Honeywell T8635L, W8835A, W8835E, W8635A, W8635B Installation Instructions Manual

Page 1
T8635L Microelectronic
Communicating Programmable
Thermostat
INSTALLATION INSTRUCTIONS
APPLICATION
Table 1. T8635L Thermostat Description.
Model System Changeover
T8635L and W8835A,E Heat-Cool or
T8635L and W8635A Heat-Cool Automatic or
T8635L and W8635B Heat Pump
a
See System and Fan Keys section for specific information.
Heat Pump
Automatic or Manual
Manual
a
System Selection
Heat-Off-Cool-Auto Em. Ht
Heat-Off-Cool-Auto On-Auto
Heat-Off-Cool-Auto Em. Ht
a
Fan Selection
On-Auto
Accessories
Required (Not Included)
W8835A,E EnviraZone Panel – For up to 3H/2C con-
ventional or heat pump applications.
W8635A – Equipment Interface Module (EIM) for up to
2H/2C conventional applications.
W8635B – Equipment Interface Module (EIM) for up to
2H/1C heat pump applications.
Optional
W8703A – Damper Interface Module. C7089B – Outdoor Temperature Sensor. C7835A – Discharge Air Temperature Sensor.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instruc­tions to check out the product operation.
CAUTION
Vol tage Ha z a r d. Can cause electrical shock or equipment damage.
Disconnect power before beginning installation.
Location
Install the thermostat about 5 ft. (1.5m) above the floor in an area with good circulation at average temperature. See Fig 1.
® U.S. Registered Trademark Copyright © 2003 Honeywell • • All Rights Reserved
69-1331-5
Page 2
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
YES
NO
NO
5 FEET
[1.5 METERS]
NO
Fig. 1. Selecting thermostat location.
M10106
Do not install the thermostat where it can be affected by: — drafts or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall or on a 2 in. by 4 in. wiring box. Position wallplate hori­zontally on the wall or on a 2 in. by 4 in. wiring box.
1. Position and level the wallplate (for appearance only). The thermostat functions properly even when not level.
2. Use a pencil to mark the mounting holes. See Fig. 2.
3. Remove the wallplate from the wall and drill two 3/16-in. holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling the wires through the wiring opening.
5. Loosely insert the mounting screws in the holes.
6. Tighten the mounting screws.
WALL ANCHORS (2)
WALL
WIRES THROUGH WALL
Fig. 2. Mounting the wallplate.
MOUNTING HOLES
MOUNTING SCREWS
M6530A
69-1331—5 2
WIRING
All wiring must comply with local electrical codes and ordinances. See Fig. 5 through 8 wiring diagrams for specific equipment applications. Refer to Table 2 for ter­minal designations.
Page 3
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
6
F I 7
8
9
1
T
CAUTION
Voltage Hazard. Can cause electrical shock or equipment
OR WRAPAROUND
NSERTION STRIP
/16 IN. (11 MM).
damage.
Disconnect power before beginning installation.
1. Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 3 and 4.
Fig. 3. Correct wiring technique.
IMPORTANT
Use 18-gauge color-coded thermostat cable for proper wiring. Shielded cable is not required.
2. Securely tighten each terminal screw.
3. Push excess wire back in the hole.
WIRE NUT
4. Plug the hole in the wall with non-flammable insu­lation to help prevent drafts from adversely affect­ing thermostat operation.
Fig. 4. Using wire nut to pigtail a
connection when three or more wires
are terminated at one terminal.
Table 2. Terminal Designations.
T8635L Terminal Designations Function
1 Data – Connect to terminal 1 on W8835 or W8635.
2 Power – Connect to terminal 2 on W8835 or W8635.
3 Power – Connect to terminal 3 on W8835 or W8635.
OT
OT
a
Use optional C7089B Outdoor Temperature Sensor.
Outdoor Temperature Sensor
Outdoor Temperature Sensor
a
a
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).
M482
M1337
L2
L1 (HOT)
SYSTEM
TRANSFORMER
T8635L
C7089B OUTDOOR TEMPERATURE SENSOR
W8635A
1
1
FACTORY INSTALLER JUMPERS.
OT
1 2 3
C R R
H
R
C
2
1
OT
G W1 W2
Y1 Y2
Fig. 5. T8635L/W8635A with
Outdoor Temperature Sensor.
T8635L
C7089B OUTDOOR
SYSTEM
TEMPERATURE SENSOR
W8635B
1
1
FACTORY INSTALLER JUMPER.
3
FAN RELAY
HEAT 1 RELAY
HEAT 2 RELAY
COOL 1 RELAY
COOL 2 RELAY
M1342
L2
L1 (HOT)
RANSFORMER
OT
1 2 3
C R R
H
2
1
AUX
3
COMPRESSOR
MONITOR
FAN RELAY
L
G
E
O
B
COMP. RELAY
AUX. HT. RELAY
EM. HT. RELAY
COOL CHANGE­OVER
HEAT CHANGE­OVER
M1343
OT
W1/Y1
Fig. 6. T8635L/W8635B with
Outdoor Temperature Sensor.
3 69-1331—5
Page 4
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
T
B
)
R
T8635L
T8635L
T8635L
C7089B OUTDOOR TEMPERATURE SENSOR
OT
2
1
OT
3
OT
2
1
OT
3
OT
1
OT
2
3
L2
L1 (HOT)
SYSTEM
RANSFORMER
FACTORY
INSTALLER
JUMPERS.
IMPORTANT
Connect outdoor sensor to only one thermo­stat and configure that thermostat Installer Setup No. 45 to 1. See Table 6. Connecting more than one outdoor sensor or configuring more than one thermostat for outdoor sensor causes the thermostat to incorrectly display the outdoor temperature.
