Honeywell th511od Installation Instructions Manual

Honeywell
TH5110DNon-programmable
Thermostat
APPLICATION
The TH511OD Non-programmable Thermostat provides electronic control of 24 Vac, single-stage heating and
cooling systems or 750 mV heating systems. See Table 1
Table 1,TH5110D Thermostat description.
Feature Description
Powering Methods Battery only
Common wire only
Common wire with battery backup
System Types (Up to 1 Heat, 1 Cool) Gas, oil or electric heat with air conditioning
Warm air, hot water, high efficiency furnaces, heat pumps, steam
and gravity Heat only-- includes power to open and power to close zone valves
(Series 20) and normally-open zone valves Heat only with fan Cool only
750 mV heating systems
Changeover Manual or auto changeover selectable
System Setting Heat-Off-Cool-Auto Fan Setting Auto-On
MERCURYNOTICE
tf this control is replacing a control that contains mercury in a sealed tube, do not place your old
control in the trash.
Contact your local waste management authority for instructions regarding recycling and the
proper disposal of the old thermostat.
¢_)U.S. Registered Trademark Copyright © 2004 Honeywell International inc. ° _ AN Rights Reserved 69-171211
TH5f10D NON-PROGRAMMABLE THERMOSTAT
INSTALLATION
When installing this product...
1. Read these instructions carefufly. Failure to follow these instructions can damage the product or
cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
CAUTION
Electrical Hazard. Can cause electrical shock or equipment
damage.
Disconnect power before beginning installation.
Select ThermostatLocation
Select a _ocation for the thermostat about 5ft (1.5m) above the floor in an area with good air circulation at
average temperature. See Fig. 1.
YES
FEET
[1 5 METER'S]
l
Fig. 1. Select thermostat location.
Do not install the thermostat where it can be affected by:
-- Drafts or dead spots behind doors and in corners.
-- Hot or cold air from ducts.
-- Radiant heat from sun or appliances.
-- Concealed pipes and chimneys.
-- Unheated (uncooled) areas such as an outside wall behind the thermostat.
SeparateWallplate from Thermostat
1. Separate the wallplate from the thermostat. See Fig. 2.
THERMOSTAT
Fig. 2. Separate wallplate from thermostat.
Install Wallplate (See Fig.3.)
Mount the thermostat hofizontafly on the wall:
1. Pull the wires through the wire hole on the
wallplate.
2. Position the waIIplate on the wall with the arrow pointing up. Level the waflplate for appearance
only.
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and drill
two 3/16-in. holes in the wall (if drywall) as marked.
For firmer material such as plaster, drill two 7/32-in. holes. Tap the wall anchors (provided) into the
drilled holes until flush with the wall.
5. Pull the wires through the wire hole on the
wallplate and position the wallplate over the wall anchors.
6. insert the mounting screws into the watl anchors
and tighten.
SCREWS (2) M22!40
Fig. 3. Install watlplate.
69-1712--1 2
TH51 f OD NON-PROGRAMMABLE THERMOSTAT
WIRING
All wiring must comply with local electrical codes and ordinances. Refer to Table 2 for descriptions of terminal
designations. See Fig. 6-13 for wiring diagrams for specific equipment applications.
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
IMPORTANT
Use f8-22 gauge thermostat wire. Shielded
cable is not required.
1, Loosen the screw terminals that are used for the
application, insert the wires into the terminal block and tighten each screw terminal. See Fig. 4.
2. Push excess wire back into the wall opening and restrict wires to the shaded area. See Fig. 5.
WALLPLATE WALL OP ENING
WIRE
M22!42
TERMINAL BL
LETTER
Fig. 5. Restrict wires to shaded area of wire hole.
3. Plug the wail opening with nonflammable insulation
to prevent drafts from affecting the thermostat.
Fig. 4. Insert wires into terminal block.
Table 2. Terminal designation descriptions.
Terminal
Designation Description
Rc (see Note t) Power for cooling--connect to secondary side of cooling system transformer R (see Note 1) Power for heating--connect to secondary side of heating system transformer Y Compressor contactor C (see Note 2) Common wire from secondary side of cooling system transformer
O/B W (see Note 3) Heat relay or changeover valve terminal for heat pumps G Fan relay
NOTES:
1.
When used in a single-transformer system, leave metal jumper in place between Rc and R. If used on a two-transformer system, remove metal jumper between Rc and R.
Common wire is optional when thermostat is used with batteries.
If thermostat is configured for a heat pump in the Installer Setup, configure changeover valve
for cool (O-factory setting) or heat (B).
3 69-1712--I
TH5f10D NON-PROGRAMMABLE THERMOSTAT
WIRING DIAGRAMS
H]ERMOS[A[ WRNG TERM NALS
C (HOT}
Z_ POWER SU;_Y ;ROV_DE D SCONNEC[ MEANS AND OVERLOAD
Z_ >OWER SUPPLY PROV DE O SCONNECF MEANS AND
M220_S
Fig. 6. Typical hookup of conventional 1H/1C system
with one transformer.
Z_ CONf GURE SYST_:M [YPE FO dEAF PUMPAND CHANGEOVER
VALVE TO E_THER O OR 8 _N THE _NSTALLER SETUP¸ M220_0
Fig. 8. Typical hookup of 1H/1C heat pump.
A POWER SUP _LY PROV DE D SCONNEC]" MEANS AND OVERLOAD
Fig. 7. Typical hookup of conventional 1H/1C system
with two transformers.
IA
_ POWER SUPPLY PROV DE D_SCONNEC[ MEANS AND
Fig. 9. Typical hookup of heat only system.
69-1712--1 4
Loading...
+ 8 hidden pages