Français : voir la page 21 • Español: vea la página 41
Wireless control for up to 3 Heat/2 Cool heat pump systems or up to 2 Heat/2
Cool conventional systems.
Installation guide for:
• Wireless equipment interface module
• FocusPRO® wireless thermostats
• Wireless remote control
• Wireless outdoor air sensor
• Return air sensor
DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause
electrical shock or equipment damage.
MERCURY NOTICE: If this product is replacing a control that contains mercury in
a sealed tube, do not place the old control in the trash. Contact your local waste
management authority for instructions regarding recycling and proper disposal.
Must be installed by a trained, experienced technician. Read these
instructions carefully. Failure to follow these instructions can damage the product or
Mount thermostat and outdoor sensor .......................................Page 13
To replace system components if needed, see page 15
For system-specific wiring guides, see pages 16-17
If you have more than one Equipment Interface Module (EIM): Thermostats
are linked to specific EIMs. Optional accessories must be linked to each EIM
separately.
DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical
shock or equipment damage.
69-2091EFS—07 2
Français : voir la page 21 • Español: vea la página 41
1
Mount and wire EIM
Mount EIM on wall near HVAC equipment, or on the equipment itself.
Do not install inside HVAC equipment. Use screws & anchors as appropriate
for mounting surface.
Install EIM
THM5320R
POWER
HEAT
COOL
FAN
Install return air sensor (optional)**
The return air sensor maintains safe
indoor temperature (62° F in Heat, 82° F
in Cool) if thermostat power is lost.
EIM wiring
WIRELESS SETUP
CONNECTED
CONNECT
FLASHING: CONNECTING TO REMOTE DEVICE
GREEN: CONNECTED TO REMOTE DEVICE(S)
RED: REMOTE DEVICE(S) NOT COMMUNICATING
Drill 1/4” hole
(6.4mm)
Install sensor on return air duct at least
12” (305mm) upstream from ventilator,
humidifier or dehumidifier (do not mount
downstream)
** For hydronic applications, use
C7189U1005 Remote Indoor Sensor and
M28467
mount in the living space.
Strip 1/4” insulation, then insert wires
as shown.
Press tabs only to remove wires from
terminal block if necessary.
Wiring must comply with local
electrical codes.
M28468
M28494
M28469
Continued on next page >>
3 69-2091EFS—07
RedLINK TM Installation Guide (EIM)
FURNACE
AIR HANDLER
EIM wiring guide
See detailed wiring guides for specific system
types on pages 16-17.
CONVENTIONAL SYSTEMS
EQUIPMENT INTERFACE MODULE
Jumper
A/B/C/D UNUSED
(reserved for future use)
HEAT PUMP SYSTEMS
EQUIPMENT INTERFACE MODULE
Transformer
24Vac
Air Conditioning
Return air sensor**
** or C7189U1005 Remote indoor sensor for hydronic
24Vac
Stage 1 heat
Stage 2 heat
Fan
Compressor
(Stage 1)
Compressor
(Stage 2)
Transformer
120Vac
M28470
120Vac
Jumper
A/B/C/D UNUSED
(reserved for future use)
69-2091EFS—07 4
Changeover
relay
Backup heat
(gas/electric)
Compressor
(Stage 1)
Compressor
(Stage 2)
Fan Relay
Relay **
Return
Air Sensor
** L terminal sends continuous output when thermostat is
set to EmHeat. L terminal is for use with zone panels.
M28471
Français : voir la page 21 • Español: vea la página 41
2
Install batteries in wireless devices
When system wiring is complete, install batteries in all devices. Make sure
batteries are inserted properly (see polarity marks on illustrations below).
Thermostat
Programmable models only
M28472
Install 2 fresh AA
batteries
M28473
Install quick reference
card
Remote control (optional)Outdoor air sensor (optional)
Install 3 fresh AA
batteries
Install 2 fresh AA
lithium batteries
M28474
M28475
3
Link all devices to wireless network
Press and release CONNECT
Restore AC power, then press and release
M28476
the CONNECT button at the EIM. Wait for
green flashing light to begin linking devic-
es to the wireless network (see pages 6-7).
If the light stops flashing before you have
linked all devices, press CONNECT again.
If light does not flash, another EIM/
wireless adapter may be in wireless setup
mode. Exit wireless setup at the other
EIM/wireless adapter.
M28495
Flashing status light times out after 15
minutes of inactivity. Press CONNECT
again if necessary.