W8635A
1 2 3
C R R
H
R
C
G W1 W2
Y1 Y2
FAN RELAY
HEAT 1 RELAY
HEAT 2 RELAY
COOL 1 RELAY
COOL 2 RELAY
546Z
213
MODEL AOBD
ZONE DAMPER
Power-closed/ Spring-open (Model ZD)
Power-closed/ Spring-open (Model ARD)
W8703A
X
OPEN CLOSE
OPEN CLOSE
OPEN CLOSE
Fig. 7. T8635L/W8703A/W8635A with Outdoor Temperature Sensor.
ZONE AZONE B
TR1 TR2
COM
ZONE C
1 2
3
L1 (HOT
L2
EXTERNAL 40 VA TRANSFORME
M13430
69-1331—5 4
Page 5
9
F
Single transformer heating/cooling
systems require a jumper to be
8
B
installed connecting RH and R (factory installed).
HVAC Equipment
HP Fault
HP Fault Common
Heating Transformer
24 VAC
Equipment
irst Stage Heating/Emergency Heat Relay
Third Stage Heating/Auxiliary Heat Relay
Reversing Valve (Cooling/Heating)
Golden Valley, MN 55422 www.honeywell.com/yourhome
Cooling Transformer
Second Stage Heating Relay
First Stage Cooling Relay
Second Stage Cooling Relay
This diagram shows the typical equipment, thermostat, and damper motor connections. For specific wiring, refer to the Installation Instructions.
Fan Relay
Auxiliary Equipment
Humidifier
Humidifier Dehumidifier Dehumidifier
Ventilator Ventilator
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
C
14XZ253
Power-open/ Power-closed (Opposed Blade Damper Motors)
HEAT COOL PURGE FAN EM. HT. COMM ZONE 1 ZONE 2 ZONE 3
BOOTDISCOVERY
O N
1
2 3 4 5 6 7 8 9 10
#1 #2 CONV HT STG 1 1 1
1 0 2 0 1 3 0 0 HP
ENVIRACOM BUS
1 2 3 1 2 31 2 3 1 23
123
ZONE DAMPER MOTORS M1 - common M4 - power open M6 - power closed
ZONE 1
M6
6
L C Rh Rc W1/E
LED STATES:
W2
Heat LED Heating Mode Cool LED Cooling Mode
W3/AUX
Purge LED Purge Mode Fan LED Fan Mode
Y1
Em Heat LED Em Heat Mode
Y2
COMM LED Communications
G O/B
DIP SWITCH SETTINGS
1 SEE TABLE ON OFF 2 SEE TABLE 1 0 3 ENVIRACOM FURN NO YES
HUM
4 PURGE TIME 2.0 MIN 3.5 MIN
HUM
5 PURGE FAN HVAC PANEL 6 PURGE DAMPER NO CHG OPEN
DHUM
7 # COMP STAGES 1 2
DHUM
8 HEAT FAN HVAC PANEL 9 HP CHANGEOVER O B
VENT
10 UNUSED
VENT
DAMPERS
ZONE 2
M4 M1
M6 M4 M1
Power-closed/ Spring-open (Model ZD)
ZONE 3
M6
M4 M1
ZONE LEDS:
On Damper open or opening Off Damper closed or closing
MOMENTARY PUSH BUTTONS
Boot Clears Microprocessor Purge Override Bypass Purge Mode Discovery Initiates Discovery Mode
(can connect to any set of 1,2,3 terminals)
Power-closed/ Spring-open (Model ARD)
PURGE
OVERRIDE
XFRM
Jumpers
Attach jumpers (factory installed in open position)
if using only
one transformer.
Enviracom
123123 12
XFRM R
C T1 T2
Damper
XFRM
3
CR
24 VAC, 40 VA
Optional
Transformer
(required if
system load
is greater than single transformer
output.)
CR
24 VAC, 40 VA
Panel
Transformer
32003618-00
M20850A
REV. B
TM
Fig. 8. W8835 EnviraZone Panel wiring.
Mounting Thermostat on Wallplate
NOTE: To remove the thermostat from the wall, first
pull out at the bottom of the thermostat; remove the top last.
1. Engage tabs at the top of the thermostat and wall­plate. See Fig. 9.
2. Press the lower edge of the case to close and latch.
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.
.
PRESS LOWER EDGE OF CASE TO LATCH.
M1462
Fig. 9. Mounting thermostat on wallplate.
5 69-1331—5
Page 6
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
E O
S P
C D A
I S F I A
D O T S
4
SETTINGS
Thermostat Keys
The thermostat keys are used to: — Set current day and time. — Program times and setpoints for heating and cooling. — Temporarily override program temperatures. — Display present setting.
SET WAKE TIMES AND SETPOINTS
NCREASE TIME
ETTING OR SCROLL
ORWARD THROUGH
NSTALLER SETUP
ND SYSTEM TEST
SET CURRENT DAY AND TIME
RETURN TO NORMAL OPERATIONS
ET CURRENT OR ROGRAM DAY
NTER INDEFINITE
R TIMED HOLD MODE
ECREASE TIME SETTING
R SCROLL BACKWARD HROUGH INSTALLER ETUP AND SYSTEM TEST
HANGE BETWEEN
AYLIGHT SAVINGS
ND STANDARD TIME
Run
Program
Hold Temp
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS
Set Current
Day/Time
Day
Daylight
Time
Time
Copy
— Configure Installer Setup. — Perform Installer System Test.
— Display outdoor temperature (when C7089B is
connected). — Set the System key setting. — Set the Fan key setting. — Set, view and clear the filter setting.
See Fig. 10 for key location.
DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS
DISPLAY INFORMATION SUCH AS PRESENT SETTINGS
SET RETURN TIMES AND SETPOINTS
Leave
Wake
Heat/Cool
Settings
CHANGE BETWEEN HEATING AND COOLING SETPOINTS
Set Program
Return Sleep
SystemFilter Fan
SELECT FILTER EXPIRATION IN NUMBER OF DAYS
SET SLEEP TIMES AND SETPOINTS
SET LEAVE TIMES AND SETPOINTS
SELECT FAN OPERATION
SELECT SYSTEM OPERATION (HEAT, COOL, OFF, AUTO)
M17765
Fig. 10. Thermostat key locations and descriptions.
