Honeywell T8631A User Manual

T8631A,R Communicating
Chronotherm III Thermostats
Application
T8631A,R can be connected to Honeywell's TotalHome system for external access and control. TotalHome system devices communicate using HBus, a Honeywell communi­cations protocol.
As long as AC power is continuously available to the transformer, the thermostat will be compatible with most control systems.
The T8631A,R models include a SYSTEM LED near the top of the thermostat face. The SYSTEM LED lights when the thermostat is signaling for heating or cooling.
TABLE I—THERMOSTAT MODELS.
Stages Switching
Thermostat Heat Cool System Fan Program
T8631A 1 1 HEAT-OFF-COOL ON-AUTO 5-1-1 T8631R 2 1 EM. HT.-HEAT-OFF-COOL ON-AUTO 5-1-1
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service tech­nician.
4. After installation is complete, check out product operation as provided in these instructions.
5. Allow thermostat to warm to room temperature before operating.
IMPORTANT: After wiring is complete, push excess wire
back into the hole, and plug hole with nonhardening caulk, putty or insulation to prevent drafts from affecting thermostat operation.
LOCATION
Install thermostat and subbase about 5 ft [1.5 m] above the floor in an area with good air circulation at room temperature.
Do not install the thermostat where it may be affected by:
— drafts or dead spots behind doors, in corners or under
cabinets. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys.
T8631R includes AUX. HT. and EM. HT LEDs near the bottom center of the subbase. The AUX. HT. LED lights whenever the thermostat is calling for operation of the backup or auxiliary heater. Backup (auxiliary) heat is more expensive to operate than the heat pump and typically is used only when the heat pump is unable to handle the load. The EM. HT. LED lights whenever the thermostat system switch is in the EM. HT. position. The EM.HT. LED may also light on some systems if the heat pump is malfunction­ing. The system switch needs to be moved to EM.HT. on these heat pumps.
Heat and cool anticipation is fixed in both models; no adjustment is necessary. T8631A has adjustable cycle rate for heating; T8631R cycle rate is adjustable only for auxiliary heat.
such as an outside wall.
WIRING TO HEATING/COOLING SYSTEM
The T8631 requires connection to both sides of the heating transformer secondary for power.
If Replacing An Existing Thermostat
Turn off power to thermostat at furnace or heat pump. A two-transformer system may require turning off two switches or disconnects. Remove any existing wallplate or subbase from wall. Label each wire with, or write down, the letter or number on the wiring terminal as the wire is removed, to avoid miswiring later.
If New Installation
Run cable to a hole at the selected wall location, and pull about 3 in. [76 mm.] of wire through the opening. Color-coded, 18-gauge thermostat cable with one conduc­tor for each wiring terminal, excluding H terminals, is recommended. Good service practice recommends select­ing cable with one or two more conductors than the immediate application requires.
WIRING TO TOTALHOME SYSTEM
The HBus connection requires an unshielded cable with 3 twisted pairs of #22 AWG solid wire. Use Belden #8742, Alpha #1304 or equivalent wire. Route this cable with the thermostat cable to the utility room. Do not connect the HBus cable to the T8631 until the other TotalHome devices are connected.
J.H . • Rev. 3-93 • © Honeywell Inc. 1993 • Form Number 69-0689—2
MOUNTING SUBBASE
The subbase does not require leveling for proper opera-
tion, but only for appearance.
Remove thermostat from subbase. See Fig. 1.
The subbase mounts directly onto the wall with the screws and anchors included in the package. Use the subbase as a template, and with a pencil, mark the two mounting screw positions. See Fig. 2. If drywall construc­tion, plastic anchors must be used; select 3/16 in. bit to drill holes for anchors. Gently tap anchors into holes until they are flush with the wall surface. Thread wires through the center opening of the subbase. Then, mount the subbase by using two screws provided. Gently tighten screws, level top surface of subbase and then securely tighten screws.
WIRING
All wiring must comply with local electrical codes and ordinances.
Fig. 1—Removing thermostat from subbase.
S
Y
S
T
E
M
HEAT
AUTO
COOL
OFF
F A
N
O
N
A
U T
O
AUX. HEAT
M3060
shock or equipment damage.
The shape of the terminal barrier permits insertion of straight or conventional wraparound wiring connections. Either method is acceptable.
Refer to Figs. 3-5 for typical hookups of subbase and thermostat.
NOTE: Keep all wiring restricted to ribbed area surround-
ing terminals to assure thermostat/subbase contact. See
Fig. 6.
