Honeywell XL 800 User Manual

HONEYWELL EXCEL 5000 OPEN SYSTEM
INSTALLATION AND COMMISSIONING INSTRUCTIONS
CONTENTS
General ............................................................................... 3
Before Installation ............................................................. 3
Installation ......................................................................... 3
Wiring ................................................................................. 4
Description of the XCL8010AU Controller Module ......... 7
System Data........................................................... 10
Operational Environment ....................................... 10
XCL8010AU, I/O Modules on Single Rail............... 12
Multiple Rails in Single Cabinet.............................. 12
LonWorks Bus I/O Modules in Separate Rooms .... 12
How to Connect Panel Bus and LONWORKS Bus Mixed
Controller Systems ...................................................... 12
Connecting I/O Modules......................................... 12
Connecting I/O Modules to the XCL8010AU.......... 12
Mounting/Dismounting Modules.................................... 14
Mounting Sockets................................................... 15
Connecting Sockets ............................................... 15
Dismounting Sockets ............................................. 16
Mounting Electronic Modules ................................. 16
Dismounting Electronic Modules ............................ 17
Connecting to the Controller................................... 17
Setting the C-Bus Termination Switch.................... 17
Shielding ................................................................ 17
Description of the I/O Modules ....................................... 21
XL 800 Series
FOR SMOKE CONTROL
Connecting the XI582 Operator Interface ............... 17
Connecting Laptops (XL-Online/CARE) ................. 18
XCL8010AU Terminals........................................... 18
LONWORKS Interface and Terminals ....................... 18
LONWORKS Service LED and Button....................... 18
C-Bus Tx LED and Rx LED ....................................19
Reset Button........................................................... 19
HMI Interface.......................................................... 19
Alarm and Power LEDs ..........................................20
Watchdog Status ....................................................20
Modem Interface..................................................... 20
I/O Bus Switch S2................................................... 20
C-Bus Termination Switch S1................................. 21
Memory .................................................................. 21
Types of Analog Input Modules .............................. 22
Features .................................................................22
Terminals................................................................ 22
XFL821AU Connection Examples ..........................23
Types of Analog Output Modules ...........................24
Features .................................................................24
Terminals................................................................ 24
Technical Data........................................................ 24
Modules with Manual Overrides .............................25
XFL822AU Connection Example ............................ 25
Synchronization Behavior of Analog Output Module
Configured as Floating Output................................ 25
Types of Binary Input Modules ............................... 26
Features .................................................................26
Terminals................................................................ 26
Technical Data........................................................ 26
Status LEDs............................................................ 27
XF823AU Connection Examples ............................ 27
Types of Relay Output Modules ............................. 28
Features .................................................................28
Terminals................................................................ 28
Permissible Loads .................................................. 29
Status LEDs with Manual Overrides ....................... 29
Connection Examples............................................. 30
Copyright © 2008 Honeywell GmbH All Rights Reserved EN1B-0410GE51 R0908A
General Excel 800
Troubleshooting............................................................... 31
Power LED (green) .................................................31
Alarm LED (red) ......................................................32
LONWORKS Service LED..........................................32
C-Bus Tx and Rx LEDs...........................................33
HMI Tx and Rx LEDs ..............................................33
Power LED of I/O Modules .....................................34
Service LED of I/O Modules.................................... 35
Trademark Information
Echelon, LON, L trademarks of Echelon Corporation registered in the United States and other countries.
ONMARK, LONTALK, LONWORKS, Neuron, are
EN1B-0410GE51 R0908A 2
Excel 800
WARNING
This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the instructions manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference. Any unauthorized modification of this equipment may result in the revocation of the owner’s authority to continue its operation.
General
The XL800 Series is designed to provide heating, ventilating and air-conditioning control. They can operate either standalone, or networked to Honeywell central workstations such as EBI. These controllers can also be used for smoke control system monitoring and control, for monitor and control of fire (UL864), and general purpose signaling (UL2017). In UL 2017 applications, the product can be used as a type NM (Non-Monitored) system. It is also approved for UL916 (Energy Management Equipment.)
The XL800 Series can be used for smoke control applications when used in conjunction with a UL listed fire alarm control panel (FACP) and UL listed fire fighters’ smoke control station (FSCS).
Installation
Mount controller subpanel in cabinet so all labeling is visible. Secure full-size subpanel in place with six no. 10 x ½-inch (13 mm) sheet metal screws (not supplied). Secure smaller subpanel with four no. 10 x ½-inch (13 mm) sheet metal screws (not supplied).
NOTE: Subpanel must mount flat and should not bulge or
recess anywhere.
FULL-SIZE
CABINET
Before Installation
1. Unpack door and remove the XL800 from carton. Check equipment and report any damage to a Honeywell representative.
2. Verify cabinet is installed correctly.
3. Securely mount the XL800 to a rigid structural surface
using at least four sets of 1/4 in. (6 mm) mounting hardware (supplied locally).
NOTE: Anchoring materials must be suitable for the
mounting surface (wood, concrete, steel). Mounting must comply with all local codes.
4. Obtain correct number and type of sheet metal screws for subpanel. Installation of a full-size subpanel requires six no. 10 x ½-inch (13 mm) sheet metal screws (not supplied). Installation of a smaller subpanel requires four no. 10 x ½-inch (13 mm) sheet metal screws (not supplied).
5. Obtain 14505159-001 Tamper Switch per job requirements. Installation of Tamper Switch is optional.
SIX NO. 10 x ½-INCH (13 mm)
SHEET METAL SCREWS
Fig. 1. Mounting controller subpanel in cabinet (full-size
subpanel cabinet shown)
3 EN1B-0410GE51 R0908A
Wiring Excel 800
Wiring
All wiring to the XL800 controller is unsupervised, except as noted.
All circuits are power limited, except for AC power circuits, relay contacts and other circuits as noted.
All field wiring terminals accept 24 AWG to 14 AWG (0.25 mm
All wiring must conform to local codes, ordinances, and regulations. Refer to job drawings for details.
Verify that the voltage difference between any conductor and earth ground does NOT exceed 150 Vac.
1. Connect input/output device wiring, C-Bus transmission
2. Connect line voltage to Terminals H and N of the
3. For Power Modules -001 through -007, leave power to
2
to 2 mm2) conductors except as noted.
wiring (minimum 18 gage [0.8012 sq mm]), LON Bus transmission wiring, and 14507063 Power Cable to Controller per job drawings. Fig. 2 and Fig. 3 show typical controller wiring. Four Power Module models are available (see Table 2).
14507287 Power Module. Connect a good earth ground to Terminal G of the Power Module. Fig. 5 through Fig. 7 show typical power wiring.
Power Supply and Controller OFF. Connect 14507063 Power Cable from Controller to Power Module.
WARNING
Risk of electric shock or equipment damage!
Subpanel and Controller power must remain OFF until
Controller is checked.
4. Install optional Tamper Switch on cabinet per instructions in the cabinet installation instructions. Wire Tamper Switch per job drawings.
5. Mount cabinet door.
CAUTION
Risk of electric equipment damage! Excessive static can burn out equipment.
Observe proper anti-static material handling practices
when installing or servicing PC parts and related components.
Observe proper equipment and body grounding practices. Discharge static electricity from your body before handling
parts.
Table 1. Connector terminal specifications
connector terminal pin signal type
analog input AI input SIGNAL ±12 V ±20 mA 9600 baud 8K ohms
digital input DI input SIGNAL ±10 V ±20 mA -- 15K ohms
analog output AO output(1 SIGNAL ±10 V ±20 mA 9600 baud 8K ohms
digital output DO output(2 AC/DC ±24 VAC/DC ±50 mA -- 10K ohms
totalizer output TI input SIGNAL ±12 V ±12 mA 100 Hz
signal ground GND -- -- -- -- -- --
J1 RS-485 (C-BUS)
2 -A input / output SIGNAL ±5 V 1 mA / 180 mA 9600 baud 100 ohms
3S Shield A -- -- -- -- -- --
(1
special application; (2 regulated; (3 supervised
model
14507287-001 120 0.5 A 60 24 120 Vac, 10A
14507287-002 120 1.7 A 60 24 24 Vac, 100 VA, 24 Vac, 40 VA 120 Vac, 10A
14507287-003 120 1.7 A 60 24 24 Vac, 100 VA, 24 Vdc, 600 mA 120 Vac, 10A
14507287-007 120 120 A 60 24 -- --
(3
1 +A input / output SIGNAL ±5 V 1 mA / 180 mA 9600 baud 100 ohms
transformer max. input
Vac current draw Hz
input / output
Table 2. Power module models
(48 VA) controller
voltage
type
VAC output
max.
voltage
max. current
accessory output convenience outlet
max.
frequency
max. line
impedance
EN1B-0410GE51 R0908A 4
Excel 800 Wiring
XL800 Series Power Consumption
When selecting the appropriate power supply, the power consumption of the XL800 modules must be taken into account.