System and Fan Keys
Use the System and Fan keys on the thermostat to select the system and fan settings.
1. Use the System key setting (Fig. 11) to control the thermostat operation:
Heat: The thermostat controls the heating. When
Cool: The thermostat controls the cooling. When
Auto: The thermostat controls heating and cool-
NOTE: Auto is an option on non-zoned systems
Off: Both Heating and cooling are off.
Em Heat: The thermostat controls heating. When
NOTE: Em Heat is an option on systems using
69-1331—5 6
the thermostat is calling for heat, a is indicated in the display.
the thermostat is calling for cool, a is indicated in the display.
ing, automatically switching from heat to cool based on room temperature and thermostat setpoints.
using W8635A,B or on zoned systems using W8835.
thermostat is calling for emergency heat, a and Em Ht are indicated in display.
the W8635B or W8835 and configured for a heat pump with auxiliary heat.
Run
Set Current
Leave
Wake
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool Settings
Copy
SystemFilter Fan
System
Fig. 11. System key setting.
IMPORTANT
• The T8635L has an adjustable compressor
protection setting
it can be set from 0 to 5
minutes.
• The thermostat waits to call for cooling (or heating when used with the heat pumps): —when power is first established, —when a power outage occurs or —when the call has just ended and another
call is immediately attempted.
• “wait” is displayed during the compressor pro­tection period.
• To override the compressor protection during installation, refer to the Installer System Test section.
• To permanently override the compressor pro­tection, see Installer Setup No. 33 and change the setting to 0. See Table 6.
Auto: The thermostat automatically changes
between heating and cooling operation, depending on the indoor temperature.
System
M1776
Heat
Off Cool Auto
Page 7
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
6
M13375
CHECK
FILTER
Em.Ht: Emergency Heat output is controlled as
stage 1 heat. Cooling system is off, and compressor is de-energized. Em.Ht and
are displayed when the thermostat is
calling for emergency heat.
a. Press the Fan key during normal operation to
change the fan setting only for the current pro­gram period.
b. To program the fan to operate in Auto or On
for each program period individually, see the Owner’s Guide, 69-1332.
2. Use the Fan key setting (Fig. 12) to control the system fan:
Auto: The fan operates with the heating and
cooling equipment.
Run
Set Current
Leave
Wake
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
SystemFilter Fan
Settings
Copy
Fan
On: The fan temporarily operates continu-
ously for the current program period. The
is displayed any time the thermostat is
Fig. 12. Fan key setting.
calling for fan operation.
Temperature Settings
NOTE: When used with the W8835 or W8703A
Damper Interface Module, a flashing is displayed when one thermostat is call­ing for fan operation while a thermostat in another zone is calling for heat or cool. After the call ends from the other thermostat, the stops flashing and the re-quested call for fan is honored for this zone.
Table 3. Default Program Settings.
Period Time Heat Setpoint Cool Setpoint Fan Setting
Wake 6:00 am 70°F (21°C) 78°F (25.5°C) Auto
Leave 8:00 am 62°F (16.5°C) 85F (29.5°C) Auto
Return 6:00 am 70°F (21°C) 78F (25.5°C) Auto
Sleep 10:00 am 62°F (16.5°C) 82F (28°C) Auto
To program the time and temperature settings:
1. Refer to Table 3 for the default program time and temperature settings.
2. If the daytime energy savings period is not used, press Leave or Return (period) until the time and temperature is blank.
3. See Owner’s Guide, 69-1332, for complete instructions on changing the program.
Fan
M1776
On
Auto
LED Indicators
There are two LED indicators on the top right of the thermostat. See Fig. 13.
• The check (red) LED lights when 24 volts are applied to the L terminal on the W8635B EIM or W8835. This indicates a problem with the heat pump equipment.
Action for Homeowner: Switch to emergency heat
and call for assistance.
• The filter (green) LED lights when the filter timer has expired.
Action for Homeowner: Replace the furnace filter
or clean the electronic air cleaner cells. Press and hold the Filter key to reset the counter and turn off the LED.
(RED) LED
(GREEN) LED
Filter Indication
This thermostat can track total fan and system run time. This feature can be used to tell the homeowner when to replace the furnace filter or clean the electronic air cleaner cells:
1. Select the number of days for the filter timer to count down from: 0, 15, 30, 60 or 120 days. (One day represents 24 hours of continuous fan/system run time.)
2. To activate this feature, select a value other than 0.
3. See Owner’s Guide, 69-1332, for more detailed information.
Communication Code Numbers
Communication codes 1-3 provide equipment and com­munication status after installation. Communication codes 4-6 can be used during initial system zoning installation when more than one thermostat is con­nected. See Table 4.
Fig. 13. Check and filter LED locations.
7 69-1331—5
Page 8
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
Table 4. Communication Code Numbers.
Thermostat
Displays This
Communication
Code Number Possible Cause Action
1 COM Terminal 1 is not connected at the thermostat or
the Equipment Interface Module in a single zone system.
Terminal 1 is not connected correctly at the thermostat in a zoned system.
Terminal 1 is incorrectly wired with either terminal 2 or terminal 3.
2 COM Communication messages are not being sent or
received correctly.
Thermostat component may be defective Replace thermostat.
3 COM Terminal 1 is not connected correctly at the
thermostat or the Equipment Interface Module in a single zone system.
Terminal 1 is not connected correctly at the Equipment Interface Module in a zoned system.
The system is not configured correctly. Enter Installer Setup and run Manual
Communication messages are not being sent or received correctly.
NOTE: During initial installation of system with more than one thermostat connected, codes 4 COM, 5 COM and
6 COM are intended to assist the installer.
4 COM Duplicate zone numbers. More than one thermo-
stat was configured with the same zone number.
