Honeywell W8635A User Manual

W8635A
Equipment Interface Module
INSTALLATION INSTRUCTIONS

APPLICATION

The W8635A Equipment Interface Module (EIM) pro­vides 24 Vac control of single or multistage conventional HVAC equipment when used with a T8635L Microelec-
Table 1. Description.
Model Application Stages Terminals Comments
W8635A Conventional gas, oil
or electric heat
Up to 2 heat/ 2 cool

INSTALLATION

tronic Communicating Programmable Thermostat. The W8635A can be used w ith up to 2 heat/2 cool conven­tional applications. See Table 1.
1, 2, 3, C, R, Rh, Rc, G, W1, W2, Y1, Y2
1.
Use with T8635L Communicating Thermostat
Locate the W8635A in the equipment room near the HVAC equipment. See Fig. 1.

When Installing this Product…

Read these instructions carefully. Failure to follow
1.
these instructions can damage the product or cause a hazardous condition. Check the ratings given in the instructions and on
2.
the product to make sure the product is suitable for your application. Installer must be a trained, experienced service
3.
technician. After completing installation, use these instructions
4.
to check out the product operation.
W8635
CAUTION
Voltage Hazard. Can cause electrical shock or equ ip m ent damage.
Disconnect power before supply before beginning installation.
POSSIBLE
MOUNTING

LOCATION

W8635 POSSIBLE MOUNTING LOCATION
Location
CAUTION
Mounting Location Hazard. Mounting W8635A inside HVAC equipment can damage the EIM.
Mount the W8635A only on the outside of HVAC equipment.
® U.S. Registered Trademark Copyright © 2000 Honeywell Inc. • • All Rights Reserved
FURNACE OR BOILER
Fig. 1. Selecting W8635A Equipm ent
Interface Module location.
Remove the cover from the W8635A by pulling on
2.
the edge of the module. Locate the two mounting holes. See Fig. 2.
3.
WATER HEATER
M16637A
69-1339- 2
W8635A EQUIPMENT INTERFACE MODULE
FOR WRAPAROUND CONNECTION STRIP 7/16 IN. (11 MM)
FOR STRAIGHT CONNECTION STRIP 5/16 IN. (8 MM)
M16639
W8635
WALL
W8635
MOUNTING HOLES (2)
Fig. 2. Mounting W8635A
Equipment Interface Modul e.
Position the W8635A on the wall or on the cold air
4.
return. Level the W8635A for appearance only; the device
5.
functions properly even when not level. Use a pencil to mark the position of the mounting
6.
holes on the wall or cold air return. Remove the W8635A from the wall or cold air
7.
return and drill 3/ 1 6 in . ho l e s in th e wall (if drywall) where marked. For firmer materials such as plaster or wood, drill 7/32 in. holes. When mounting on the cold air return, drill a pilot
8.
hole where marked. Gently tap the anchors (provided) into the holes
9.
until flush with the w all. Reposition the W8635A over the holes.
10.
Loosely insert the screws into the holes and tighten
11.
each screw.

WIRING

All wiring must comply with local electrical code s and ordinances. See Fig. 4 through 6 wiring diagrams for specific equipment applications. Refer to Table 2 for terminal designations.
CAUTION
Voltage Hazard. Can cause electrical shock or equ ip m ent damage.
Disconnect power before beginning installation.
Loosen the terminal screws on the W8635A and
1.
connect the system wires. See Fig.3. Securely tighten each terminal screw.
2.
1 2 3
C R R
H
R
C
G W W
Y1 Y2
1 2
MOUNTING SCREWS (2)
M16636
Fig. 3. Wiring the W8635A terminals.
Table 2. Terminal Designations.
W8635A
Terminal
Designations Function
1 To Communicating Thermostat
Terminal 1
2 To Communicating Thermostat
Terminal 2
3 To Communicating Thermostat
Terminal 3
R 24 Vac System Transformer Rh 24 Vac Heating Transformer Rc 24 Vac Cooling Transformer
C 24 Vac Transformer Common
GFan Relay W1 Stage 1 Heat Relay W2 Stage 2 Heat Relay Y1 Stage 1 Cool Relay Y2 Stage 2 Cool Relay
Green LED Indicates Data Communication
T8635L
OT
OT
W8635A
1 2 3
C R R
H
R
C
1
FACTORY INSTALLER JUMPERS.
1
G W1 W2
Y1 Y2
L2
L1 (HOT)
SYSTEM
TRANSFORMER
C7089B OUTDOOR TEMPERATURE SENSOR
1
Fig. 4. 2H/2C single transformer.
69-133922
2
3
FAN RELAY
HEAT 1 RELAY
HEAT 2 RELAY
COOL 1 RELAY
COOL 2 RELAY
M13429
W8635A EQUIPMEN T INTERFACE MODULE
T8635L
3
OT
FAN RELAY
HEAT 1 RELAY
HEAT 2 RELAY
COOL 1 RELAY
COOL 2 RELAY
L1 (HOT)
L2
SYSTEM
TRANSFORMER
C7089B OUTDOOR TEMPERATURE SENSOR
1
1
T8635L
OT
OT
W8635A
1 2 3
C R R
H
R
C
FACTORY INSTALLER JUMPERS.
2
1
G W1 W2
Y1 Y2
Fig. 5. Three zone configuration.
WIRE NUT
M13378
Fig. 6. Using wire nut to pigtail a connection when
three or more wires are terminated at one terminal.

