The T8635L is a microelectronic communicating programmable thermostat that supports single-stage or multi-stage
conventional and heat pump applications when used with the W8835 (3H/2C) or W8635A (up to 2H/2C conventional) or W8635B (up to 2H/1C heat pump) Equipment Interface Module (EIM). See Table 1.
Table 1. T8635L Thermostat Description.
ModelSystemChangeover
T8635L and W8835A,EHeat-Cool or
T8635L and W8635AHeat-CoolAutomatic or
T8635L and W8635BHeat Pump
a
See System and Fan Keys section for specific information.
Heat Pump
Automatic or
Manual
Manual
a
System Selection
Heat-Off-Cool-Auto
Em. Ht
Heat-Off-Cool-AutoOn-Auto
Heat-Off-Cool-Auto
Em. Ht
a
Fan Selection
On-Auto
Accessories
Required (Not Included)
W8835A,E EnviraZone Panel – For up to 3H/2C con-
ventional or heat pump applications.
W8635A – Equipment Interface Module (EIM) for up to
2H/2C conventional applications.
W8635B – Equipment Interface Module (EIM) for up to
2H/1C heat pump applications.
Optional
W8703A – Damper Interface Module.
C7089B – Outdoor Temperature Sensor.
C7835A – Discharge Air Temperature Sensor.
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of an old control.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
these instructions can damage the product or
cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable
for your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions to check out the product operation.
CAUTION
Vol tage Ha z a r d.
Can cause electrical shock or equipment
damage.
Disconnect power before beginning installation.
Location
Install the thermostat about 5 ft. (1.5m) above the floor
in an area with good circulation at average temperature.
See Fig 1.
Do not install the thermostat where it can be affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall
or on a 2 in. by 4 in. wiring box. Position wallplate horizontally on the wall or on a 2 in. by 4 in. wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat functions properly even
when not level.
2. Use a pencil to mark the mounting holes. See
Fig. 2.
3. Remove the wallplate from the wall and drill two
3/16-in. holes in the wall (if drywall) as marked.
For firmer material such as plaster, drill two
7/32-in. holes. Gently tap anchors (provided) into
the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling the
wires through the wiring opening.
5. Loosely insert the mounting screws in the holes.
6. Tighten the mounting screws.
WALL
ANCHORS
(2)
WALL
WIRES
THROUGH WALL
Fig. 2. Mounting the wallplate.
MOUNTING
HOLES
MOUNTING
SCREWS
M6530A
69-1331—52
WIRING
All wiring must comply with local electrical codes and
ordinances. See Fig. 5 through 8 wiring diagrams for
specific equipment applications. Refer to Table 2 for terminal designations.
Connect outdoor sensor to only one thermostat and configure that thermostat Installer
Setup No. 45 to 1. See Table 6. Connecting
more than one outdoor sensor or configuring
more than one thermostat for outdoor sensor
causes the thermostat to incorrectly display
the outdoor temperature.
W8635A
1
2
3
C
R
R
H
R
C
G
W1
W2
Y1
Y2
FAN
RELAY
HEAT 1
RELAY
HEAT 2
RELAY
COOL 1
RELAY
COOL 2
RELAY
546Z
213
MODEL AOBD
ZONE DAMPER
Power-closed/
Spring-open
(Model ZD)
Power-closed/
Spring-open
(Model ARD)
W8703A
X
OPEN
CLOSE
OPEN
CLOSE
OPEN
CLOSE
Fig. 7. T8635L/W8703A/W8635A with Outdoor Temperature Sensor.
ZONE AZONE B
TR1
TR2
COM
ZONE C
1
2
3
L1
(HOT
L2
EXTERNAL
40 VA
TRANSFORME
M13430
69-1331—54
Page 5
9
F
Single transformer heating/cooling
systems require a jumper to be
8
B
installed connecting RH and R
(factory installed).
