.
Some features of the XLS80e Series control panel may , if used inappropriately , contravene the requirements of EN54. Where there is a possibility of such an occurrence, a suitable warning is given with brief details of the EN54 requirement. A typical EN54 non-compliance warning is illustrated at left.
EN54-2: 13.7
Maximum of 512
Sensors and/or MCPs
per panel unless
ELIBs are used
2Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
1.3 Glossary of Icons
Throughout this manual, and the other related XLS80e Series manuals, a number of icons are used in the illustrations to help clarify, or simplify, p articular configuration procedures.
The following icons are used to advise or indicate:
a. DO follow the recommended procedure or
method.
b. DO NOT use this procedure or method.
c. Inspection of an item or sub-assembly is
required at this point.
d. Following a defined process meets the
required approval/inspection criteria or standards.
e. Following a defined process does not meet
the required approval/inspection criteria or standards.
f. Additional items to be considered.
g. This icon placed next to a pushbutton
requires you to press it while configuring the panel. Where two or more icons are used, a number may be placed on or near each hand to indicate the order of selection: 1 coming before 2.
h. Activity process step - flow arrow for single
action or iterative actions.
i. Leader arrow - used with activity processes.
j. Sounder operating/Sounder not operating
or silenced.
k. Internal buzzer operating/not-operating or
silenced.
l. Digital clock timer - press and hold the
applicable pushbutton for the time indicated.
00:00:03
3 Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
m. Mains power connected and switched ON.
n. Panel batteries power connected/
disconnected.
o. Manual Call Point (MCP)/Sensor.
p. Access 3A passcode entry requested to
continue with selected panel configuration action (access 2 & 3 shown with three asterisks).
q. IBM-compatible Personal Computer (PC)/
laptop.
r. Loop device address switch.
1
22
33
4455
66
77
81 8
0
09
9
230 V AC
50/60 Hz
Access 3A
*****
4Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
1.4 Software Version Number
The XLS80e Series control panel software version can be viewed by performing a lamp test function.
Software version numbers are displayed for the following:
a. The panel. b. The Loop Interface PCB. c. The Enhanced Loop Interface PCB.
1.5 EN54 Functions
This fire control panel complies with the requirements of EN54-2/4:1997. In addition to the basic requirements of EN54-2, the panel may be configured to conform with the following optional functions - the applicable clauses of EN54-2 are referenced as follows.
Options Clause
Indications: Fault signals from points 8.3 Recording of the numbers of
entries into fire alarm condition 7.13 Controls:
Coincidence detection 7.12 Delay of the actioning of outputs 7.11 Disablement of each address
point 9.5 Test condition 10
Outputs: Fire alarm devices 7.8 Fire alarm routing equipment 7.9 Fault warning routing equipment 8.9
5 Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
The following features are provided by the Power Supply Unit (PSU) of the XLS80e Series Fire Control Panel Range to comply with EN 54-4:
Feature of the XLS80e PSU EN 54-4
Clause
Derive power from the mains supply 5.1
Derive power from a standby battery source 5.2
Charge and monitor the standby battery / batteries 5.3
Detect and signal various PSU faults 5.4
1.6 Ancillary Functions
The following is a list of ancillary functions that are provided by the XLS80e Series Fire Control Panel Range in addition to those required by EN54-2/4. These functions are described in the section of this manual as referenced (except the Sounder volt-free contact option, which is described in the Installation and Commissioning Manual):
Ancillary Function Manual
Section Refs.
Change sensitivity 5.1.2.7, 13 Control Matrix:
Output modes 7.4 Input type filtering 7.6.1.1 Output type filtering 7.6.2.2 Time-of-day filtering 7.6.2.2 Auto disable/enablement 7.7
Networking 14 Time-of-day functions -
disablements/configuration 3.11 Self-learn configuration 5.3.2 Module supervision options 5.1.1.4 Module silence options 5.1.4.7 Text editing 6 Sensor LED blinking mode 1 1 .1 Sounder pulsing periods 1 1. 4 Signal degraded monitoring
period 11.8
(continued)
6Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
Ancillary Function Manual
Section Refs.
