Honeywell VP522 Catalog Page

Honeywell VP522 Catalog Page

Pneumatic Valves

VP522 Pneumatic Sequencing Water Valve

Dimensions in inches (millimeters)

B

A

C

VALVE

A

B

C

SIZE

IN INCHES (mm)

IN INCHES (mm)

IN INCHES (mm)

3/8 IN.

9-13/16 (249)

5-1/8 (130)

3-5/8 (92)

1/2 IN.

9-15/16 (252)

5-1/8 (130)

3-5/32 (80)

 

 

 

 

3/4 IN.

9-15/16 (252)

5-1/8 (130)

3-5/32 (80)

 

 

 

 

C4671A

Three-pipe, sequencing, pneumatically operated water valve for controlling both hot and cold water flow in fan-coil and induction units. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices.

Corrosion resistant.

Molded-in composition discs for tight shutoff.

Flare connections for easy installation.

Operator rotates 360 degrees for convenient air piping alignment.

Valve Type: Unitary Body Pattern: Three-way

Body Pressure: 250 psi (1724 kPa)

Air Connections: 1/8 in. NPT Controlled Medium: Water

Type of End Connection: 45 degree. SAE flare Operating Humidity Range (% RH): 5 to 95% RH

Temperature Range: 35 F to 250 F (2 C to 121 C)

Maximum Actuator Temperature: 160 F (71 C) Maximum Diaphragm Pressure: 25 psi (172 kPa)

Accessories:

312817Y-Actuator assembly for VP522B1011 andVP522B1029

Replacement Parts:

312760-MP953A,C,E (5 in. diameter) regular temperature Neoprene diaphragm - new style

312817S-Actuator for VP522A1039, VP522A1047, VP522A1237

312817W-Actuator for VP522B1003

312817Y-Actuator assembly for VP522B1011 andVP522B1029 313824A-Rebuild kit, include Stem and Disc holder, button with screw,

packing and instruction, VP522A1005

314459A-Rebuild kit, include Stem and Disc holder, button with screw, packing and instruction, VP522A1039

314459B-Rebuild kit, includes stem and disc holder, Button with screw, packing and instructions, VP522A1047

315407A-Rebuild kit, include Stem and Disc holder, button with screw, packing and instruction for the VP522B1003

 

 

 

 

 

 

 

 

 

 

 

End Connection Size

Capacity

 

Close-off

 

Spring Range

 

 

 

 

 

Ratings at

 

 

 

 

 

 

 

 

 

Branch Line

 

 

 

 

Product Number

(inch)

(mm)

(Cv)

(Kv)

Pressure

Valve Action

(psi)

 

(kPa)

 

 

 

 

 

 

 

 

 

 

VP522A1005/U

O.D.: 1/2 in.;

O.D.: 12.7 mm;

Port A: 1.5 Cv,

Port A: 1.3 Kv,

50 psid at 13 psi

Proportional/

3 psi to

 

21 kPa to

 

Nominal: 3/8 in.

Nominal: 9.5 mm

Port B: 1.5 Cv

Port B: 1.3 Kv

 

Sequencing; Mixing

11.5 psi

 

79 kPa

 

 

 

 

 

 

 

 

 

 

VP522A1039/U

O.D.: 5/8 in.;

O.D.: 15.9 mm;

Port A: 2.5 Cv,

Port A: 2.2 Kv,

50 psid at 13 psi

Proportional/

2 psi to

 

14 kPa to

 

Nominal: 1/2 in.

Nominal: 12.7 mm

Port B: 1.6 Cv

Port B: 1.4 Kv

 

Sequencing; Mixing

13 psi

 

90 kPa

 

 

 

 

 

 

 

 

 

 

VP522A1047/U

O.D.: 7/8 in.;

O.D.: 22.2 mm;

Port A: 4 Cv,

Port A: 3.5 Kv,

45 psid at 13 psi

Proportional/

2 psi to

 

14 kPa to

 

Nominal: 3/4 in.

Nominal: 19.1 mm

Port B: 2.5 Cv

Port B: 2.2 Kv

 

Sequencing; Mixing

13 psi

 

90 kPa

 

 

 

 

 

 

 

 

 

 

VP522B1003/U

O.D.: 1/2 in.;

O.D.: 12.7 mm;

Port A: 1.5 Cv,

Port A: 1.3 Kv,

15 psid at 13 psi

Diverting/Sequencing

Adjustable

 

 

Nominal: 3/8 in.

Nominal: 9.5 mm

Port B: 1.5 Cv

Port B: 1.3 Kv

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VP522B1011/U

O.D.: 5/8 in.;

O.D.: 15.9 mm;

Port A: 2.5 Cv,

Port A: 2.2 Kv,

15 psid at 13 psi

Diverting/Sequencing

Adjustable

 

 

Nominal: 1/2 in.

Nominal: 12.7 mm

Port B: 2.5 Cv

Port B: 2.2 Kv

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VP522B1029/U

O.D.: 7/8 in.;

O.D.: 22.2 mm;

Port A: 4 Cv,

Port A: 3.5 Kv,

15 psid at 13 psi

Diverting/Sequencing

Adjustable

 

 

Nominal: 3/4 in.

Nominal: 19.1 mm

Port B: 3.5 Cv

Port B: 3.0 Kv

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

716

customer.honeywell.com

70-6910

Loading...