Table 3. XL800 power consumption
model 24 Vac, 60 Hz 24 Vdc
XCL8010AU with watchdog load
XCL8010AU without watchdog load
XF821AU, XFL821AU 130 mA 80 mA
XF822AU, XFR822AU, XFL822AU, XFLR822AU
XF823AU, XFL823AU 180 mA 130 mA
XF824AU, XFR824AU, XFL824AU, XFLR824AU
XFR825AU 140 mA 90 mA
max. power consumption
690 mA 640 mA
190 mA 140 mA
160 mA 90 mA
140 mA 90 mA
I/O Modules
Variants of I/O Modules
There are two variants of I/O modules:
Panel Bus I/O modules with communication via Panel Bus (light-gray housings) Modules are automatically commissioned (with firmware download) by the XCL8010AU
L
ONWORKS Bus I/O modules (dark-gray housings) with
communication via L compatible) for easy integration and use with 3 controllers
Terminal Sockets
I/O modules are mounted on the appropriate terminal sockets. Panel Bus I/O modules and L modules use the same terminal sockets.
Color Coding
To distinguish modules and components, the following color coding is used:
Table 4. Color coding of Excel 800 Modules
color part
ONWORKS (FTT10-A, link power
ONWORKS Bus I/O
rd
-party
red All of the user-accessible adjustable
mechanical parts (i.e., bridge connectors and locking mechanism) and operating controls (manual overrides, etc.)
light-gray
dark-gray
Panel Bus I/O modules
ONWORKS Bus I/O modules
L
5 EN1B-0410GE51 R0908A
Wiring Excel 800
X
X
X
X
LonWorks
BUS
MODULES
PANEL
BUS
MODULES
ANALOG
INPUT
XFL821AU
XF821AU
ANALOG
OUTPUT
XFLR822AU
XFL822AU XFL823AU
XFR822AU
XF822AU XF823AU
BINARY
INPUT
RELAY
OUTPUT
FLR824AU
FL824AU
XFR824AU
F824AU
FLOATING
OUTPUT
XFR825AU
XCL8010AU
CONTROLLER MODULE
XS821-22
S823 XS824-25
LonWorks or Panel Bus
Fig. 2. Overview of I/O modules and terminal sockets
EN1B-0410GE51 R0908A
6
Excel 800 Description of the XCL8010AU Controller Module
Description of the XCL8010AU Controller Module
Overview
I/O MODULES
LonWorks BUS C-BUS
EXCELON
Fig. 3. Connections to the XCL8010AU Controller
PC or HMI
NO CONNECTION
Fig. 4. XCL8010AU
Controller Module front details
Legend
1 Power supply for I/O modules
2 I/O Bus communication terminals
3 L
ONWORKS interface
4 LONWORKS service button
5 L
ONWORKS service LED
6 C-Bus Tx LED
7 C-Bus Rx LED
8 Reset button
9 HMI interface (for field use, only)
10 Alarm LED
11 Power LED
12 Power supply terminals
13 Alarm/watchdog outputs
14 NO CONNECTION
15 S2 I/O Bus switch
16 S1 C-Bus termination switch
17 C-Bus terminals
18 L
ONWORKS terminals
7 EN1B-0410GE51 R0908A
Description of the XCL8010AU Controller Module Excel 800
24 VAC CONTROLLER
CONNECTOR TO
XL800 CONTROLLER
J5
POWER SWITCH
MAIN LINE VOLTAGE 120 VAC, 60 HZ TERMINAL MUST BE CONNECTED TO A GOOD EARTH GROUND.
14507063-002 POWER CABLE
(incl. with 14507287 power modules
14507287-001 through -003, only.)
CONNECTORS ARE KEYED TO
PREVENT MISALIGNMENT.
CONVENIENCE OUTLET
(UNFILTERED, UNSWITCHED)
-001 = 120 VAC, 10 AMP
““
G
BRN GRN BLK
120 VAC, 60 HZ
LINE INPUT
CONTROLLER
POWER
*
ON
H N
OFF
G
CONTROLLER SUPPLY 24VAC 48VA
~
G
““
G MUST BE
WIRED TO EARTH GROUND
* 14507287-001 POWER TERMINALS LABELED H-N-G.
2 AMP
F1
MUST BE WIRED
TO EARTH GROUND
UNSWITCHED
UNFILTERED
120 VAC
FUSE F1 (2 AMPS) PART NUMBERS ARE AS FOLLOWS: –HONEYWELL PART NO. 14000485-007 (AVAILABLE FROM HONEYWELL BRANCH LOCATIONS, ONLY) –BUSSMAN PART NO. AGC-2 –LITTLEFUSE PART NO. 312002
Fig. 5. Typical 14507287-001 Power Module wiring
CONNECTOR TO
XL800 CONTROLLER
J5
24 VAC CONTROLLER
POWER SWITCH
MAIN LINE VOLTAGE 120 VAC, 60 HZ TERMINAL MUST BE CONNECTED TO A GOOD EARTH GROUND.
14507063-002 POWER CABLE
(incl. with 14507287 power modules
14507287-001 through -003, only.)
CONNECTORS ARE KEYED TO
PREVENT MISALIGNMENT.
CONVENIENCE OUTLET
(UNFILTERED, UNSWITCHED)
-002 AND -003 = 10 AMP
““
G
BRN GRN BLK
Fig. 6. Typical 14507287-002, -003 Power Module wiring
120 VAC, 60 HZ
LINE INPUT
““
G MUST BE
WIRED TO EARTH GROUND
* 14507287-001 POWER TERMINALS LABELED H-N-G.
POWER MODULE
14507287-001 THROUGH -003
14507287-002 AND -003 14507287-002 AND -003
CONTROLLER
POWER
*
ON ON
H N
OFF OFF
G
CONTROLLER SUPPLY 24VAC 48VA
FUSE NO.
F1 F2 F3
TO EARTH GROUND
~
G
-002 MODEL, ONLY. 2 AMP MAX.
FUSE RATING
2 AMPS 5 AMPS 2 AMPS
2 AMP 5 AMP
F1 F2
2 AMP
MUST BE WIRED
24 VAC ACCESSORY POWER
FOR 14507287-003 (24VDC) FOR 14507287-002 (24VAC)
UNSWITCHED
UNFILTERED 120 VAC
HONEYWELL PART NO.
14000485-007 14507374-001 14000485-007
F3
120 VAC, 60 HZ
LINE INPUT
24VAC ACCESSORY
POWER -002 AND -003
MODELS (4 AMP MAX.)
~
BRN
BUSSMAN PART NO.
AGC-2
GMA 5AMP
AGC-2
GRY GRY
BRN
BRNRED
GRYGRY
LITTLEFUSE PART NO.
312002 235005 312002
EN1B-0410GE51 R0908A
8
Excel 800 Description of the XCL8010AU Controller Module
CONTROLLER TRANSFORMER
CONTROLLER
SUPPLY 24 VAC
48 VA
G
~
70
71
72
BRN
BLK
3
GRN
1
4
H
N
G
BLK
WHT
GRN
24 V 50 VA
14507351-001
429P156A
E1A 1052 XXXX
COM 120 V
1
2
MAIN LINE (120 VAC, 60 Hz) TERMINAL “G” MUST BE CONNECTED TO A GOOD EARTH GROUND.