Loop start-up boost 1 1. 8 Calendar-based automatic
test selection 11.6 Automatic cancellation of
disablements 11.7 Mains Fail Fault
additional delay 1 1.13 RS232 Printer Output &
PC Interface 11.1 T emporary Configurations 1 1.1, 11.2 Volt-free cont act
output option 7.7
1
Extinguishing system 7.6.1.6 features 7.6.2.5
7.8, 1 1.20
1
Installation and Commissioning Manual
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
7
XLS80e Fire Alarm Control Panels
March 2007
2 Power On/Start Up
To power up the system from a completely powered-down condition:
1 Connect the two leads (A) from within the
panel to the two 12 V sealed lead-acid batteries and then fit one end only of the supplied interlink (B).
2 Connect and switch on the mains supply. 3 Connect the interlink to the remaining
terminal - but see item a. below.
After a few seconds the Status: NORMAL display appears, indicating that the panel is now ready to accept panel configuration instructions. If the display is too dark to read, adjust the contrast (see Section 3.3.2.1).
Be advised that....
a. If the battery connections are not completed
within 60 seconds of the mains supply being switched on, the panel will indicate a charger/battery fault. If this occurs:
1 Press the MUTE BUZZER pushbutton to
silence the buzzer (access level 1 or 2, depending upon panel configuration).
2 After all necessary connections are
completed, press the RESET pushbutton to clear the fault condition (access level 2).
IF BATTERIES ARE NOT CONNECTED WITHIN
60 SECONDS OF POWER-ON:
ALL FAULT INDICATIONS ARE CANCELLED
8
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9 March 2007
b. If the panel has not been configured with
any sensor or module data, i.e. the normal system status at initial power up, the panel displays ‘*UNCONFIGURED*’ unless it is part of a network, in which case it displays ‘NORMAL’.
Powering up a network - special considerations
Master/Slave network
The following is recommended: i When configuring a panel (either directly
or using the Offline Support Tool), first disconnect the panel from the network. When the COMMS FAIL message is displayed (may take up to 2 minutes for a Slave), press MUTE BUZZER to stop the buzzer.
ii When all panels have been configured,
remove power from all of them. Connect the Master panel to the network - set the termination link on its RS485 PCB to the ‘ON’ (lower) position if it is not already so configured (see Section 6 of the XLS80e Series Installation and Commissioning Manual).
iii Power-on just the Master panel. Wait until it
reports COMMS FAIL. Use MUTE BUZZER to mute the buzzer. W ait one minute.
iv Connect and power-on each Slave panel
and Repeater in turn. There is no time restriction on doing this. When all the panels have been powered-on, wait one minute, then press the RESET pushbutton at the Master panel. The network should stabilise (i.e. no error messages or buzzers).
v If the site arrangement does not require that
a termination link be set at the Master (see Section 6 of the XLS80e Series Installation and Commissioning Manual), fit the termination links at the correct panels and then set the link at the Master panel to the ‘OFF’ (upper) position. This can be done with the system powered-on.
XLSNET peer-to-peer network
When all panels have been powered-up, allow time for the network to settle. When no new fault messages are being generated, press RESET .
9
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
3 Panel Configuration Overview
This section gives a brief guide to the methods for configuring the XLS80e Series panels.
3.1 Where to Access the Configuration Actions
The panel can be configured at one of the following:
a. The panel, using its controls and indicators.
This is the slowest method, so the manufacturer recommends that you only use this method to perform small-scale operational amendments after the panel is fully commissioned. Refer to Section 3.3.
b. Off-line, using a Personal Computer (PC,
e.g. a laptop) running the Off-line Support Tool. The updated configuration is subsequently uploaded to the panel via its internal RS232 port. Refer to Section 3.4.
At the start
The Access 3 passcode is required to configure the panel. Refer to Section 3.5.
At the finish
A ‘Confirm Changes’ prompt is displayed. The changes you have made are not permanently stored in the panel’s memory unless you press
to select ‘confirm’. If you press to select
‘cancel’, the changes are lost.
