Application
A Radiator Thermostat is installed onto a Thermostatic Radiator Valve Body (TRV body). The combination of both, the
Thermostatic Radiator Valve (TRV), controls the room temperature by adjusting the flow of hot water through a radiator.
TRVs are installed in water-based heating systems on the
supply or, less commonly on the return connection of radiators.
3
4
2
1
5
Radiator thermostats of this type fulfill the European Standard
EN 215 when used with certified Honeywell TRV bodies.
Honeywell radiator thermostats with Honeywell (HW) M30 x 1.5
connection are suitable for all TRV body and radiator inserts
with M30 x 1.5 connection and 11.5 mm closing dimension.
Radiator Thermostats of this type with snapring (DA) type
connection are suitable for TRV bodies and valve inserts with
Danfoss (RA) type compatible snap connection.
3
4
2
5
1
Design
The radiator thermostat consists of:
• Handwheel with socket
• Honeywell HW M30 x 1.5 connection and 11.5 mm closing
dimension or
Danfoss snapring RA type connection
• Sensor with support cage
• Spindle assembly
• Connection nut
Materials
• Handwheel, lid and socket made of plastic, white to RAL9016
• Socket, support cage and spindle assembly made of plastic
• Sensor filled with liquid or wax
• Connection nut made of nickel-plated brass
Features
• Conforms with M30 x 1.5 connection to European standard EN 215
• Available with liquid- or wax sensor
• Equipped with easy to use range stoppers
• Modern ergonomical design
Specifications
Thermostat
connection
Setpoint range 0 - ❄ - 1..5 (with zero-position)
Temperature range 1...26°C (34...79°F)(with zero-position)
Closing dimension 11.5 mm HW type
NOTE: Zero-position is also thermostatically controlled -
when temperature falls the TRV may open.
M30 x 1.5 HW type or
Snap connection DA type
❄ - 1..5 (without zero-position)
6...28°C (43...82°F)(without zero-position)
Function
Radiator thermostats of this type control the TRV body. The air
passing around the sensor of the radiator thermostat causes
the sensor to expand when the temperature rises. The
expanding sensor closes the TRV accordingly. When the room
temperature changes the TRV opens or closes proportionally.
Only the amount of water required to maintain the room temperature set on the radiator thermostat is allowed to flow through
the valve.
Honeywell y Subject to change EN0H-2003GE25 R0109
T9000 SERIESTHERA-2
Dimensions and Ordering Information
ø
H
H
35
98
Fig. 1. Thera-2 with internal sensor Fig. 2. Thera-2 with remote sensor
Table 1. Dimensions
Type H closed H open Ø L
Thera-2 (Fig. 1.) 82.5 88.5 52 Thera 2 DA (Fig. 1.) 90.0 96.0 52 Thera-2 with remote sensor (Fig. 2.) 82.5 88.5 52 0.8 - 2.0 - 5.0 m
NOTE: All dimensions in mm unless stated otherwise.
Table 2. Available versions and OS-Nos (OS=Ordering Specification)
Type EN215
certification
Zero-
position
(’0’)
Connection Capillary
tube
length
Colour Cap OS-No.
Thera-2 and Thera-2-DA with internal sensor
Liquid sensor • M30 x 1.5 - white MNG T9001
• • M30 x 1.5 - white MNG T9001W0
• • M30 x 1.5 - white Honeywell T9001W0H
DA type - white MNG T9001DA
DA type - white Honeywell T9001DAH
• DA type - white MNG T9001DAW0
• DA type - white Honeywell T9011DAW0H
Eastern European
version
• M30 x 1.5 - white MNG T9001HP
• • M30 x 1.5 - white MNG T9001HPW0
Wax sensor • M30 x 1.5 - white MNG T9002
• • M30 x 1.5 - white MNG T9002W0
• • M30 x 1.5 - white Honeywell T9002W0H
Thera-2 and Thera-2-DA with remote sensor
Liquid sensor M30 x 1.5 0.8 m white MNG T900108
• M30 x 1.5 2.0 m white MNG T900120
M30 x 1.5 5.0 m white MNG T900150
• M30 x 1.5 0.8 m white MNG T900108W0
• • M30 x 1.5 2.0 m white MNG T900120W0
• M30 x 1.5 5.0 m white MNG T900150W0
EN0H-2003GE25 R0109 2 Honeywell y Subject to change