HVAC Equipment
HP Fault
HP Fault Common
Heating Transformer
24 VAC
Equipment
irst Stage Heating/Emergency Heat Relay
Third Stage Heating/Auxiliary Heat Relay
Reversing Valve (Cooling/Heating)
Golden Valley, MN 55422www.honeywell.com/yourhome
Cooling Transformer
Second Stage Heating Relay
First Stage Cooling Relay
Second Stage Cooling Relay
This diagram shows the typical
equipment, thermostat, and
damper motor connections.
For specific wiring,
refer to the Installation
Instructions.
The thermostat keys are used to:
— Set current day and time.
— Program times and setpoints for heating and cooling.
— Temporarily override program temperatures.
— Display present setting.
SET WAKE TIMES
AND SETPOINTS
NCREASE TIME
ETTING OR SCROLL
ORWARD THROUGH
NSTALLER SETUP
ND SYSTEM TEST
SET CURRENT
DAY AND TIME
RETURN TO NORMAL
OPERATIONS
ET CURRENT OR
ROGRAM DAY
NTER INDEFINITE
R TIMED HOLD MODE
ECREASE TIME SETTING
R SCROLL BACKWARD
HROUGH INSTALLER
ETUP AND SYSTEM TEST
HANGE BETWEEN
AYLIGHT SAVINGS
ND STANDARD TIME
Run
Program
Hold Temp
COPY ONE
PROGRAMMED DAY
TO ANOTHER DAY
INCREASE TEMPERATURE SETTING OR SCROLL
FORWARD THROUGH INSTALLER SETUP OPTIONS
Set Current
Day/Time
Day
Daylight
Time
Time
Copy
— Configure Installer Setup.
— Perform Installer System Test.
— Display outdoor temperature (when C7089B is
connected).
— Set the System key setting.
— Set the Fan key setting.
— Set, view and clear the filter setting.
See Fig. 10 for key location.
DECREASE
TEMPERATURE
SETTING OR
SCROLL BACKWARD
THROUGH INSTALLER
SETUP OPTIONS
DISPLAY
INFORMATION
SUCH AS PRESENT
SETTINGS
SET RETURN TIMES
AND SETPOINTS
Leave
Wake
Heat/Cool
Settings
CHANGE BETWEEN
HEATING AND
COOLING SETPOINTS
Set Program
ReturnSleep
SystemFilterFan
SELECT FILTER
EXPIRATION IN
NUMBER OF DAYS
SET SLEEP TIMES
AND SETPOINTS
SET LEAVE TIMES
AND SETPOINTS
SELECT FAN
OPERATION
SELECT SYSTEM
OPERATION (HEAT,
COOL, OFF, AUTO)
M17765
Fig. 10. Thermostat key locations and descriptions.
System and Fan Keys
Use the System and Fan keys on the thermostat to
select the system and fan settings.
1. Use the System key setting (Fig. 11) to control the
thermostat operation:
Heat: The thermostat controls the heating. When
Cool: The thermostat controls the cooling. When
Auto: The thermostat controls heating and cool-
NOTE: Auto is an option on non-zoned systems
Off: Both Heating and cooling are off.
Em Heat: The thermostat controls heating. When
NOTE: Em Heat is an option on systems using
69-1331—56
the thermostat is calling for heat, a is
indicated in the display.
the thermostat is calling for cool, a is
indicated in the display.
ing, automatically switching from heat to
cool based on room temperature and
thermostat setpoints.
using W8635A,B or on zoned systems
using W8835.
thermostat is calling for emergency heat,
a and Em Ht are indicated in display.
the W8635B or W8835 and configured
for a heat pump with auxiliary heat.
Run
Set Current
Leave
Wake
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
Settings
Copy
SystemFilterFan
System
Fig. 11. System key setting.
IMPORTANT
• The T8635L has an adjustable compressor
protection setting
it can be set from 0 to 5
minutes.
• The thermostat waits to call for cooling (or
heating when used with the heat pumps):
—when power is first established,
—when a power outage occurs or
—when the call has just ended and another
call is immediately attempted.
• “wait” is displayed during the compressor protection period.
