Honeywell U2-1018S-PF, U2-1018S, U2-1016S, U2-1012S, U2-1010S-PF-100 User Manual

...
32-00015-04
U2-S Model Combination Viewing
WARNING
AVERTISSEMENT
AVERTISSEMENT
WARNUNG
ATENÇÃO
Head and Signal Processor
USER MANUAL

GENERAL INFORMATION

The Honeywell U2-101xS series model is a viewing head and signal processor in a single enclosure intended for use with a burner control system in Industrial Flame Monitoring applications. There are several options available (see Table 1 on page 2). Each model includes one, two, or all three sensors, and can be ordered with quick disconnect (non-PF Models DIV2,ZN2) or pigtail external connection method (PF Models DIV1,ZN1).
Each sensor operates independently from another, allowing adjustment of each sensor.
Read the instructions before use. This control shall be installed in accordance with the rules in force. Additional versions of this manual are available online at https://customer.honeywell.com/en­US/Pages/default.aspx in Canadian French, Portuguese, and German. Please enter 32-00015 in the search box and choose Technical Literature from the drop-down box.
Lire les instructions avant l'utilisation. Cette commande doit être installée conformément aux lois en vigueur. Des versions supplémentaires de ce manuel sont disponibles enligne à https://customer.honeywell.com/en­US/Pages/default.aspx en français du Canada, en portugais et en allemand. Veuillez inscrire 32-00015 dans le casier de recherche et choisissez Documentation technique à partir du menu déroulant.
Lesen Sie vor der Verwendung die Anweisung. Diese Konsole muss entsprechend den geltenden Vorschriften installiert werden. Zusätzliche Versionen dieses Handbuchs sind online unter https://customer.honeywell.com/en­US/Pages/default.aspx in Frankokanadisch, Portugiesisch und Deutsch verfügbar. Bitte geben Sie im Suchfeld 32-00015 ein und wählen Sie Fachliteratur im Drop-Down Menü aus
IMPORTANT
Flame monitoring systems are safety systems. Please read this manual carefully and completely
before installation and before attempting adjust­ments.
Only qualified personnel familiar with Flame Safety System should carry out installation and configuration.
U2 is certified to be used in prescribed manner. Any modification or inappropriate installation or
operation may result in unsafe operation and will void implied or expressed warranty.

Sensors

The UV tube detector has a peak response at 210 nm.
The IR solid state sensor has a peak response at 1400 nm.
The UV solid state sensor has a peak response at 310 nm.
Cabling Options (Sold Separately)
ASYU2S - Quick Disconnect (non-PF) models molded connector cable assembly with 50 foot of C22S cable.
Leia as instruções antes de usar. Esse controle tem que ser instalado de acordo com as normas vigentes. Outras versões desse manual estão disponíveis online em https://customer.honeywell.com/en­US/Pages/default.aspx em francês do Canadá, português e alemão. Insira 32-00015 em cada caixa e selecione Literatura Técnica na caixa suspensa.
Disposal and Recycling
Waste electrical products should not be disposed of with general waste. Please recycle where these facilities exist. Check with your local authority for recycling advice.
Contents
GENERAL INFORMATION ............................................... 1
SPECIFICATIONS ............................................................ 2
INSTALLATION ................................................................. 3
OPERATION ..................................................................... 6
U2 MENU PARAMETER SETTINGS ................................ 7
TROUBLESHOOTING ...................................................... 10
SAFETY MANUAL ............................................................ 13
Safety Function of the U2-S Model .............................. 14
Proof Test Procedure ................................................... 14
Proof Test Interval ........................................................ 14
Product Decommissioning ........................................... 15
U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR
WARNING
WARNING
ASYU2S-100 - Quick Disconnect (non-PF) models molded connector cable assembly with 100 foot of C22S cable.
ASYU2S-200 - Quick Disconnect (non-PF) models molded connector cable assembly with 200 foot of C22S cable.
Table 1. Models and Associated Features.
Quick
Model
U2-1010S X X X X All Fuels U2-1010S-PF X X X X All Fuels U2-1010S-PF-050* X X X X All Fuels U2-1010S-PF-100 X X X X All Fuels U2-1012S X X Oil and Coal U2-1012S-PF X X Oil and Coal U2-1016S X X Gas and Light Oils U2-1016S-PF X X Gas and Light Oils U2-1018S X X X All Fuels U2-1018S-PF X X X All Fuels
* The U2-1010S-PF-050 has a 50-ft (15m) pigtail and the U2-1010S-PF-100 has a 100-ft (30m) pigtail.
Connector
Pipe Fit
Connection