OR
Access 3
***
10
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9 March 2007
3.2 Configuration Actions
The following configuration actions can be performed:
a. An unconfigured panel can scan the loops
and learn what devices are installed, either automatically or with manual user intervention. Refer to Section 3.6.
b. Groups of devices on a configured panel can
be selected for deletion or change to a different logical type. Refer to Section 3.7.
c. Individual devices can be added, removed
or changed manually. Refer to Section 3.8 .
d. The panel zone and device text descriptions
can be edited. Refer to Section 3.9.
e. The relationship between input devices (e.g.
sensors, manual call points) and output devices (e.g. sounders) can be configured. This is done in the Control Matrix, which is a table of inputs, outputs and relationships. Refer to Section 3.10.
g. The status of devices (e.g. the sensitivity)
can be set to vary depending upon the time of day. Refer to Section 3.11.
h. The panel clock can be adjusted. Refer to
Section 3.12.
i. Various temporary and permanent
configuration options can be set. Refer to Section 3.13.
j. The panel can be configured to be part of a
network. Refer to Section 3.14.
k. Sounders or remote fire outputs can be
delayed. Refer to Section 3.15.
l. Virtual input and output points can be
configured. Refer to Section 3.16.
LOOP DEVICE CONFIGURA TION - Sections 3.6-3.8
TEXT EDITING - Section 3.9
CONTROL MA TRIX - Section 3.10
TIME-OF-DA Y - Section 3.11
CLOCK SETTINGS - Section 3.12
P ANEL SETTINGS - Section 3.13
NETWORKING - Section 3.14
Z X C V B N M
Q W E R T Y U I O P
A S D F G H J K L
? ?
DELAYS - Section 3.15
Certain options on non-configuration menus also require the access level 3 or 3A passcodes. These options are described in Section 12.
VIRTUAL POINT CONFIGURA TION - Section 3.16
11
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
3.3 Using the Panel Controls and Indicators
All of the configuration operations described in this manual can be done using the panel pushbuttons and Liquid Crystal Display (LCD), with no external equipment required.
The panel remains ‘on watch’ during the configuration sequence, and will therefore respond appropriately to any fire or fault conditions that arise.
The manufacturer recommends that you keep a secure copy of the system configuration on a PC as a backup, in case of difficulties in the configuration sequence.
3.3.1 Pushbuttons
OPERA TING PUSHBUTTONS
CHANGE TABS - Scrolls through the tabbed displays. Refer to Section 4.2 for further information.
RESET - Restores normal operating status when all alarm conditions have been removed.
Note: The other operating pushbuttons are not
used during configuration. Their operation is described in the XLS80e Series Operating Manual (997-474).
CURSOR AND NUMERIC PUSHBUTTONS
- Used to move around the LCD menus. When the panel status is normal and if the printer is fitted, advances the printer paper.
Used to: select menu options, select quick
methods of dis/enablement and walk test cancellation, control the event log display , select loop device parameters for edit, display existing time-of-day programs, create a new Control Matrix entry and select characters during text editing.
0
to 9 - Used to select items and enter
data on the LCD.
- Used to accept an item or state on the LCD.
- Used to cancel an item or state on the LCD.
KEYSWITCH - Setting the keyswitch to the right has the same effect as entering an access 2 passcode. Set it to the centre to deselect access 2.
XLS80e
0 1
2 3
4 5
6 7
8 9
ENDDELAY /
EVACUATE
MUTE
BUZZER
EXTEND
DELAY
SILENCE/ RESOUND
RESET
DAY
MODE
FIREO/P DISABLE
CHANGE
TABS
ZONESIN
ALARM
PRE-ALARM
FIRE
FAULT
SYSTEM FAULT
SOUNDER FAULT/ DISABLED
FIRE O/PFAULT / DISABLED
FIRE O/PACTIVE
DAYMODE
DELAYSACTIVE
TECHNICALALARM
DISABLEMENT
TEST
POWER
EN54-2/41997
12
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9 March 2007
3.3.2 Liquid Crystal Display
The 6-line x 40 character display (using 240 x 64 pixels) provides a menu structure for the operation and configuration of the panel. Most of the operations described in this manual are accessed from the Configuration Menu.
Further information about the display is given in Section 4.
3.3.2.1 LCD Contrast Adjustment
This adjustment procedure as shown at left is only available within the first two minutes after power is applied to the panel.