5 69-2091EFS—07
Continued on next page >>
RedLINK TM Installation Guide (EIM)
Link thermostat to wireless network
Zone number
Wireless Setup
0
Wireless Setup
36
0
Next
Zone name
52
Press NEXT (always leave zone number set
to zero).
Zone numbers 1-4 are for use with
TrueZONE panels only.
M28477
Press NEXT (or see page 11 to change the
zone name if needed).
Change zone name only if you have more
than one thermostat and EIM.
Done
Back
Wireless Setup
Back
Wireless Setup
Connected
Next
M28478
Press CONNECT to establish a link to the wireless network.
If E1 appears, see error codes on page 14.
Connect
M28479
After a brief pause, the confirmation screen
at left should be displayed, to verify that the
wireless connection has been established.
Press DONE to display the home screen.
M28480
69-2091EFS—07 6
Français : voir la page 21 • Español: vea la página 41
Link remote control to wireless network (optional)
1 Make sure the Connected light on the
EIM is flashing (see page 5).
2 Press CONNECT at the remote. There will
WIRELESS SETUP
Press to link
another EIM
CONNECT
M28481
Press to save
and exit
be a short delay as the remote seeks a
signal from the wireless network.
3 When the screen displays "Connected,"
press DONE.
4 Press NO at the next screen to save and
exit. (Or press YES and repeat steps 1-4
to link another EIM.)
If E1 appears, see error codes on page 14.
NOYES
CONNECT MORE?
M28482
The linking procedure may time out if there is
no keypress within 30 minutes. To begin again,
press and hold the blank space (or arrow, if
present) in the lower right corner of the screen
until the display changes (about 3 seconds).
Link outdoor sensor to wireless network (optional)
Press and release
1 Make sure the Connected light on the
EIM is flashing (see page 5).
2 Press and release the CONNECT button
on the back of the sensor.
3 Check thermostat to verify that the
outdoor sensor is working. After about
15 seconds, the thermostat should
display outdoor temperature and
humidity.
(If you are installing more than one EIM,
repeat steps 1-3 for each.)
M28483
7 69-2091EFS—07
RedLINK TM Installation Guide (EIM)
4
Exit wireless setup
Press CONNECT at the EIM to exit wireless setup (light should stop flashing).
Note: The EIM will automatically exit wireless setup after 15 minutes of inactivity.
Note: If installing more than one thermostat and EIM, you must exit wireless setup
before installing an additional thermostat and EIM.
5
Customize thermostat (installer setup)
Follow the steps below to begin installer setup. At each function screen, press
s or t to change the setting as desired, then press NEXT to advance to the
next function screen.
See tables on pages 9-11 for a description of options for each function.
FAN
M28485
To begin, press and hold the FAN and s buttons
until the display changes (about 3 seconds).
Function
1
Done
Press DONE to save & exit.
Back
Setting
0
Next
M28487
0
Done
Back
Press s or t to change
setting (see tables on pages
9-11).
Press NEXT to display next
function screen.
0
Next
M28486
69-2091EFS—07 8
Français : voir la page 21 • Español: vea la página 41
Installer setup tables
Setup function Settings & options (factory default in bold)
0 Zone number0 No zoning (single thermostat used with THM5320R EIM)
1 System type0 1 heat/1 cool conventional
2 Changeover valve
(O/B terminal)
3 Fan control
(conventional heat)
4 Backup heat (Aux &
EmHeat)
5 Stage 1 heat cycle
rate (CPH: cycles/
hour)
6 Stage 2 heat cycle
rate (CPH)
7 Stage 3 heat cycle
rate (CPH)
8 Emergency heat cycle
rate (CPH)
9 Stage 1 compressor
cycle rate
10 Stage 2 compressor
cycle rate
11 Heat pump type0 Air to Air Heat Pump
12 Manual/Auto
changeover
13 Adaptive Intelligent
Recovery™
14 Temperature
display
[Options: select zone 1, 2, 3 or 4]
1 1 heat/1 cool heat pump (no aux. heat)
2 Heat only (includes Series 20)
3 Heat only with fan
1 5° F (-15° C) 7 35° F (1.5° C)
2 10° F (-12° C) 8 40° F (4.5° C)
3 15° F (-9.5° C) 9 45° F (7° C)420° F (-6.5° C)10 50° F (10° C)
5 25° F (-4° C) 11 55° F (13° C)
630° F (-1° C)1260° F (15.5° C)
0 No heat pump auxiliary lockout**
1 5° F (-15° C) 8 40° F (4.5° C)
2 10° F (-12° C) 9 45° F (7° C)
3 15° F (-9.5° C) 10 50° F (10° C)420° F (-6.5° C)11 55° F (13° C)
5 25° F (-4° C) 12 60° F (15.5° C)
6 30° F (-1° C) 13 65° F (18.5° C)
7 35° F (1.5° C)
Français : voir la page 21 • Español: vea la página 41
COMPRESSOR AND FAN ONLY
OPTION 0: NO DROOP CONTROL
OUTDOOR TEMP.