5 COM The system found a thermostat with its zone
number set to zero. When more than one thermostat is connected to the zoning system, no thermostat can have its zone number set to zero.
6 COM The system does not have a thermostat with a
zone number one. When more than one thermo­stat is connected to the zoning system, there must be a thermostat with a zone number of one.
7 COM The system is configured to use an external filter
timer. This is feature that is not yet system-sup­ported.
Check the connection on terminal 1 at the thermostat or the Equipment Interface Module. Check for broken wire if the connection is good.
Check the connection on terminal 1 at the thermostat. Check for broken wire if the connection is good.
Ensure terminals 1, 2 and 3 are connected to the correct terminals at all devices.
Check the connection on terminal 1 at the thermostat or the Equipment Interface Module. Check for broken wire if the connection is good.
Check the connection on terminal 1 at the thermostat or the Equipment Interface Module. Check for broken wire if the connection is good.
Check the connection on terminal 1 at the Equipment Interface Module. Check for broken wire if the connection is good.
Discovery.
Check the connection on terminal 1 at the thermostat or the Equipment Interface Module. Check for broken wire if the connection is good.
Configure each thermostat in the system with a different zone number beginning with one.
Configure the thermostat zone numbers to begin with one.
Configure the thermostat zone numbers to begin with one.
Configure Installer Setup No. 43 to 0.
INSTALLER SETUP
The installer can use the Installer Setup options to change factory settings to customize installations. See Table 6.
NOTE: The Advanced Setup options in Table 7 are for
reference only and should remain as set at the factory.
Scope
The installer can determine if the scope of the Installer Setup change will be globally applied to all thermostat locations in the system (when used in a zoned system); or locally applied to only one thermostat location.
Local: Only the thermostat where the installer setup
option is changed is affected by the change.
69-1331—5 8
Global: All thermostats are affected by the change.
Zoning
Using the T8635L in a zoned application enables these features: — Time synchronization. — Shared filter indication. — Outdoor temperature display in all zones with only
one temperature sensor connected. — Vacation hold in all zones. — Check LED in all zones (when used with the
W8635B or W8835 configured for heat pump). — System switch setting automatically changed for all
zones when used with W8635A or W8635B. — System switch on each T8635 can be set
individually when used with a W8835. — Individual fan control by zone.
Page 9
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
6
Up to three T8635 Thermostats can be connected to the W8835 or W8703A Damper Interface Module. Up to nine T8535 Thermostats can be used with two addi­tional W8703 Damper Interface Modules:
1. Select zone number for each thermostat in the system.
2. If there is only one thermostat in the system, set the Installer Setup No. 1 to 0. See Table 6.
3. When more than one thermostat in the system, set Installer Setup No.1 at first thermostat to 1, second thermostat to 2, third thermostat to 3, etc, up to nine zones. Do not set more than one ther­mostat in the system to the same zone number.
4. Then match each thermostat with the correspond­ing zone on the W8703 Damper Interface Module or W8835 EnviraZone Panel.
5. Attach the zone number stickers, included with the thermostat, onto the thermostat case on the inside of the thermostat cover. See Fig. 14.
Zone 2
IMPORTANT
Notice that if more than one thermostat is set to the same zone number, the thermostat dis­plays “4 COM”.
Zone 3
Place one label inside each thermostat door.
Fig. 14. Zone stickers included
with T8635L Thermostat.
Zone 1
M1342
NOTE: While in Discovery mode, the thermostat dis-
plays “wait” for 20 seconds.
To change these and other installer settings: — Follow the instructions in Table 6. — Manually changing the stage configuration and cycle
rate settings locks Discovery mode so if power is lost, all custom settings are retained in memory.
If at any time (such as adding new equipment or mod­ules) it is necessary to run Discovery mode: — Enter Installer Setup and follow the instructions in
Table 6.
— Manually running Discovery mode unlocks it until
the stage configurations or cycle rates are changed.
Stage Configuration
To configure thermostat stages: — W8835 EnviraZone Panel:
a. automatically configures staging based on the
W8835 configuration.
b. set Installer Setup No. 5, 8, and 9 to the num-
ber of stages controlled. See Table 6.
— W8635A EIM and T8635L:
a. automatically configures for two stages of
heat and two stages of cool.
b. set Installer Setup No. 5 and No. 8 to 1 for
one stage heat /one stage cool conventional application. See Table 6.
— W8635B EIM and T8635L:
a. automatically configures for two stages of
heat and one stage of cool.
b. set Installer Setup No. 5 to 1 and Installer
Setup No. 9 to 0 for single-stage heat pump application. See Table 6.
Discovery Mode
Discovery mode begins when T8635L Thermostat and the modules are first installed and power is connected: — The W8835 transmits data based on its configuration
on initial powerup and when its Disovery switch is pressed.
— The W8635 EIM transmits information to T8635L
Thermostat that indicates maximum number of stages that are enabled and type of EIM connected.
— The thermostat receives information from the W8635
and then sets the cycle rates and equipment types automatically.
Default Cycle Rate Settings.
nd
2
1st Stage Heat
W8635A Equipment Interface Module, or W8835 configured for conventional heat
6 cph 6 cph 3 cph 3 cph
st
1
Stage Heat/Cool 2nd Stage Heat (Auxiliary) Emergency Heat
W8635B Equipment Interface Module or W8835 configured for heat pump
3 cph 9 cph 9 cph
Stage Heat and 3rd
Stage Heat, W8835 1
Cycle Rate
The thermostat automatically sets the cycle rate based on the information it received during Discovery mode.
To change the default cycle rate settings: — see Table 5 for typical cycle rate settings. — enter Installer Setup and select the desired cycle
rate settings for each stage. (All stages can be set between 1 and 12 cph.)
st
Stage Cool 2nd Stage Cool
9 69-1331—5
Page 10
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
t f l
(COLUMN 1 OF TABLE 5)
Table 5. Typical Heating Cycle Rate Settings.