To adjust the LCD contrast at other times, select LAMP TEST (refer to the XLS80e Series Operating Manual 997-474, Section 6.4 Lamp
Test) while at access level 3. Hold while the test progresses. The contrast then cycles
and the remainder of the procedure is as shown at left.
HOLD
THE DISPLA Y CYCLES BETWEEN MAXIMUM AND MINIMUM CONTRAST :
MOMENT ARILY
WHEN THE REQUIRED CONTRAST IS PRESENT ON THE DISPLAY, RELEASE .
TO FINE-ADJUST , USE:
WHEN COMPLETED, PRESS:
TO INVOKE THE SELECTED CONTRAST VALUE.
AND
AND PRESS
13
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
3.4 Using the Off-line Support T ool
This is a means of preparing the configuration data, using an optionally-supplied software tool which you can use without any connection to the panel:
i. Save the prepared data to your PC hard disk. ii. When the panel is ready to accept the
configuration data, simply connect it to your PC, for the final data transfer to be made.
The XLS80e Off-line Support T ool is a complete package for off-line configuration preparation. It is supplied with all necessary panel configuration instructions, consequently no further details are given here.
This software package is available from HONEYWELL or your supplier (Part Number: 020-558-100).
3.5 Passcodes
A passcode is required for all configuration functions. You will be asked for the passcode at the appropriate time (Sections 4.4.1 and 12.1 give examples). There are three access passcodes:
Access 2 - Permits operation of the panel pushbutton controls and provides access to all menus except the Configuration menu. It can be overridden by the panel keyswitch.
Note: Some menus have options which can
only be accessed using an Access 3 or Access 3A passcode; these options are described in Section 12.
Access 3 - Provides access to the Configuration menu. Most operations described in this manual require this passcode.
Access 3A - Certain operations (changing passcodes, and panel settings) require this passcode.
Default passcodes are supplied with the panel. These can be changed and the manufacturer strongly recommends that you do so once commissioning has been completed (see Section 8 for default passcodes and the means of changing the passcodes from these defaults).
Passcodes are not required for off-line configuration using a PC, but they are required when uploading or downloading configuration data using this method.
Access 2
Access 3A
**
*****
*
Access 3
**
*
14
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9 March 2007
3.6 Learn Devices on Loops
The panel scans the loops and detects what devices are fitted. This can be done on an unconfigured panel. Section 5.3 describes how to start, run and end a configuration learn.
There are two learn methods: a. Auto-Learn. Loop device decisions are made
without the need for user intervention. Refer to Section 5.3.2.
b. Manual Learn. Prompts the user each time
a new or changed device is detected. Refer to Section 5.3.3.
Limitations on the Number of Devices
The XLS80e Series Control Panel design allows for the connection of up to 198 loop devices per analogue loop; i.e. up to 99 sensors and 99 modules. The maximum number of devices per panel is:
a. 1584, if the Enhanced Loop Interface Board
(ELIB) is used for loops 3 to 8.
b. 512, if the Loop Interface Board (LIB) is used
for loops 3 to 8.
T o comply with EN54-2 in the event of a system fault, a maximum of 512 sensors and/or MCPs should be connected to the control panel across those analogue loops that are not connected to an ELIB. This number includes all conventional zone detectors and/or MCPs connected.
If the number of sensors and/or MCPs connected to a loop exceeds 32, then isolators MUST be used to segregate parts of the loop. This will ensure that a short or open circuit will not cause the loss of more than 32 sensors or MCPs. For the XLS80e Series, do not place more than 25 loop devices between isolators (20 if FET isolators are used).
There may be a further restriction, depending on the types of sensor used, because of drive limitations of the isolators. HONEYWELL provide a PC-based tool to simplify loop loading calculations. Contact the Te chnical Support Department or your supplier for further information.
EN54-2: 12.5.2
Maximum of 32 Sensors
and/or MCPs between
isolators
Before configuring
your panel, ensure all
loop devices are
installed
and each loop is
connected
EN54-2: 13.7
Maximum of 512
Sensors and/or
MCPs per panel unless
ELIBs are used
15
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
Limitations of the Auto-learn Method
If the auto-learn method is used on an
incomplete system it will give the false impression that the system is fully operational. In such cases, the auto-learnt data MUST be checked carefully against the system specification.