OPTION 1: DROOP CONTROL
OPTION 2: DROOP CONTROL WITH AUX HEAT LOCKOUT
Installer setup tables
Setup function Settings & options (factory default in bold)
36 Zone name52 Thermostat
39 Wireless setup0 Disconnect thermostat from wireless system
90 RESET0 No reset
1 Basement16 Exercise Room 30 Library44 Porch
2 Bathroom17 Family Room31 Living Room45 Rec Room
3 Bathroom 118 Fireplace32 Lower Level46 Sewing Room
4 Bathroom 219 Foyer33 Master Bath47 Spa
5 Bathroom 320 Game Room34 Master Bed48 Storage Room
6 Bedroom21 Garage35 Media Room49 Studio
7 Bedroom 122 Great Room36 Music Room50 Sun Room
8 Bedroom 223 Guest Room37 Nursery51 Theater
9 Bedroom 324 Gym38 Office52 Thermostat
10 Bedroom 425 Kid's Room39 Office 153 Upper Level
11 Boat House26 Kitchen40 Office 254 Utility Room
12 Bonus Room27 Kitchen 141 Pantry55 Walk In Closet13 Computer Room 28 Kitchen 242 Play Room56 Wine Cellar
14 Den29 Laundry Room 43 Pool Room57 Workshop
15 Dining Room
1 Thermostat is connected to wireless system
1 Reset installer options & program schedule to factory default settings
Special functions
Heat Pump Control — Electric Backup (Setup Functions 24-25):
55
COMPRESSOR AND FAN OPERATE
1
40
OUTDOOR TEMP.
ELECTRIC BACKUP HEAT AND FAN ONLY
1
IF THE COMPRESSOR CANNOT REACH OR MAINTAIN TEMPERATURE SETTING,
BOTH THE COMPRESSOR AND ELECTRIC BACKUP HEAT WILL OPERATE.
AUXILIARY LOCKOUT
COMPRESSOR LOCKOUT
M28705
Heat Pump Control — Fossil Fuel Backup (Setup Function 18):
Note: If temperature is not reached in a reasonable time, set the upstage to furnace timer
(function 21). After the designated time, the compressor will turn off and the system will switch to
back up heat.
COMPRESSOR AND
COMPRESSOR AND
FAN ONLY
40
FOSSIL FUEL
BACKUP HEAT ONLY
1
IF ROOM TEMPERATURE DROPS (EXCEEDS DROOP SETTING AT FUNCTION 20), COMPRESSOR IS DEACTIVATED. FOSSIL FUEL
BACKUP HEAT IS ACTIVATED AFTER 3 MINUTE DELAY.
**
FOR GEOTHERMAL HEAT PUMPS, THE BALANCE POINT CAN BE DISABLED AT SETUP FUNCTION 24.
Comfort/Economy — Setup Function 26 (Not available when Setup Function 17 is set to 0):
BALANCE
POINT **
FAN OPERATE
1
40
FOSSIL FUEL
OUTDOOR TEMP.
BACKUP HEAT ONLY
BALANCE
POINT **
COMPRESSOR AND FAN ONLY
55
COMPRESSOR AND FAN OPERATE
1
40
OUTDOOR TEMP.
FOSSIL FUEL BACKUP HEAT ONLY
If you choose Comfort, auxiliary heat will respond quickly to meet the temperature setpoint. If you
choose Economy, the system will wait longer. Auxiliary heat will be activated only if the setpoint is
not reached within a reasonable time.
AUXILIARY
LOCKOUT
BALANCE
POINT **
M28706
11 69-2091EFS—07
RedLINK TM Installation Guide (EIM)
System test
Follow the procedure below to test for proper operation.
System test numberSystem status
M28488
To begin, press and hold the s and t buttons
until the display changes (about 3 seconds).
