Honeywell T915 Product Information Sheet

Proportional Temperature
Remote bulb temperature controllers for ducts, tanks, boilers, pipes, and other heat exchangers. These controllers are used with modulating motors for proportional control of three-wire, low-voltage valves or damper motors.
T915A-D,F,M,P
Controllers
T915M and T915P have spdt switches to control Series
20 motors. T915M controls at high or low end; T915P controls at low end.
Controllers may be used to regulate temperatures of
either air or liquids.
All models ambient compensated.
Capillary tubing allows remote bulb mounting up to 20 ft
(6.0m) from controller case.
Temperature setting scale markings in both Fahrenheit
and Celsius.
Steel case with clear plastic cover makes settings readily
visible.
Surface mounting using two screws through back of case.
CONTENTS
Specifications .................................................2
Ordering Information.....................................2
Installation .....................................................4
Operation .......................................................6
Settings and Adjustments................................6
1 60-2201—7S. M. • Rev. 10-94 • ©Honeywell Inc. 1994 • Form Number 60-2201—7
T915A-D,F,M,P SPECIFICATIONS • ORDERING INFORMATION
Specifications
MODELS (also refer to Table 1):
T915A: One potentiometer for controlling a modulating
motor. Nonadjustable throttling range.
T915B: Two potentiometers for controlling two mod-
ulating motors in unison or in sequence, factory set for unison control. Nonadjustable throttling range.
T915C: One potentiometer for controlling a modulating
motor. Adjustable throttling range.
T915D: Two potentiometers for controlling two modu-
lating motors in unison. Adjustable throttling range.
T915F: Two potentiometers for controlling two mod-
ulating motors in sequence. Adjustable deadspot be­tween potentiometers and adjustable throttling range.
T915M and T915P: One potentiometer and Series 20
contacts for controlling one modulating motor and one
Fig. 1—Mounting dimensions in in. (mm).
2-3/4 (70)
1-1/16 (27)
5-1/32 (128)
3-7/8 (98)
5-1/2 (140)
13/16 (21)
7/8 (22.2) DIA.
13/16 (21)
Series 20 motor or relay in sequence on a temperature rise. The Series 20 contacts on the T915M operate above the throttling range and the Series 20 contacts on the T915P operate below the throttling range. Both models have nonadjustable throttling ranges and dif­ferentials.
BULB HOLDER: Furnished with copper elements. RANGES: Fahrenheit and Celsius on the same scaleplate. TEMPERATURE SETTING: Screws on top of controller
provide main and differential adjustment. ELECTRICAL RATING: Low voltage ac only. POTENTIOMETER: Standard 135 ohm. Available with
280 ohm potentiometer in some models; see Table 1. FINISH: Gray enamel. DIMENSIONS: See Fig. 1.
4-1/2 (114)
3-13/32
MOUNTING HOLE KNOCKOUTS (2)
3-23/32 (95)
1-3/32 (28)
1-13/16 (46)
(87)
1-5/32 (29)
1-3/16 (30)
M7358
Ordering Information
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE Catalog or price sheets for complete ordering number, or specify—
1. Order number. 4. Capillary length.
2. Scale range. 5. Accessories, if desired.
3. Bulb size.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory).
2. Home and Building Control Customer Logistics Honeywell, Inc., 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P2V9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
®
60-2201—7 2
T915A-D,F,M,P
SPECIFICATIONS
ACCESSORIES:
1. 33312B Knurled Knob for finger adjustment of temp-
erature setpoint.
2. 311266D Bulb Holder for mounting sensing bulb in an
3. Immersion well assemblies or pressure fittings—see appropriate Honeywell specification or TRADELINE Catalog to order. Wells available in copper and stainless steel.
air duct (furnished with some models).
TABLE 1—T915 TEMPERATURE CONTROLLER MODELS.
Maximum
Model
Number °F °C °F °C °F °C ft m in. mm Fill
T915A 15 to 90 -9 to +32 3,
T915B 15 to 90 -9 to +32 3,
T915C 15 to 90 -9 to +32 7 to 38 3.9 to
T915C 15 to 90 -9 to +32 7 to 38 3.9 to
T915C 15 to 90 -9 to +32 7 to 38 3.9 to
T915C 15 to 90 -9 to +32 7 to 38 3.9 to
T915C 15 to 90 -9 to +32 7 to 38 3.9 to
T915C 80 to 210 27 to 99 6 to 32 3.3 to
T915C 80 to 120 27 to 99 6 to 32 3.3 to
T915D 15 to 90 -9 to +32 7 to 38 3.9 to
T915D 15 to 90 -9 to +32 7 to 38 3.9 to
T915D 105 to
T915F 15 to 90 -9 to +32 8 to 52 4.4 to
T915F 15 to 90 -9 to +32 8 to 52 4.4 to
T915Me15 to 90 -9 to +32 3,
T915M 105 to
T915Pf15 to 90 -9 to +32 3,
a
Throttling range adjustable except where noted.