• To override the compressor protection during
installation, refer to the Installer System Test
section.
• To permanently override the compressor protection, see Installer Setup No. 33 and change
the setting to 0. See Table 6.
Auto:The thermostat automatically changes
between heating and cooling operation,
depending on the indoor temperature.
stage 1 heat. Cooling system is off, and
compressor is de-energized. Em.Ht and
are displayed when the thermostat is
calling for emergency heat.
a. Press the Fan key during normal operation to
change the fan setting only for the current program period.
b. To program the fan to operate in Auto or On
for each program period individually, see the
Owner’s Guide, 69-1332.
2. Use the Fan key setting (Fig. 12) to control the
system fan:
Auto:The fan operates with the heating and
cooling equipment.
Run
Set Current
Leave
Wake
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
SystemFilterFan
Settings
Copy
Fan
On:The fan temporarily operates continu-
ously for the current program period. The
is displayed any time the thermostat is
Fig. 12. Fan key setting.
calling for fan operation.
Temperature Settings
NOTE: When used with the W8835 or W8703A
Damper Interface Module, a flashing
is displayed when one thermostat is calling for fan operation while a thermostat
in another zone is calling for heat or
cool. After the call ends from the other
thermostat, the stops flashing and
the re-quested call for fan is honored for
this zone.
Table 3. Default Program Settings.
PeriodTimeHeat SetpointCool SetpointFan Setting
Wake6:00 am70°F (21°C)78°F (25.5°C)Auto
Leave8:00 am62°F (16.5°C)85F (29.5°C)Auto
Return6:00 am70°F (21°C)78F (25.5°C)Auto
Sleep10:00 am62°F (16.5°C)82F (28°C)Auto
To program the time and temperature settings:
1. Refer to Table 3 for the default program time and
temperature settings.
2. If the daytime energy savings period is not used,
press Leave or Return (period) until the time and
temperature is blank.
3. See Owner’s Guide, 69-1332, for complete
instructions on changing the program.
Fan
M1776
On
Auto
LED Indicators
There are two LED indicators on the top right of the
thermostat. See Fig. 13.
• The check (red) LED lights when 24 volts are applied
to the L terminal on the W8635B EIM or W8835. This
indicates a problem with the heat pump equipment.
Action for Homeowner: Switch to emergency heat
and call for assistance.
• The filter (green) LED lights when the filter timer has
expired.
Action for Homeowner: Replace the furnace filter
or clean the electronic air cleaner cells. Press and
hold the Filter key to reset the counter and turn off
the LED.
(RED) LED
(GREEN) LED
Filter Indication
This thermostat can track total fan and system run time.
This feature can be used to tell the homeowner when to
replace the furnace filter or clean the electronic air
cleaner cells:
1. Select the number of days for the filter timer to
count down from: 0, 15, 30, 60 or 120 days. (One
day represents 24 hours of continuous fan/system
run time.)
2. To activate this feature, select a value other
than 0.
3. See Owner’s Guide, 69-1332, for more detailed
information.
Communication Code Numbers
Communication codes 1-3 provide equipment and communication status after installation. Communication
codes 4-6 can be used during initial system zoning
installation when more than one thermostat is connected. See Table 4.
1 COMTerminal 1 is not connected at the thermostat or
the Equipment Interface Module in a single zone
system.
Terminal 1 is not connected correctly at the
thermostat in a zoned system.
Terminal 1 is incorrectly wired with either terminal
2 or terminal 3.
2 COMCommunication messages are not being sent or
received correctly.
Thermostat component may be defectiveReplace thermostat.
3 COMTerminal 1 is not connected correctly at the
thermostat or the Equipment Interface Module in a
single zone system.
Terminal 1 is not connected correctly at the
Equipment Interface Module in a zoned system.
The system is not configured correctly.Enter Installer Setup and run Manual
Communication messages are not being sent or
received correctly.
NOTE: During initial installation of system with more than one thermostat connected, codes 4 COM, 5 COM and
6 COM are intended to assist the installer.
4 COMDuplicate zone numbers. More than one thermo-
stat was configured with the same zone number.