During the auto-learn procedure, input
module logical types are set to defaults. Modules not conforming to the defaults must be re-configured using the Manual Learn or Configure Individual Device procedures.
3.7 Configure Group of Devices
On a configured panel, this configuration method allows a group of devices at consecutive addresses to be deleted or all set to the same type.
Refer to Section 5.2.
3.8 Configure Individual Device
This configuration method requires the user to select each loop device and set all parameters and conditions, e.g. sensitivity, time-of-day, device text, etc. appropriate to it.
It can also be used to add further details to the configuration resulting from the auto-learn method.
Refer to Section 5.1. Note: Sensitivity and alarm verification delay
recommendations are given in Section 13.
Caution - a false indication
of a fully-functional system
is given if the Auto-learn
procedure is used on an
incomplete system.
Input module types are
set to defaults during the
Auto-learn procedure
and may require manual
re-configuration.
16
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9 March 2007
3.9 T ext Editing
There are three types of text that can be entered and edited:
a. The panel or site name. b. The zone description. c. The device location text, which is shown on
the display when the system status is not normal (i.e. alarm, test etc.). The device description is also used at the printer, if fitted.
The text is entered and edited from a text editor which uses the LCD and the panel pushbuttons. Refer to Section 6.
For panel and zone descriptions, the text editor is invoked from dedicated menu options (Sections 6.4 and 6.3 respectively). For device location text it is invoked during the Configure Devices on Loops procedure (Sections 5.1.2.3 and 5.1.4.3) or Virtual Point Configuration procedure (Section 15).
3.10 Control Matrix
This very versatile system allows you to define exactly which outputs (bells, etc.) are to be activated depending upon which inputs (sensors, etc.) have given a fire indication.
The capacity of the system is 512 matrix entries.
Certain auxiliary functions may be specified using the Control Matrix.
Refer to Section 7.
<Entry 1 input> activates: <Entry 1 output> <Entry 2 input> activates: <Entry 2 output> <Entry 3 input> activates: <Entry 3 output>
⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓
<Entry 512 input> activates: <Entry 512 output>
CONTROL MA TRIX:
E.G.
17
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
3.11 Time-of-Day
This facility allows panel functions to be modified depending upon the time of day . There are three major applications:
a. Altering the sensitivity of sensors at certain
times of day - see Section 5.1.2.7.
b. Making some actions in the Control Matrix
(e.g. a delay) apply only at certain times of day - see Section 7.6.2.2.
c. Cancelling all disablements on the panel at
certain times of day (not EN54-2 compliant)
- see Section 11.7. Note: A Control Matrix entry can be used to
control disablement and enablement functions, independent of the CANCEL DISABLE function (see Section 7.7).
A typical Time-of-day program consists of one or two daily periods specified by start and end times, with an optional alternative for weekends. Up to seven such programs can be in operation in any one panel.
These programs run completely independently of each other. Any particular sensor sensitivity , or Control Matrix entry , may be modified only according to one of the programs.
Full details on Time-of-day program editing are given in Section 9.
3.12 Setting the Clock
This facility allows: a. The date and time to be adjusted.
b. The clock running speed to be adjusted. c. The start and end dates of Summer Time to
be selected.
Refer to Section 10.
3.13 Panel Settings
For a number of panel functions, various options are available e.g. Pulsing Sounder Modes, Access Level for MUTE BUZZER etc, Relay Circuits SILENCE Option. Some options are temporary , most are permanent.
Refer to Section 11.
EN54-2: 9.1.2
Disablement and
re-enablement MUST be
a manual operation.
NIGHT - SET TO HIGH SENSITIVITY
DAY - SET T O LOW SENSITIVITY
NIGHT - CONTROL MA TRIX
HAS NO DELAY SET
DAY - CONTROL MA TRIX
HAS DELAY SET
18
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9 March 2007
3.14 System Networking
The XLS80e Fire Control system is designed so that control panels can work either as stand­alone units or networked with other panels. When networked, each panel supervises its own detection system of up to eight loops of sensors and modules and functions independently of all other panels.
A communication system enables events at any panel to be relayed to other panels. This causes appropriate annunciations and actions at those panels.