b
LTD—Limited-fill elements require that controller, including all of capillary (except bulb and adjacent 4 in. [102 mm] of capillary), be in an ambient temperature at least 10°F (5.6°C) above bulb temperature. These controllers become inoperative when temperature of controlled air or liquid is above 120°F (49°C). HT—High-temperature-fill elements require that controller and all of capillary (except bulb and adjacent 4 in. [102 mm] of capillary) be in an ambient temperature at least 10°F (5.6°C) below bulb temperature. CA—Cross ambient.
c
Wiper moves toward W on temperature rise.
d
Factory set for unison control.
e
Spdt contacts operate approximately 1°F (0.6°C) above the throttling range (0.5°F [0.3°C] differential at midscale).
f
Spdt contacts operate approximately 1°F (0.6°C) below the throttling range (0.5°F [0.3°C] differential at midscale).
Scale
Range
40 to 105 9 to 39 5.0 to
220
40 to 105 3,
220
fixed
fixed
fixed
fixed
fixed
Throttle
Range
c
f
c
c
c
a
1.7,
fixed
1.7,
fixed
21.1
21.1
21.1
21.1
21.1
17.8
17.8
21.1
21.1
21.7
28.9
28.9
1.7,
fixed
1.7,
fixed
1.7,
fixed
Bulb
Temp -
erature
200 93 5 1.5 1/2 x 4 13 x 102 LTD 135 1 modulating
c
130 54 5 1.5 11/16 x
f
200 93 11 3.4 1/2 x 4 13 x 102 LTD 135 1 modulating
200 93 20 6.1 1/2 x 4 13 x 102 LTD 135
130 54 5 1.5 11/16 x
130 54 15 4.5 11/16 x 7 17 x 177 CA 135
130 54 5 1.5 11/16 x
230 110 5 1.5 1/2 x 4 13 x 102 HT 135
230 110 20 6.1 1/2 x 4 13 x 102 HT 135
130 54 5 1.5 11/16 x
130
240 116 5 1.5 1/2 x 4 13 x 102 HT 135
130 54 5 1.5 11/16 x
130
130 54 5 1.5 11/16 x
c
240
c
130 54 5 1.5 11/16 x
c
Capillary
(Copper) Size of Bulb
54 20
54 20
116 5
6.1 11/16 x
6.1 11/16 x
1.5 1/2 x 4 13 x 102 HT 135 Series 20 motor
Type
17 x 368 CA 135 2 modulating
14-1/2
17x 368 CA 135
14-1/2
17 x 368 CA 280
14-1/2
17 x 368 CA 135 2 modulating
14-1/2
17 x 445 CA 135 unison
17-1/2
17 x 368 CA 135 2 modulating
14-1/2
17 x 445 CA 135 sequence
17-1/2
17 x 368 CA 135 1 modulating
14-1/2
17 x 368 CA 135
14-1/2
of
Potenti -
ometer
Resistance
b
(ohms) Controls
motor
motors in unison or sequence
motor
motors in
motors in
motor and 1
or relay
®
d
3 60-2201—7
T915A-D,F,M,P INSTALLATION
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Disconnect the power supply before connecting wiring to prevent electrical shock and equipment damage.
MOUNTING
Locate the bulb where it will sense the average tempera-
ture of the controlled air or liquid.
Mount the case and the bulb of these controllers within 2 ft (0.6m) above or below each other. If the case is more than 2 ft (0.6m) above or below the bulb, the calibration can change (Fig. 2). The controller case mounts on a wall or panel using the two screws through the knockouts on the rear of the case. Bulb mounts with a bulb holder, pressure fitting or immersion well assembly.
When running the capillary tubing, avoid kinks by mak­ing sure all bends have at least 2 in. (51 mm) radius. Kinking the tubing renders the controllers inoperable. Leave any excess tubing coiled under the controller case.
A bulb holder for mounting the bulb in an air duct is furnished with models having copper elements. If the in­stallation requires a pressure tight fit, use a pressure fitting (Figs. 3 and 4).
If the bulb is located in an agitated liquid, support it firmly or protect it with a separable well (Fig. 5). Refer to the TRADELINE® Catalog for more detailed information on accessories.
Mount low temperature controller where the case and the capillary tubing are always warmer than the bulb; mount high temperature controllers where the case and capillary tubing are colder than the bulb.
