Honeywell VP513 Catalog Page

Pneumatic Valves
VP513 Pneumatic Water Valve
Valve Type: Unitary Body Pressure: 250 psi (1724 kPa) Air Connections: 1/8 in. NPT Valve Action: Proportional Normally Open Controlled Medium: Water Type of End Connection: 45 degree. SAE flare Operating Humidity Range (% RH): 5 to 95% RH Temperature Range: 35 F to 250 F (2 C to 121 C) Maximum Actuator Temperature: 160 F (71 C) Maximum Diaphragm Pressure: 25 psi (172 kPa)
Single-seated, straight-through, pneumatic valves used for proportional control of unit air conditioners using hot and/or chilled water. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices.
• Available in normally-open (A models) or normally-closed models (B models).
• Straight-through pattern.
• Rotating actuator for aligning air connection with control air piping.
• Molded replaceable composition disc for tight shut-off.
• Flare tube connections.
• Small physical size.
Accessories:
312817T-Actuator assembly, 3 to 10 psi, 21 to 69 kPa, and 1/2 in. stroke. 312817U-Actuator Assembly, 3 to 7 psi, 21 to 48 kPa, and 1/2 in. stroke. 312817V-Actuator Assembly, 8 to 12 psi, 55 to 83 kPa, and 1/2 in.
stroke.
Replacement Parts:
310143-Black Packing, 3 required 310135-Packing Spring, 1 Required 312760-MP953A,C,E (5 in. diameter) regular temperature Neoprene
diaphragm - new style
14002734-002-Lubricant, packing, AMOCO H-100
Pneumatic
End Connection Size Capacity Close-off
Product Number
VP513A1048/U O.D.: 7/8 in.;
Nominal: 3/4 in.
VP513A1055/U O.D.: 7/8 in.;
Nominal: 3/4 in.
VP513A1188/U O.D.: 5/8 in.;
Nominal: 1/2 in.
VP513A1204/U O.D.: 5/8 in.;
Nominal: 1/2 in.
VP513B1012/U O.D.: 5/8 in.;
Nominal: 1/2 in.
VP513B1038/U O.D.: 5/8 in.;
Nominal: 1/2 in.
VP513B1053/U O.D.: 5/8 in.;
Nominal: 1/2 in.
O.D.: 22.2 mm; Nominal: 19.1 mm
O.D.: 22.2 mm; Nominal: 19.1 mm
O.D.: 15.9 mm; Nominal: 12.7 mm
O.D.: 15.9 mm; Nominal: 12.7 mm
O.D.: 15.9 mm; Nominal: 12.7 mm
O.D.: 15.9 mm; Nominal: 12.7 mm
O.D.: 15.9 mm; Nominal: 12.7 mm
Ratings at Branch Line Pressure
2.5 Cv 2.16 Kv 79 psid (545 kPa)
4 Cv 3.46 Kv 79 psid (545 kPa)
2.5 Cv 2.16 Kv 79 psid (545 kPa)
2.5 Cv 2.16 Kv 79 psid (545 kPa)
1.0 Cv 0.86 Kv 50 psid (345 kPa)
1.6 Cv 1.38 Kv 50 psid (345 kPa)
2.5 Cv 2.16 Kv 50 psid (345 kPa)
at 13 psi (90 kPa)
at 13 psi (90 kPa)
at 13 psi (90 kPa)
at 13 psi (90 kPa)
at 7 psi (48 kPa)
at 7 psi (48 kPa)
at 7 psi (48 kPa)
Spring Range
Body Pattern(inch) (mm) (Cv) (Kv) (psi) (kPa)
3 psi to 10 psi 21 kPa to 69 kPa Two-way, Straight-
through
3 psi to 10 psi 21 kPa to 69 kPa Two-way, Straight-
through
3 psi to 7 psi 21 kPa to 48 kPa Two-way, Straight-
through
3 psi to 10 psi 21 kPa to 69 kPa Two-way, Straight-
through
9 psi to 13 psi 62 kPa to 90 kPa Two-way, Straight-
through, Offset
9 psi to 13 psi 62 kPa to 90 kPa Two-way, Straight-
through, Offset
9 psi to 13 psi 62 kPa to 90 kPa Two-way, Straight-
through, Offset
Controls