Network Programming
The XLS80e Series panel can be used with one of two networks:
a. Master/Slave network. Refer to Section 14
for further information.
b. XLSNET peer-to-peer fault-tolerant network.
Refer to Appendix 3 for further information.
Local Codes of Practice
Master/Slave network: The existence of network communications is not, normally, intended to replace the essential functions of the individual panels (considered as isolated systems) but to supplement and extend the facilities offered. This means that each panel must be configured, independently of the others, to comply with the appropriate Code of Practice in force in the area of the installation (i.e. in respect of the activation of alarm devices in response to an Alarm of Fire). This compliance must be maintained at all times, even when communication with other panels is suspended.
The Master/Slave
network does not
provide the transmission
path integrity required
by EN54-2: 12.5.3
OR XLSNET PEER-TO-PEER NETWORK
XLS80e: ST AND-ALONE
OR MASTER/SLAVE NETWORK
RS485
19
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
3.15 Delays
Either the sounders or the fire alarm routing equipment (remote fire outputs) which is used to summon the fire brigade can be delayed:
a. To activate sounders immediately but delay
the remote fire outputs, use the Day/Night
Modes Configuration Option (Section 11.19). The delay may be
extended to allow investigation. MCPs are normally configured to override any delay.
b. T o delay sounders but activate the remote
fire outputs immediately, use the Control Matrix to put an output delay on modules of type BELL (Section 7.6.2.2). The delay must then be enabled by the Operator (see 997-474, Operating Manual Section 7.5). MCPs are normally configured to override any delay .
3.16 Virtual Point Configuration
Up to 64 Virtual Input Points and up to 512 Virtual Output Points can be configured. They are used with external systems (e.g. a Voice Alarm panel) with which they communicate via an RS232 port. They must be placed in a zone; they then become possible inputs to or outputs from the Control Matrix. Further information is given in Section 15.
20Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
4 The Display - Tabs, Events
and Menus
4.1 Introduction
4.1.1 Status: NORMAL
The Status: NORMAL display appears when: a. No alarm or test conditions exist, and
b. No menus are being accessed.
4.1.2 Tabs
When conditions other than Status: NORMAL exist, the LCD displays event data. More than one type of data may be available for display at any one time (eg, Fire Alarms, Fault s, Menus etc.). When this occurs, the types of data available are identified by tabs at the bottom of the display .
4.1.3 Events
Fire Alarms, Pre-alarms, Faults, Disablement s, Tests, Evacuate mode and Auxiliary input activations are shown on Event displays. A Fault event display is shown.
4.1.4 Menus
Menus displays are arranged in a heirarchy, the top of which is a User Menu from which other menus are accessed.
21 Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
4.2 Tabs
When tabs are displayed, use the CHANGE TABS key to scroll through the tabs and thus display the corresponding data.
The tabs are (in descending order of priority): EXTINGUISHING (if about to release;
otherwise priority is below FIRE) FIRE TECH. ALARM PRE-ALARM FAULT DISABLE TEST EVACUATE AUX MAINT (access level 3 only unless Maintenance
Urgent)
USER (at access level 2) or SERVICE (at access level 3)
The tabs are displayed in this order from left to right. All the tabs display events except for the USER and SERVICE tabs, which display menus. The current tab is that without a line above it.
Note: If there is insufficient room to display all
the tabs, the ones at the right (those with the lowest priority) are omitted.
Use ZONES IN ALARM to go directly to the FIRE tab without scrolling through the other tabs. If there is more than one zone in alarm, subsequent operations of the ZONES IN ALARM pushbutton scroll through these zones.
Note: If the FIRE tab is present but not
selected, and for 20 seconds none of the panel pushbuttons are pressed, the FIRE tab is then selected automatically .
Note: If the SERVICE or USER tab is selected,
and for 2 minutes none of the panel pushbuttons are pressed, the tab is deselected automatically and all passcodes are cancelled (except the access level 2 passcode when the keyswitch is set to the horizontal position).
22Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
4.3 Event Displays
When a fire alarm, pre-alarm, fault, disablement, walk test, evacuation, or auxiliary input activation (if logging is configured) occurs, an event display replaces the Status: NORMAL display .