SPECIFICATIONS

Input Power Supply: 22-26 VDC, 120 mA max (approxi-
mately 3.5 watts)
Remote Communication: 2 wire RS485 compatible with
Modbus RTU protocol.
Flame And Fault Relay Contact Ratings:
1 A, 30 VDC (Resistive).
Maximum load current of 1A must be de-rated at tem-
peratures higher than 50C ambient according to 1%/C, or 10mA/C. For example, the maximum current at 70C = 1A – (20C x 10mA) = 0.8A.
Do not apply more than 30VDC to flame relay or self check relay.
The U2 requires the use of an isolated 24VDC SELV (Safety Extra Low Voltage) power supply.
User Selectable Analog Output: 0-20 mA and 4-20 mA;
500 Ohm Load Max
File Select Input logic high: 21VDC min
File Select Input logic low: 16VDC max
User Interface: Capacitive TouchWheel with LED Display
Ambient temperature: -40 to 70 ºC (-40 to 158 ºF)
Enclosure: IP66
Weight: 2.8 kg (6.1 lbs)
Physical Dimensions: Diameter: 11.7 cm (4.6 inches)
Length: 15.5 cm (6.1 inches)
Finish: Silicone free powder coated
ASYU2S-300 - Quick Disconnect (non-PF) models molded connector cable assembly with 300 foot of C22S cable.
C22S - Raw shielded 12 conductor, 22g, ITC, CIC approved. Order by the foot.
Sensor Type
Typical FuelsUVTron IR UVSS
Mounting/Process Connection: 1” NPT female
Pipe Fit Models (PF version): 3/4” NPT
Fuses: Automatically resettable for power source and
Flame Relay.
Maximum furnace back pressure: 35 Kg/Cm2 (500 PSI)
Selectable Flame Failure Response Time (FFRT):
1, 2, 3 seconds, Error= +0.0sec, -0.5sec.
Internal Temperature Indication: Degrees C or F in dis-
play menu of U2, or available at Modbus register
40019.
Self-Checking
Internal electronic self checking is performed once per
second, to verify that system is operating properly. If self check detects an error, the flame relay, and self check relays will open, and the device will display "lock­out". This lockout may only be cleared by manual entry reset at the U2 Touchwheel interface.
Approvals:
Quick disconnect type General FM, CSA, CE (EN298), and EAC
Hazardous Location CSA
CLASS I, DIVISION 2, GROUPS A, B, C, D CLASS II, DIVISION 1, GROUPS E, F, G CLASS III DIVISION 1 T5 Ex nA nC IIC T5 Gc Ex tb IIIC T85°C Db CLASS I, ZONE 2, AEx nA nC IIC T5 Gc ZONE 21 AEx tb IIIC T85°C Db
IECEx SIR 15.0068X Ex nA nC IIC T5 Gc Ex tb IIIC T85°C Db IP66
SIRA 15ATEX4193X Ex nA nC IIC T5 Gc Ex tb IIIC T85°C Dc IP66
32-00015—04 2
U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR
CAUTION
CAUTION
!
CAUTION
CAUTION
!
CAUTION
CAUTION
!
WARNING
WARNING
PF version
General
FM, CSA, CE (EN298), and EAC
Hazardous Location CSA
CLASS I, DIVISION 1, GROUPS A, B, C, D CLASS II, DIVISION 1, GROUPS E, F, G CLASS III DIVISION 1 T6 Ex d IIC T6 Gb Ex tb IIIC T85°C Db CLASS I, ZONE 1, AEx d IIC T5 Gb ZONE 21 AEx tb IIIC T85°C Db
IECEx SIR 15.0068X Ex db IIC T6 Gb Ex tb IIIC T85°C Db IP66
SIRA 15ATEX1192X Ex db IIC T6 Gb Ex tb IIIC T85°C Db IP66
Possible Equipment Damage
The aluminum surface of the U2 may store an electrostatic charge and become a source of ignition in applications with a low (<30%) relative humidity. Cleaning the surface should only be done with a damp cloth.
Do not expose to acetone, gasoline, hexane, or ethyl acetate. label is not approved for these chemicals.
Non-PF/
Color Function Connection
9-Tan File Select Output, 0 or +24V
output. Feedback for system controlling file input select.
10-White +RS485 Modbus To Modbus +
11-Drain Cable Overall Shield To Earth Ground
12-Brown -RS485 Modbus To Modbus -
*Note - pink wire unused, leave unconnected.
Check wiring before applying power to the system to make sure it is in accordance with the wiring chart. Incorrect wiring may result in unsafe operation or damage to U2.
NOTES:
1. For remote configuration and monitoring, refer to Honeywell manuals for FlameTool for PC (32-00001-01) and HMI S7999 Panel (32­00003-01).
2. A total of eight parameter files are available. Files 2 through 7 may be accessed using Fla­metools, and configured using Modbus regis­ter 40093.
To burner control system. 0V = File Select Input is low, or +24V if FileSelect Input is high.