5 COMThe system found a thermostat with its zone
number set to zero. When more than one
thermostat is connected to the zoning system, no
thermostat can have its zone number set to zero.
6 COMThe system does not have a thermostat with a
zone number one. When more than one thermostat is connected to the zoning system, there must
be a thermostat with a zone number of one.
7 COMThe system is configured to use an external filter
timer. This is feature that is not yet system-supported.
Check the connection on terminal 1 at the
thermostat or the Equipment Interface Module.
Check for broken wire if the connection is good.
Check the connection on terminal 1 at the
thermostat. Check for broken wire if the
connection is good.
Ensure terminals 1, 2 and 3 are connected to
the correct terminals at all devices.
Check the connection on terminal 1 at the
thermostat or the Equipment Interface Module.
Check for broken wire if the connection is good.
Check the connection on terminal 1 at the
thermostat or the Equipment Interface Module.
Check for broken wire if the connection is good.
Check the connection on terminal 1 at the
Equipment Interface Module. Check for broken
wire if the connection is good.
Discovery.
Check the connection on terminal 1 at the
thermostat or the Equipment Interface Module.
Check for broken wire if the connection is good.
Configure each thermostat in the system with a
different zone number beginning with one.
Configure the thermostat zone numbers to
begin with one.
Configure the thermostat zone numbers to
begin with one.
Configure Installer Setup No. 43 to 0.
INSTALLER SETUP
The installer can use the Installer Setup options to
change factory settings to customize installations. See
Table 6.
NOTE: The Advanced Setup options in Table 7 are for
reference only and should remain as set at the
factory.
Scope
The installer can determine if the scope of the Installer
Setup change will be globally applied to all thermostat
locations in the system (when used in a zoned system);
or locally applied to only one thermostat location.
— Local: Only the thermostat where the installer setup
option is changed is affected by the change.
69-1331—58
— Global: All thermostats are affected by the change.
Zoning
Using the T8635L in a zoned application enables these
features:
— Time synchronization.
— Shared filter indication.
— Outdoor temperature display in all zones with only
one temperature sensor connected.
— Vacation hold in all zones.
— Check LED in all zones (when used with the
W8635B or W8835 configured for heat pump).
— System switch setting automatically changed for all
zones when used with W8635A or W8635B.
— System switch on each T8635 can be set
individually when used with a W8835.
— Individual fan control by zone.
Up to three T8635 Thermostats can be connected to the
W8835 or W8703A Damper Interface Module. Up to
nine T8535 Thermostats can be used with two additional W8703 Damper Interface Modules:
1. Select zone number for each thermostat in the
system.
2. If there is only one thermostat in the system, set
the Installer Setup No. 1 to 0. See Table 6.
3. When more than one thermostat in the system,
set Installer Setup No.1 at first thermostat to 1,
second thermostat to 2, third thermostat to 3, etc,
up to nine zones. Do not set more than one thermostat in the system to the same zone number.
4. Then match each thermostat with the corresponding zone on the W8703 Damper Interface Module
or W8835 EnviraZone Panel.
5. Attach the zone number stickers, included with
the thermostat, onto the thermostat case on the
inside of the thermostat cover. See Fig. 14.
Zone 2
IMPORTANT
Notice that if more than one thermostat is set
to the same zone number, the thermostat displays “4 COM”.
Zone 3
Place one label inside
each thermostat door.
Fig. 14. Zone stickers included
with T8635L Thermostat.
Zone 1
M1342
NOTE: While in Discovery mode, the thermostat dis-
plays “wait” for 20 seconds.
To change these and other installer settings:
— Follow the instructions in Table 6.
— Manually changing the stage configuration and cycle
rate settings locks Discovery mode so if power is
lost, all custom settings are retained in memory.
If at any time (such as adding new equipment or modules) it is necessary to run Discovery mode:
— Enter Installer Setup and follow the instructions in
Table 6.
— Manually running Discovery mode unlocks it until
the stage configurations or cycle rates are changed.