System test System status
02 Wireless test
04 Return air sensor
10 Heating system
20 Emergency heating
system
30 Cooling system
40 Fan system
70 Thermostat information
(for reference only)
0 Off
1 Test radio signal (after a brief pause, screen displays 1-10 to show
signal strength; 5 or higher recommended)
Screen displays return air temperature if device is installed and
working properly
0 Heat and fan turn off.
1 Heat turns on
2 Stage 2 heat turns on
3 Stage 3 heat turns on
0 Heat and fan turn off
1 Heat and fan turn on
0 Compressor and fan turn off
1 Compressor and fan turn on
2 Stage 2 compressor turns on
0 Fan turns off
1 Fan turns on
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
02
Done
Press s or t to check system status
Press NEXT to advance to next test
Press DONE to terminate system test
Back
0
Next
M28489
CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection (minimum
off time) is bypassed during testing. To prevent equipment damage, avoid cycling
the compressor quickly.
69-2091EFS—07 12
Français : voir la page 21 • Español: vea la página 41
6
Mount thermostat & outdoor sensor
3/16" holes for drywall
7/32" holes for plaster
Wall anchor
Detach wallplate
Wallplate
Outdoor sensor (optional)
Mount the sensor on
a vertical exterior wall,
at least 6 inches below
any overhang. Choose a
location protected from
direct sunlight.
Mounting screw
M28490
Place sensor securely
in bracket, facing
M28491
away from wall.
Press and release
M28492
To check location before mounting: Restore
thermostat Home screen, then hold the sensor
where you intend to install it and press the
CONNECT button. If sensor is working properly,
thermostat will switch to display outdoor
temperature and humidity.
M28483
13 69-2091EFS—07
RedLINK TM Installation Guide (EIM)
EIM status lights
When installation is complete, check the status lights on the equipment
interface module to verify proper operation.
System status lights
• Power: EIM is working properly.
• Heat: Heating system is on.
• Cool: Cooling system is on.
• Fan: Fan is on.
Note: If connected light is flashing, press
CONNECT button to turn off flashing light, then
recheck status lights.
Wireless status lights
• Solid green: EIM is working properly
and communicating with wireless
devices
• Flashing green: Linking to wireless
devices (light flashes for 15 minutes
after you press CONNECT).
• Solid red: Communication problem.
M28496
Check EIM and wireless devices.
Error codes (thermostat & remote control)
If E1 or E appears, check error code number (right side of screen):
23EIM does not have dual fuel capability. Replace EIM if you have fossil fuel
backup heat or change Installer Setup Function 4 to ELECTRIC if you have
electric backup heat (see pages 8-10).
29Attempting to connect incompatible wireless devices.
30 Invalid zone number. Zone number must be set to zero (see page 6).
33Check Return Air Sensor wiring. If removing the sensor permanently, press and
hold the CONNECT button on the EIM for 10 seconds (until flashing orange) to clear
this error code. See page 15, then pages 5-8 to reconnect wireless devices.
34Low signal strength. Move wireless device to a different location and try again.
38 Make sure Connected light on EIM is flashing and you are 2+ feet away from EIM.
53Thermostat is not receiving Outdoor Temperature and Outdoor Humidity:
1. Thermostat may be configured for dual fuel, compressor lockout or auxiliary
lockout with no outdoor sensor. Follow Wireless Setup procedure to connect
outdoor sensor to the EIM (see pages 5 and 7).
2. If E53 continues, outdoor sensor may not be communicating. Install 2 fresh AA
Lithium batteries in the outdoor sensor.
69-2091EFS—07 14
Français : voir la page 21 • Español: vea la página 41
Replacing system components
Thermostat
To replace a thermostat, install batteries and follow the procedures on pages 5-6
to link it to the wireless network. If necessary, modify settings as needed (see
tables on pages 9-11).
Remote control & outdoor sensor
To replace a remote control or outdoor air sensor, install batteries and follow the
procedures on pages 5-7 to link it to the wireless network.
Equipment interface module (EIM)
After installing a new EIM, you must re-set the thermostat and remote control to
communicate with the new EIM, as described below.
At the thermostat:
1 Press and hold the FAN and s buttons for 3 seconds.
2 Press BACK twice to display Function 39 (wireless setup).
3 Press t to change Function 39 setting to 0 (disconnect from old EIM).
4 Follow the procedures on pages 5-6 to link to new EIM.
At the remote control:
1 Press and hold the blank space (or arrow if present) in the lower right
corner of the screen until the display changes (about 3 seconds).
2 Press REMOVE, then YES to disconnect from old EIM.
3 Follow the procedure on page 7 to link to new EIM.
Press and hold for
about 3 seconds.