When these instructions are followed, ambient tempera­ture will not affect temperature control point.
Fig. 2—Installation of control and sensing element.
TANK OR DUCT WALL
CAPILLARY TUBING
WASTE NUT
BULB (CAPSULE)
PRESSURE FITTING
Fig. 3—Assembly of pressure fitting.
1/2 IN. (13mm) PIPE THREAD FOR 1/2 IN. (13mm)CAPSULES 3/4 IN. (19mm) PIPE THREAD FOR 11/16 IN. (17mm) CAPSULES
BOILER PLUG
CAPILLARY TUBING
COMPOSITION DISK (SLOTTED)
M7357
60-2201—7 4
PACKING NUT
SLOTTED WASHERS ASSEMBLED IN PAIRS THUS-
M7354
T915A-D,F,M,P
INSTALLATION
Fig. 4—Use of bulb holder for mounting
sensing element in air duct application.
Dimensions in in. (mm).
THERMOMETER BULB
14
ADJUSTABLE
CONTROLLER BULB
2-1/4 x 2-1/4 (57 x 57) APPROXIMATE HOLE IN DUCT FOR INATALLATION
3-1/4 (83)
2-3/4 (70)
ACCESS HOLE
1-5/8 (41)
3-1/4 (83)
1-3/8 (35)
RUBBER GROMET
NO. 8 SHEET METAL MOUNTING SCREWS (2)
Fig. 5—Use separable well for mounting
sensing bulb in an agitated liquid.
PACKING NUT
TUBING
COMPOSITION DISK
FITTING (INCLUDING WELL)
SLOTTED BRASS WASHERS (4) (SLOTS 180 DEGREES APART)
FITTING
MINIMUM INSERTION LENGTH
APPROXIMATELY 4-3/4 IN. (121mm)
BULB
SPRING CLIPS (2)
M7355
BULB
Fig. 6—Typical heating connections for T915A,C. For cooling, reverse B and W at motor.
SERIES 90 MOTOR
R
W
B
T915A,C
1
POWER SUPPLY
R
T
W
T
B
PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
Fig. 7—Typical connections for T915B,D and F.
POWER SUPPLY
SERIES 90 MOTOR
1
R
W
B
R
T
W
T
B
PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
R
W
B
T915B,D,F
R
W
B
SERIES 90 MOTOR
T
T
POWER SUPPLY
M7362
M7364
1
TUBING
SPRING CLIP
INSERTION LENGTH
APPROXIMATELY 3-3/8 IN. (86mm)
M7356
WIRING
Disconnect the power supply before connecting wiring to prevent electrical shock and equipment damage. All wiring must agree with local codes, ordinances, and regula­tions.
There are two 7/8 in. knockouts for 1/2 in. conduit on the right side of the case. When wiring, refer to the instructions packed with the motor or valve and the following typical wiring hookups (Fig. 6 through 8). Refer to Fig. 9 for internal schematics of T915 controllers.
NOTE: Connect B models, which control two motors or
valves in sequence on a temperature rise, so that the first
motor or valve to operate is connected to the front poten-
tiometer terminals (Fig. 7). Connect F models when used
in the above application so that the first operator is
connected to the rear potentiometer.
Fig. 8—Typical connections for T915M and P.
POWER SUPPLY
SERIES 90 MOTOR
1
R
SERIES 20 TERMINALS
R
T
W
T
B
PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
W
B
R
W
B
T915M,P
R
W
B
SERIES 20 DEVICE
SERIES 90 TERMINALS
T
T
1
POWER SUPPLY
M7363
5 60-2201—7
T915A-D,F,M,P INSTALLATION • OPERATION • SETTINGS AND ADJUSTMENTS
Fig. 9—Internal schematics of T915 temperature controllers.
BACK POTENTIOMETER
R
W
B
T915A,C
FRONT POTENTIOMETER
T915B,D,F T915M,P
Temperature changes at the remote sensing bulb cause a pressure change within the bulb and capillary of the T915 Proportional Temperature Controller. This pressure change is transmitted to the bellows inside the controller case that operate the potentiometer wiper. Proportional control of a valve or damper is obtained.
R
W
B
R
W
B
SERIES 20 CONTACTS
BACK POTENTIOMETER
R
W
B
R
W
B
M7361
Operation
Operation of T915M and P models is the same except that at the high or low end of the proportioning range (depending on the model), an spdt switch is used to operate a Series 20 system component.
Settings and Adjustments
TEMPERATURE SETTING
Set the main scale setting at the desired temperature on all models except C,D, and F; set those models so the main scale indicator is at the low end of the desired proportioning range.