MECHANICALLY SECURED TO SUBPANEL WITH MOUNTING SCREW
1
Fig. 7. Typical 14507287-007 Power Module wiring
I/O Module Overview
Table 5. Overview of I/O modules
1
Panel Bus
module
XF821AU XFL821AU Analog Input Module 8
XF822AU XFL822AU Analog Output Module 8 8 status LEDs
XFR822AU XFLR822AU Analog Output Module 8 8 manual overrides 8 status LEDs
XF823AU XFL823AU Binary Input Module 12 12 status LEDs
XF824AU XFL824AU Relay Output Module 6 2) 6 status LEDs
XFR824AU XFLR824AU Relay Output Module 6 2) 6 manual overrides 6 status LEDs
XFR825AU Floating Output Module 3 3 manual overrides 3 pairs of status LEDs
1)
In addition to the power LED and service LED
2)
Changeover outputs
9 EN1B-0410GE51 R0908A
LONWORKS
Bus module
description inputs outputs manual controls LEDs 1)
Description of the XCL8010AU Controller Module Excel 800
X
1
2
3
Corresponding Terminal Sockets
Table 6. I/O modules and corresponding terminal sockets
I/O module socket scope of delivery
XF821AU, XFL821AU
XF822AU,
XS821-22
1 terminal socket, 1 bridge connector 1 swivel label holder
XFL822AU, XFLR822AU, XFR822AU
XF823AU, XFL823AU
XF824AU, XFL824AU, XFLR824AU, XFR824AU
XS823
XS824-25
1 terminal socket, 1 bridge connector 1 swivel label holder
1 terminal socket, 1 bridge connector 1 swivel label holder 1 long cross connector
XFR825AU
Interfaces and Bus Connections
The Excel 800 System can be connected to the following devices and systems:
Panel Bus
For communication with up to 16 Panel Bus I/O modules
Polarity-insensitive
LonWorks Bus
For communication with other L within the building
FTT10, link power compatible
Polarity-insensitive
C-Bus
For communication with other controllers
HMI
For connecting an operator interface, e.g., XI582 or a laptop, e.g., for CARE
Modem
NO CONNECTION
ONWORKS Bus devices
Technical Data
System Data
Table 7. System data
Operating voltage 24 VAC/DC, 60 Hz
Power consumption
Max. 3.57 A (1 XCL8010AU Controller + 16 I/O modules)
Operational Environment
Table 8. Operational environment
ambient operating temperature
ambient operating humidity
ambient storage temperature
ambient storage humidity
0 49 °C (32 122 °F)
5 93 % rel. humidity (non-condensing)
–20 +70 °C (–4 +158 °F)
5 95 % rel. humidity (non-condensing)
Smoke Control Configuration
SMOKE CONTROL CONFIGURATION
L800
AO
UL-LISTED FIRE ALARM CONTROL UNIT
14505068 AUDIBLE ANNUNCIATOR
8
FIREFIGHTERS’ SMOKE CONTROL PAN EL (F SCS)
1
Fig. 8. Typical smoke control configuration
NOTES:
Locate and configure per NFPA 92A, Section 3-4.3.4.
UL-listed annunciator / FSCS panel switches have a minimum rating of 24 V, 1/10 Amp, and lamps / LEDs have a rating of 24 V, limited to 50 mA.
Locate so as to minimize control wiring and piping.
Avoid running wires or piping through areas that have a high fire risk.
11
AO
12
AO
2 3
STATUS CONTROL
9
SUPPLY FAN
AIRFLOW SENSOR
EXHAUST FAN
DAMPER
VERIFICATION
6 7
10
4
5
EN1B-0410GE51 R0908A
Locate per UL 555S.
10
Excel 800 Description of the XCL8010AU Controller Module
4
5
6
7
8
9
3
4
Locate separate from and below all building exhaust
fans and upstream of any prevailing winds.
Exhaust to outside of building.
Locate airflow differential switch.
Locate UL-listed damper pressure / position indicator
per damper installation instructions.
Smoke control must be initiated by a listed fire alarm
control unit or in zone automatic alarm devices and not devices located outside of the smoke control zone. Interconnecting wiring must be within 20 ft. (6 meters) and in conduit.
Refer to NFPA 92A.
10
Verify that the AC voltage source connected to the
inside of the main line voltage terminal block is from a UL-1481 listed uninterruptible power supply. The main line voltage terminal block maximum current draw is
0.5 A. For 220/240 VAC (60 Hz) applications, verify that no potential between any conductor and the earth ground exceeds 150 VAC.
11
All external LONWORKS bus field wiring must be limited
to 4000 ft. (1200 meters) and be terminated to 14506944-001 transient protector (35 V, 290 mA max.) except C-Bus field wiring communicating at 1 MHZ, which uses 14502412-014 transient protector (19 V, 500 mA).
12
Panel Bus wiring must be in the same enclosure or
less than 20 ft. to adjacent enclosure. No protection is required.
Data File Set-Up
Generate the engineering data file for the XL800 Series Controllers. This data file has a mix of hardware points for the necessary inputs and outputs to control fans, dampers, and other equipment. In addition to the inputs and outputs, a custom control program is written to control the outputs per the sequence. The XL800 controllers can reset the program once the data from the operator interface indicates a normal condition for the dedicated smoke control equipment. Wire conditions must be programmed to provide annunciation of trouble conditions.
Also required for a dedicated application for the XL800, is a weekly time program to test control points, fans, and dampers by exercising the equipment and verifying feedback automatically during low building activity periods.
Panel Reset
When in Smoke Control Mode, panel reset is accomplished by resetting the initiating panel contact circuit or by the separate initiating/reset switch on the FSCS panel.
CAUTION
Risk of electric equipment damage!
Failure to use listed/approved replacement parts can
damage product, degrade operation and result in loss of safety function.
This product must be installed and operated within its
environmental, mechanical, and electrical specifications as contained in this document.
When servicing, use only listed/approved replacement
parts ordered directly from the manufacturer.
Typical Power Limited Circuit for XL800
POWER LIMITED
2
CPU
1 1
NON-POWER
LIMITED
Fig. 9. Typical power-limited circuit for XL800
1
14507287-001 through -003 power module accessory
24 VAC output (rated 2A) must be wired in accordance with NFPA 70, Article 725 when routed within the cabinet or adjacent cabinets and also for external field wiring.
2
14507287-001, -002, -003, and -007 control power
module 24 VAC output is inherently power-limited. Thus, all sourced power from the XL800 controller is power-limited. All field wiring from these controllers meet NFPA 70, Article 725 power limited Class II requirements.
If a separate auxiliary power-limited 24 VAC power
source is required, use a control power module (14507287-001 or -007 control supply).
Devices must be installed in areas as shown. All cable
must be routed as shown. All internal power-limited wiring must be separated by ¼ inch (6 mm) or barrier from non-power-limited wire. Excess wiring must be cut, trimmed, and dressed properly to ensure that proper clearances are maintained.
LIMITED
ANALOG INPUT
MODULE
CONTROL
24VAC
2
3
NON-POWER
POWER
ACCESSORY
LIMITED
ANALOG OUTPUT
MODULE
24VAC
DIGITAL INPUT
MODULE
POWER LIMITED
24VAC
2
DIGITAL OUTPUT
MODULE
NON-POWER
LIMITED
NON-POWER
LIMITED
Connecting Single Bus Controller Systems
This section describes how to connect a controller system which uses Panel Bus I/O modules, only or L
I/O modules, only.
ONWORKS Bus
11 EN1B-0410GE51 R0908A
Description of the XCL8010AU Controller Module Excel 800
XCL8010AU, I/O Modules on Single Rail
Connect XCL8010AU Controller Module and I/O modules
using the bridge connectors.
This provides power supply and communication connection. No further wiring is necessary.
ROOM 1
71
LonWorks
72
I/O MODULE
73 74
XCL8010AU
1 2
LonWorks
I/O MODULE
75 76 77 78
Multiple Rails in Single Cabinet
The multiple rails of a controller system are connected in series.
Connect the rail ends as follows:
Power supply
via power supply terminals 73, 74 or 77, 78
Communication
via communication terminals 71, 72 or 75, 76
71 72
I/O MODULE
73 74
ROOM 2
I/O MODULE
73 74
LonWorks
LonWorks
I/O MODULE
LonWorks
I/O MODULE
75 76 77 78
71
72
I/O MODULE
73 74
71 72
I/O MODULE
73 74
71 72
I/O MODULE
73 74
I/O MODULE
XCL8010AU
1 2
I/O MODULE
I/O MODULE
75 76 77 78
75 76 77 78
Fig. 10. Wiring the power supply and the communication
lines to the I/O modules
LonWorks Bus I/O Modules in Separate Rooms
In this scenario, only communication lines must be connected between the rooms.
