Honeywell T9000 User Manual

T9000 Series
Thera-2
RADIATOR THERMOSTATS
Application
A Radiator Thermostat is installed onto a Thermostatic Radi­ator Valve Body (TRV body). The combination of both, the Thermostatic Radiator Valve (TRV), controls the room temper­ature by adjusting the flow of hot water through a radiator.
TRVs are installed in water-based heating systems on the supply or, less commonly on the return connection of radiators.
3
4
2
1
5
Radiator thermostats of this type fulfill the European Standard EN 215 when used with certified Honeywell TRV bodies.
Honeywell radiator thermostats with Honeywell (HW) M30 x 1.5 connection are suitable for all TRV body and radiator inserts with M30 x 1.5 connection and 11.5 mm closing dimension.
Radiator Thermostats of this type with snapring (DA) type connection are suitable for TRV bodies and valve inserts with Danfoss (RA) type compatible snap connection.
4
2
5
1
Design
The radiator thermostat consists of:
• Handwheel with socket
• Honeywell HW M30 x 1.5 connection and 11.5 mm closing dimension or Danfoss snapring RA type connection
• Sensor with support cage
• Spindle assembly
• Connection nut
Materials
• Handwheel, lid and socket made of plastic, white to RAL9016
• Socket, support cage and spindle assembly made of plastic
• Sensor filled with liquid or wax
• Connection nut made of nickel-plated brass
Features
• Conforms with M30 x 1.5 connection to European stan­dard EN 215
• Available with liquid- or wax sensor
• Equipped with easy to use range stoppers
• Modern ergonomical design
Specifications
Thermostat connection
Setpoint range 0 - - 1..5 (with zero-position)
Temperature range 1...26°C (34...79°F)(with zero-position)
Closing dimension 11.5 mm HW type
NOTE: Zero-position is also thermostatically controlled -
when temperature falls the TRV may open.
M30 x 1.5 HW type or
Snap connection DA type
- 1..5 (without zero-position)
6...28°C (43...82°F)(without zero-position)
Function
Radiator thermostats of this type control the TRV body. The air passing around the sensor of the radiator thermostat causes the sensor to expand when the temperature rises. The expanding sensor closes the TRV accordingly. When the room temperature changes the TRV opens or closes proportionally. Only the amount of water required to maintain the room temper­ature set on the radiator thermostat is allowed to flow through the valve.
Honeywell y Subject to change EN0H-2003GE25 R0109
T9000 SERIESTHERA-2
Dimensions and Ordering Information
ø
H
H
35
98
Fig. 1. Thera-2 with internal sensor Fig. 2. Thera-2 with remote sensor
Table 1. Dimensions
Type H closed H open Ø L
Thera-2 (Fig. 1.) 82.5 88.5 52 ­Thera 2 DA (Fig. 1.) 90.0 96.0 52 ­Thera-2 with remote sensor (Fig. 2.) 82.5 88.5 52 0.8 - 2.0 - 5.0 m
NOTE: All dimensions in mm unless stated otherwise.
Table 2. Available versions and OS-Nos (OS=Ordering Specification)
Type EN215
certification
Zero-
position
(’0’)
Connection Capillary
tube
length
Colour Cap OS-No.
Thera-2 and Thera-2-DA with internal sensor Liquid sensor M30 x 1.5 - white MNG T9001
M30 x 1.5 - white MNG T9001W0
M30 x 1.5 - white Honeywell T9001W0H DA type - white MNG T9001DA DA type - white Honeywell T9001DAH
DA type - white MNG T9001DAW0
DA type - white Honeywell T9011DAW0H Eastern European version
M30 x 1.5 - white MNG T9001HP
M30 x 1.5 - white MNG T9001HPW0
Wax sensor M30 x 1.5 - white MNG T9002
M30 x 1.5 - white MNG T9002W0
M30 x 1.5 - white Honeywell T9002W0H Thera-2 and Thera-2-DA with remote sensor Liquid sensor M30 x 1.5 0.8 m white MNG T900108
M30 x 1.5 2.0 m white MNG T900120
M30 x 1.5 5.0 m white MNG T900150
M30 x 1.5 0.8 m white MNG T900108W0
M30 x 1.5 2.0 m white MNG T900120W0
M30 x 1.5 5.0 m white MNG T900150W0
EN0H-2003GE25 R0109 2 Honeywell y Subject to change
Loading...
+ 2 hidden pages