The T915B is factory set for simultaneous operation and is adjustable to full sequence. Depending on the setting, the first operator may complete its full cycle or any portion before the second operator starts.
Adjustable proportional ranges (differentials) on T915C,D, and F are additive to the main scale setting. The T915D is designed for simultaneous operation and has no sequence adjustment. The T915F is factory set for se­quence operation and has a deadspot equal to about one­third of the proportional range. This deadspot cannot be increased, but it can be set to zero or to a partial overlap.
The T915M and P have one potentiometer and a set of Series 20 contacts for controlling one Series 90 operator and a Series 20 motor or relay in sequence.
The T915M contacts operate above the proportioning range about 1°F (0.6°C); the T915P contacts operate be­low the proportioning range. Both models have non­adjustable proportional ranges (Series 90) and differen­tials (Series 20).
Turn the adjustment screw (Fig. 10) until the indicator is opposite the desired mark on the scaleplate.
Fig. 10—Internal view of T915F (see Specifica­tions for differences between models).
TEMPERATURE SETTING INDICATOR
DIFFERENTIAL (PROPORTIONAL RANGE) SETTING INDICATOR
TEMPERATURE ADJUSTMENT SCREW
PROPORTIONAL RANGE ADJUSTMENT SCREW
BELLOWS HOUSING
POTENTIOMETER COIL(S)
SLIDING CONTACTS
WIRING TERMINALS
DEADSPOT (ECCENTRIC) ADJUSTMENT SCREW
OPERATING LEVER
M7360
60-2201—7 6
T915A-D,F,M,P
SETTINGS AND ADJUSTMENTS
PROPORTIONAL RANGE (Differential) SETTING
Refer to proportional range curve, Fig. 11.
1. If this graph covers the scale and proportional ranges
of your controller, refer to the graph and read as follows:
a. Locate the horizontal line that represents the desired
main scale temperature setting of the controller.
b. Locate the vertical line that represents the desired
proportional range setting. c. Determine the point at which the lines intersect. d. The relation of this point to the proportional range
setting curves, labeled at the top of the graph, deter-
mine the proportional range indicator setting. Thus, if
the point lies between curve A and curve B, turn the
proportional range adjustment screw (Fig. 10) until
the proportional range indicator is between A and B on
the scaleplate.
2. If the controller model being installed is not covered
by this graph, use a trial and error method:
a. Refer to the graph in Fig. 11. b. Select a tentative setting by following steps 1.a through
1.d.
c. Run a test to determine the direction for further adjust-
ment.
NOTE: Too narrow a proportional range may make the sy-
stem unstable. Increase the range to stabilize the system, remembering that increasing the proportional range also increases offset (control point rise at very light load and drop at very heavy load).
Fig. 11—Proportional range curve for T915 with 15°F to 90°F (minus 9°C to plus 32°C) scale range.
PROPORTIONAL RANGE SETTING
F
C
MIN A
B
90
30
80
CDEF
ADJUSTMENT OF SEQUENCE OPERATION (T915B)
1. For simultaneous operation, no adjustment is required.
2. (On a temperature rise, the front wiper sweeps a portion of the active windings of its potentiometer before the back wiper enters the active windings of its potentiometer.) For operation with partial overlap of wiper travel, turn the eccentric screw to the left an amount proportional to the desired overlap of wiper travel. For example, if on a tempera­ture rise, the back wiper is to enter its active windings after the front wiper has swept one-half of its active windings, turn the eccentric screw to the left one-half as far as it will go.
3. (On a temperature rise, the front wiper leaves the active windings of its potentiometer as the back wiper enters the active windings of its potentiometer.) For se­quence operation, turn the eccentric screw to the left as far as it will go.
4. For sequence operation with a deadspot equal to one-third of the overall proportioning range, no adjust­ment is required.
5. For sequence operation without deadspot or with a deadspot of less than one-third of the overall proportion­ing, turn the eccentric screw to the left. Turning the eccentric screw three-fourths of its full travel to the left will reduce the deadspot to zero. Turning the eccentric screw less than three-fourths of its full travel will reduce the deadspot proportionally.
6. (Front wiper enters the active windings of its poten­tiometer before the back wiper leaves the active windings of its potentiometer.) For operation with partial overlap of wiper travel, turn the eccentric screw to the left as far as it will go.
70
20
60
50
10
40
0
30
MAIN SCALE SETTING – DEGREES
20 15
–10
01020304050
051015 20 25
PROPORTIONAL RANGE – DEGREES
F
C
M7365
7 60-2201—7
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Home and Building Control Home and Building Control Helping You Control Your World
Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario
M1P 2V9
60-2201—7 8
Printed in U.S.A.
QUALITY IS KEY
Loading...