System Cycles Per Hour
Steam, Gravity 1
a
Hydronic Heat, Condensing Gas Furnaces
, Compressor Stages
Gas or Oil Forced Air, Auxiliary Heat 6
Electric Heat, Emergency Heat 9
a
High efficiency furnace (90+).
3
Backlight Option
The T8635L has a backlight that is activated: — on-demand: the thermostat is pre-set to turn on the
backlight when any key is pressed.
continuously: set Installer Setup No. 44 to 1 for
applications where the display is difficult to read due to poor lighting conditions.
Advanced Settings
These settings are automatically configured during Dis­covery and should not be changed when using the T8635L with the W8635A or W8635B EIM.
The advanced settings, see Table 7, are not available to view or change when the ADV setting is set to Off. When ADV is set to Off, press to scroll to the beginning of the Installer Setup selections.
NOTE: If any of the settings in ADV are inadvertently
changed, press Enter and run Discovery mode to reset the settings to the original selection.
ENTERING INSTALLER SETUP
To enter Installer Setup: — simultaneously press and hold the , and ▼ keys
until Installer Setup No. 1 is displayed.
— all display segments appear for approximately three
seconds before Installer Setup No.1 is displayed.
— see Fig. 15 and 16.
Wait Recovery
Hold for
Filter
Em Ht
Mon
TueWed Thu Fri Sat Sun
Wake Leave Return Sleep
Set Day/TimeSet Program
Aux Ht
Days
Temporary Setting
AM
PM
Repl Batt
DST
Heat
OutdoorRoom
Cool
System
Em Hea
Coo Auto
Fan
Auto
Of
On
Fig. 15. LCD segments display.
INSTALLER SETUP NUMBER DISPLAY
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 4 OR 5 OF TABLE 5)
M13376
Fig. 16. Installer Setup number and setting display.
1. To advance to the next Installer Setup No., press
the key.
2. To go back, press the key.
3. To change an Installer Setup, use the or key.
4. To exit Installer Setup, press Run Program key.
Table 6. Installer Setup Numbers and Default Settings and Options.
Installer
Setup
Number
(Press
key to
change) Description Scope
1 Zone number Local 0 No zoning. 1 to 9 Zone numbers can be set
LOC Lock/Unlock the system
to Automatic Discovery
a
mode
dIS Runs Automatic
Discovery mode.
4 Fan operation (only
when used with W8635A).
69-1331—5 10
Default Setting
Display Description Display Description
Global LOC
off.
Automatic Discovery mode occurs.
Global dIS Press the key to
start Automatic Discovery mode.
Global 0 Conventional
applications where equipment controls fan operation in heat mode.
Other Options (Press or
key to change
to zones 1 through 9.
LOC on Automatic Discovery
mode does not occur.
——
1 Electric heat applications
where thermostat controls fan operation in heat mode.
Page 11
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
Table 6. Installer Setup Numbers and Default Settings and Options. (Continued)
Installer
Setup
Number
(Press
key to
change) Description Scope
5 Number of heating
Global 1, 2 Number of heating
stages.
Default Setting
Display Description Display Description
stages found during Automatic Discovery
Other Options (Press or
key to change
0, 1, 2, 3 Select the number of
heating stages for this application.
mode.
8 Number of cooling
stages (maximum for W8635B is one).
Global 1, 2 Number of cooling
stages found during Automatic Discovery
0, 1, 2 Select the number of
cooling stages for this application.
mode.
9 Number of emergency
heat stages (only when used with W8835 or
Global 1 Number of
emergency heating stages.
0, 1, 2 Select the number of
emergency heat stages for this application.
W8635B).
13 Adaptive Intelligent
Recovery™ (system starts early so setpoint
Global 0 Adaptive Intelligent
Recovery™ is activated.
1 Conventional recovery
(system starts recovery
at period start time). is reached by start of program period).
14 Temperature indication
scale (°F or °C)
Global 0 Temperature is
indicated in °F.
1 Temperature is indicated
in °C.
16 Clock format Global 0 12-hour clock format 1 24-hour clock format.
19 Fan overrun in heating
(not implemented for gas/oil heat).
20 Fan overrun in cooling. Global 0 0 seconds of fan
Global 0 0 seconds of fan
operation after heating turns off.
operation after cooling turns off.
1 90 seconds of fan
operation after heating
turns off.
1 90 seconds of fan
operation after cooling
turns off.
25 Keypad lockout. Local 0 No lockout 1 1—Locks out all except
i, run, dst, and set
current day/time.
2—Locks out all except i,
run, dst, and set current
day/time.
(In all cases, the
combination to enter the
Installer Setup and the
Installer Test is
available.)
30 Minimum deadband
between heating and cooling.
33 Minimum off time for
cooling and compressor.
34 Maximum setpoint
range stop for heating.
35 Minimum setpoint range
stop for cooling.
Global 3 Heating and cooling
setpoints can be set no closer than 3°F (1.5°C) to 10°F (5 °C).
Global 5 Five-minute minimum
off time for the compressor.
Global 90°F
(32°C).
Heating setpoint range can be set no higher than 90°F (30°C).
Global 45°F
(7°C).
Cooling setpoint range can be set no lower than 45°F.
4 to 10 Heating and cooling
setpoints can be set no
closer than the chosen
value between 3° F and
10 °F (1.5 and 5 °C).
0, 1, 2, 3, 4 or 5
Choose 0, 1, 2, 3, 4 or 5
minute minimum off time
for the compressor.
40°F through 90°F (4.5°C to 32°C).
45°F through 99°F (7°C to 37°C).
Maximum setpoint range
stop can be set
anywhere between 40° F
and 90°F in 1°F (0.5°C)
increments.
Minimum setpoint range
stop can be set
anywhere between 45°F
and 99°F in 1°F (0.5°C.)
increments.