Connect the last module of room 1 to the first module of
room 2:
– via communication terminals 71, 72 or 75, 76
Fig. 11. Wiring the L
ONWORKS Bus I/O modules in
separate rooms
Maximum Cable Length
Max. cable length: 1200 meters (4000 ft), supervised.
How to Connect Panel Bus and LONWORKS Bus Mixed Controller Systems
Connecting I/O Modules
For connecting the I/O modules with each other, proceed as described for single-bus controller systems.
Connecting I/O Modules to the XCL8010AU
Panel Bus I/O Modules
Connect communication terminals 71 ─ 74 or 75 78 of
Panel Bus I/O modules to communication terminals 71 74 or 75 78 of the XCL8010AU Controller Module using either
– Bridge connectors
for flush mounting on a single DIN rail or
– Cables
for separate mounting, e.g., on multiple rails, separate cabinets, etc.
L
ONWORKS Bus I/O Modules
Connect communication terminals 71 ─ 74 or 75 78 of
L
ONWORKS Bus I/O modules to LONWORKS terminals 11
14 of the XCL8010AU using cables.
EN1B-0410GE51 R0908A
12
Excel 800 Description of the XCL8010AU Controller Module
Panel Bus modules
71 72 73 74
LonWorks Bus modules
71 72 73 74
71 72 73 74
Panel Bus modules
75 76 77 78
75 76 77 78
71 72
XCL8010AU
73 74
11 1 12 2 13 3 14 4
Fig. 12. Mixed bus system – correct wiring
75 76 77 78 78
71 72 73 74
LonWorks Bus modulesPanel Bus modules
75 75 76 76 77 77 78
71 72
XCL8010AU
73 74
75 76 77 78 78
71 72 73 74
75 76 77
11 1 12 2 13 3 14 4
Fig. 13. Mixed bus system – incorrect wiring
Setting Address of Panel Bus I/O Modules
Each Panel Bus I/O module is assigned its own unique address. For the sake of clarity for maintenance personnel, it is recommended that you address the Panel Bus I/O modules in ascending order 0 through F.
Table 9. HEX switch settings and addresses
HEX switch
address
HEX switch
address
0 1 2 3 4 5 6 7
01 02 03 04 05 06 07 08
8 9 A B C D E F
09 10 11 12 13 14 15 16
Use the rotary HEX switch to set the address to the one
already defined during engineering.
13 EN1B-0410GE51 R0908A
Mounting/Dismounting Modules Excel 800
LONWORKS Bus Topologies
4
4
LOCK
Fig. 14. HEX switch location
NOTE: If the HEX switch setting is changed, the Panel
Bus I/O module will revert to its default configuration. With L the HEX switch is without function.
ONWORKS Bus I/O modules,
Setting the I/O Bus Switch
Set the I/O Bus switch S2 of the XCL8010AU Controller
Module depending on the modules connected to terminals 71 78 and the desired communication as follows:
Table 10. I/O Bus switch settings
communication S2 setting terminals
LONWORKS Bus only
Panel Bus and L
ONWORKS Bus
LON 71 ─ 74 L
75 78
11 14
Panel 71 ─ 74 Panel Bus
75 78 Panel Bus
11 14 L
ONWORKS Bus
LONWORKS Bus
LONWORKS Bus
ONWORKS Bus
The LONWORKS Bus is a 78-kilobit serial link that uses transformer isolation so that the bus wiring does not have a polarity. I.e. it is not important which of the two LONWORKS Bus terminals are connected to each wire of the twisted pair.
The L
ONWORKS Bus does not need to be shielded on the
controller module side.
The LONWORKS Bus can be wired in daisy chain, star, loop or any combination thereof as long as the maximum wire length requirements are met.
Configuration
The recommended configuration is a daisy chain with two bus terminations. This layout allows for max. L lengths, and its simple structure presents the least number of possible problems, particularly when adding on to an existing bus.
ONWORKS Bus
C-Bus Topologies
Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.) can communicate with one another and a PC central. The C­Bus must be connected via the individual controllers (open ring).
NOTE: Star connection is not allowed because
uncontrollable line reflections may occur.
Mounting/Dismounting Modules
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet. Disconnect the power supply before you start to install the
Excel 800 System. More than one disconnect switch may be required to de­energize the system.
Do not reconnect the power supply until you have
completed the installation.
Fig. 15. S2 I/O Bus switch
EN1B-0410GE51 R0908A
NOTE: The terminal socket of each I/O module can be
mounted and wired before inserting and locking the corresponding electronic module.
14
Excel 800 Mounting/Dismounting Modules
Mounting/Dismounting Controller/Sockets
Mounting Sockets
NOTE: When using both Panel Bus and LONWORKS Bus
I/O modules in an Excel 800 System, group both Panel Bus modules (light-gray) and L Bus I/O modules (dark-gray), e.g., on different rails. Up to 10 Panel Bus I/O modules can be mounted to one side of the XCL8010AU. In total, up to 16 Panel Bus I/O modules can be mounted to one controller. The XCL8010AU Controller Module is mounted on the DIN rail in the same way as a terminal socket.
ONWORKS
Panel
BUS I/O
max. 10
Panel
BUS I/O
XCL8010AU
max. 16
BUS I/O
Panel
LonWorks
Panel
BUS
BUS I/O
I/O
max. 10
Fig. 16. Max. number of Panel Bus I/O modules
LonWorks
BUS I/O
NOTE: MAX. OF 16 DIGITAL INPUT MODULES MAY BE USED.
Fig. 17. Max. number of L
max. 10
LonWorks
BUS I/O
XCL8010AU
max. 20
ONWORKS Bus I/O modules with
LonWorks
BUS I/O
LonWorks LonWorks
BUS
BUS I/O
I/O
max. 10
power supply via XCL8010AU
Angle the terminal socket at the upper edge of the DIN rail
until it snaps in.
Swing the terminal socket down and apply gentle force
until it snaps into position with an audible "click".
Position XCL8010AU Controller Module and terminal
sockets flush with one another along the rail.
If desired, mount stoppers at the ends of the rail to prevent
sliding.
Fig. 18. Mounting terminal sockets
NOTE: Take care to not bend the Omega clamp, which
serves to establish the electrical contact with the DIN rail and which located on the back of the terminal socket.
Connecting Sockets
Controller and terminal sockets on the same DIN rail can be connected mechanically and electrically with bridge connectors.
Controller and terminal sockets on different DIN rails must be connected using cables.
NOTICE
Risk of malfunction!
Wire Panel Bus I/O modules and LONWORKS Bus
I/O modules separately.
When using both Panel Bus and LONWORKS Bus
I/O modules in an Excel 800 System, L I/O modules must be connected to the XCL8010AU Controller Module via LON terminals 11 14.
Position the bridge connector on terminals 71 74 of the right hand terminal socket or XCL8010AU Controller Module and on terminals 75 78 of the left hand terminal socket or XCL8010AU Controller Module. Then press the bridge connector down.
ONWORKS Bus
15 EN1B-0410GE51 R0908A
Mounting/Dismounting Modules Excel 800
Fig. 21. Releasing latch
Fig. 19. Connecting terminal sockets with bridge
connector
Mounting/Dismounting Electronic Modules
NOTE: Bridge connectors transmit both communication
signals and power supply between modules. Removing bridge connectors will interrupt the transmission of both communication signals and power supply between the modules.
Dismounting Sockets
Disconnecting Sockets
Release all bridge connectors before removing the XCL8010AU Controller Module and/or the terminal sockets from the DIN rail.
Press down at the same time both the gray side wings next
to the red button and then pull the bridge connector out of the module.
Mounting Electronic Modules
NOTE: Electronic modules can be removed from the
socket or inserted into the sockets without switching off the power supply. The behavior of connected field devices must be taken into consideration.
Make sure that terminal socket und I/O module match.
Make sure that the red locking mechanism is in the open,
i.e., left, position.