Stage Configuration
To configure thermostat stages:
— W8835 EnviraZone Panel:
a. automatically configures staging based on the
W8835 configuration.
b. set Installer Setup No. 5, 8, and 9 to the num-
ber of stages controlled. See Table 6.
— W8635A EIM and T8635L:
a. automatically configures for two stages of
heat and two stages of cool.
b. set Installer Setup No. 5 and No. 8 to 1 for
one stage heat /one stage cool conventional
application. See Table 6.
— W8635B EIM and T8635L:
a. automatically configures for two stages of
heat and one stage of cool.
b. set Installer Setup No. 5 to 1 and Installer
Setup No. 9 to 0 for single-stage heat pump
application. See Table 6.
Discovery Mode
Discovery mode begins when T8635L Thermostat and
the modules are first installed and power is connected:
— The W8835 transmits data based on its configuration
on initial powerup and when its Disovery switch is
pressed.
— The W8635 EIM transmits information to T8635L
Thermostat that indicates maximum number of
stages that are enabled and type of EIM connected.
— The thermostat receives information from the W8635
and then sets the cycle rates and equipment types
automatically.
Default Cycle Rate Settings.
nd
2
1st Stage Heat
W8635A Equipment Interface Module, or W8835 configured for conventional heat
The T8635L has a backlight that is activated:
— on-demand: the thermostat is pre-set to turn on the
backlight when any key is pressed.
— continuously: set Installer Setup No. 44 to 1 for
applications where the display is difficult to read due
to poor lighting conditions.
Advanced Settings
These settings are automatically configured during Discovery and should not be changed when using the
T8635L with the W8635A or W8635B EIM.
The advanced settings, see Table 7, are not available to
view or change when the ADV setting is set to Off.
When ADV is set to Off, press to scroll to the
beginning of the Installer Setup selections.
NOTE: If any of the settings in ADV are inadvertently
changed, press Enter and run Discovery mode
to reset the settings to the original selection.
ENTERING INSTALLER SETUP
To enter Installer Setup:
— simultaneously press and hold the , ▲ and ▼ keys
until Installer Setup No. 1 is displayed.
— all display segments appear for approximately three
seconds before Installer Setup No.1 is displayed.
— see Fig. 15 and 16.
Wait
Recovery
Hold for
Filter
Em Ht
Mon
TueWed Thu Fri Sat Sun
Wake Leave Return Sleep
Set Day/TimeSet Program
Aux Ht
Days
Temporary Setting
AM
PM
Repl Batt
DST
Heat
OutdoorRoom
Cool
System
Em Hea
Coo
Auto
Fan
Auto
Of
On
Fig. 15. LCD segments display.
INSTALLER SETUP
NUMBER DISPLAY
FACTORY SETTING OR OTHER
CHOICE DISPLAY (COLUMN 4
OR 5 OF TABLE 5)
M13376
Fig. 16. Installer Setup number and setting display.
1. To advance to the next Installer Setup No., press
the key.
2. To go back, press the key.
3. To change an Installer Setup, use the ▲ or ▼ key.
4. To exit Installer Setup, press Run Program key.
Table 6. Installer Setup Numbers and Default Settings and Options.
Installer
Setup
Number
(Press
key to
change)DescriptionScope
1Zone numberLocal0No zoning.1 to 9Zone numbers can be set
LOCLock/Unlock the system
to Automatic Discovery
a
mode
dISRuns Automatic
Discovery mode.
4Fan operation (only
when used with
W8635A).
69-1331—510
Default Setting
DisplayDescriptionDisplayDescription
Global LOC
off.
Automatic Discovery
mode occurs.
Global dISPress the ▲ key to
start Automatic
Discovery mode.
Global 0Conventional
applications where
equipment controls
fan operation in heat
mode.
Other Options (Press ▲ or
▼ key to change
to zones 1 through 9.
LOC onAutomatic Discovery
mode does not occur.
——
1Electric heat applications
where thermostat
controls fan operation in
heat mode.