Discovery Mode

Discovery mode begins when the T8635L Thermost at and W8635 EIM are first installed and power is connected: The W8635 EIM transmits i nformation to the T8635L
Thermostat that indicates the maximum number of stages that are enabled and the type of EIM connected.
The thermostat receives informati on from the W8635
and then sets the cycle rates and equipment types automatically.

Stage Configuration

The W8635A automatically configures the T8635L for two stages of heat and two stages of cool. If using the W8635A and the T8635L on a one heat/one cool application, set Installer Setup No. 5 and 8 to 1 when configuring the T8635L Communicati ng Thermostat.
For configuration combinations, see Table 3.
T8635L
OT
2
1
3
546Z 213X
546Z 213X
546Z 213X
TROL-A-TEMP MODEL AOBD
ZONE DAMPER
OT
W8703A
1
OT
OPEN CLOSE
OPEN CLOSE
OPEN CLOSE
OPTIONAL
TROL-A-TEMP
MODEL ARD-PC
OR MODEL ZD
2
3
ZONE AZONE B
TR1 TR2
COM
ZONE C
1 2 3
Table 3. Stage Combinations.
Heat Stages Cool Stages
10 20 01 02 11 22

Cycle Rate

The thermostat automatically sets the cycle rate based on the information it received during Discovery M ode. See Table 4.
To change the default cycle rate settings: enter T8635L Thermostat Installer Setup and select
the desired cycle rate settings for each stage. (All stages can be set bet ween 1 and 12 cph.)
Table 4. Default Cycle Rate Settings.
st
1
W8635A
Equipment
Interface
Module
Stage
Heat
2nd
Stage
Heat
6 cph 6 cph 3 cph 3 cph
1st
Stage
Cool

Electric Heat Setting

When using the W8635A on an electric heat application, set the T8635L Thermostat Installer Setup No. 4 to 1. This instructs the W8635A EIM to energize the fan with any call for heat.
L1 (HOT)
L2
EXTERNAL 40 VA TRANSFORMER
M13430A
2nd
Stage
Cool
3 69-1339—2
W8635A EQUIPMENT INTERFACE MODULE

Flash COM OK LED Description

LED blinks rapidly
mitting information on the communications bus.
LED blinks once
acknowledged a message.
LED on constantly
device.
LED off constantly
device is not functioning properly and there is no LED activity at least once a minute. Check wiring to communications bus terminals 1, 2 and 3.
NOTE: It is normal for LED to blink continuously dur-
ing startup and discovery.
LED blinks continuously
if device is not functioning properly and there is a continuous series of LED blinks. Check wiring to communications bus terminals 1, 2 and 3.
indicates device is currently trans-
indicates device received and
indicates device failure. Replace indicates a wiring probl em if
indicates a wiring problem
CAUTION
Equipment Damage Hazard. Minimum compressor off-tim e is bypassed during Installer System Test.
Do not allow compressor rapid cycling (on and off). Observe compressor protection period.
To start the Installer System Test:
Press and hold the T8635L Thermostat increase
1.
and decrease ▼ keys at the same time until 10
appears. All display segments display before the 10 appears. See Fig. 7 and 8.
Set Program
Hold for
Em Ht Aux Ht
Mon
TueWedThuFriSatSun
Wake
System Fan
Heat
Em