Gently push the electronic module onto the terminal socket
until snug.
Fig. 20. Releasing bridge connectors
Dismounting Controller/Terminal Sockets
Insert a screwdriver into the latch on the underside of the
module and lever the red latch 2–3 mm downwards. The module can then be swung away from the rail.
EN1B-0410GE51 R0908A
Lock the red locking mechanism by sliding it to the right.
16
Fig. 22. Inserting the electronic module
Excel 800 Mounting/Dismounting Modules
Setting the C-Bus Termination Switch
Set the C-Bus termination switch S1 appropriately.
Fig. 23. Locking the electronic module
NOTE: The red locking mechanism will not close if the
electronic module is not properly mounted.
Dismounting Electronic Modules
NOTE: Electronic modules can be removed from the
socket or inserted into the sockets without switching off the power supply. The behavior of connected field devices must be taken into consideration.
Open the red locking mechanism by sliding it to the left
and then gently pull the electronic module out of the terminal socket.
Table 11. XCL8010AU
switch setting
9.6k all
76k mid Up to 76800 baud without bus termination
76k end Up to 76800 baud with bus termination
Shielding
In principle, data transmitting cables should be shielded in case of RFI.
On the controller side, connect the shield to terminals 7
and 10.
On the side of the device, connect the shield to the
respective terminals. Do not connect it to the cabinet ground or any other ground points.
Fig. 25. C-Bus termination switch S1
C-Bus termination switch settings
S1
Up to 9600 baud (default setting)
baud rate
Connecting HMIs or Laptops
Fig. 24. Dismounting the electronic module
Connecting via C-Bus
Via C-Bus, an XCL8010AU Controller Module can be connected to other controller systems to form a network.
Connecting to the Controller
Connect the C-Bus to the XCL8010AU Controller Module
as follows:
– Input to C-Bus terminals 8 and 9
– Output to C-Bus terminals 5 and 6
– Do not connect the C-Bus to the cabinet earth or any
other earth ground points
17 EN1B-0410GE51 R0908A
Laptops or HMIs, e.g., XI582, can either be connected via the HMI interface of the XCL8010AU Controller Module or via the L
ONWORKS interface.
Connecting the XI582 Operator Interface
Connect the XI582AH Operator Interface to the HMI
interface or L Controller Module by means of
– the XW882 cable or
– the XW582 cable connected with an XW586 cable.
ONWORKS interface of the XCL8010AU
Mounting/Dismounting Modules Excel 800
Connecting Laptops (XL-Online/CARE)
Connect a laptop (on which e.g., XL-Online or CARE has
been installed) to the HMI interface or L of the XCL8010AU
Controller Module by means of
ONWORKS interface
– the XW885 cable or
– the XW585 cable connected with an XW586 Cable.
XCL8010AU Terminals
COM
71
A
COM
72
B
24
73
V~ 24
74
V~ 0
87 6543 21
LON
11
1
12
13
14
LON
LON
LON
2
1
2
8 5
C+ C+
9 6
C- C-
SHIELD SHIELD
10 7
*Watch Dog
Fig. 26. Terminal assignment and internal connections of
the XCL8010AU Controller Module
Table 12. Description of XCL8010AU terminals
ter-
minal
71, 75 COM a
72, 76 COM b
signal comment
2-wire communication bus (LON/Panel Bus)
2-wire communication bus (LON/Panel Bus)
73, 77 24 V~ Power supply for I/O modules
74, 78 24 V~0 Power supply for I/O modules
1 24 V~ Power supply from transformer
2 24 V~0 Power supply from transformer
3 24 V~0 Alarm/watchdog output
4 NC Alarm/watchdog output
5, 8 C+ C-Bus
6, 9 C- C-Bus
7, 10 Shield C-Bus shield
11, 12 LON LONWORKS IN
13, 14 LON LONWORKS OUT
Relay
COM
75
A
COM
76
B 24
77
V~ 24
78
V~0
24
1
V~ 24
2
V~0
24
3
V~0
NC
4
*
Features
LONWORKS Interface and Terminals
The XCL8010AU Controller Module features
An RJ45 socket serving as an interface to connect laptops or HMIs to the L
LONWORKS terminals 11, 12, 13, and 14 to connect L
ONWORKS devices to the XCL8010AU Controller or other
L L
ONWORKS controllers.
ONWORKS Bus I/O modules or other
Fig. 27. L
ONWORKS interface and LONWORKS terminals
LONWORKS Interface Signals on RJ45 Socket
Table 13. Signals of L
pin signal type
1 Connection to LONWORKS Bus
2 Connection to LONWORKS Bus
3 8 Not used
LONWORKS Service LED and Button
The XCL8010AU Controller Module is equipped with a L
ONWORKS service button and corresponding LONWORKS
Service LED (status: yellow/OFF).
Fig. 28. L
ONWORKS service button (1) and service LED (2)
ONWORKS Bus
ONWORKS interface
LON
1
2
EN1B-0410GE51 R0908A
See also section "Troubleshooting" on page 31.
18
Excel 800 Mounting/Dismounting Modules
C-Bus Tx LED and Rx LED
The XCL8010AU Controller Module is equipped with a Tx LED (status: yellow/OFF) and an Rx LED (status: yellow/OFF).
C-Bus
1
2
Fig. 29. C-Bus Tx LED (1) and Rx LED (2)
C-Bus LEDs
Table 14. Controller C-Bus LEDs
Tx (1) flickering
Rx (2)
flickering
The controller is sending data onto the C-Bus
The controller is receiving data from the C-Bus
Reset Button
The XCL8010AU Controller Module is equipped with a reset button.
RESET
1
Fig. 30. Reset button (1)
Pushing the reset button (1), e.g. using a paperclip, will cause the XCL8010AU
NOTE: In the event of a reset, all non-volatile memory
Controller Module to reset.
contents are permanently deleted, though the clock will not be set to zero. In order to avoid problems, we therefore recommend that you always save your application changes (e.g., time program changes) to FLASH memory.
HMI Interface
The XCL8010AU Controller Module is equipped with an HMI Interface for the connection of HMIs, e.g., XI582 Operator Interface or a laptop (with XL-Online/CARE).
Fig. 31. HMI interface, Tx LED (1) and Rx LED (2)
HMI interface LEDs on RJ45 socket
Table 15. HMI interface LEDs
Tx (1) flickering
Rx (2) flickering
HMI interface Signals on RJ45 socket
1 -
2 Receive
3 Transmit
4 -
5 Signal ground
6 -
7 5 V
8 -
The controller is transmitting data to the HMI
The controller is receiving data from the HMI
Table 16. Signals of the HMI interface
pin signal type
NOTICE
Equipment damage!
If earth grounding is required, make sure that only terminal
2 is connected to earth ground. Terminal 1 must not be connected to earth ground. See also Appendix 1.
19 EN1B-0410GE51 R0908A
Mounting/Dismounting Modules Excel 800
Alarm and Power LEDs
The XCL8010AU Controller Module is equipped with an alarm LED and a power LED.
Fig. 32. Alarm LED (1) and power LED (2)
Alarm LED (1, red)
Table 17. Controller alarm LED
Off
On
Flashing The watchdog alarm output has not yet been
Power LED (2, green)
On
Flashing One or more of the internal voltage supplies
Goes out briefly
Normal operation
Watchdog alarm output is powered
The controller has encountered a hardware problem
The application has a fault
The controller has been powered up without
an application or the operator has manually stopped the application. In this case, the LED will light up 13 minutes after power-up without application
powered, although the controller has encountered a problem.
The controller performs a warm start.
If problem persists, the LED will become lit constantly, see above.
See section "Troubleshooting" on page 31.
Table 18. Controller power LED
Normal operation
are outside of the permissible ranges.
The controller stops operation.
Check wiring or see section
"Troubleshooting" on page 31.
The operator has activated the reset
button
The controller is performing a warm start
Watchdog Status
Table 19. Watchdog status (terminal 4)
status signal on terminal 4
Failure (= alarm) 24 V
Normal operation 0 V
Modem Interface
NO CONNECTION.
I/O Bus Switch S2
The XCL8010AU Controller Module features a 2-position I/O Bus switch S2.