Table 6. Installer Setup Numbers and Default Settings and Options. (Continued)
Installer
Setup
Number
(Press
key to
change)DescriptionScope
37Field calibration
Local0No difference
adjustment.
Default Setting
DisplayDescriptionDisplayDescription
between displayed
temperature and
actual room
Other Options (Press ▲ or
▼ key to change
-3, -2, -1,
1, 2, 3
Display adjusts to the
chosen °F higher or
lower than room
temperature.
temperature.
43Filter timer.Global 0Thermostat filter timer
is used.
44Backlight operates
continuously or with a
Local0Backlight operates
with a key press.
1External filter timer is
used.
1Backlight operates
continuously.
key press.
45Outdoor temperature
sensor.
Local0Outdoor temperature
sensor is not
1Outdoor temperature
sensor is configured.
configured.
46 Enable humidity display. Global 0Humidity display
disabled.
51Stage 1 heat cycle rate. Global
52Stage 2 heat cycle rate.
b
6
Cycle rate of
equipment (cph).
1Humidity display
enabled.
1, 2, 3, 4,
5, 6, 7, 8,
Cycle rate of equipment
(cph).
9, 10, 11,
or 12
55Emergency heat cycle
rate.
Global 9Cycle rate of
equipment (cph).
1, 2, 3, 4,
5, 6, 7, 8,
Cycle rate of equipment
(cph).
9, 10, 11,
or 12
57Stage 1 cool cycle rate. Global 3Cycle rate of
58Stage 2 cool cycle rate.
equipment (cph).
0, 1, 2, 3,
4, 5, 6, 7,
8, 9, 10,
Cycle rate of equipment
(cph).
11, or 12
ADVAdvance configuration
menu to review/modify
equipment ID and type.
ADV
off.
No access to
Advanced Installer
Setup No. 61-63,
ADV onAccess to Advanced
Installer Setup No. 61-63,
65-69, 71-73, 75-79.
65-69, 71-73, 75-79.
a
This value is not installer adjustable. If any of these Installer Setup No. are changed: 4, 5, 8, 9, 51, 52, 55-ADV from
Table 6 and 62-63, 65-69, 71-73, 75-80 from Table 7, the settings are locked and Automatic Discovery cannot
occur. To unlock Discovery, advance to “dIS” and press the ▲ key to manually initiate Discovery mode. During Discovery, “wait” appears in the display for approximately 20 seconds and the thermostat is not functional.
b
3 cph when used with W8635B or W8835 configured for heat pump; 9 cph when used with the T8635 set for electric
heat.
IMPORTANT
Review the settings to confirm that they are correct for your application. Press Run Program key to exit
Installer Setup. The settings will be saved indefinitely in memory. Upon exiting Installer Setup, “wait”
appears in the display for approximately 20 seconds.
Set the time and day on the last thermostat configured after exiting Installer Setup. See Setting Current Day
and Time section.
3. Press or until the current time is dis-
played.
Time
Run
Set Current
Leave
Wake
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
SystemFilterFan
Settings
Copy
Set Day/Time
AM
Tue
M17769
NOTE: Tapping the Set Current Day/Time key
changes the time in one-hour increments.
4. If the current time is Daylight Savings Time, press
Daylight Time key to display DST.
Set Day/Time
AM
Run
Set Current
Leave
Wake
Daylight
Time
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
SystemFilterFan
Settings
Copy
Tue
M17770
5. Press Run Program key.
System
Run
Program
AM
Run
Set Current
Leave
Wake
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
SystemFilterFan
Settings
Copy
Tue
Wake
Room
DST
Fan
M1777
Hea
Auto
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat
and W8635 Equipment Interface Module operation for
each thermostat in the system. Table 8 lists the available system tests.
IMPORTANT
When used in zoning, you must exit Installer
System Test before entering Installer System
Test at another thermostat.
See Table 9 for Installer System Test descriptions.
Table 8. Installer System Tests.
Tes t
NumberSystem Test Description
10-12Heating stages can be turned on and off in
sequence.