Fig. 2—Mounting subbase on wall.
WALL
WIRES THROUGH WALL OPENING
WALL ANCHORS (2)
MOUNTING HOLES
SUBBASE
SWITCH UP DISCONNECTS THE HBUS.
1 2
FAN CAN BE SET FOR ELECTRIC HEAT OR CONVENTIONAL.
1 HBUS SWITCH
2 FAN OPERATIONAL SWITCH FOR T8631A ONLY
MOUNTING SCREWS (2)
M3061
Fig. 3—T8631A 1-stage heat/1-stage cool thermostat with HEAT-OFF-COOL system and ON-AUTO fan switching.
POWER
3
SUPPLY
FAN SWITCH
STAT LOGIC CIRCUIT
H3
TRANS­CEIVER
POWER SUPPLY
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. JUMPER R AND RC FOR SINGLE TRANSFORMER SYSTEM.
2 3
DENOTES THERMOSTAT TO SUBBASE INTERCONNECT.
4
DO NOT CONNECT H BUS WIRES TO THERMOSTAT UNTIL OTHER TotalHome DEVICES ARE CONNECTED. FAN OPERATION SWITCH (4A) IN ELEC. POSITION, USE ONE SYSTEM TRANSFORMER AND JUMPER R TO RC.
5
FOR SINGLE STAGE HEAT PUMP APPLICATIONS, JUMPER W TO Y FOR SINGLE COMPRESSOR CONTACTOR
6
OPERATION.
BUS IN
H3
H4 H4 H1
H2
BUS OUT
13.7 VDC
+
_
4
BUS POWER SUPPLY
SUBBASE LOGIC/ CONTROL CIRCUIT
ELEC.
ON
AUTO
SYSTEM SWITCH
HEAT
OFF
COOL
HEAT/
HIGH LIMIT
COOL
5
CONV.
R
C
B
HEAT DAMPER OR CHANGEOVER RELAY
W
G
6
O
COOL DAMPER OR CHANGEOVER RELAY
Y
RC
1
HEATING SYSTEM TRANSFORMER
HEAT RELAY
2
FAN RELAY
5
COMPRESSOR CONTACTOR
1
COOLING SYSTEM TRANSFORMER
M3066A
2
L1 (HOT)
L2
L2 L1
(HOT)
Fig. 4—T8631A 1-stage oil heat/1-stage cool. Oil Primary has its own transformer.
HEATING-COOLING WALLPLATE
O G
1
RELAY
T
T
OIL PRIMARY
COOLING DAMPER/ COOLING CHANGE­OVER
1
L1 (HOT)
L2
Fig. 5—T8631R 2-stage heat/1-stage cool thermostat with EM. HT.-HEAT-OFF-COOL system and ON-AUTO fan switching.
L1 (HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
C B
FAN RELAY
RW
HEATING DAMPER/ HEATING CHANGE­OVER
AIR COND. EQUIP.
Y
M3089
3
POWER SUPPLY
FAN
STAT LOGIC CIRCUIT
SUBBASE LOGIC/ CONTROL CIRCUIT
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS
1
REQUIRED. REMOVE JUMPER ( IF PRESENT) FOR SYSTEM WITH ISOLATED STAGE 1 HEATING
2
AND COOLING CONNECTIONS. DENOTES THERMOSTAT TO SUBBASE INTERCONNECT.
3
DO NOT CONNECT H BUS WIRES TO THERMOSTAT UNTIL OTHER TotalHome
4
DEVICES ARE CONNECTED.
SWITCH
SYSTEM SWITCH
ON
AUTO
HIGH LIMIT
OFF
COOL
HEAT/ COOL 1
E. HEAT HEAT
E. HEAT RED
HIGH LIMIT
AUX. HEAT GREEN
HEAT 2
R
C
L
W2
E
W1
G
O
B
Y1
TRANS­CEIVER
POWER SUPPLY
MONITOR
2
H3 H3
H4 H4 H1 H2
TRANSFORMER
AUXILIARY HEAT RELAY
EMERGENCY HEAT RELAY
STAGE 1 HEAT RELAY
FAN RELAY
CHANGEOVER RELAY (COOL)
CHANGEOVER RELAY (HEAT)
COMPRESSOR CONTACTOR
BUS IN
BUS OUT
13.7 VDC
+
_
4
BUS
POWER
SUPPLY
M3065A
1
L1 (HOT)
L2
3 69-0689—2
Loading...
+ 5 hidden pages