I/O Bus switch S2 must be set in accordance with the kind of I/O modules connected to communication terminals 71, 72 and 75, 76 of the XCL8010AU Controller Module.
Terminals 71, 72 and 75, 76 must be all connected either to Panel Bus I/O modules or to L
The default setting is Panel.
Fig. 33. I/O Bus switch S2
Table 20. I/O Bus switch settings
communication S2 setting
LONWORKS Bus only LON
Panel Bus and LONWORKS Bus
ONWORKS BUS modules connected to
L terminals 11 14 of the XCL8010AU Controller Module
Panel Bus connected to terminals 71, 72 or 75, 76 of the XCL8010AU Controller Module
ONWORKS Bus I/O modules.
Panel
Panel
EN1B-0410GE51 R0908A
20
Excel 800 Description of the I/O Modules
C-Bus Termination Switch S1
The XCL8010AU Controller Module features a 3-position C­Bus termination switch S1.
This switch must be set in accordance with the given C-Bus configuration.
Fig. 34. C-Bus termination switch
Table 21. XCL8010AU
switch setting
S1
9.6k all
76k mid Up to 76800 baud without bus termination
76k end
Up to 9600 baud (default setting)
Up to 76800 baud with bus termination controller at the end of the C-Bus
C-Bus termination switch S1
settings
baud rate
Description of the I/O Modules
Common Features
Switches Located on the Terminal Socket
Table 23. Terminal socket switches
feature function
Service button S1
Hex switch S2
LEDs Located on the I/O Module
feature function
Service LED (yellow)
Power LED (green)
For the location of these elements, see figures of the respective modules.
LED test, see section "Troubleshooting" on page 31
L
ONWORKS service button functionality
for L
ONWORKS Bus I/O modules
Module addressing for Panel Bus I/O modules
Table 24. LEDs on I/O module
Service information, see section "Troubleshooting" on page 31
Information on power supply, see section "Troubleshooting" on page 31
Memory
Table 22. XCL8010AU memory
memory size usage
SRAM 512 KB
Flash 2 MB
EPROM 128 KB For bootstrap loader
NOTE: The XCL8010AU
contain a battery. RAM (data and realtime clocktime) is buffered for 3 days by a super capacitor.
For controller application, modem trend and firmware
RACL application: 128 KB
Total application: 192 KB
Firmware (1 MB) and application (1 MB) storage
Controller Module does not
21 EN1B-0410GE51 R0908A
Description of the I/O Modules Excel 800
Analog Input Modules
Types of Analog Input Modules
Table 25. Excel 800 Analog Input Modules
type description housing
XF821 Panel Bus Analog Input Module light-gray
L
XFL821
ONWORKS Bus Analog Input
Module
XS821-822 terminal socket light-gray
Features
8 analog inputs
Sensor-break and short-circuit detection, see section
"Troubleshooting" on page 31.
Fig. 35. XF821AU Analog Input Module with terminal
socket
Legend
1 Service button S1
2 Hex switch S2
3 Service LED
4 Power LED
Functionality of service LED and power LED: see Table 42 and following.
dark-gray
Terminals
COM
71
A
COM
72 76
B
24
73 77
V~ 24
74
V~0
AI8
AI7
AI6
AI5
AI4
AI3
AI2
V
AUXVAUX
22
21
GND9GND
10
Fig. 36. Terminal assignment and internal connections of
Table 26. Description of Analog Input Module terminals
ter-
minal
71, 75 COM a
72, 76 COM b
73, 77 24 V~ Power supply
74, 78 24 V~0 Power supply
1 8 AI1 AI8 Analog inputs 1 8
9 18 GND
21, 22
25, 26
NOTE: Shield connection to be used for shielded I/O
AI1
8
7
6
5
4
3
2
1
GND11GND GNDGND GND GND GND GND
18171615141312
Analog Input Modules
signal comment
2-wire communication bus (LON/Panel Bus)
2-wire communication bus (LON/Panel Bus)
Ground. All grounds are connected internally to each other
Auxiliary voltage signal (used e.g. for
10 VDC /
5 mA
supplying setpoint potentiometers).
Connections to these terminals must be made in the same room.
Shield connection (functional earth), internally connected to the DIN rail
cables only. It is not allowed to connect a
ONWORKS shield.
L
COM
A
COM
B 24
V~ 24
V~0
25 26
75
78
EN1B-0410GE51 R0908A
22
Excel 800 Description of the I/O Modules
XFL821AU Connection Examples
400 OHM
25
18
1
SHIELD SHIELD
1
2
0(4) to 20 mA
0(4) to 20 mA (VIA EXTERNAL 500 OHM RESISTOR).
5
14
10 1
11 12 2
25 25
22
SHIELD SHIELD
VMP Pt1000 NTC20kW
Fig. 37. XFL821AU Analog Input Module
2
12
1
2
0 to 10 V
0 TO 10 VDC
3
13
25
23 EN1B-0410GE51 R0908A
Description of the I/O Modules Excel 800
Analog Output Modules
Types of Analog Output Modules
Table 27. Excel 800 Analog Output Modules
type description housing
XF822
XFR822
XFL822
XFLR822
XS821-22 terminal socket light-gray
Panel Bus Analog Output Module
Panel Bus Analog Output Module with manual overrides
L
ONWORKS Bus Analog Output
Module
L
ONWORKS Bus Analog Output
Module with manual overrides
Features
8 analog outputs; can also be configured per output as binary outputs (0 10 V, 2 ─ 10 V, ON/OFF, or floating)
Corresponding output status LEDs (red)
XFR822AU/XFLR822AU: 8 manual overrides, see figure
below
Fig. 38. XF822AU Analog Output Module with terminal
socket
light-gray
light-gray
dark-gray
dark-gray
Terminals
Fig. 39. Terminal assignment and internal connections of
the Analog Output Modules
Table 28. Description of the Analog Output Module
terminals
ter-
minal
71, 75 COM a
72, 76 COM b
73, 77 24 V~ Power supply
74, 78 24 V~0 Power supply
1 8 AO1 AO8 Analog outputs 1 8
9 18 GND
21, 22 N.C. Do not use!
25, 26
NOTE: Shield connection to be used for shielded I/O
signal comment
2-wire communication bus (LON/Panel Bus)
2-wire communication bus (LON/Panel Bus)
Ground. All grounds are connected internally to each other
Shield connection (functional earth), internally connected to the DIN rail
cables only. It is not allowed to connect a L
ONWORKS shield.
Technical Data
Output status LEDs behavior
Table 29. Analog Output Module status LED behavior
Legend
1 Service button S1
2 Hex switch S2
3 Manual overrides
4 Output LEDs
5 Service LED
6 Power LED
Functionality of service LED and power LED: see Table 42 and following.
EN1B-0410GE51 R0908A
automatic mode brightness follows the
commanded output signal
override mode
24
flashes
Excel 800 Description of the I/O Modules
X
Modules with Manual Overrides
The XFR822AU/XFLR822AU Analog Output Modules are equipped with manual overrides: one rotary knob for each analog output.
The manual overrides can be set manually to either "auto" or "0 110%".
NOTICE
Damage to the electronic module!
Do not use a tool to adjust the rotary knobs.
Do not use excessive force. Adjust only by hand.
XFL822AU Connection Example
LN
24V
14507287
POWER
MODULE
This updating (synchronization) is performed:
If the calculated position of the actuator < lower synchronization threshold (2 %) = synchronization towards 0 %
If the calculated position of the actuator > upper synchronization threshold (98 %) = synchronization towards 100 %
Following any power-up or any reset
~
XFL822AU
11
1
738
Umax = 11 VDC Imax = 1 mA, -1 mA
SL511
GND SIGNAL 24VAC
M
Fig. 40. XFL822AU Analog Output Module
Synchronization Behavior of Analog Output Module Configured as Floating Output
In order to regularly update the real actuator position with the calculated position and thus ensure that the actuator definitely reaches its end position, a synchronization process is performed by the Analog Output Module.
During the synchronization process, the Analog Output Module will continue running for the configured runtime once it reaches the calculated end position.