20-21Emergency heating can be turned on and off.
30-32Cooling stages can be turned on and off in
sequence.
40-42Fan and damper test.
60Keyboard keys test.
70-74Thermostat information, including date code
and software versions, are displayed.
Programming
See the Owner’s Guide, 69-1332, for complete programming instructions.
CAUTION
Equipment Damage Hazard.
Minimum compressor off-time is bypassed
during Installer System Test.
Do not allow compressor rapid cycling (on and
off).
Observe compressor protection period.
Starting Installer System Test
Press and hold the ▲ and ▼ keys at the same time
until 10 appears. All segments of the display are shown
before the test number 10 appears. See Fig. 15 and 17.
Table 9. Installer System Test Options. (Continued)
Key to PressTest NumberDescription
Emergency Heat System Test (available only when using W8635B)
20Enter Emergency Heat Equipment system test.
▲
▼
Cooling Equipment System Test
▲
▲
▼
▼
Fan and Damper Test Damper Test available only when using W8703A)
▲
▲
▼
▼
Key Operation Test
21Emergency Heat turns on.
20Emergency Heat turns off.
30Enter Cooling Equipment system test.
31First Stage Cool turns on.
32Second Stage Cool turns on (W8635A only).
31Second Stage Cool turns off (W8635A only).
30First Stage Cool turns off.
40Enter Fan and Damper test.
41Fan turns on; damper for this zone opens.
42Damper closes for this zone (if not already closed); fan stays on.
41Damper opens for this zone.
40Fan turns off.
60Enter Key Operation test.
Press any key to test if the key is functional. Each time a key is pressed, a different number is displayed. This
indicates the key is functioning properly. Pressing enters the next test.
Thermostat Information
70Enter Thermostat Information mode.
▲
▲
▲
▲
Exit Installer Test Mode
Run Program keyThermostat returns to normal operating mode.
71Production date code is displayed. The first two large digits are the month
and the third digit is the last digit of the year (example: 031 = March 2001).
72Software identification code is displayed.
73Software revision number is displayed.
74EEPROM identification code is displayed.
CHECKOUT
Outdoor Temperature Sensor
Allow the C7089B Outdoor Temperature Sensor to absorb the outdoor air for a minimum of five minutes before taking
a reading.
TROUBLESHOOTING GUIDE
Refer to Table 10 for troubleshooting information.
Thermostat zone number is not
set to the corresponding W8703
zone number.
Terminal 1 on W8703 Damper
Interface Module is not properly
connected.
W8703 Damper Interface Module
is defective.
Communication is not being
completed.
Set zone number at the thermostat to correspond with the
correct zone number for the W8703 Damper Interface
Module.
Properly connect terminal 1 on the W8703 Damper
Interface Module.
If the W8703 indicates the damper is closed (red LED
lights), replace the W8703 Damper Interface Module.
End the call and repeat the call. Check the Flash Com OK
LED on the W8835 or W8635 EIM while the call is being
made.
If the Flash Com OK LED does not blink:
—check communication bus wiring.
Heat load at W8635 EIM is not
connected correctly.
If the Flash Com OK LED blinks correctly:
—check that 24 Vac is present at W1 or W1/Y1 terminal,
depending on which equipment module is being used.
If 24 Vac is not present, check the R to Rh connection. If
the connection is good, replace the W8835 or W8635 EIM.
End and repeat the call for cool. Check the Flash Com OK
LED on the W8635 EIM or W8835 while the call is being
made.
If the Flash Com OK LED does not blink:
—check communication bus wiring.
Cool load at W8635 EIM is not
connected correctly.
If the Flash Com OK LED blinks correctly:
—check that 24 Vac is present at Y1 or W1/Y1 terminal,
depending on which EIM is being used.
If 24 Vac is not present, check R to Rc and/or Rh
connections. If the R to Rc and/or Rh connections are
good, replace the W8635 EIM or W8835.