15 69-2091EFS—07
RedLINK TM Installation Guide (EIM)
System-specific wiring guides
Conventional systems
1H/1C System (1 transformer)
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
W Heat relay
Y Compressor contactor
G Fan relay
Heat-only System [3]
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
W Heat relay
Heat-only System (Series 20) [3]
C 24VAC common
R Series 20 valve terminal "R" [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
W Series 20 valve terminal "B"
Y Series 20 valve terminal “W”
Heat-only System
(normally open zone valve) [3]
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
Y Normally open zone valve
Heat Only System With Fan [4]
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
W Heat relay
G Fan relay
See [notes] on next page.
Cool Only System [5]
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
Y Compressor contactor
G Fan relay
1H/1C System (2 transformers)
C 24VAC common
R Power [1]
Rc Power (cooling) [1, 2]
Rh Power (heating) [1, 2]
W Heat relay
Y Compressor contactor
G Fan relay
2H/2C System (1 transformer) [6]
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
W Heat relay (stage 1)
W2 Heat relay (stage 2)
Y Compressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
G Fan relay
2H/2C System (2 transformers) [6]
C 24VAC common
R Power [1]
Rc Power (cooling) [1, 2]
Rh Power (heating) [1, 2]
W Heat relay (stage 1)
W2 Heat relay (stage 2)
Y Compressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
G Fan relay
69-2091EFS—07 16
Français : voir la page 21 • Español: vea la página 41
System-specific wiring guides
Heat pump systems
1H/1C Heat Pump [8]
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
O/B Changeover valve [7]
Y Compressor contactor
G Fan relay
2H/1C Heat Pump [9]
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
O/B Changeover valve [7]
Aux Auxiliary heat relay
Y Compressor contactor
G Fan relay
L Relay [12]
See [notes] below.
2H/2C Heat Pump [10]
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
O/B Changeover valve [7]
Y Compressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
G Fan relay
3H/2C Heat Pump [11]
C 24VAC common
R Power [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
O/B Changeover valve [7]
Aux Auxiliary heat relay
Y Compressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
G Fan relay
L Relay [12]
[1] Power supply. Provide disconnect means and overload protection as required.
[2] Remove jumper (Rc to Rh) for systems with two transformers.
[3] In Installer Setup, set system type to Heat Only.
[4] In Installer Setup, set system type to Heat Only with Fan.
[5] In Installer Setup, set system type to Cool Only.
[6] In Installer Setup, set system type to 2 Heat/2 Cool Conventional.
[7] In Installer Setup, set changeover valve to O or B.
[8] In Installer Setup, set system type to 1 Heat/1 Cool Heat Pump.
[9] In Installer Setup, set system type to 2 Heat/1 Cool Heat Pump.
[10] In Installer Setup, set system type to 2 Heat/2 Cool Heat Pump.
[11] In Installer Setup, set system type to 3 Heat/2 Cool Heat Pump.
[12] “L” terminal sends a continuous output when thermostat is set to Em. Heat. Connect
to zoning panel and switch to Emergency Heat.
17 69-2091EFS—07
RedLINK TM Installation Guide (EIM)
Specifications & replacement parts
Operating Ambient Temperature
Thermostat: 32 to 120° F (0 to 48.9° C)
Remote control: 32 to 120° F (0 to 48.9° C)
EIM: -40 to 165° F (-40 to 73.9° C)
Outdoor air sensor: -40 to 140° F (-40 to 60° C)
Return air sensor: 0 to 200° F (-17.8 to 93.3° C)
Operating Relative Humidity
Thermostat: 5% to 90% (non-condensing)
Remote control: 5% to 90% (non-condensing)
EIM: 5% to 95% (non-condensing)
Outdoor air sensor: 0% to 100% (condensing)
Physical Dimensions (height, width, depth)
Thermostat: 3-9/16 x 5-13/16 x 1-1/2 inches (91 x 147 x 38 mm)
EIM: 8-1/8 x 8 x 1-7/8 inches (206 x 203 x 47 mm)
Outdoor air sensor: 5 x 3-1/2 x 1-11/16 inches (127 x 89 x 43 mm)
Return air sensor: 3-7/8 x 4-1/8 x 1-1/4 inches (77 x 102 x 25 mm)
Sensor probe is 3-3/4 inches long (77 mm)
Electrical Ratings (EIM)
Terminal Voltage (50/60Hz) Running Current
W (heating) 18-30 VAC 1.00A
Y (cooling) 18-30 VAC 1.00A
G (fan) 18-30 VAC 0.60A
O/B (changeover) 18-30 VAC 0.60A
W2 (heating) 18-30 VAC 0.60A
Y2 (cooling) 18-30 VAC 0.60A
Aux/E (auxiliary) 18-30 VAC 1.00A
L (output) 18-30 VAC 0.60A