25 EN1B-0410GE51 R0908A
Description of the I/O Modules Excel 800
Binary Input Modules
Types of Binary Input Modules
Table 30. Excel 800 Binary Input Modules
type description housing
XF823 Panel Bus Binary Input Module light-gray
L
XFL823
ONWORKS Bus Binary Input
Module
XS823 terminal socket light-gray
Features
12 binary inputs
12 configurable status LEDs (green/red, yellow/OFF)
Binary inputs can be used as
– Static digital inputs as dry-contacts
Fig. 41. XF823AU Binary Input Module with terminal
socket
Legend
1 Service button S1
2 Hex switch S2
3 Input LEDs
4 Service LED
5 Power LED
Functionality of service LED and power LED: see Table 42 and following.
dark-gray
Terminals
COM
71
A
COM
72 76
B
24
73 77
V~ 24
74
V~0
BI12
BI11
BI10
BI9
BI8
BI7
BI6
BI5
BI4
BI3
BI2
BI1
12
11
10
9
8
7
6
5
4
3
2
1
GND13GND GNDGND GND GND GNDGND GND GNDGND GND
2423222120191817161514
Fig. 42. Terminal assignment and internal connections of
Binary Input Modules
Table 31. Description of Binary Input Module terminals
ter-
minal
71, 75 COM a
72, 76 COM b
signal comment
2-wire communication bus (LON/Panel Bus)
2-wire communication bus (LON/Panel Bus)
73, 77 24 V~ Power supply
74, 78 24 V~0 Power supply
1 12 BI1 BI12 Binary inputs 1 12
13
24
25, 26
GND
Ground. All grounds are connected internally to each other.
Shield connection (functional earth), internally connected to the DIN rail.
NOTE: Shield connection to be used for shielded I/O
cables only. It is not allowed to connect a L
ONWORKS shield.
COM
A
COM
B
24 V~
24
V~0
25 26
75
78
Technical Data
Table 32. Technical data for of Binary Input Modules
input type
current rating (closed input)
open contact voltage
dry-contact
2 mA
16 22 VDC
EN1B-0410GE51 R0908A
26
Excel 800 Description of the I/O Modules
Status LEDs
The status LEDs can be configured individually for use as either alarm LEDs (red/green) or as status LEDs (yellow/OFF [default]).
Given a state of "logical ON," the LED will be lit (yellow or red).
XF823AU Connection Examples
25
13
SHIELD
1
2
5 TO 24V
2 1
MIN.
25 MS
3 15
MIN.
25 MS
CONTACT SUITABLE FOR LO W V OLTA GE (G OL D) .
1
PROTECTED SWITCHING
2
UP TO 40 VDC / 24 VAC.
21
14
5 TO 24
VDC
1
~ 120V
PT1000 NTC20kW
Fig. 43. XFL823AU Binary Input Module
27 EN1B-0410GE51 R0908A
Description of the I/O Modules Excel 800
Relay Output Modules
Types of Relay Output Modules
Table 33. Excel 800 Relay Output Modules
type description housing
XF824 Panel Bus Relay Output Module light-gray
XFR824
Panel Bus Relay Output Module with manual overrides
L
XFL824
ONWORKS Bus Relay Output
Module
L
XFLR824
ONWORKS Bus Relay Output
Module with manual overrides
XS824-25
terminal socket; can be fitted with long (red) cross connector (incl. in scope of the delivery)
Features
6 relays (changeover contacts), arranged in two blocks
XFLR824AU, XFR824AU: 6 manual overrides
Low and line voltage allowed, see WARNING.
light-gray
dark-gray
dark-gray
light-gray
Terminals
COM
71 75
A
COM
72 76
B
24
73 77
V~ 24
74
V~ 0
NO
NC
COM
CON
Relay block 1
11
12
13
14
NO
NC
COM
CON
NO
21
22
23
24
31 41 51 61
NC
32
COM
33 43 53 63
CON
34 44 54 64
Cross connector (can be removed, as desired)
NO
NC
COM
CON
42
Relay block 2
NO
NC
52 62
COM
CON
Fig. 45. Terminal assignment and internal connections of
Relay Output Modules
NO
NC
COM
CON
COM
A
COM
B
24 V~
24
V~0
78
25
Fig. 44. XF824AU Relay Output Module with terminal
socket
Legend
1 Service button S1
2 Hex switch S2
3 Manual overrides
4 Status LEDs
5 Service LED
6 Power LED
Functionality of service LED and power LED: see Table 42 and following.
EN1B-0410GE51 R0908A
28
Excel 800 Description of the I/O Modules
Table 34. Description of Relay Output Module terminals
terminal signal comment
2-wire communication bus (LON/Panel Bus)
2-wire communication bus (LON/Panel Bus)
Power supply Power supply Relay 1 N.O. contact Relay 1 N.C. contact relay 1 common contact For connection of relay 1 common via
cross connector* Relay 2 N.O. contact Relay 2 N.C. contact Relay 2 common contact For connection of relay 2 common via
cross connector* Relay 3 N.O. contact Relay 3 N.C. contact Relay 3 common contact For connection of relay 3 common via
cross connector* Relay 4 N.O. contact Relay 4 N.C. contact Relay 4 common contact For connection of relay 4 common via
cross connector* Relay 5 N.O. contact Relay 5 N.C. contact Relay 5 common contact For connection of relay 5 common via
cross connector* Relay 6 N.O. contact Relay 6 N.C. contact Relay 6 common contact For connection of relay 6 common via
cross connector* Shield connection (functional earth),
internally connected to the DIN rail
11 12 13
14
21 22 23
24
31 32 33
34
41 42 43
44
51 52 53
54
61 62 63
64
COM a
COM b
24 V~
24 V~0
REL1 N.O.
REL1 N.C.
R1 COM
R1 COM
REL2 N.O.
REL2 N.C.
R2 COM
R2 COM
REL3 N.O.
REL3 N.C.
R3 COM
R3 COM
REL4 N.O.
REL4 N.C.
R4 COM
R4 COM
REL5 N.O.
REL5 N.C.
R5 COM
R5 COM
REL6 N.O.
REL6 N.C.
R6 COM
R6 COM
71, 75
72, 76
73, 77 74, 78
RELAY BLOCK 1
RELAY BLOCK 2
25
* Do not connect by wire!
Permissible Loads
Table 35. Permissible loads of Relay Output Modules
max. load
per relay output module (total) (common)
24 VAC, 60 Hz
12 A 24 VDC
12 A resistive, 12 A, 0.6 PF
per normally open contact (common)
24 VAC, 60 Hz
4 A 24 VDC
4 A resistive, 4 A, 0.6 PF
per normally closed contact (common)
24 VAC, 2 A, 60 Hz 24 VDC
4 A resistive, 4 A, 0.6 PF
Status LEDs with Manual Overrides
5
12
4
3
6
Fig. 46. Manual overrides (toggle switches)
The XFR824AU and XFLR824AU Relay Output Modules are equipped with six manual overrides: one for each relay output. These toggle switches can manually be set to either "auto" or "0" or "1".
Table 36. Relay Output Module status LED behavior
mode LED
automatic mode, state
ON ON OFF
N.O.*
(direct)
“logical ON”
automatic mode, state
OFF OFF ON
“logical OFF”
override mode (setting “0”) flashes OFF ON
override mode (setting “1”) flashes ON OFF
*As configured during engineering.
Honeywell
--1
--0
--AUTO
!
N.C.*
(reverse)
29 EN1B-0410GE51 R0908A
Description of the I/O Modules Excel 800
Connection Examples
14507287 SERIES POWER MODULE
COM
71 71
A
COM
72 72
B
24
73 7377
V
~
24
74 74
V
~
0
NO
NC
COM
CON
12
13
14
11
NO
NC
COM
CON
22
23
24
21
NO
NC
COM
CON
31
32
33
34
NO
NC
COM
CON
41
42
43
44
NO
NC
COM
CON
51
52
53
54
NO
NC
COM
CON
COM
COM
24
V
24
V
61
62
63
64
75
A
76
B
~
78
~
0
25
1 2
Fig. 47. XF824AU connection example
COM
A
COM
B
24 V
~
24
V
~
0
M
14507287 SERIES POWER MODULE
COM
71 71
A
COM
72 72
B
24
73 7377
V
~
24
74 74
V
~
0
NO
NC
COM
CON
12
13
14
11
NO
NC
COM
CON
22
23
24
21
NO
NC
COM
CON
31
32
33
34
NO
NC
COM
CON
41
42
43
44
NO
NC
COM
CON
51
52
53
54
NO
NC
COM
CON
COM
COM
24
V
24
V
61
62
63
64
75
A
76
B
~
78
~
0
25
123
M
Fig. 48. XFR825AU connection example
COM
A
COM
B
24 V
24
V
~
~
0
EN1B-0410GE51 R0908A
30
Excel 800 Troubleshooting
Troubleshooting
Testing Wiring Connections
The push-in terminals feature small holes (1 mm in diameter) which can be used to measure the signals.