“wait” is displayed
and the call for Cool
(or Heat when used
in a heat pump
application) has not
Compressor protection is in effect. Compressor protection can be set from 0 to 5 minutes to
prevent compressor damage due to rapid cycling. Wait
until the compressor protection period expires.
To bypass compressor protection during the installation
phase, see the Installer System Test section.
started.
nd
stage heat or
2
cool does not
energize (only
when used with
W8635A).
Stage configuration is not set
correctly to match the number of
selected stages.
Cool load at W8635 EIM is not
connected correctly.
Set the Stage configuration in Installer Setup for two stages
of heat and/or two stages of cool.
Check that 24 Vac is present at Y2, W2 or Aux. Terminal,
depending on EIM used. If 24 Vac is not present, all
connections are good and the thermostat is properly
configured, replace W8635A EIM or W8835.
Emergency Heat
does not energize
(only when used
Emergency Heat load at W8635
or W8835 is not connected
correctly.
Check that 24 Vac is present at E terminal. If 24 Vac is not
present, all connections are good, and the thermostat is
properly configured, replace W8635B or W8835.
with W8635B or
W8835).
Emergency Heat
can not be selected
with the System
Stage configuration is not set
correctly to match the number of
stages selected.
Set the Stage configuration, Installer Setup No. 9 to 1, see
table 5 for one stage of Emergency Heat.
switch (W8635B
only).
Fan does not come
on with a call for
Electric heat setting is not
configured.
Set Installer Setup No. 4 to 1 for electric heat, see Table 6.
electric heat.
Fan load at the W8835 or W8635
EIM is not connected correctly.
Check that 24 Vac is present at G terminal. If 24 Vac is not
present, all connections are good, and the thermostat is
configured, replace the W8635 EIM or W8835.
The is flashing
and the damper
does not open.
Temperature setting
does not change
(example: cannot
set the heating
higher or the
cooling lower).
Fan runs
continuously.
Thermostat is waiting for a call for
heat or cool to end in another
zone before opening this zone
damper.
The upper or lower temperature
limits are reached.
Fan setting set to On or
programmed to On.
Wait until call from other zone ends.
Check temperature setpoint limits; setpoint limit ranges
are:
—heating: 40° to 90°F (4.5° to 32°C).
—cooling: 45° to 99°F (7° to 37°C).
See Installer Setup no. 34 and no. 35 to change the
setpoint limits, see Table 6.
Pressing the Fan key changes the fan from On to Auto or
vice versa for the duration of the current program period.
To set the fan to run continuously for all periods, program
the fan to On for each period and day.
The green LED is
on.
Filter expired.Replace filter or clean electronic air cleaner cells. Press
and hold the filter key to reset the timer.
To disable the filter timer, select 0 as the timer value.
The red LED is on. Check LED. 24 Vac is present at
Outdoor
temperature not
displayed or is
incorrect.
Outdoor temperature setting is not
enabled in Installer Setup.
Install one C7089B Outdoor Temperature Sensor to OT
terminals on one thermostat in the system and configure
Installer Setup No. 45 to 1, see Table 6, only at the zone
where the outdoor sensor is connected.
Heat or cool turns
on before
programmed time.
Outdoor sensor is not connected,
is connected incorrectly or is outof-range.
Outdoor sensor is configured at
more than one thermostat zone
location.
Filter expired.
Adaptive Intelligent Recovery™ is
on.
If the outdoor sensor is not connected or is out-of-range
(below –40°F or above 120°F) “- -” is displayed on the
thermostat where the outdoor sensor is located. All other
thermostats do not display an outdoor temperature until the
sensor is in range or connected correctly.
Outdoor temperature alternates between displaying
outdoor temperature and “- -” . Configure only the
thermostat where the outdoor sensor is connected.
Press key twice for outdoor temperature when filter
expiration displays. Refer to the Filter Indication section.
Adaptive Intelligent Recovery™ brings on the heat or cool
early to meet the temperature set for the programmed
period. To disable Adaptive Intelligent Recovery™,
configure Installer Setup No. 13 to 1, see Table 6.