Note: FIRE, FAUL T , DISABLEMENT, or TEST
LEDs illuminate (also ZONE LEDs, if fitted) as appropriate.
Example event displays are shown at the left. In general, to move through the displays:
a. If more than one zone is affected by the
event, use the and arrows to scroll through the zones. For FIRE events these
arrows scroll through device data; ZONES IN ALARM scrolls through the zones.
b. If more than one device is affected, use the
and arrows to scroll through the
devices and device descriptions.
If a FIRE event occurs and the CHANGE T ABS pushbutton is used to display other data, the display area is reformatted so that the top two lines continue to display fire information.
Further details about the event displays and their operation are given in the XLS80e Series Operating Manual, 997-474.
Aux T ab
At the end of the list of activated AUX inputs, the AUX tab displays details of unconfigured loop devices, should the panel find any during polling. These are only shown on the panel local to the devices. If multiple devices are
found, use the and pushbuttons to scroll through the list of unconfigured devices (and
through the list of activated AUX inputs). In the example, 1/3 means that ‘L3 S79’ is the first of a total of three unconfigured devices found (on all loops).
Note: Modules: the only types that may be
displayed are MON, CTRL and ZMX.
L3 S79 [OPT ] 1/3 Press * for user actions
Aux Tue 27-Jul-2004 11:20:07
Unconfigured Device found on loop
23 Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
Tech.Alarm: ZONES: 1; Events: 2
Panel 13:Security Office L4 S05 Corridor 13 Ceiling Sensor GAS Tech.Alarm User 27-Jul-2004 11:20:07
P13 ZONE 31 (x2) 27-Jul 11:20
By default, the panel does not scan for unconfigured devices when the panel is completely unconfigured (i.e. no sensors or modules on any loop), however scanning can be enabled by the user.
There is an optional, configurable upper limit on the number of devices to be scanned. When this number is reached, scanning can be continued if extended by the user. The default upper limit is 50 devices.
Press the pushbutton (level 3 access) to display options to hide or show these devices
for access level 1 or 2 users, and to disable/ enable scanning for unconfigured devices.
a. If there are no devices left to show as a
result of HIDE, the AUX tab disappears (assuming there are no AUX inputs active).
b. RE-SCAN causes the panel to clear all
indications of unconfigured devices, scan the loops and then store the list of any devices still unconfigured. This allows devices that were present on the loop but have since been removed to be identified. The process takes up to about five minutes.
c. DISABLE clears the indicated devices from
the AUX tab and prevents the panel from detecting further unconfigured devices. To re-enable the scan, use the Log/Display/ Print menu as described in Section 12.4.
Note: Entry of access level 3 passcode for any
reason (except to display the above menu from the AUX tab) always results in SHOW ALL, unless the scan for unconfigured devices has been disabled. Any loop device configuration operation always leads to a RE-SCAN.
If the configured upper limit is reached, the option to extend the scanning is provided.
Note: The number of devices listed may be
slightly higher than the set limit (because of synchronisation effects).
The DISABLE option resets the upper limit to 50 (this is the only method or reimposing a limit if ‘0’, i.e. no limit has been selected).
T ech. Alarm tab
The T ech. Alarm tab is displayed when any Gas Sensor Interface configured as Technical Alarm is activated.
Unconfigured Devices Scan Menu
1: 2:HIDE All Unconfigured Devices 3:SHOW All Unconfigured Devices 4:RE-SCAN for Unconfigured Devices
Aux Service Tue 27-Jul-2004 11:20:07
HIDE This Device
Unconfigured Devices Scan Menu
2:HIDE All Unconfigured Devices 3:SHOW All Unconfigured Devices 4:RE-SCAN for Unconfigured Devices 5:
Aux Service Tue 27-Jul-2004 11:20:07
DISABLE Unconfigured Devices Scan
Unconfigured Devices Scan Menu (50-devices limit reached)
1: 2:HIDE This Device 3:HIDE All Unconfigured Devices
Aux Service Tue 27-Jul-2004 11:20:07
EXTEND Unconfigured Devices limit
es Scan
Set limit to number of unconfigured devices to be scanned for (1-1584; 0=no limit): 50
Aux Service Tue 27-Jul-2004 11:20:07
Loading...
+ 108 hidden pages