11 69-1331—5
Page 12
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
Table 6. Installer Setup Numbers and Default Settings and Options. (Continued)
Installer
Setup
Number
(Press
key to
change) Description Scope
37 Field calibration
Local 0 No difference
adjustment.
Default Setting
Display Description Display Description
between displayed temperature and actual room
Other Options (Press or
key to change
-3, -2, -1, 1, 2, 3
Display adjusts to the
chosen °F higher or
lower than room
temperature.
temperature.
43 Filter timer. Global 0 Thermostat filter timer
is used.
44 Backlight operates
continuously or with a
Local 0 Backlight operates
with a key press.
1 External filter timer is
used.
1 Backlight operates
continuously. key press.
45 Outdoor temperature
sensor.
Local 0 Outdoor temperature
sensor is not
1 Outdoor temperature
sensor is configured.
configured.
46 Enable humidity display. Global 0 Humidity display
disabled.
51 Stage 1 heat cycle rate. Global
52 Stage 2 heat cycle rate.
b
6
Cycle rate of equipment (cph).
1 Humidity display
enabled.
1, 2, 3, 4, 5, 6, 7, 8,
Cycle rate of equipment
(cph).
9, 10, 11, or 12
55 Emergency heat cycle
rate.
Global 9 Cycle rate of
equipment (cph).
1, 2, 3, 4, 5, 6, 7, 8,
Cycle rate of equipment
(cph).
9, 10, 11, or 12
57 Stage 1 cool cycle rate. Global 3 Cycle rate of
58 Stage 2 cool cycle rate.
equipment (cph).
0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10,
Cycle rate of equipment
(cph).
11, or 12
ADV Advance configuration
menu to review/modify equipment ID and type.
ADV off.
No access to Advanced Installer Setup No. 61-63,
ADV on Access to Advanced
Installer Setup No. 61-63,
65-69, 71-73, 75-79.
65-69, 71-73, 75-79.
a
This value is not installer adjustable. If any of these Installer Setup No. are changed: 4, 5, 8, 9, 51, 52, 55-ADV from Table 6 and 62-63, 65-69, 71-73, 75-80 from Table 7, the settings are locked and Automatic Discovery cannot occur. To unlock Discovery, advance to “dIS” and press the key to manually initiate Discovery mode. During Dis­covery, “wait” appears in the display for approximately 20 seconds and the thermostat is not functional.
b
3 cph when used with W8635B or W8835 configured for heat pump; 9 cph when used with the T8635 set for electric heat.
IMPORTANT
Review the settings to confirm that they are correct for your application. Press Run Program key to exit Installer Setup. The settings will be saved indefinitely in memory. Upon exiting Installer Setup, “wait” appears in the display for approximately 20 seconds.
Set the time and day on the last thermostat configured after exiting Installer Setup. See Setting Current Day and Time section.
69-1331—5 12
Page 13
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
7
Advanced
Installer
Setup
Number
(Press
key to
change) Description
62
Equipment Type 1 of Heat
63
Equipment Type 2 Stage of Heat
64
Equipment Type 3 of Heat
65
Equipment Type 1 of Emergency Heat
67
Equipment Type 2 Stage of Emergency Heat
68
Equipment Type 1 of Cool
69
Equipment Type 2 Stage of Cool
70
Equipment Type 3 of Cool
72
Equipment ID 1 Heat
73
Equipment ID 2 Heat
74
Equipment ID 3 Heat
76
Equipment ID 1 Emergency Heat
77
Equipment ID 2 Emergency Heat
78
Equipment ID 1 Cool
79
Equipment ID 2 Cool
80
Equipment ID 3 Cool
(For reference only. Do not change any of these settings.)
Table 7. Advanced Setup Options.
Default Setting
Display Description Display Description
st
Stage
nd
1, 2, 3, 4 or 5
1 - Natural gas or oil heating. 2 - Free heating (outside) air
1, 2, 3, 4 or 5
without ventilation.
3 - Free heating (outside) air
with ventilation.
rd
Stage
st
Stage
4 - Compressor heating (heat
pump). 5 - Electric heating. Default display indicates the equipment that was found
nd
st
Stage
nd
1, 2, 3, 4 or 5
during Discovery mode.
1 - Evaporative cooling. 2 - Free cooling (outside) air
without ventilation. 3 - Free cooling (outside) air
with ventilation.
rd
Stage
4 - Compressor cooling. Default display indicates the equipment that was found during Discovery mode.
st
Stage of
nd
Stage of
rd
Stage of
st
Stage of
nd
Stage of
st
Stage of
nd
Stage of
rd
Stage of
0, 1, 2 or 3
This is a unique identification number corresponding to the equipment assigned the same number.
Default display indicates the equipment that was found during Discovery mode.
0, 1, 2 or 3
Other Options Press or
key to change)
1 - Natural gas or oil
heating.
2 - Free heating (outside)
air without ventilation.
3 - Free heating (outside)
air with ventilation.
4 - Compressor heating
(heat pump). 5 - Electric heating. Default display indicates the equipment that was found during Discovery mode.
1 - Evaporative cooling. 2 - Free cooling (outside)
air without ventilation. 3 - Free cooling (outside)
air with ventilation. 4 - Compressor cooling. Default display indicates the equipment that was found during Discovery mode.
This is a unique identification number corresponding to the equipment assigned the same number.
SETTINGS
Setting Current Day and Time
1. Press Set Current Day/Time key.
Run
Set Current
Leave
Wake
Set Current
Day/Time
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
SystemFilter Fan
Mon
Set Program
Time
Heat/Cool
Settings
Copy
Set Day/Time
NOTE: On initial powerup or after an extended
power loss, 1:00pm flashes in the dis­play until a key is pressed.
2. Press Day key until the current day is displayed.
Set Day/Time
Run
Set Current
Leave
Wake
Program
PM
M1776
Day
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
SystemFilter Fan
Settings
Copy
Tue
13 69-1331—5
PM
M17768
Page 14
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
1
t
A
TEST NUMBER
3. Press or until the current time is dis- played.
Time
Run
Set Current
Leave
Wake
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
SystemFilter Fan
Settings
Copy
Set Day/Time
AM
Tue
M17769
NOTE: Tapping the Set Current Day/Time key
changes the time in one-hour incre­ments.