Wiring

See “Typical Installation Diagram.” on page 12.
Non-PF/
Color Function Connection
1-Red Power Supply +24 VDC
Connect to 22-26 VDC
2-Purple File Select Input, 0 or 1 To control output.
3-Orange mA output (+) To current meter
4-Blue mA output (-) To current meter
5-Black Power Supply Return (-) or 0
VDC
6-Yellow Flame Relay (NO)
(power in)
7-Green Fault Relay (NO) (fault output) To fault monitoring of
8-Grey Flame Relay (NO) (safety
output)
To power supply positive terminal
>21V input = file 1, <16V = active file defined at Modbus register 40093(default 0).
positive
negative
To Power Supply negative terminal.
To flame/fault relay power source
burner control system
To burner control system

INSTALLATION

See “Typical Installation Diagram.” on page 12.
Installation should be carried out by a qualified engineer and should meet all local standards and safety requirements.
Hazardous location installations require the use of ITC/CIC approved cable installed in cable tray for non-PF models, and in metal conduit for -PF models. The cable installation must conform to the latest revision of the National Electrical Code, or Canadian Electrical Code for Class I, Division 2 (non-PF models), or for Class I, Division 1 (-PF models).
Approved CLI, DIV1 conduit seal must be installed at PF model enclosure fitting for CLI, DIV1 hazardous location use.
Non-PF models must be secured as follows: hand-tighten the connector at viewing head until it can be turned no more. Continue tightening the connector an additional 180 degrees using pliers, or similar tool. Verify that connector cannot be loosened by hand.
Over-tightening the connector can damage the connector or housing.
Damage will void warranty and hazardous location approvals. Do not exceed 180 degrees of further rotation after hand tightening!
3 32-00015—04
U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR
WARNING
3/4 (19) NPT CONNECTION
2-29/32 (73)
1(25)
1 (25) NPT CONNECTION
5-3/32 (130)
4-19/32
(118)
M34431
R-518-CL12-PG PURGE AIR COUPLER AND R-518-PT12 INSULATING LOCKING COUPLER ADAPTER
BURNER FRONT PLATE OR WINDOWBOX
M33628
1 (25) NPTF PIPE
FLANGE (OPTIONAL)
1. Ensure location provides clear view of the flame under all operating conditions.
EXPLOSION HAZARD DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NONHAZARDOUS.
Substitution of components may impair suitability for class i, division 2.
2. If the burner is provided with a pipe mount, use a bell type reducer to 1" NPT (M).
3. When using purge/cooling air, make sure hoses are electrically isolated from the Earth to prevent multi­ple ground loops.
4. Depending upon the application, purge/cooling air pressure and flow will be different. As it is easier to
The U2-S model viewing port is designed for interface to a 1" NPT (M) fitting. The viewing head can be mounted in any orientation, any angle, upward or downwards.
It is recommended that earth ground is applied at the labeled earth ground screw connection on the housing. It is recommended the drain wire be connected to earth at power supply.
To reduce noise interference from ignition transformer or other high voltage sources, make sure all high voltage cables are in good condition and are at least 300 mm (12") away from U2 wiring.

Location/Mounting on Burner

Honeywell can provide mounting accessories such as a swivel mount, heat/electrical insulator, quick mechanical
measure pressure than flow, ensure that the entrance to air connection is a minimum of 25 mm WC (1" wc) above back pressure at all the time, from minimum to maximum load.
5. IMPORTANT!
FLAME DISCRIMINATION In multi-burner applications, it is important to sight for high frequency, high radiation intensity zone of the target flame, while sighting the low frequency, low radiation intensity zone of the background flame see Fig. 3 for IR, or Fig. 4 for UV for an example. This allows for filter, gain, and threshold settings to prop­erly discriminate or recognize the target flame while rejecting background flame.
6. Where practical, use a swivel mount to allow for adjustments to optimize the flame viewing location.
disconnect, high pressure isolation unit, etc. Check with your sales representative for your application.
Fig. 1. Dimensional drawings.
32-00015—04 4
Fig. 2. Typical mounting example.
U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR
UV VIEWING HEAD SIGHTED ON UV ZONE
BURNER NOZZLE CENTERLINE
UV RADIATION ZONE
M33286B
HIGH FREQUENCY FLICKER ZONE
DETECTOR IN GOOD SIGHTING POSITION (PARALLEL SIGHTING)
BURNER NOZZLE CENTERLINE
LOW FREQUENCY FLICKER ZONE
Fig. 3. IR viewing head location.
DETECTOR IN POOR SIGHTING POSITION
M33285B
Fig. 4. UV viewing head location.
5 32-00015—04
Loading...
+ 11 hidden pages