INSTALLER SYSTEM TEST

Use the Installer System Test to check the thermostat and W8635A EIM operation for each thermostat in the system. Table 5 lists the available system tests.
Table 5. Installer System Tests.
Test Number System Test Description
10-12 Heating stages can be turned on and
30-32 Cooling stages can be turned on and
40-42 Fan and damper test
70-74 Thermostat information including date
Heating Equipment Sys te m Test
Cooling Equipment Sy stem Test
off in sequence
off in sequence
60 Keyboard keys test
code and software versions are displayed.
Fig. 8. Installer Test Number display.
Refer to Table 6 for Installer System Test option.
2.
Table 6. Installer System Test Options.
Key to Press Test Number Description
10 Enter Heating Equipment system test.
▲ ▲ ▼ ▼
11 First Stage Heat turns on. 12 Second Stage Heat turns on. 11 Second Stage Heat turns off. 10 First Stage Heat turns off.
30 Enter Cooling Equipment system test.
▲ ▲ ▼ ▼
31 First Stage Cool turns on. 32 Second Stage Cool turns on. 31 Second Stage Cool turns off. 30 First Stage Cool turns off.
Temporary Setting Enrg
Set Day/Time
Start Time
AM
PM
Heat
Cool
Filter
Recovery
LeaveReturnSleep
Off Auto
Cool
In
Wait
DST
Auto
Fig. 7. LCD segments display.
TEST NUMBER
Room
%Humid
Outdoor
Repl Batt
Auto
On
M10345A
Sav
M10257A
69-133924
W8635A EQUIPMEN T INTERFACE MODULE
Table 6. Installer System Test Options. (Continued)
Key to Press Test Number Description
Fan and Damper Test (Damper Test available only when using W8703A)
40 Enter Fan and Damper test.
▲ ▲ ▼ ▼
41 Fan turns on; damper for this zone opens. 42 Damper closes for this zone (if not already closed); fan stays on. 41 Damper opens for this zone. 40 Fan turns off.
Key Operation Test
60 Enter Key Operation test.
Press any key to test if the key is functional. Each time a key is pressed, a different num ber is disp lay ed. This indicates the key is functioning properly . Pressing enters the next test .
Thermostat Information
70 Enter Thermostat Information mode.
▲ ▲ ▲
71 Production date code is displayed. The fir st two large digits are
the month and the third digit is the last digit of the year (exam pl e:
031 = March 2001). 72 Software identification code is displayed. 73 Software revision number is displayed. 74 EEPROM identification code is displayed.
Exit Installer Test Mode
Run
Program
Thermostat returns to normal operating mode.

TROUBLESHOOTING GUIDE

Refer to Table 7 for troubleshooting informat ion .
Table 7. Troubleshooting Guide.
Symptom Possible Cause Action
Display does not come on at thermostat.
1 COM”, “2 COM or3 COM is displayed.
System Switch setting displays off only.
Thermostat is not being powered. Check if the therm ost at is mounted and latched on the
Thermostat is unable to communicate with the W8635A.
During Discovery Mode, the thermostat did not correctly set the number of heat or cool stages.
wallplate; if not:
mount and latch the thermostat on the wallplate.
Check if the circuit breaker is tripped; if it is:
reset the circuit breaker.
Check if the fuse is blown; if it is:
replace the fuse. Check if the power switch at the equipment is in the Off position; if it is:
set to the On p o s ition. Check for 24 Vac on terminals 2 and 3: replace any broken wires.
If 24 Vac is present on terminals 2 and 3:
replace the thermostat.
Check the connection to terminal 1 at the thermostat and W8635A EIM:
replace any broken wires.
cycle power.
Manually run Discovery Mode; see Installer Setup.
manually configure heat and/or cool stages
(Installer Setup 5 and 8).
5 69-1339—2
W8635A EQUIPMENT INTERFACE MODULE
Table 7. Troubleshooting Guide. (Contin ued)
Symptom Possible Cause Action
Heating does not come on. System on indicator
( = heat) displays.
Cooling does not come on. System on indicator
( = cool) displays.
wait is displaye d and the call for Cool has not started.
nd
2
stage heat or cool
does not energize.
Fan does not come on with a call for electric heat.
Communication is not being completed.
Heat load at W8635A is not connected correctly.
Communication is not being completed.
Cool load at W8635A is not connected correctly.
Compressor protection is in effect.
Stage configuration not set correctly to match the number of selected stages.
Cool load at W8635A is not connected correctly.
Electric heat setting is not configured.
Fan load at W8635A is not connected correctly.
End and repeat the call for heat. Check the Flas h COM OK LED on the W8635A EIM while the call is being made. If the Flash COM OK LED does not blink:
check communication Bus wiring.
If the Flash COM OK LED blinks:
check that 24 Vac is present at W1 terminal.
If 24 Vac is not present:
check R to Rh connection.
If the connection is good:
replace the W8635A EIM.
End and repeat the call for cool. Check the Flash COM OK LED on the W8635A EIM while the call is being made. If the Flash COM OK LED does not blink:
check communication bus wiring.
If the Flash COM OK LED blinks:
check that 24 Vac is present at Y1 terminal.
If 24 Vac is not present:
check R to Rh to Rc jumper connection. If the R to Rh to Rc connection is good:
replace the W8635A EIM.
Compressor protection can be set from 0 to 5 minutes to prevent compressor damage due to rapid cycling. Wait until the compressor protection period expires.
To bypass compressor protection during the installat ion phase, see the Installer System Test section.
Set the Stage configuration in Ins tal ler Setup for two stages or heat and/or two stages of cool.
Check that 24 Vac is present at Y2 or W2 terminal. If 24 Vac is not present, all connections are good and the thermostat is correctly configured, replace W8635A EIM.
Set Installer Setup No. 4 to 1 for electric heat.
Check that 24 Vac is present at G terminal. If 24 Vac is not present, all connections are good and the thermostat is configured, replace the W8635A EIM.
Home and Building Control Home and Building Control
Honeywell Inc. Honeywell Limited-Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P.O. Box 524 North York, Ontario Minneapolis, MN 55408-0524 M2H 3N7
69-13392 G.H. Rev. 6-00 www.honeywell.com
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Loading...