4. If the current time is Daylight Savings Time, press Daylight Time key to display DST.
Set Day/Time
AM
Run
Set Current
Leave
Wake
Daylight
Time
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
SystemFilter Fan
Settings
Copy
Tue
M17770
5. Press Run Program key.
System
Run
Program
AM
Run
Set Current
Leave
Wake
Program
Day/Time
Hold Temp
Day
Daylight
Time
Return Sleep
Set Program
Time
Heat/Cool
SystemFilter Fan
Settings
Copy
Tue
Wake
Room
DST
Fan
M1777
Hea
Auto
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat and W8635 Equipment Interface Module operation for each thermostat in the system. Table 8 lists the avail­able system tests.
IMPORTANT
When used in zoning, you must exit Installer System Test before entering Installer System Test at another thermostat.
See Table 9 for Installer System Test descriptions.
Table 8. Installer System Tests.
Tes t
Number System Test Description
10-12 Heating stages can be turned on and off in
sequence.
20-21 Emergency heating can be turned on and off.
30-32 Cooling stages can be turned on and off in
sequence.
40-42 Fan and damper test.
60 Keyboard keys test.
70-74 Thermostat information, including date code
and software versions, are displayed.
Programming
See the Owner’s Guide, 69-1332, for complete pro­gramming instructions.
CAUTION
Equipment Damage Hazard. Minimum compressor off-time is bypassed during Installer System Test.
Do not allow compressor rapid cycling (on and off). Observe compressor protection period.
Starting Installer System Test
Press and hold the and ▼ keys at the same time until 10 appears. All segments of the display are shown before the test number 10 appears. See Fig. 15 and 17.
Table 9. Installer System Test Options.
Key to Press Test Number Description
Heating Equipment System Test
10 Enter Heating Equipment system test.
M10257
Fig. 17. Test number display.
11 First Stage Heat turns on.
12 Second Stage Heat turns on.
11 Second Stage Heat turns off.
10 First Stage Heat turns off.
69-1331—5 14
Page 15
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
Table 9. Installer System Test Options. (Continued)
Key to Press Test Number Description
Emergency Heat System Test (available only when using W8635B)
20 Enter Emergency Heat Equipment system test.
Cooling Equipment System Test
Fan and Damper Test Damper Test available only when using W8703A)
Key Operation Test
21 Emergency Heat turns on.
20 Emergency Heat turns off.
30 Enter Cooling Equipment system test.
31 First Stage Cool turns on.
32 Second Stage Cool turns on (W8635A only).
31 Second Stage Cool turns off (W8635A only).
30 First Stage Cool turns off.
40 Enter Fan and Damper test.
41 Fan turns on; damper for this zone opens.
42 Damper closes for this zone (if not already closed); fan stays on.
41 Damper opens for this zone.
40 Fan turns off.
60 Enter Key Operation test.
Press any key to test if the key is functional. Each time a key is pressed, a different number is displayed. This indicates the key is functioning properly. Pressing enters the next test.
Thermostat Information
70 Enter Thermostat Information mode.
Exit Installer Test Mode
Run Program key Thermostat returns to normal operating mode.
71 Production date code is displayed. The first two large digits are the month
and the third digit is the last digit of the year (example: 031 = March 2001).
72 Software identification code is displayed.
73 Software revision number is displayed.
74 EEPROM identification code is displayed.
CHECKOUT
Outdoor Temperature Sensor
Allow the C7089B Outdoor Temperature Sensor to absorb the outdoor air for a minimum of five minutes before taking a reading.
TROUBLESHOOTING GUIDE
Refer to Table 10 for troubleshooting information.
15 69-1331—5
Page 16
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
Table 10. Troubleshooting Information.
Symptom Possible Cause Action
Display does not come on.
Thermostat is not being powered. Check if the thermostat is mounted and latched on the
wallplate; if not:
—mount and latch the thermostat on the wallplate.
Check if the circuit breaker is tripped; if it is:
—reset the circuit breaker.
Check if the fuse in the fuse box is blown; if it is:
—replace the fuse.
Check if the power switch at the equipment is in the Off position; if it is:
—set to the On position.
Check for 24 vac on terminals 2 and 3:
—replace any broken wires.
If 24 Vac is present on terminals 2 and 3, replace the thermostat.
“1 COM”, “2 COM”, or “3 COM” is displayed.
Thermostat is not communicating correctly with the W8835 or W8635A,B.
Check the connection to terminal 1 at the thermostat and W8835 or W8635 EIM:
—replace any broken wires. —cycle power.
“4 COM” is displayed on left side of the display.
5 COM Zone 0 was found in a zoned
More than one thermostat is set to the same zone number.
system
Enter Installer Setup and change Installer Setup Number 1 to another value (1-3) that is different from the thermostat with the same zone number.
Enter Installer Setup and change Installer Setup Number 1 to another value (1-9) that corresponds to the zone it is controlling.
6 COM Zone 1 was not found. Enter Installer Setup on the Zone 1 Thermostat and
change Installer Setup Number 1 to 1.
7 COM System is configured to use
external timer.
System switch setting displays “off only.”
During Automatic Discovery mode, the thermostat did not correctly set the number of heat or cool stages.
The external timer function is not currently available. Enter Installer Setup and change Installer Setup 43 to 0.
Run Automatic Discovery mode by cycling power to the equipment.
Manually run Discovery mode in Installer Setup.
Manually configure heat and/or cool stages (Installer Setups 5, 8 and 9).
Thermostat is calling for heat or
cool; or displays and the
corresponding damper does not open.
Heating does not come on. System
on indicator displays.
Thermostat zone number is not set to the corresponding W8703 zone number.