Insert a probe (1) as shown on the right.
Fig. 49. Testing wiring connections
Troubleshooting on the XCL8010AU Controller
The following LEDs of the XCL8010AU Controller can be used for troubleshooting purposes:
Power LED (green)
Alarm LED (red)
L
ONWORKS service LED
C-Bus Tx and Rx LEDs
HMI Tx and Rx LEDs
Power LED (green)
Table 37. XCL8010AU power LED
case power LED meaning remedy
1 ON
2 Flashing
3 Goes out briefly
Normal operation No action necessary
One or more of the internal voltage supplies are outside of the permissible ranges. The controller stops operation.
The operator has activated the reset button
The controller is performing a warm start
Check power
Check wiring
If problem persists, replace hardware
No action necessary
31 EN1B-0410GE51 R0908A
Excel 800
Alarm LED (red)
Table 38. XCL8010AU alarm LED
case alarm LED meaning remedy
1 OFF
2 ON
Normal operation No action necessary
Watchdog alarm output is powered
– The controller has encountered a
hardware problem
- or -
– The application has a fault
- or -
– The controller has been powered up
without an application or the operator has manually stopped the application, e.g., using XL-Online. In this case, the LED will light up 13 minutes after power-up without application
3 Flashing Although the controller has encountered a
problem, the watchdog alarm output has not yet been powered.
If problem persists, the LED will become lit constantly, see case #2.
The controller performs a warm start.
LONWORKS Service LED
Try powering down and then
powering up the XCL8010AU.
If problem persists, check and – if
necessary – reload the application.
If problem still persists, replace
hardware
If it happens only once, the controller has performed a restart
If, however, it happens multiple times, then there is an application or hardware problem (see case #2)
Fig. 50. Flashing pattern of the L
ONWORKS service LED
ONWORKS service LED of the XCL8010AU Controller Module displays the following flashing patterns indicating possible
The L failure modes:
EN1B-0410GE51 R0908A
32
Excel 800 Troubleshooting
Table 39. XCL8010AU L
ONWORKS service LED
case When can it occur? meaning remedy
1
2
3
4
Anytime
Power up of controller
Power up of controller
Power up / reset
Node is configured and running normally
Bad node hardware
Bad node hardware
Node lacks application. May be caused by neuron chip firmware when a mismatch occurs on application checksum
No action necessary
Replace hardware
Replace hardware
Using EXCELON, set module to
“configured online”
If problem persists, the MIP software
on LW interface has been erased due to wrong setting performed using ECHELON tool: Replace hardware
5
Anytime
Watchdog timer resets occurring.
Download firmware
Possible corrupt EEPROM and bootstrap mode
6
Anytime
Node is unconfigured but has an application
Proceed with commissioning
C-Bus Tx and Rx LEDs
Table 40. XCL8010AU C-Bus Tx and Rx LEDs
case C-Bus LEDs meaning remedy
1
Both LEDs are flashing
2
Both LEDs are OFF
3 Both LEDs are flashing
synchronously
If the C-bus is functioning properly, then the XCL8010AU is functioning properly
If the C-bus is not functioning properly, then the termination can be wrong
No C-bus communication
No C-bus communication
No action necessary
Check C-bus termination switch S1
(location: see Fig. 4 on page 7)
Check C-bus settings
Check C-bus wiring
HMI Tx and Rx LEDs
Table 41. XCL8010AU HMI Tx and Rx LEDs
case HMI LEDs meaning remedy
1
2
Both LEDs are flashing
Both LEDs are OFF
33 EN1B-0410GE51 R0908A
If the HMI Interface is functioning properly, then the XCL8010AU is functioning properly
No HMI Interface communication
No action necessary
Check HMI Interface connection and
proper earthing of connected hardware
Excel 800
I/O Modules Troubleshooting
Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the
inputs/outputs of the XF821AU, XFL821AU, XF822AU, XFL822AU, XFR822AU, XFLR822AU, XF823AU, and XFL823AU I/O modules.
Replace the problem I/O module with another module of the same kind.
– If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring.
– If the problem is solved, this is an indication that the I/O module was defective.
For troubleshooting purposes on all I/O modules the following features can be used:
Power LED
Service LED
Service button
In addition, a module-specific troubleshooting may be necessary.
Power LED of I/O Modules
Table 42. Power LED of I/O modules
case power LED meaning remedy
1 ON
2 OFF
3 Flashing continuously
I/O module is powered
No power
If the I/O module’s service LED is likewise flashing, the I/O module is in the boot mode
No action necessary
Check power supply
Wait until rebooting (firmware
download) has been completed
EN1B-0410GE51 R0908A
34
Excel 800 Troubleshooting
Service LED of I/O Modules
Table 43. Service LED of I/O modules
case Service LED meaning remedy
1
2
3
4
5
6
7
8
9
10
LED remains OFF after power-up
LED is lit continuously after first power-up
Alternating flash between service LED and power LED
LED flashes at power up, goes OFF, and then is lit continuously
LED repeatedly blinks ON for 1 sec and OFF for 1 sec
LED remains OFF after a short ON duration
LED flashes continuously in following pattern: 4 x ON/OFF followed by pause
LED flashes continuously in following pattern: 5 x ON/OFF followed by pause
LED flashes continuously in following pattern: 6 x ON/OFF followed by pause
LED flashes continuously in following pattern: 7 x ON/OFF followed by pause
If the power LED is also OFF, then
– Defective device hardware – Possible power supply problems, clock
problems, defective processor
ONWORKS Bus I/O modules:
L – Defective hardware
Panel Bus I/O modules: – I/O module has not yet been configured
by XCL8010AU – Boot loader is active – Failure during last firmware download – Checksum error
Panel Bus I/O modules, only: Download error or application checksum error. Boot loader is running
ONWORKS Bus I/O modules, only:
L
ONWORKS Bus I/O module lacks application
L
ONWORKS Bus I/O modules, only:
L
ONWORKS Bus I/O module is unconfigured, but
L has an application
I/O module is configured and running normally
Sensor failure of Analog Input Module (in case of L
ONWORKS Bus I/O modules, this
behavior can occur only if the appropriate NV has been bound)
ONWORKS Bus I/O modules, only: LONWORKS
L I/O Bus module has received the wink command from network, physical outputs are unaffected
Boot loader problem or hardware defect
Communications failure
Replace hardware
L
ONWORKS Bus I/O modules:
Replace hardware Panel Bus I/O modules: Set the hex address to the position configured
with CARE
Ensure that I/O Bus switch S2 of XCL8010AU is
set to position "Panel"
Check the Panel Bus wiring:
- Check for cable breaks
- Check for cable short-circuits
- If using separate transformers: Check ground connection
Eliminate any mixture of Panel Bus I/Os and
LonWorks I/Os on same wire
Allow XCL8010AU to configure I/O module Unplug and replug the module If problem persists, replace hardware
Panel Bus I/O modules, only:
Wait until rebooting (firmware download) has been completed
Download application
Set module to configured mode
No action necessary
Check sensor or connection Check sensor configuration
No action necessary
Replace hardware
Check bus wiring Ensure that I/O Bus switch S2 of XCL8010AU is
set to correct position
Ensure that L
ONWORKS Bus I/O modules and
Panel Bus I/O modules are not sharing same bus
In case of Panel Bus I/O modules, only:
Check for incorrect HEX addresses (2 Panel Bus I/O modules using same HEX address)
In case of L
ONWORKS Bus I/O modules, only:
Check heartbeat
35 EN1B-0410GE51 R0908A
Excel 800
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich / Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN1B-0410GE51 R0908A
Loading...