Terminal 1 on W8703 Damper Interface Module is not properly connected.
W8703 Damper Interface Module is defective.
Communication is not being completed.
Set zone number at the thermostat to correspond with the correct zone number for the W8703 Damper Interface Module.
Properly connect terminal 1 on the W8703 Damper Interface Module.
If the W8703 indicates the damper is closed (red LED lights), replace the W8703 Damper Interface Module.
End the call and repeat the call. Check the Flash Com OK LED on the W8835 or W8635 EIM while the call is being made. If the Flash Com OK LED does not blink:
—check communication bus wiring. Heat load at W8635 EIM is not connected correctly.
If the Flash Com OK LED blinks correctly:
—check that 24 Vac is present at W1 or W1/Y1 terminal,
depending on which equipment module is being used.
If 24 Vac is not present, check the R to Rh connection. If the connection is good, replace the W8835 or W8635 EIM.
69-1331—5 16
Page 17
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
Table 10. Troubleshooting Information. (Continued)
Symptom Possible Cause Action
Cooling does not come on. System
on indicator displays.
Communication is not being completed.
End and repeat the call for cool. Check the Flash Com OK LED on the W8635 EIM or W8835 while the call is being made. If the Flash Com OK LED does not blink:
—check communication bus wiring. Cool load at W8635 EIM is not connected correctly.
If the Flash Com OK LED blinks correctly:
—check that 24 Vac is present at Y1 or W1/Y1 terminal, depending on which EIM is being used. If 24 Vac is not present, check R to Rc and/or Rh connections. If the R to Rc and/or Rh connections are good, replace the W8635 EIM or W8835.
“wait” is displayed and the call for Cool (or Heat when used in a heat pump application) has not
Compressor protection is in effect. Compressor protection can be set from 0 to 5 minutes to
prevent compressor damage due to rapid cycling. Wait until the compressor protection period expires. To bypass compressor protection during the installation phase, see the Installer System Test section.
started.
nd
stage heat or
2 cool does not energize (only when used with W8635A).
Stage configuration is not set correctly to match the number of selected stages.
Cool load at W8635 EIM is not connected correctly.
Set the Stage configuration in Installer Setup for two stages of heat and/or two stages of cool.
Check that 24 Vac is present at Y2, W2 or Aux. Terminal, depending on EIM used. If 24 Vac is not present, all connections are good and the thermostat is properly configured, replace W8635A EIM or W8835.
Emergency Heat does not energize (only when used
Emergency Heat load at W8635 or W8835 is not connected correctly.
Check that 24 Vac is present at E terminal. If 24 Vac is not present, all connections are good, and the thermostat is properly configured, replace W8635B or W8835.
with W8635B or W8835).
Emergency Heat can not be selected with the System
Stage configuration is not set correctly to match the number of stages selected.
Set the Stage configuration, Installer Setup No. 9 to 1, see table 5 for one stage of Emergency Heat.
switch (W8635B only).
Fan does not come on with a call for
Electric heat setting is not configured.
Set Installer Setup No. 4 to 1 for electric heat, see Table 6.
electric heat.
Fan load at the W8835 or W8635 EIM is not connected correctly.
Check that 24 Vac is present at G terminal. If 24 Vac is not present, all connections are good, and the thermostat is configured, replace the W8635 EIM or W8835.
The is flashing and the damper does not open.
Temperature setting does not change (example: cannot set the heating higher or the cooling lower).
Fan runs continuously.
Thermostat is waiting for a call for heat or cool to end in another zone before opening this zone damper.
The upper or lower temperature limits are reached.
Fan setting set to On or programmed to On.
Wait until call from other zone ends.
Check temperature setpoint limits; setpoint limit ranges are:
—heating: 40° to 90°F (4.5° to 32°C).
—cooling: 45° to 99°F (7° to 37°C). See Installer Setup no. 34 and no. 35 to change the setpoint limits, see Table 6.
Pressing the Fan key changes the fan from On to Auto or vice versa for the duration of the current program period. To set the fan to run continuously for all periods, program the fan to On for each period and day.
The green LED is on.
Filter expired. Replace filter or clean electronic air cleaner cells. Press
and hold the filter key to reset the timer. To disable the filter timer, select 0 as the timer value.
The red LED is on. Check LED. 24 Vac is present at
Check heat pump manufacturer instructions.
the L terminal on the W8835 or W8635B EIM.
17 69-1331—5
Page 18
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
Table 10. Troubleshooting Information. (Continued)
Symptom Possible Cause Action
Outdoor temperature not displayed or is incorrect.
Outdoor temperature setting is not enabled in Installer Setup.
Install one C7089B Outdoor Temperature Sensor to OT terminals on one thermostat in the system and configure Installer Setup No. 45 to 1, see Table 6, only at the zone where the outdoor sensor is connected.
Heat or cool turns on before programmed time.
Outdoor sensor is not connected, is connected incorrectly or is out­of-range.
Outdoor sensor is configured at more than one thermostat zone location.
Filter expired.
Adaptive Intelligent Recovery™ is on.
If the outdoor sensor is not connected or is out-of-range (below –40°F or above 120°F) “- -” is displayed on the thermostat where the outdoor sensor is located. All other thermostats do not display an outdoor temperature until the sensor is in range or connected correctly.
Outdoor temperature alternates between displaying outdoor temperature and “- -” . Configure only the thermostat where the outdoor sensor is connected.
Press key twice for outdoor temperature when filter expiration displays. Refer to the Filter Indication section.
Adaptive Intelligent Recovery™ brings on the heat or cool early to meet the temperature set for the programmed period. To disable Adaptive Intelligent Recovery™, configure Installer Setup No. 13 to 1, see Table 6.
69-1331—5 18
Page 19
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
19 69-1331—5
Page 20
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough, Ontario
69-1331—5 G.H. Rev. 02-03 Printed in Taiwan R.O.C. www.honeywell.com/yourhome
M1V 4Z9
Loading...